0% found this document useful (0 votes)
322 views22 pages

Documentation

The SPAU pressure sensor is designed for monitoring compressed air and non-corrosive gases, offering variants with or without a display for local pressure reading. It transmits pressure values to control systems via analogue signals or IO-Link, allowing for easy parameterization and monitoring. The sensor is versatile in mounting options and features various electrical outputs to suit different applications.

Uploaded by

gabriel acevedo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
322 views22 pages

Documentation

The SPAU pressure sensor is designed for monitoring compressed air and non-corrosive gases, offering variants with or without a display for local pressure reading. It transmits pressure values to control systems via analogue signals or IO-Link, allowing for easy parameterization and monitoring. The sensor is versatile in mounting options and features various electrical outputs to suit different applications.

Uploaded by

gabriel acevedo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 22

Pressure sensors SPAU

Pressure sensors SPAU

Characteristics
At a glance
Product description
The pressure sensor SPAU is suitable for monitoring compressed air and non-​ The pressure sensor without display transmits the pressure value to the connect-
corrosive gases. The variant with display offers the option of reading the pressure ed control system as an analogue signal. Display of the pressure and parameteri-
and set values on-site. The pressure value is transmitted to the connected control sation of the sensor are provided centrally, e.g. via a display that is part of a ma-
system as a switching signal, as an analogue signal or via IO-Link. chine control system. The pressure sensor can be parameterised using IO-Link as
a tamper-proof pressure switch without display with up to two switching outputs.

Areas of application
• Network monitoring (pressure present) • Vacuum (part picked up)
• Regulator monitoring (pressure in the setpoint range) • Leak test (pressure drop over time)
• Object detection (back pressure present)

Product benefits
A mounting concept that is quick to Mounting: Electronics:
mount and that is easy to implement in • Threaded mounting • Maximum versatility and reduced
all installation situations. Female/male • H-rail mounting warehousing thanks to switchable
thread or push-in fitting QS – the • Front panel mounting electrical outputs (PNP/NPN/N/C
perfect pneumatic adapter for every • Mounting bracket contact/N/O contact and current/
application. • Wall mounting voltage output)
• Adapter to MS4, MS6

2 d Internet: www.festo.com/catalogue/... Subject to change – 2025/03


Pressure sensors SPAU

Characteristics
Operation
Monitoring and setting of a pressure
threshold, a pressure range or a
pressure difference, using a teach-in
function or by entering values.

Variants with display:


• Pressure indicator, pressure switch- • Min./max. value memory for moni- • Choice of pressure units: bar, MPa, • All the settings for one sensor (mas-
ing outputs and analogue value out- toring compressed air (display of PSI and more ter) can be transferred (replication)
put from a device can be set on-site rapid pressure peaks that are not • Offset compensation possible to other, identical sensors (device).
• Quick commissioning of the pres- visible to the human eye) • ECO function "Switch off display" This significantly shortens the
sure sensor thanks to straightfor- • Adjustable filter evens out the sen- available commissioning time
ward menu navigation sor signal generated by pressure • Optional security code can be freely
• Display colour blue/red as visual peaks chosen (4-digit code)
feedback about the pressure of the • Scaling the analogue output to
medium increase the signal dynamics

Variants without display:


• Analogue value output and pressure • Switching output behaviour can be • Other functions can be set using
switching outputs proportional to set on the machine display using IO-Link
the pressure IO-Link

Variants with IO-Link:


• With and without display • The sensor can be parameterised • Automatic parameterisation follow-
• Serial communication integrated and maintained remotely at control ing a sensor change means there is
using IO-Link 1.1 level using an IO-Link master no need to re-parameterise or enter
• Analogue process value is provided the settings again after changing
digitally the sensor

2025/03 – Subject to change d Internet: www.festo.com/catalogue/... 3


Pressure sensors SPAU

Characteristics
Device variants
Variants with display

Variants with display for front panel mounting

The connections shown are by way of example.

Variants with display and MS adapter

4 d Internet: www.festo.com/catalogue/... Subject to change – 2025/03


Pressure sensors SPAU

Characteristics
Device variants
Variants without display

The connections shown are by way of example.

2025/03 – Subject to change d Internet: www.festo.com/catalogue/... 5


Pressure sensors SPAU

Characteristics
Housing variants Types of mounting Pneumatic connection
Pneumatic connection at rear Male thread:
Electrical connection on top G1/8, R1/8, N1/8, R1/4

Female thread:
M5, M7
Threaded mounting1) Mounting bracket (standing)

Front panel mounting


Pneumatic connection at rear Male thread:
Electrical connection underneath G1/8, R1/8, N1/8, R1/4

Female thread:
M5, M7
Threaded mounting Mounting bracket (suspended)
Flange

Front panel mounting MS adapter


Pneumatic connection underneath Female thread:
Electrical connection on top G1/8, R1/8, N1/8, M7

Push-in connector:
QS4, QS6, QS5/32
Threaded mounting H-rail

Front panel mounting Wall mounting


Pneumatic connection underneath Push-in connector:
Electrical connection underneath QS4, QS5/32

H-rail Wall mounting

Front panel mounting


Pneumatic connection at rear Push-in connector:
Electrical connection at rear QS4, QS6, QS5/32

Front panel mounting Mounting bracket (standing)


1) Threaded mounting with M5 female thread not recommended

6 d Internet: www.festo.com/catalogue/... Subject to change – 2025/03


Pressure sensors SPAU

Peripherals overview

12

12

10 2

6
5 6
5
5 6
7
10 3
6 8
11

10 4
11 9

10

Accessories a Page/ Accessories a Page/


Internet Internet
[1] Pressure sensors SPAU, 9 [6] Connecting cable, straight socket 22
display variants for MS service unit components M12x1
[2] Pressure sensors SPAU, 9 [7] Wall mounting 20
variants for threaded mounting SAMH-PU-W
[3] Pressure sensors SPAU, variants for H-rail, w
­ all mounting or 9 [8] Mounting bracket 20
mounting bracket SAMH-PU-A
[4] Pressure sensors SPAU, 9 [9] H-rail nrh
variants for front panel mounting to DIN EN 60715
[5] Connecting cable, angled plug socket 22 [10] Safety guard 21
M8x1 SACC-PU-G
[6] Connecting cable, straight socket 22 [11] Pressure supply port –
M8x1
[5] Connecting cable, angled plug socket 22 [12] Service unit component ms4, ms6
M12x1 MS4, MS6

2025/03 – Subject to change d Internet: www.festo.com/catalogue/... 7


Pressure sensors SPAU

Type codes
001 Series 007 Outlet orientation
SPAU Pressure sensor Rear
D Underneath
002 Pressure measuring range
B2 -1 ... 1 bar 008 Display
B11 -1 ... 10 bar None
V025 0 ... -0.25 bar L LCD, backlit
V05 0 ... -0.5 bar
V1 0 ... -1 bar 009 Electrical output 1
P025 0 ... 0.25 bar LK IO-Link®
P05 0 ... 0.5 bar PNLK PNP or NPN or IO-Link®
P1 0 ... 1 bar
P2 0 ... 2 bar 010 Electrical output 2
P6 0 ... 6 bar V 0 ... 10 V
P10 0 ... 10 bar B 1 ... 5 V
P12 0 ... 12 bar A 4 ... 20 mA
P16 0 ... 16 bar PNVBA PNP or NPN or 0 ... 10 V or 1 ... 5 V or 4 ... 20 mA

003 Pressure inlet 011 Electrical connection


R Relative pressure M8 Plug M8
M12 Plug M12, A-coded
004 Type of mounting
T Threaded mounting 012 Electrical outlet direction
A Mounting bracket Rear
F Front panel mounting U Top
H H-rail mounting D Underneath
W Wall mounting
MS4 Adapter MS4 013 Electrical accessories
MS6 Adapter MS6 None
2.5A Angled socket, cable 2.5 m
005 Pneumatic connection
2.5S Straight socket, cable 2.5 m
G18 G1/8 5A Angled socket, cable 5 m
M5 M5 5S Straight socket, cable 5 m
M7 M7
N18 1/8 NPT 014 Protective devices
Q4 Push-in connector 4 mm None
Q6 Push-in connector 6 mm G Protective hood
R14 R1/4
R18 R1/8 015 Certificate
T532 Push-in connector 5/32“ None
F Flange/sub-base T Test report

006 Thread type


None
M Male
F Female

8 d Internet: www.festo.com/catalogue/... Subject to change – 2025/03


Pressure sensors SPAU

Data sheet
Display … -L
-P- Voltage
20 ... 30 V DC

-L- Pressure measuring range


Variant without display –1 ... +16 bar
Voltage output preset
… -LK-V -Q- Temperature range
0 ... +50°C

Variant without display


Current output preset
… -LK-A

General technical data ...-M8 ...-M12


Certification RCM compliance mark
c UL us listed (OL)
CE marking To EU EMC Directive
(see declaration of conformity) To EU RoHS Directive
KC mark KC EMC
UKCA marking UK instructions for EMC
(see declaration of conformity) UK RoHS instructions
Electrical connection To EN 60947-5-2, plug 4-pin, round design
Mounting position Any
Note on materials RoHS-compliant
LABS (PWIS) conformity VDMA24364-B1/B2-L
Electrical connection 1
Connection type Plug
Connection technology M8x1,A-coded to EN 61076-2-104 M12x1,A-coded to EN 61076-2-101
Number of pins/cores 4

Inlet signal, measuring element


SPAU -B2 -B11 -V025 -V05 -V1 -P025 -P05
Measured variable Relative pressure
Measurement method Piezoresistive pressure sensor
Pressure measuring range start value [MPa] –0.1 –0.1 0
[bar] –1 –1 0
[psi] –14.5 –14.5 0
Pressure measuring range end value [MPa] 0.1 1 –0.025 –0.05 –0.1 0.025 0.05
[bar] 1 10 –0.25 –0.5 –1 0.25 0.5
[psi] 14.5 145 –3.6 –7.25 –14.5 3.6 7.25
Overload range [bar] 5 15 1 2 5 1 2
Overload pressure [MPa] 0.5 1.5 0.1 0.2 0.5 0.1 0.2
[bar] 5 15 1 2 5 1 2
[psi] 72.5 217.5 14.5 29 72.5 14.5 29
Operating medium Compressed air to ISO 8573-1:2010 [7:4:4]
Inert gases
Note on operating/pilot medium Lubricated operation possible
Temperature of medium [°C] 0 ... +50
Ambient temperature [°C] 0 ... +50

2025/03 – Subject to change d Internet: www.festo.com/catalogue/... 9


Pressure sensors SPAU

Data sheet
SPAU -P1 -P2 -P6 -P10 -P12 -P16
Measured variable Relative pressure
Measurement method Piezoresistive pressure sensor
Pressure measuring range start value [MPa] 0
[bar] 0
[psi] 0
Pressure measuring range end value [MPa] 0.1 0.2 0.6 1 1.2 1.6
[bar] 1 2 6 10 12 16
[psi] 14.5 29 87 145 174 232
Overload range [bar] 5 6 15 15 15 20
Overload pressure [MPa] 0.5 0.6 1.5 1.5 1.5 2
[bar] 5 6 15 15 15 20
[psi] 72.5 87 217.5 217.5 217.5 290
Operating medium Compressed air to ISO 8573-1:2010 [7:4:4]
Inert gases
Note on operating/pilot medium Lubricated operation possible
Temperature of medium [°C] 0 ... +50
Ambient temperature [°C] 0 ... +50

Signal processing
Resolution ADC [bit] 12

Output, general -B2 -B11 -V025 -V05 -V1 -P025 -P05


Accuracy FS [%] ±1.5
Repetition accuracy [%FS] ±0.3
Temperature coefficient [%FS/K] ±0.05

Output, general -P1 -P2 -P6 -P10 -P12 -P16


Accuracy FS [%] ±1.5 ±2
Repetition accuracy [%FS] ±0.3
Temperature coefficient [%FS/K] ±0.05

Switching output
-PNLK -LK
Switching output 2x PNP or 2x NPN, switchable 2x PNP1)
Switching function Freely programmable
Switching element function N/C or N/O contact, switchable

1) Second PNP output can only be activated using IO-Link

Analogue output
-PNLK-PNVBA -LK-A -LK-V -LK-B
Analogue output [V] 0 ... 10 – 1) 0 ... 10 – 1)
[V] 1 ... 5 – 2) – 2) 1 ... 5
[mA] 4 ... 20 4 ... 20 – 3) – 3)
Rise time [ms] 3
Max. output current [mA] 100
Max. load resistance of current output [Ω] 500
Min. load resistance of voltage output [kΩ] 10

1) 0 ... 10 V analogue output can only be activated using IO-Link


2) 1 ... 5 V analogue output can only be activated using IO-Link
3) 4 ... 20 mA analogue output can only be activated using IO-Link

10 d Internet: www.festo.com/catalogue/... Subject to change – 2025/03


Pressure sensors SPAU

Data sheet
Output, additional data
Short circuit current rating Yes
Overload protection Present

IO-Link device to IEC 61131-9


Protocol IO-Link
IO-Link
Protocol version Device V 1.1
Profile Smart sensor profile
Function classes Binary data channel (BDC)
Diagnostics
Identification
Process data variable (PDV)
Teach channel
Communication mode COM2 (38.4 kBaud)
SIO-mode support Yes
Port class A
Process data width OUT 0 bytes
Process data width IN 2 bytes
Process data content IN 14 bit PDV (pressure measurement value)
2 bit BDC (pressure monitoring)
Minimum cycle time [ms] 3
Data storage required [Kbyte] 0.5

Electronics
Operating voltage range DC [V] 20 ... 30
Reverse polarity protection For all electrical connections

Pin allocation to EN 60947-5-2


Plug, 4-pin
M8x1 M12x1 Pin Wire colour Allocation
1 Brown Operating voltage +24 V DC
3 Blue Operating voltage 0 V
4 Black Switching output (C/Q-...)
2 White Switching output or analogue output

2025/03 – Subject to change d Internet: www.festo.com/catalogue/... 11


Pressure sensors SPAU

Data sheet
Display/operation
SPAU –L–PNLK –LK
Display type Backlit LCD LED
Displayable units bar –
inchH2O –
inchHg –
kgf/cm² –
kPa –
mmHg –
MPa –
psi –
Setting options IO-Link
Teach-in –
Via display and pushbuttons –
Protection against tampering IO-Link
PIN code –
Threshold value setting range [%] 0 ... 100
Hysteresis setting range [%] 0 ... 90

Immission/emission –T/H/W/A –F/MS4/MS6


Degree of protection IP67, IP65 IP65
Corrosion resistance class CRC1) 2

1) Corrosion resistance class CRC 2 to Festo standard FN 940070


Moderate corrosion stress. Indoor applications in which condensation can occur. External visible parts with primarily decorative surface requirements which are in direct contact with a normal industrial environment.

12 d Internet: www.festo.com/catalogue/... Subject to change – 2025/03


Pressure sensors SPAU

Data sheet
Dimensions Download CAD data a www.festo.com
SPAU-...-F-...-L-PNLK-... SPAU-...-L-PNLK-... SPAU-...-LK-...

Type B1 B2 B3 L1 L3

SPAU-...-F-...-L-PNLK-... 40 23 48 67 24.8
SPAU-...-L-PNLK-... 32 – 54
SPAU-...-LK-... – –

Service unit dimensions Download CAD data a www.festo.com

[1] Pressure supply port


[2] Adapter for MS4,
MS6 series (is enclosed for
the customer to fit)

Type B1 B2 B3 B8 D1 D2 H1 H12 L1 L2 L3 L12 L13


SPAU-P10R-MS-...-L-...-M8 32 23 – 1.8 M8x1 1.8 29.8 – – 69.8 24.8 6.7 33.8
SPAU-P10R-MS-...-L-...-M12 32 23 – 1.8 M12x1 1.8 29.8 – – 69.8 24.8 6.7 33.8
SPAU-P10R-MS4-F-L-...-M8D 32 23 32 1.8 M8x1 1.8 29.8 ~38.3 70.2 69.8 24.8 6.7 33.8
SPAU-P10R-MS6-F-L-...-M8D 32 23 51 1.8 M8x1 1.8 29.8 ~38.3 70.2 69.8 24.8 10 33.8
SPAU-P10R-MS4-F-L-...-M12D 32 23 32 1.8 M12x1 1.8 29.8 ~38.3 70.2 69.8 24.8 6.7 33.8
SPAU-P10R-MS6-F-L-...-M12D 32 23 51 1.8 M12x1 1.8 29.8 ~38.3 70.2 69.8 24.8 10 33.8

2025/03 – Subject to change d Internet: www.festo.com/catalogue/... 13


Pressure sensors SPAU

Data sheet
Dimensions of connections Download CAD data a www.festo.com
SPAU-…-G18M-… SPAU-…-R14M-… SPAU-…-M7F-…
SPAU-…-R18M-…
SPAU-…-N18M-…
SPAU-…-M5F-…

SPAU-…-G18MD-… SPAU-…-Q4D-…-MxU SPAU-…-Q4D-…-MxD SPAU-…-Q4-…-Mx


SPAU-…-R18MD-… SPAU-…-Q6D-…MxU SPAU-…-Q532D-…MxD SPAU-…-Q532-…Mx
SPAU-…-N18MD-… SPAU-…-Q532D-…MxU
SPAU-…-M7FD-…

[3] Connections
SPAU-…-M12… M12, 4-pin
SPAU-…-M8… M8, 4-pin

Type B1 B5 B6 D2 Thread length Length of thread D4 H1 H8 H9 L8 L9 ß1


Male (M) Female (F) engagement
SPAU-...-G18M-...-MxD – – – G1/8 8 – Until stop M5 37.9 19 – 27 – 12
SPAU-...-R18M-...-MxD R1/8 Min. 6.5
SPAU-...-N18M-...-MxD 1/8NPT Min. 6.9
SPAU-...-M5F-...-MxD G1/8 8 6 Until stop
SPAU-...-R14M-...-MxD R1/4 12 – Min. 9.7 23
SPAU-...-M7F-...-MxD M7 – 8 Until stop M7 3 –
SPAU-...-G18FD-...-MxU 32 G1/8 12 – 39.4 – 10 –
SPAU-...-R18FD-...-MxU R1/8 8 Min. 6.5
SPAU-...-N18FD-...-MxU 1/8NPT Min. 6.9
SPAU-...-M7FD-...-MxU M7 Until stop
SPAU-...-Q4D-...-MxU QS4 – – – 6.1
SPAU-...-Q6D-...-MxU QS6
SPAU-...-T532D-...-MxU T5/32
SPAU-...-Q4D-...-MxD 8 13.5 QS4 45.9 9.5 3
SPAU-...-T532D-...-MxD T5/32
SPAU-...-Q4-...-Mx – – – QS4 33.9 14.8 – 27 –
SPAU-...-Q6-...-Mx QS6
SPAU-...-T532-...-Mx T5/32

14 d Internet: www.festo.com/catalogue/... Subject to change – 2025/03


Pressure sensors SPAU

Data sheet
Dimensions for front panel mounting Download CAD data a www.festo.com

[1] Pressure supply port Recess for front panel

SPAU-…-F-… -MxD SPAU-…-F-… -MxU SPAU-…-F-… FD-…-MxU

SPAU-…-F-Q… D-…-MxU SPAU-…-F-Q4D-…-MxD SPAU-…-F-Q…-…-Mx


SPAU-…-F-T532D-…-MxU SPAU-…-F-T532D-…-MxD SPAU-…-F-T532-…-Mx

Type B1 B2 B3 B4 B7 D2 D3 H3 H4 H10 H11 L1 L3 L4 L11


±0.3 ±0.3
SPAU-...-F-...18M-...-MxD 40 23 48 33.5 34 – M3 44.4 8.4 29.5 – 67 24.8 60.5 61
SPAU-...-F-R14M-...-MxD R1/8 48.4
SPAU-...-F-M7F-...-MxD M7 28.4
SPAU-...-F-M5F-...-MxD M5 –
SPAU-...-F-...18M-...-MxU – 44.4
SPAU-...-F-R14M-...-MxU R1/4 48.4
SPAU-...-F-M7F-...-MxU M7 28.4
SPAU-...-F-M5F-...-MxU M5 –
SPAU-...-F-...18FD-...-MxU – 31 16.9
SPAU-...-F-M7FD-...-MxU M7
SPAU-...-F-Q...D-...-MxU –
SPAU-...-F-T532D-...-MxU T5/32
SPAU-...-F-Q4D-...-MxD QS4 37.5 13.4
SPAU-...-F-T532D-...-MxD T5/32
SPAU-...-F-Q...-...-Mx – 36.1 25.5 –
SPAU-...-F-T532-...-Mx T5/32

2025/03 – Subject to change d Internet: www.festo.com/catalogue/... 15


Pressure sensors SPAU

Data sheet
Ordering data – Variants with display
Type of Pneumatic Outlet Electrical Outlet Product Part no. Type
mounting connection orientation connection orientation weight
Pressure measuring range –1 ... +1
Thread R1/8 Rear M8x1 Under- 80 8001207 SPAU-B2R-T-R18M-L-PNLK-PNVBA-M8D
neath
H-rail G1/8 Underneath M8x1 Top 70 8001219 SPAU-B2R-H-G18FD-L-PNLK-PNVBA-M8U

Pressure measuring range 0 ... –1


Thread R1/8 Rear M8x1 Under- 80 8200258 SPAU-V1R-T-G18M-L-PNLK-PNVBA-M8D
neath
H-rail G1/8 Underneath M8x1 Top 70 8001223 SPAU-V1R-H-G18FD-L-PNLK-PNVBA-M8U
QS-4 Underneath M8x1 Under- 65 8001213 SPAU-V1R-H-Q4D-L-PNLK-PNVBA-M8D
neath
Wall/surface G1/8 Underneath M8x1 Top 70 8001235 SPAU-V1R-W-G18FD-L-PNLK-PNVBA-M8U
bracket G1/8 Underneath M12x1 Top 70 8001234 SPAU-V1R-W-G18FD-L-PNLK-PNVBA-M12U
QS-4 Underneath M8x1 Under- 65 8001239 SPAU-V1R-W-Q4D-L-PNLK-PNVBA-M8D
neath
QS-4 Underneath M12x1 Under- 65 8001214 SPAU-V1R-H-Q4D-L-PNLK-PNVBA-M12D
neath
QS-4 Underneath M12x1 Under- 65 8001238 SPAU-V1R-W-Q4D-L-PNLK-PNVBA-M12D
neath
QS6 Underneath M12x1 Top 70 8187488 SPAU-V1R-W-Q6D-LK-A-M12U
Front panel QS-4 Rear M12x1 Rear 70 8001227 SPAU-V1R-F-Q4-L-PNLK-PNVBA-M12
mounting QS-6 Rear M12x1 Rear 70 8001228 SPAU-V1R-F-Q6-L-PNLK-PNVBA-M12

Pressure measuring range 0 ... 2


Wall/surface G1/8 Underneath M8x1 Top 70 8001232 SPAU-P2R-W-G18FD-L-PNLK-PNVBA-M8U
bracket

Pressure measuring range 0 ... 6


Wall/surface G1/8 Underneath M8x1 Top 70 8001233 SPAU-P6R-W-G18FD-L-PNLK-PNVBA-M8U
bracket

Pressure measuring range –1 ... 10


Thread G1/8 Underneath M12x1 Top 70 594864 SPAU-B11R-T-G18FD-L-PNLK-PNVBA-M12U
H-rail G1/8 Underneath M12x1 Top 70 610566 SPAU-B11R-H-G18FD-L-PNLK-PNVBA-M12U
H-rail G1/8 Underneath M8x1 Top 70 8200257 SPAU-B11R-H-G18FD-L-PNLK-PNVBA-M8U
H-rail QS-6 Underneath M8x1 Top 70 8200259 SPAU-B11R-H-Q6D-L-PNLK-PNVBA-M8U

Wall/surface G1/8 Underneath M8x1 Top 70 607216 SPAU-B11R-W-G18FD-L-PNLK-PNVBA-M12U


bracket QS-6 Underneath M8x1 Top 70 610878 SPAU-B11R-W-Q6D-L-PNLK-PNVBA-M8U

16 d Internet: www.festo.com/catalogue/... Subject to change – 2025/03


Pressure sensors SPAU

Data sheet
Ordering data – Variants with display
Type of Pneumatic Outlet Electrical Outlet Product Part no. Type
mounting connection orientation connection orientation weight
Pressure measuring range 0 ... 10
Thread G1/8 Rear M8x1 Underneath 80 8001201 SPAU-P10R-T-G18M-L-PNLK-PNVBA-M8D
G1/8 Rear M12x1 Underneath 80 8001204 SPAU-P10R-T-G18M-L-PNLK-PNVBA-M12D
G1/8 Rear M12x1 Top 70 595878 SPAU-P10R-T-G18FD-L-PNLK-PNVBA-M12U
R1/8 Rear M8x1 Underneath 80 8001203 SPAU-P10R-T-R18M-L-PNLK-PNVBA-M8D
R1/8 Rear M12x1 Underneath 80 8001206 SPAU-P10R-T-R18M-L-PNLK-PNVBA-M12D
R1/4 Rear M8x1 Underneath 80 8001209 SPAU-P10R-T-R14M-L-PNLK-PNVBA-M8D
R1/4 Rear M12x1 Underneath 80 8001208 SPAU-P10R-T-R14M-L-PNLK-PNVBA-M12D
1/8-27NPT Rear M8x1 Underneath 80 8001202 SPAU-P10R-T-N18M-L-PNLK-PNVBA-M8D
1/8-27NPT Rear M12x1 Underneath 80 8001205 SPAU-P10R-T-N18M-L-PNLK-PNVBA-M12D
H-rail G1/8 Underneath M8x1 Top 70 8001221 SPAU-P10R-H-G18FD-L-PNLK-PNVBA-M8U
G1/8 Underneath M12x1 Top 70 8001220 SPAU-P10R-H-G18FD-L-PNLK-PNVBA-M12U
QS-4 Underneath M8x1 Underneath 65 8001211 SPAU-P10R-H-Q4D-L-PNLK-PNVBA-M8D
QS-4 Underneath M12x1 Underneath 65 8001212 SPAU-P10R-H-Q4D-L-PNLK-PNVBA-M12D
Wall/surface G1/8 Underneath M8x1 Top 70 8001231 SPAU-P10R-W-G18FD-L-PNLK-PNVBA-M8U
bracket G1/8 Underneath M12x1 Top 70 8001230 SPAU-P10R-W-G18FD-L-PNLK-PNVBA-M12U
QS-4 Underneath M8x1 Underneath 70 8001237 SPAU-P10R-W-Q4D-L-PNLK-PNVBA-M8D
QS-4 Underneath M12x1 Underneath 70 8001236 SPAU-P10R-W-Q4D-L-PNLK-PNVBA-M12D
Front panel QS-4 Rear M8x1 Rear 70 8186653 SPAU-P10R-F-Q4-L-PNLK-PNVBA-M8
mounting QS-4 Rear M12x1 Rear 70 8001224 SPAU-P10R-F-Q4-L-PNLK-PNVBA-M12
QS-6 Rear M12x1 Rear 70 8001225 SPAU-P10R-F-Q6-L-PNLK-PNVBA-M12

Service unit Flange MS4 Rear M8x1 Underneath 80 8035302 SPAU-P10R-MS4-F-L-PNLK-PNVBA-M8D


Flange MS4 Rear M12x1 Underneath 80 8035304 SPAU-P10R-MS4-F-L-PNLK-PNVBA-M12D
Flange MS6 Rear M8x1 Underneath 80 8035303 SPAU-P10R-MS6-F-L-PNLK-PNVBA-M8D
Flange MS6 Rear M12x1 Underneath 80 8074906 SPAU-P10R-MS6-F-L-PNLK-PNVBA-M12D

Pressure measuring range 0 ... 12


Thread R1/4 Rear M8x1 Underneath 80 8184451 SPAU-P12R-T-R18M-L-PNLK-PNVBA-M8D
H-rail G1/8 Underneath M12x1 Top 70 8182149 SPAU-P12R-H-G18FD-L-PNLK-PNVBA-M12U

Pressure measuring range 0 ... 16


Thread R1/4 Rear M8x1 Underneath 80 8001210 SPAU-P16R-T-R14M-L-PNLK-PNVBA-M8D
H-rail G1/8 Underneath M12x1 Top 70 8001222 SPAU-P16R-H-G18FD-L-PNLK-PNVBA-M12U

Ordering data – Variants without display


Type of Pneumatic Outlet Electrical Analogue Product Part no. Type
mounting connection orientation connection output weight
Pressure measuring range 0 ... –1
Thread G1/8 Rear M12x1 0 ... 10 V 80 8003347 SPAU-V1R-T-G18M-LK-V-M12D
Rear 4 ... 20 mA 8003348 SPAU-V1R-T-G18M-LK-A-M12D
H-rail QS-4 Underneath 0 ... 10 V 65 8003351 SPAU-V1R-H-Q4D-LK-V-M12D
Underneath 4 ... 20 mA 8003352 SPAU-V1R-H-Q4D-LK-A-M12D

Pressure measuring range 0 ... 10


Thread G1/8 Rear M12x1 0 ... 10 V 80 8003345 SPAU-P10R-T-G18M-LK-V-M12D
Rear 4 ... 20 mA 8003346 SPAU-P10R-T-G18M-LK-A-M12D
H-rail QS-4 Underneath 0 ... 10 V 65 8003349 SPAU-P10R-H-Q4D-LK-V-M12D
Underneath 4 ... 20 mA 8003350 SPAU-P10R-H-Q4D-LK-A-M12D

2025/03 – Subject to change d Internet: www.festo.com/catalogue/... 17


Pressure sensors SPAU

Ordering data – Modular product system


Ordering table
Pressure sensor SPAU Conditions Code Enter code
Module no. 8001200
Product type SPAU series U SPAU SPAU
Pressure measuring range –1 ... 1 bar -B2
–1 ... 10 bar -B11
0 ... –0.25 bar -V025
0 ... –0.5 bar -V05
0 ... –1 bar -V1
0 ... 0.25 bar -P025
0 ... 0.5 bar -P05
0 ... 1 bar -P1
0 ... 2 bar -P2
0 ... 6 bar -P6
0 ... 10 bar -P10
0 ... 12 bar -P12
0 ... 16 bar -P16
Pressure inlet Relative pressure R R
Type of mounting Threaded mounting -T
Mounting bracket -A
Front panel mounting -F
H-rail mounting -H
Wall mounting -W
Adapter MS4 -MS4
Adapter MS6 -MS6
Pneumatic connection G1/8 -G18
M5 [1] -M5
M7 -M7
1/8 NPT -N18
Push-in connector 4 mm [2] -Q4
Push-in connector 6 mm [2] -Q6
R1/4 [15] -R14
R1/8 -R18
Push-in connector 5/32 [2] -T532
Flange [17] -F
Thread type None
Male thread [3] [4] M
Female thread [3] [5] F
Outlet orientation Rear [6]
Underneath [7] D
Display Without
LCD, backlit [8] -L

[1] M5 Only with type of mounting A, F.


[2] Q4, Q6, T532 Not with type of mounting T.
Not with pressure measuring range P16.
[3] M, F Mandatory information in combination with pneumatic connection G18, N18, R18, R14, M7, M5.
[4] M Not with type of mounting H, W, MS4, MS6.
Not with pneumatic connection Q4, Q6, T532, M7, M5.
[5] F Not with type of mounting A if pneumatic connection G18, R18, N18.
Not with type of mounting MS4, MS6.
Not with pneumatic connection Q4, Q6, Q532.
[6] Not with type of mounting W, H.
Not with thread type F if pneumatic connection G18, R18, N18.
[7] D Not with pneumatic connection M5.
Not with type of mounting A, MS4, MS6.
Not with thread type M.
[8] L Mandatory information in combination with type of mounting F, MS4, MS6.

18 d Internet: www.festo.com/catalogue/... Subject to change – 2025/03


Pressure sensors SPAU

Ordering data – Modular product system


Ordering table
Pressure sensor SPAU Conditions Code Enter code
Electrical output 1 IO-Link [9] -LK
PNP or NPN or IO-Link [10] -PNLK
Electrical output 2 0 ... 10 V [9] -V
1 ... 5 V [9] -B
4 ... 20 mA [9] -A
PNP or NPN or 0 ... 10 V or 1 ... 5 V or 4 ... 20 mA [10] -PNVBA
Electrical connection Plug M8 -M8
M12 plug, A-coded -M12
Electrical outlet orientation Rear [11]
Underneath [12] D
Top [13] U
Electrical accessories Without accessories
Angled plug socket, cable 2.5 m +2.5A
Straight socket, cable 2.5 m +2.5S
Angled plug socket, cable 5 m +5A
Straight socket, cable 5 m +5S
Protective devices Without
Safety guard [16] G
Certificate Without
Test report T

[9] LK, V, B, A Not with display L.


[10] PNLK, PNVBA Not without display.
[11] Only with type of mounting A, F.
Not with pneumatic connection G18, N18, R18, M7, M5.
Not with outlet orientation D, U.
Only with thread type "without".
[12] D Mandatory information in combination with type of mounting MS4, MS6.
Only with outlet orientation D if pneumatic connection Q4 or T532 selected.
Not with outlet at rear if pneumatic connection Q4, Q6, T532.
[13] U Only with outlet orientation U if pneumatic connection Q4 or T532 selected.
Not with outlet at rear if pneumatic connection Q4, Q6, T532.
[15] R14 Only with thread type M.
Outlet at rear only.
Not with type of mounting W, H.
Not with electrical outlet at rear.
[16] G Only with display L.
[17] F Only with type of mounting MS4, MS6.

2025/03 – Subject to change d Internet: www.festo.com/catalogue/... 19


Pressure sensors SPAU

Accessories
Mounting bracket SAMH-PU-A

Type of mounting: via through-hole and


screw

Material:
High-alloy stainless steel

Note on materials: RoHS-compliant


[1] The bracket can also be
Only for variants with: pneumatic turned 180° during
connection with outlet at rear mounting

Ordering data
Type B1 B2 B3 D1 D2 H1 H2 L1 L2 L3 L4 L5 CRC1) Part no. Type
-N-
SAMH-PU-A 29 20 22 M3x8 4 14 9 49 25.6 20 8.6 2 2 8003354 SAMH-PU-A

1) Corrosion resistance class 2 to Festo standard 940 070


Components subject to moderate corrosion stress. External visible parts with primarily decorative surface requirements which are in direct contact with a normal industrial environment or media such as coolants or lubricating agents.

Wall mounting SAMH-PU-W

Type of mounting: via through-hole

Material:
High-alloy stainless steel

Note on materials: RoHS-compliant

Only for variants with: pneumatic


connection with outlet underneath

Dimensions and ordering data


Type B1 B2 D1 H1 H2 H3 L1 L2 L3 L4 CRC1) Part no. Type
-N-
SAMH-PU-W 29.4 20 3.5 7.5 3.4 1 43.8 35.4 12 10 2 8003355 SAMH-PU-W

1) Corrosion resistance class CRC 2 to Festo standard FN 940070


Moderate corrosion stress. Indoor applications in which condensation can occur. External visible parts with primarily decorative surface requirements which are in direct contact with a normal industrial environment.

20 d Internet: www.festo.com/catalogue/... Subject to change – 2025/03


Pressure sensors SPAU

Accessories – Ordering data


Safety guard SACC-PU-G
to protect the display and control
elements

Material: PA

Note on materials:
RoHS-compliant

Only for variants with: display

Dimensions and ordering data


Type B1 H1 H2 L1 CRC1) Part no. Type
SACC-PU-G SPAU- ... R-T- ... 34.5 41.6 9.6 60.8 2 8003353 SACC-PU-G
SPAU- ... R-H- ... -D-L- ... 49.6
SPAU- ... R-H- ... -FD-L- ... 43.6
SPAU- ... R-F- ... 37.6
SPAU- ... R-W- ... -D-L- ... 43.6
SPAU- ... R-W- ... -FD-L- ... 49.6

1) Corrosion resistance class CRC 2 to Festo standard FN 940070


Moderate corrosion stress. Indoor applications in which condensation can occur. External visible parts with primarily decorative surface requirements which are in direct contact with a normal industrial environment.

2025/03 – Subject to change d Internet: www.festo.com/catalogue/... 21


Pressure sensors SPAU

Accessories
Connecting cables
L10
M8 Straight socket 36.3

Angled plug socket 18.7

M12 Straight socket 50

Angled plug socket 28.5

Ordering data
Data sheets a Internet: nebu
Number of wires Cable length [m] Part no. Type
M8x1, straight socket
4 2.5 8078227 NEBA-M8G4-U-2.5-N-LE4
5 8078228 NEBU-M8G4-K-5-LE4

M8x1, angled plug socket


4 2.5 8078233 NEBA-M8W4-U-2.5-N-LE4
5 8078234 NEBA-M8W4-U-5-N-LE4

Ordering data
Data sheets a Internet: nebu
Number of wires Cable length [m] Part no. Type
M12x1, straight socket
4 2.5 8078239 NEBA-M12G5-U-2.5-N-LE4
5 8078240 NEBA-M12G5-U-5-N-LE4

M12x1, angled plug socket


4 2.5 8078248 NEBA-M12W5-U-2.5-N-LE4
5 8078249 NEBA-M12W5-U-5-N-LE4

22 d Internet: www.festo.com/catalogue/... Subject to change – 2025/03

You might also like