e -01/UJVNL/EE (M&G)/KPS/2025-26
Rated Short Time Withstand Current for 3
  25     sec – Asymmetrical                                1.55 times of 25 KArms
  26     Trip Relay                                        Hand Reset Mechanical
  27     Hooter                                            Hooter for alarm and tripping
  28     Annunciators                                      4 Window for OTI, WTI, Bucz, OC/EF
Current Transformer
  29     Rated voltage                                     12 KV
  30     Impulse withstand voltage                         75 KVP
  31     Primary winding                                   28KV rms
  32     Secondary winding                                 3KV rms
  33     Frequency                                         50Hz
  34     Rated continuous thermal current                  120% of rated primary current
  35     Short time thermal rating and its duration        25KA for 3 sec.
  36     Rated output                                      15VA 15VA
  37     Class of accuracy                                 1
  38     Type                                              Resin Casted
  39     ALF                                               5P20
  40     Standard                                          IS:2705
  41     Potential Transformer                             As Per Design & Standards
  42     Other Design Aspects                              As per Site Requirements
Equipment- 6.6KV/415V, 500kVA Transformer
  1      HV Voltage                                        6.6kV
  2      LV Voltage                                        415V
  3      HV Current                                        As per design
  4      LV Current                                        As per design
  5      Vector Group                                      DYN11
  6      Cooling Type                                      ONAN
  7      Protections Involved                              OTI, WTI, BUCZ
  8      Tap Steps                                         5% (+/-)
  9      Highest System Voltage                            6.8 KV
  10     HV Side Termination                               CABLE BOX
  11     LV Side Termination                               CABLE BOX
  12     Percentage Impedance                              4.50%
  13     Confirming Standard                               IS 2026
  14     Frequency Variations                              3% (+/-)
  15     Standard Frequency                                50Hz
  16     Pressure Release Mechanism                        PRV Valve
  17     Other Design Aspects                              As per Site Requirements
Equipment- 6.6/11KV, 500kVA Transformer
  1      HV Voltage                                        11kV
  2      LV Voltage                                        6.6kV
  3      HV Current                                        As per design
  4      LV Current                                        As per design
  5      Vector Group                                      DYN11
  6      Cooling Type                                      ONAN
                                                      53
                                                                            e -01/UJVNL/EE (M&G)/KPS/2025-26
 7    Protections Involved                             OTI, WTI, BUCZ
 8    Tap Steps                                        5% (+/-)
 9    Highest System Voltage                           12KV
 10   HV Side Termination                              CABLE BOX
 11   LV Side Termination                              CABLE BOX
 12   Percentage Impedance                             4.50%
 13   Confirming Standard                              IS 2026
 14   Frequency Variations                             3% (+/-)
 15   Standard Frequency                               50Hz
 16   Pressure Release Mechanism                       PRV Valve
 17   Other Design Aspects                             As per Site Requirements
Equipment-11 KV Lightening Arrester
 1    Standards applicable                          IS 15086 Part 5, IEC 60099 Part 5
 2    Arrestor Voltage Rating                       9 kV rms
 3    Discharge Class                               Station Low (SL) as per IEC60099-4
 4    Type of Construction                          Gapless Polymeric
 5    Connection                                    Phase to Earth
 6    Maximum Continuous Operating voltage          8 kV
 7    Nominal Discharge Current                     10 kAp
 8    Energy Discharge capacity (kJ/kV)             > 4.5 at Ur (minimum)
 9    Reference current                             5 mA peak
 10   Rated Frequency                               50 Hz
 11   Application / Installation                    Outdoor
 12   System voltage & Design Ambient Temperature
 13   a) Nominal Voltage                            11 Kv
 14   b) Highest Voltage                            12 kV
 15   c) Design Ambient Temperature                 50°C
 16   Type of System Earthing                       Solidly Grounded
 17   Thermal stability                             As per IEC 60099-4
 18   Withstand test voltages value of LA to be protected
 19   a) One Minute Power frequency                 28 kV
 20   b) Lightning Impulse                          75 kV
 21   Nominal Discharge                             10 kA Heavy duty
 22   Nominal Creepage Distance (mm)                31 mm / kV
 23   Type of mounting                              Vertical / Pedestal Mounting
 24   Temperature rise                              As per IEC 60099-4
Equipment- 6.6kV VCB Panel
 1    Rated Voltage                                    6.6kV
 2    Rated Current                                    1250A
 3    Breaking Current                                 25kA
 4    Rated short circuit making current (peak)        62.5KA
 5    Maximum break time                               3 cycles
 6    First – pole – to clear factor                   1.5
 7    Rated Auxiliary supply for spring charge
      motor, lamp & heater circuit.                    230V A.C
                                                  54