ADDA
ADDA
AJ65VBTCU-68ADVN/ADIN
User's Manual
SAFETY PRECAUTIONS
(Read these precautions before using this product.)
Before using this product, please read this manual and the relevant manuals introduced in this manual
carefully and pay full attention to safety to handle the product correctly.
The precautions given in this manual are concerned with this product. Refer to the user’s manual of the
CPU module to use for a description of the programmable controller system safety precautions.
In this manual, the safety precautions are classified into two levels: " ! WARNING" and " ! CAUTION".
Under some circumstances, failure to observe the precautions given under " ! CAUTION" may lead to
serious consequences.
Observe the precautions of both levels because they are important for personal and system safety.
Make sure that the end users read this manual and then keep the manual in a safe place for future
reference.
[Design Precautions]
! WARNING
In the case of a communication failure in the network, data in the master module are held.
Check the communication status information (SB, SW) and configure an interlock circuit in the
sequence program to ensure that the entire system will operate safely.
! CAUTION
Do not install the control lines or communication cables together with the main circuit lines or
power cables.
Keep a distance of 100mm or more between them.
Failure to do so may result in malfunction due to noise.
A-1 A-1
[Installation Precautions]
! CAUTION
Use the programmable controller in an environment that meets the general specifications in the
detailed manual.
Failure to do so may result in electric shock, fire, malfunction, or damage to or deterioration of
the product.
Securely fix the module with a DIN rail or CC-Link connector type metal installation fitting.
Not doing so can cause a drop or malfunction.
Do not directly touch any conductive part of the module.
Doing so can cause malfunction or failure of the module.
[Wiring Precautions]
! CAUTION
Shut off the external power supply for the system in all phases before wiring.
Individually ground the FG terminal of the programmable controller with a ground resistance of
100Ω or less.
Failure to do so may result in malfunction.
Check the rated voltage and pin layout before wiring to the module, and connect the cables
correctly.
Connecting a power supply with a different voltage rating or incorrect wiring may cause a fire or
failure.
Prevent foreign matter such as dust or wire chips from entering the module.
Such foreign matter can cause a fire, failure, or malfunction.
Do not insert the one-touch connector plug for I/O of the one-touch connector type/connector
type compact remote I/O unit into the one-touch connector for analog I/O accidentally.
Doing so can cause the module to be damaged.
Attach an unwired connector plug to an unused one-touch connector for power supply and FG.
Not doing so can cause a failure or malfunction.
Place the cables in a duct or clamp them.
If not, dangling cable may swing or inadvertently be pulled, resulting in damage to the module or
cables or malfunction due to poor contact.
Do not install the control lines or communication cables together with the main circuit lines or
power cables.
Failure to do so may result in malfunction due to noise.
When disconnecting the cable from the module, do not pull the cable by the cable part.
Loosen the screws of connector before disconnecting the cable.
Failure to do so may result in damage to the module or cable or malfunction due to poor contact.
Smoke and fire may occur when an overcurrent flows intermittently for a long period of time. To
avoid this, configure a safety circuit, such as an external fuse, to protect the product.
A-2 A-2
[Starting and Maintenance Precautions]
! CAUTION
Do not touch any pin while power is on. Doing so will cause malfunction.
Shut off the external power supply for the system in all phases before cleaning the module.
Failure to do so may cause the module to fail or malfunction.
Do not disassemble or modify the modules.
Doing so may cause failure, malfunction, injury, or a fire.
Do not drop or apply strong shock to the module. Doing so may damage the module.
Shut off the external power supply for the system in all phases before mounting or removing the
module to or from the panel.
Failure to do so may cause the module to fail or malfunction.
Before handling the module, touch a grounded metal object to discharge the static electricity
from the human body.
Failure to do so may cause the module to fail or malfunction.
[Disposal Precautions]
! CAUTION
When disposing of this product, treat it as industrial waste.
A-3 A-3
CONDITIONS OF USE FOR THE PRODUCT
A-4 A-4
REVISIONS
* The manual number is given on the bottom left of the back cover.
Revision Date * Manual Number Description
Apr., 2003 SH(NA)-080401E-A First Edition
Sep., 2004 SH(NA)-080401E-B Addition
Section 4.8.3, 4.10.1 to 4.10.3
Correction
About Manuals, Section 1.2, 2.3, 3.2, 4.8.2, 4.9.2
Jul., 2005 SH(NA)-080401E-C Correction
SAFETY PRECAUTIONS
Apr., 2007 SH(NA)-080401E-D Correction
Section 4.3, 4.9.2, Appendix 2
Sep., 2010 SH(NA)-080401E-E Addition
CONDITIONS OF USE FOR THE PRODUCT, Section 4.10.1
Correction
SAFETY PRECAUTIONS , Conformation to the EMC Directive and
Low Voltage Instruction, GENERIC TERMS AND ABBREVIATIONS,
Section 3.1, 3.2, 4.8.2, 4.10.1, 5.1, 5.3.3, 5.4.3
Renumbering
Section 4.10.1 to 4.10.3Section 4.10.2 to 4.10.4
Jun., 2012 SH(NA)-080401E-F Correction
ABOUT MANUALS, COMPLIANCE WITH EMC AND LOW
VOLTAGE DIRECTIVES, Section 2.3, 3.1, 3.2, 4.8.1, 4.8.2, 4.9.2,
5.2.2, 5.2.5
Jul., 2022 SH(NA)-080401E-G Correction
Section 2.3, 3.2, 3.6
Jun., 2023 SH(NA)-080401E-H Correction
GENERIC TERMS AND ABBREVIATIONS, Section 3.2, 3.5.2, 4.3,
4.9.2
Dec., 2024 SH(NA)-080401E-I Addition
INFORMATION AND SERVICES, TRADEMARKS
Correction
SAFETY PRECAUTIONS, ABOUT MANUALS, Section 2.2, 3.2,
3.3.5, 3.5.1, 3.6.1, 4.2, 4.3, 4.4, 5.2.1, 5.3.1, 5.4.1, 6.2, 6.4,
Appendix 1, Appendix 2
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual.
2003 MITSUBISHI ELECTRIC CORPORATION
A-5 A-5
INTRODUCTION
CONTENTS
1 OVERVIEW 1- 1 to 1- 3
2 SYSTEM CONFIGURATION 2- 1 to 2- 6
3 SPECIFICATIONS 3- 1 to 3-20
5 PROGRAMMING 5- 1 to 5-33
6 TROUBLESHOOTING 6- 1 to 6- 6
Appendix 1 Comparison, Differences and Compatibility between New and Conventional Models .... APPX- 1
Appendix 2 External dimension diagram ............................................................................................... APPX- 3
A-7 A-7
ABOUT MANUALS
Relevant manuals
A-8 A-8
GENERIC TERMS AND ABBREVIATIONS
Unless otherwise specified, the following generic terms and abbreviations are used in this manual to
describe Type AJ65VBTCU-68ADVN/ADIN analog-digital converter module.
A-9 A-9
Generic Term/Abbreviation Description
Remote input (for CC-Link)
RX Information entered in bit units from the remote station to the master station.
(Expressed as RX for convenience)
Remote output (for CC-Link)
RY Information output in bit units from the master station to the remote station.
(Expressed as RY for convenience)
Remote register (Write area for CC-Link)
RWw Information output in 16-bit units from the master station to the remote device station.
(Expressed as RWw for convenience)
Remote register (Read area for CC-Link)
Information entered in 16-bit units from the remote device station to the master
RWr
station.
(Expressed as RWr for convenience)
A - 10 A - 10
PACKING LIST
A - 11 A - 11
1 OVERVIEW
MELSEC-A
1 OVERVIEW
1 This user's manual explains the specifications, handling, programming methods and
others of Type AJ65VBTCU-68ADVN analog-digital converter module (hereafter
abbreviated to the "AJ65VBTCU-68ADVN") and Type AJ65VBTCU-68ADIN analog-
digital converter module (hereafter abbreviated to the “AJ65VBTCU-68ADIN”) which is
used as a remote device station of a CC-Link system.
In this manual, the AJ65VBTCU-68ADVN and AJ65VBTCU-68ADIN are generically
referred to as the AJ65VBTCU-68ADVN/ADIN.
The AJ65VBTCU-68ADVN/ADIN converts the analog signals (voltage or current input)
from the programmable controller’s external source to a 16-bit encoded binary data
digital value.
• Cyclic transmission
• Expanded cyclic transmission
• Interstation cable length lessening
1-1 1-1
1 OVERVIEW
MELSEC-A
1.2 Features
Connector
1-2 1-2
1 OVERVIEW
MELSEC-A
1-3 1-3
2 SYSTEM CONFIGURATION
MELSEC-A
2 SYSTEM CONFIGURATION
This chapter describes the system configuration for use of the AJ65VBTCU-
68ADVN/ADIN.
CC-Link master/local module (master station) CC-Link master/local module (local station)
AJ65VBTCU-68ADVN/ADIN
(Remote device station) (Remote device station)
3 stations occupied
Object whose
voltage/current
will be detected
2-1 2-1
2 SYSTEM CONFIGURATION
MELSEC-A
CC-Link master/local module (master station) CC-Link master/local module (local station)
AJ65VBTCU-68ADVN/ADIN
(Remote device station)
(Remote device station)
1 station occupied
Object whose
voltage/current
will be detected
2-2 2-2
2 SYSTEM CONFIGURATION
MELSEC-A
(b) For use in the remote net ver. 2 mode or remote net additional
mode
QJ61BT11N
2-3 2-3
2 SYSTEM CONFIGURATION
MELSEC-A
POINT
For use in the remote net ver. 2 mode or remote net additional mode, the master
module of QJ61BT11N and the peripheral software package of GX Developer
Version 8.03D or later are required.
For more information on the applicable modules (CPU modules, network modules)
and applicable software packages, refer to the CC-Link System Master/Local
Module User's Manual (Details) QJ61BT11N.
2-4 2-4
2 SYSTEM CONFIGURATION
MELSEC-A
2-5 2-5
2 SYSTEM CONFIGURATION
MELSEC-A
REMARK
The following table indicates the connectors of this module with which the above
plugs/connectors are compatible.
2-6 2-6
3 SPECIFICATIONS
MELSEC-A
3 SPECIFICATIONS
*1 This indicates the section of the power supply to which the equipment is assumed to be connected between the
public electrical power distribution network and the machinery within premises.
Category II applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage
withstand level for up to the rated voltage of 300V is 2500V.
*2 This index indicates the degree to which conductive material is generated in terms of the environment in which the
equipment is used.
Pollution level 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensing must
be expected occasionally.
*3 Do not use or store the programmable controller under pressure higher than the atmospheric pressure of altitude 0m.
Doing so may cause malfunction. When using the programmable controller under pressure, please consult your
local Mitsubishi representative.
3-1 3-1
3 SPECIFICATIONS
MELSEC-A
3-2 3-2
3 SPECIFICATIONS
MELSEC-A
The I/O characteristics is the slope created by connecting the offset and gain values,
with a straight line when converting the analog signals (voltage or current input) from
an external source of the programmable controller to digital values.
The offset value is an analog input value (voltage or current) at which the digital output
value is 0.
The gain value is an analog input value (voltage or current) at which the digital output
value is 4000.
3-3 3-3
3 SPECIFICATIONS
MELSEC-A
4095
4000
3
0 1
-96
-2000
-4000
-4096
-15 -10 -5 0 5 10 15
Analog input voltage (V)
POINT
(1) Do not input more than ±15V. The element may be damaged.
(2) If the analog input provided corresponds to the digital output value* beyond its
range, the digital output value is fixed to the maximum or minimum.
For 0 to 4000, the digital output value is within the range -96 to 4095.
For -4000 to +4000, the digital output value is within the range -4096 to +4095.
(3) Within the analog input and digital output scopes of each input range, the
maximum resolution and accuracy are within the performance specification
range. Outside those scopes, however, they may not fall within the performance
specification range. (Avoid using the dotted line part in Fig. 3.1.)
(4) Set the offset and gain values of the user range setting within the range
satisfying the following conditions.
(a) Setting range when user range setting 1 is selected: -10 to +10V
(b) Setting range when user range setting 2 is selected: 0 to 5V
(c) (Gain value) > (Offset value)
If you attempt to make setting outside the setting range of (a) or (b), the "RUN"
LED flickers at 0.5s intervals.
Set the values within the setting range.
If you attempt to make setting outside the setting range of (c), the "RUN" LED
flickers at 0.5s intervals.
Make setting again.
3-4 3-4
3 SPECIFICATIONS
MELSEC-A
Analog input
parcitcal value
4095
4000
2
2000
Digital output value
0
-96 4
-2000
-4000
-30 -20 -10 0 10 20 30
Analog input current (mA)
POINT
(1) Do not input more than ±30mA. A breakdown may result due to heat increase.
(2) If the analog input provided corresponds to the digital output value* beyond its
range, the digital output value is fixed to the maximum or minimum.
For 0 to 4000, the digital output value is within the range -96 to 4095.
(3) Within the analog input and digital output scopes of each input range, the
maximum resolution and accuracy are within the performance specification
range. Outside those scopes, however, they may not fall within the performance
specification range. (Avoid using the dotted line part in Fig. 3.2.)
(4) Set the offset and gain values of the user range setting within the range
satisfying the following conditions.
(a) Setting range when user range setting is selected: 0 to 20mA
(b) (Gain value) > (Offset value)
If you attempt to make setting outside the setting range of (a), the "RUN" LED
flickers at 0.5s intervals.
Set the values within the setting range.
If you attempt to make setting outside the setting range of (b), the "RUN" LED
flickers at 0.5s intervals.
Make setting again.
3-5 3-5
3 SPECIFICATIONS
MELSEC-A
3.3.3 Relationship between the offset/gain setting and digital output value
The relationship between the offset/gain setting and digital output value is described.
(1) Resolution
The resolution is obtained by the following formula:
(a) For the AJ65VBTCU-68ADVN:
(Gain value) - (Offset value)
Resolution =
4000
3.3.4 Accuracy
4000
-4000
-10V 0V 10V
Analog input value
3-6 3-6
3 SPECIFICATIONS
MELSEC-A
4000
0
0 20mA
Analog input value
Conversion speed indicates time from channel changing to A/D conversion completion.
Conversion speed per channel of the AJ65VBTCU-68ADVN/ADIN is 1ms.
Due to the data link processing time of the CC-Link system, there is a transmission
delay until the A/D conversion value is read actually.
For the data link processing time, refer to the user's manual of the master module used.
Example1) Ver. 1 remote device station (ver. 1 compatible device station) setting
Data link processing time taken in the asynchronous mode when the
master module is the QJ61BT11 (normal value)
[Calculation expression]
SM+LS×1+remote device station processing time
SM : Scan time of master station sequence program
LS : Link scan time
Remote device station processing time: (Number of channels used+1 )
× 1ms
: Internal processing time of AJ65VBTCU-68ADVN/ADIN
Example2) Ver. 2 remote device station (ver. 2 compatible device station) setting
Data link processing time taken in the asynchronous mode when the
master module is the QJ61BT11N (normal value)
[Calculation expression]
(a) In the case of the remote input (RX), remote register (RWw)
SM + LS × 1 × m + remote device station processing time
(b) In the case of the remote output (RY), remote register (RWr)
SM + LS × 1 × (m + 1) + remote device station processing time
SM : Scan time of master station sequence program
LS : Link scan time
m : Constant 1
Remote device station processing time: (Number of channels used + 1 2)
× 1ms
1: Expanded cyclic setting is quadruple in this module, m = 7.
2: Internal processing time of AJ65VBTCU-68ADVN/ADIN
3-7 3-7
3 SPECIFICATIONS
MELSEC-A
The offset/gain setting can be performed volumeless for each channel, and the I/O
Offset/gain setting Section 4.4
conversion characteristics can be changed.
3-8 3-8
3 SPECIFICATIONS
MELSEC-A
The A/D conversion is performed successively for the analog input, and the converted
digital output values are stored in the remote register.
The processing time to store the digital output value into the remote register after the
sampling processing differs depending on the number of A/D conversion enabled
channels.
[Example] When three channels, channels 1, 2, and 3 are enabled for conversion:
3×1 = 3 (ms)
[Example] When the number of A/D conversion enabled channels is two, and the
set time is 1000 ms:
1000/(2 × 1)=500 times
(2) When the average processing specification is made for the number
of times
The processing time to store the average value (average of number of times) into
the remote register depends on the number of A/D conversion enabled channels.
(Processing time) = (Set number of times) × (Number of A/D conversion enabled channels) × 1 (ms)
[Example] When two channels, channels 1 and 3 are A/D conversion enabled,
and the set number of times is 500:
500 × 2 × 1=1000 (ms)
3-9 3-9
3 SPECIFICATIONS
MELSEC-A
This section describes the assignment and functions of the remote I/O signals.
Remote inputs (RX) mean the input signals from the AJ65VBTCU-68ADVN/ADIN to
the master module, and remote outputs (RY) mean the output signals from the master
module to the AJ65VBTCU-68ADVN/ADIN.
In communications with the master station, the AJ65VBTCU-68ADVN/ADIN uses 32
points of the remote inputs (RX) and 32 points of the remote outputs (RY).
The number of stations occupied by this module differs between ver. 1 remote device
station (ver. 1 compatible device station) setting and ver. 2 remote device station (ver.
2 compatible device station) setting.
3 stations are occupied in the case of ver. 1 remote device station (ver. 1 compatible
device station) setting. The latter 64 points are not used.
1 station is occupied in the case of ver. 2 remote device station (ver. 2 compatible
device station) setting. Expanded cyclic setting is fixed to quadruple and the latter 32
points are not used.
3 - 10 3 - 10
3 SPECIFICATIONS
MELSEC-A
(1) Remote I/O signal list for ver. 1 remote device station (ver. 1
compatible device station) setting
Table 3.4 indicates the assignment and names of the remote I/O signals for ver.
1 remote device station (ver. 1 compatible device station) setting.
Table 3.4 Remote I/O Signal List for Ver. 1 Remote Device Station
(Ver. 1 Compatible Device Station) Setting
Signal direction: AJ65VBTCU-68ADVN/ADIN Master Module Signal direction: Master Module AJ65VBTCU-68ADVN/ADIN
Remote input (RX) Signal name Remote output (RY) Signal name
RXn0 CH.1 A/D conversion completion flag
RXn1 CH.2 A/D conversion completion flag
RXn2 CH.3 A/D conversion completion flag
RXn3 CH.4 A/D conversion completion flag
RXn4 CH.5 A/D conversion completion flag
RXn5 CH.6 A/D conversion completion flag
RXn6 CH.7 A/D conversion completion flag RYn0
RXn7 CH.8 A/D conversion completion flag to Reserved
RXn8 RY(n+1)7
to Reserved
RXnB
RXnC E2PROM write error flag
RXnD
to Reserved
RX(n+1)7
RX(n+1)8 Initial data processing request flag RY(n+1)8 Initial data processing completion flag
RX(n+1)9 Initial data setting completion flag RY(n+1)9 Initial data setting request flag
RX(n+1)A Error status flag RY(n+1)A Error reset request flag
RX(n+1)B Remote READY
RY(n+1)8
RX(n+1)C
to Reserved
to Reserved
RY(n+5)F
RX(n+5)F
POINT
The reserved devices given in Table 3.4 are used by the system and cannot be
used by the user.
If the user has used (turned on/off) any of them, we cannot guarantee the functions
of the AJ65VBTCU-68ADVN/ADIN.
3 - 11 3 - 11
3 SPECIFICATIONS
MELSEC-A
(2) Remote I/O signal list for ver. 2 remote device station (ver. 2
compatible device station) setting
Table 3.5 indicates the assignment and names of the remote I/O signals for ver.
2 remote device station (ver. 2 compatible device station) setting.
Table 3.5 Remote I/O Signal List for Ver. 2 Remote Device Station
(Ver. 2 Compatible Device Station) Setting
Signal direction: AJ65VBTCU-68ADVN/ADIN Master Module Signal direction: Master Module AJ65VBTCU-68ADVN/ADIN
Remote input (RX) Signal name Remote output (RY) Signal name
RXn0 CH.1 A/D conversion completion flag
RXn1 CH.2 A/D conversion completion flag
RXn2 CH.3 A/D conversion completion flag
RXn3 CH.4 A/D conversion completion flag
RXn4 CH.5 A/D conversion completion flag
RXn5 CH.6 A/D conversion completion flag
RXn6 CH.7 A/D conversion completion flag RYn0
RXn7 CH.8 A/D conversion completion flag to Reserved
RXn8 RY(n+1)7
to Reserved
RXnB
RXnC E2PROM write error flag
RXnD
to Reserved
RX(n+1)7
RX(n+1)8 Initial data processing request flag RY(n+1)8 Initial data processing completion flag
RX(n+1)9 Initial data setting completion flag RY(n+1)9 Initial data setting request flag
RX(n+1)A Error status flag RY(n+1)A Error reset request flag
RX(n+1)B Remote READY
RY(n+1)8
RX(n+1)C
to Reserved
to Reserved
RY(n+3)F
RX(n+3)F
POINT
The reserved devices given in Table 3.5 are used by the system and cannot be
used by the user.
If the user has used (turned on/off) any of them, we cannot guarantee the functions
of the AJ65VBTCU-68ADVN/ADIN.
3 - 12 3 - 12
3 SPECIFICATIONS
MELSEC-A
Table 3.6 explains the functions of the remote I/O signals of the AJ65VBTCU-
68ADVN/ADIN.
RX(n+1)8
Initial data processing request flag
RY(n+1)8
Initial data processing completion flag
RX(n+1)9
Initial data processing
RX(n+1)8 Initial data setting completion flag
request flag
RY(n+1)9
Initial data setting request flag
RX(n+1)B
Remote ready
RXn0 to RXn7
CH. A/D conversion completion flag
When the initial data setting request (RY(n+1)9 ON) is made, the flag turns on after the
Initial data setting initial data setting completion is done.
RX(n+1)9
completion flag Also, after the initial data setting is complete, the initial data setting completion flag
turns off when the initial data setting request flag turns off.
3 - 13 3 - 13
3 SPECIFICATIONS
MELSEC-A
RX(n+1)A
Error status flag
RY(n+1)A
RX(n+1)A Error status flag Error reset request flag
RWrn+8
0 Error code 0
Error code
Turns on at the completion of both of the following after power-on: initial data setting,
RX(n+1)B Remote READY A/D conversion of all the channels set to A/D conversion enabled.
(Used for an interlock of read/write from/to the master module.)
Initial data processing Turns on at the completion of initial data processing when initial data processing is
RY(n+1)8
completion flag requested after power-on.
Initial data setting request
RY(n+1)9 Turns on at the time of initial data setting or changing.
flag
When this flag turns on, the error status flag (RX(n+1)A) is reset, but the E2PROM
RY(n+1)A Error reset request flag
write error flag (RXnC) cannot be rest and therefore the error status flag remains on.
3 - 14 3 - 14
3 SPECIFICATIONS
MELSEC-A
(1) Remote register assignment for ver. 1 remote device station (ver. 1
compatible device station) setting
Table 3.7 indicates the remote register assignment for ver. 1 remote device
station (ver. 1 compatible device station) setting.
Table 3.7 Remote Register Assignment for Ver. 1 Remote Device Station (Ver. 1
Compatible Device Station) Setting
Communication direction Address Description Default value Reference section
RWwm+0H A/D conversion enable/prohibit specification 0 Section 3.6.2
RWwm+1H CH.1 to 4 input range setting 0
Section 3.6.3
RWwm+2H CH.5 to 8 input range setting 0
RWwm+3H Average processing specification 0 Section 3.6.4
RWwm+4H CH.1 average time, number of times setting 0
RWwm+5H CH.2 average time, number of times setting 0
Master Remote
RWwm+6H CH.3 average time, number of times setting 0
RWwm+7H CH.4 average time, number of times setting 0
Section 3.6.5
RWwm+8H CH.5 average time, number of times setting 0
RWwm+9H CH.6 average time, number of times setting 0
RWwm+AH CH.7 average time, number of times setting 0
RWwm+BH CH.8 average time, number of times setting 0
RWrn+0H CH.1 digital output value 0
RWrn+1H CH.2 digital output value 0
RWrn+2v CH.3 digital output value 0
RWrn+3H CH.4 digital output value 0
Section 3.6.6
RWrn+4H CH.5 digital output value 0
RWrn+5H CH.6 digital output value 0
Remote Master
RWrn+6H CH.7 digital output value 0
RWrn+7H CH.8 digital output value 0
RWrn+8H Error code 0 Section 3.6.7
RWrn+9H
to Reserved 0 ——
RWrn+BH
POINT
Do not read or write data from or to the reserved area of the remote register. If data
is read or written, we cannot guarantee the functions of the AJ65VBTCU-
68ADVN/ADIN.
3 - 15 3 - 15
3 SPECIFICATIONS
MELSEC-A
(2) Remote register assignment for ver. 2 remote device station (ver. 2
compatible device station) setting
Table 3.8 indicates the remote register assignment for ver. 2 remote device
station (ver. 2 compatible device station) setting.
Table 3.8 Remote Register Assignment for Ver. 2 Remote Device Station
(Ver. 2 Compatible Device Station) Setting
Communication direction Address Description Default value Reference section
RWwm+0H A/D conversion enable/prohibit specification 0 Section 3.6.2
RWwm+1H CH.1 to 4 input range setting 0
Section 3.6.3
RWwm+2H CH.5 to 8 input range setting 0
RWwm+3H Average processing specification 0 Section 3.6.4
RWwm+4H CH.1 average time, number of times setting 0
RWwm+5H CH.2 average time, number of times setting 0
RWwm+6H CH.3 average time, number of times setting 0
Master Remote RWwm+7H CH.4 average time, number of times setting 0
Section 3.6.5
RWwm+8H CH.5 average time, number of times setting 0
RWwm+9H CH.6 average time, number of times setting 0
RWwm+AH CH.7 average time, number of times setting 0
RWwm+BH CH.8 average time, number of times setting 0
RWwm+CH
to Reserved 0 ——
RWwm+FH
RWrn+0H CH.1 digital output value 0
RWrn+1H CH.2 digital output value 0
RWrn+2v CH.3 digital output value 0
RWrn+3H CH.4 digital output value 0
Section 3.6.6
RWrn+4H CH.5 digital output value 0
RWrn+5H CH.6 digital output value 0
Remote Master
RWrn+6H CH.7 digital output value 0
RWrn+7H CH.8 digital output value 0
RWrn+8H Error code 0 Section 3.6.7
RWrn+9H
to Reserved 0 ——
RWrn+FH
POINT
Do not read or write data from or to the reserved area of the remote register. If data
is read or written, we cannot guarantee the functions of the AJ65VBTCU-
68ADVN/ADIN.
3 - 16 3 - 16
3 SPECIFICATIONS
MELSEC-A
(2) By setting the unused channels to conversion prohibit, the sampling cycle can be
shortened.
Example) The sampling cycle when only channels 1 and 3 are set to A/D
conversion enabled:
2 (Number of channels enabled) × 1ms (Conversion speed at one channel) = 2ms
(3) Operation is performed according to the setting made for the leading edges of
initial data setting request flag (RY(n+1)9).
(4) The default setting is A/D conversion disable for all channels.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
CH.8 CH.7 CH.6 CH.5 CH.4 CH.3 CH.2 CH.1
3 - 17 3 - 17
3 SPECIFICATIONS
MELSEC-A
(2) Operation is performed according to the setting made for the leading edges of the
initial data setting request flag (RY(n+1)9).
POINT
If the set value is outside the setting range, error "20 " occurs, the "RUN" LED
flickers at intervals of 0.1s, and all channels do not make A/D conversion.
indicates the channel No. where the error occurred.
3 - 18 3 - 18
3 SPECIFICATIONS
MELSEC-A
(1) Selects between sampling processing and average processing selection and
when average processing is selected, the processing method is specified.
POINT
(1) When performing an average processing specification, the average number of
processing or time must be set.
(2) When the average processing specification is not performed, the sampling
processing is performed regardless of the time/number of times setting.
(1) On each channel specified for average processing, the average time or average
number of times is written to the address corresponding to the channel at the
remote register address RWwm+4H to RWwM+BH.
At power-on, the average time and average number of times are 0.
(3) Operation is performed according to the setting made for the leading edges of the
initial data setting request flag (RY(n+1)9).
POINT
If the set value written is outside the above range, the corresponding channel
results in error "10 , 11 " and performs A/D conversion processing using the
average time/number of times used prior to error occurrence.
indicates the channel No. where the error occurred.
3 - 19 3 - 19
3 SPECIFICATIONS
MELSEC-A
(1) The digital value after the A/D conversion is stored in the remote register address
from RWrn+0H to RWrn+7H for each channel.
Date section
Sign bit
1: Negative
0: Positive
If an error occurs (the RUN LED flickers) when data is written to the AJ65VBTCU-
68ADVN/ADIN, the corresponding error code is stored into the remote register
(address RWrn+8H) of the AJ65VBTCU-68ADVN/ADIN.
Refer to Section 6.1 for details of the error codes.
3 - 20 3 - 20
4 SETUP AND PREPARATION BEFORE OPERATION
MELSEC-A
This section explains the preparatory procedure for operating the AJ65VBTCU-
68ADVN/ADIN.
START
4
No
Make offset/gain setting?
Yes
Start data link.
END
Do not touch the pins while power is on. Doing so can cause a malfunction.
CAUTION
Ensure that no foreign matter such as chips and wire-offcuts enter the module.
Foreign matter can cause a fire, failure or malfunction.
Do not disassemble or modify the module.
Doing so can cause a failure, malfunction, injury or fire.
Do not touch the conductive and electronic parts of the module directly.
Doing so can cause the module to malfunction or fail.
4-1 4-1
4 SETUP AND PREPARATION BEFORE OPERATION
MELSEC-A
4 (1) When using the DIN rail adapter, install the DIN rail by making sure of the
following:
(a) Applicable DIN rail models (conforming to the JIS C 2812)
TH35-7.5Fe
TH35-7.5Al
(2) As the CC-Link connector type metal installation fitting, use the narrow-width type
(width 41)-dedicated fitting.
(a) CC-Link connector type metal installation fitting model
A6PLT-J65V1
(3) Refer to the Master Module user's manual for specification, and manufacturers of
supported cables for the use with AJ65VBTCU-68ADVN/ADIN.
4-2 4-2
4 SETUP AND PREPARATION BEFORE OPERATION
MELSEC-A
AJ65VBTCU-68AD N 1 DA
CON 2 DB
A L
I CONA, B 3 DG
7) N
CON
K 4 NC
B 3) 5 SLD
SEL
C 1 CH1 V+/I+
H POWER
1
SET 2 CH1 V-/I-
RUN CON1
2 1) 3 NC
L RUN
4 SLD
3 L ERR
SW1 1 CH2 V+/I+
4
TEST
5 4 3 2 1 2 CH2 V-/I-
CON2
9) 1 3 NC
2 CONA
5 4 4 SLD
8 2) CONB
OFFSET 1 CH3 V+/I+
6
4321 2 CH3 V-/I-
GAIN CON3
ON
7 CON1 3 NC
5), 6) 4 SLD
8 CON2
MODE 1 CH4 V+/I+
4) CON3
2 CH4 V-/I-
CON
CON4
C P
CON4 3 NC
O
8) W 4 SLD
E CON5
CON R 1 CH5 V+/I+
D
CON6 2 CH5 V-/I-
CON5
CON7 3 NC
4 SLD
10) CON8
1 CH6 V+/I+
5 4 3 21 2 CH6 V-/I-
CON6
CONC 3 NC
4 SLD
COND
1 CH7 V+/I+
A module view 2 CH7 V-/I-
from the top CON7
3 NC
4 SLD
1 CH8 V+/I+
2 CH8 V-/I-
CON8
3 NC
4 SLD
1 FG
2 +24V(UNIT)
CONC, D 3 24G (UNIT)
4 AG
5 FG1
4-3 4-3
4 SETUP AND PREPARATION BEFORE OPERATION
MELSEC-A
Name and
Number Description
appearance
ON : Power supply on
POWER
OFF : Power supply off
On : Normal operation
Flashing: 0.1s intervals : Input range setting error, mode select switch setting error.
This module is used as the Ver.2 remote device station (Ver.2
Normal compatible device station) when the network parameter mode
mode is set to remote network Ver.1 mode.
0.5s intervals : Average value setting (count) time error. Mode select switch
RUN setting is changed after power-on.
Off : 24VDC power supply shutoff or watchdog timer error occurred
On : Indicates that the SELECT/SET switch is in the SET position.
Operation status
1) Flashing : 0.1s intervals : Mode select switch setting error
display LED Test
0.5s intervals : An attempt was made to make setting outside the setting
mode
range at the time of offset/gain setting.
Off : Indicates that the SELECT/SET switch is in the SELECT or center position.
On : Normal communication
L RUN
Off : Communication cutoff (time expiration error)
On : Indicates that transmission speed setting or station number setting is outside the range.
Flicker at fixed intervals : Indicates that transmission speed setting or station number setting
was changed from that at power-on.
L ERR.
Flicker at unfixed intervals : Indicates that you forgot fitting the terminating resistor or the module or
CC-Link dedicated cable is affected by noise.
Off : Indicates normal communications.
Normal
TEST Normally OFF
mode
Offset/gain CH
2) TEST:ON
adjusting LEDs OFFSET Test
The OFFSET/GAIN/ CH LEDs lit change every time the SELECT/SET switch is
GAIN mode
moved to SELECT. (Refer to section 4.5)
SELECT/SET
3) Used to make offset/gain setting in the test mode.
switch
The switch to be used for selecting the mode among Ver. remote device station (Ver. -compatible device
station)/Normal mode/Test mode
AJ65VBTCU-68ADVN AJ65VBTCU-68ADIN
Ver.1 remote 0: Normal mode Ver.1 remote 0: Normal mode
device station 1: Test mode device station 1: Test mode
(Ver.1-compatible (User range setting 1) (Ver.1-compatible (User range setting)
Mode select
device station) 2: Test mode device station)
switch
4) (User range setting 2)
(Factory-set to
"0") Ver.2 remote 3: Normal mode Ver.2 remote 3: Normal mode
device station 4: Test mode device station 4: Test mode
(Ver.2-compatible (User range setting 1) (Ver.2-compatible (User range setting)
device station) 5: Test mode device station)
(User range setting 2)
- 6 to 7: Use prohibited - 2, 5 to 7: Use prohibited
4-4 4-4
4 SETUP AND PREPARATION BEFORE OPERATION
MELSEC-A
Name and
Number Description
appearance
Setting Switches
Set Value Transmission Speed
Transmission 4 2 1
speed setting 0 OFF OFF OFF 156kbps
switches 1 OFF OFF ON 625kbps
2 OFF ON OFF 2.5Mbps
B RATE
5) 3 OFF ON ON 5.0Mbps
1 2 4
Confirm the transmission speed setting switch numbers on the seal located on the side face of the connector
for analog I/O.
Use the switches in STATION NO. "10", "20" and "40" to set the tens of the station number.
Use the switches in STATION NO. "1", "2", "4" and "8" to set the units of the station number.
The switches are all factory-set to OFF.
Always set the station number within the range 1 to 64.
When a number other than 1 to 64 is set, an error occurs and the "L ERR." LED turns on.
Station number You cannot set the same station number to two or more stations.
setting switches Station Tens Units
Number 40 20 10 8 4 2 1
1 OFF OFF OFF OFF OFF OFF ON
1 2 4 8 10 20 40
(Example) To set the station number to "32", set the switches as indicated below.
ON
POINT
After power-on, do not change the mode select switch setting.
If you change it midway during operation, the setting at power-on is valid.
4-5 4-5
4 SETUP AND PREPARATION BEFORE OPERATION
MELSEC-A
4.4 Concept of Mode Select Switch Setting (Selection of Remote Device Station Compatible
Version)
Set the remote device station version with the "mode select switch" of the
AJ65VBTCU-68ADVN/ADIN. Refer to Section 4.3 for details of the mode select switch.
In addition, "mode setting" and "station information (station type)" in the network
parameters of GX Developer must be set simultaneously. For details, refer to (2) in this
section and Chapter 5 Programming.
POINT
In the case of the system where the maximum number of connected stations of the
master station, including the AJ65VBTCU-68ADVN/ADIN that occupies 3 stations,
does not exceed 64 stations, set and use the ver. 1 remote device station (ver. 1
compatible device station). It is not particularly necessary to set and use the ver. 2
remote device station (ver. 2 compatible device station).
4-6 4-6
4 SETUP AND PREPARATION BEFORE OPERATION
MELSEC-A
POINT
For use in the remote net ver. 2 mode or remote net additional mode, the master
module of QJ61BT11N and the peripheral software package of GX Developer
Version 8.03D or later are required.
For more information on the applicable modules (CPU modules, network modules)
and applicable software packages, refer to the CC-Link System Master/Local
Module User's Manual (Details) QJ61BT11N.
4-7 4-7
4 SETUP AND PREPARATION BEFORE OPERATION
MELSEC-A
When changing the I/O conversion characteristics, follow the procedure below.
If the "RUN" LED is not lit, E2PROM may have failed. For details, refer to Section 3.5.2.
4-8 4-8
4 SETUP AND PREPARATION BEFORE OPERATION
MELSEC-A
POINT
(1) Set the offset and gain values in the actual usage state.
(2) The offset and gain values are stored on E2PROM in the AJ65VBTCU-
68ADVN/ADIN and are not cleared at power-off.
(3) Make offset/gain setting within the range indicated in POINT of Section 3.3.1
and Section 3.3.2. If setting is made outside this range, the maximum
resolution/accuracy may not fall within the performance specifications range.
(4) When making offset/gain setting (in the test mode), set any of the following test
modes with the mode select switch.
AJ65VBTCU-68ADVN (Ver. 1 remote device station): 1, 2
AJ65VBTCU-68ADVN (Ver. 2 remote device station): 4, 5
AJ65VBTCU-68ADIN (Ver. 1 remote device station): 1
AJ65VBTCU-68ADIN (Ver. 2 remote device station): 4
The user range settings 1 selected with the mode select switch set to 1 and 4
are the same. The setting of the user range setting 1 can be changed by setting
the mode select switch to either 1 or 4. This also applies to the user range
settings 2 selected with the mode select switch set to 2 and 5.
If the switch has been set to any unusable number, an error occurs and the
"RUN" LED flickers at intervals of 0.1s.
(5) When the grounding indicated in Section 4.8.2 *5 is changed (not performed
perform, or performed to removed), repeat the offset/gain setting from the start.
4-9 4-9
4 SETUP AND PREPARATION BEFORE OPERATION
MELSEC-A
Ceilling installation
DIN rail
Front installation
Flat installation
4 - 10 4 - 10
4 SETUP AND PREPARATION BEFORE OPERATION
MELSEC-A
This section explains the wiring of the CC-Link dedicated cable used for connection of
the AJ65VBTCU-68ADVN/ADIN and master module.
4 - 11 4 - 11
4 SETUP AND PREPARATION BEFORE OPERATION
MELSEC-A
4 - 12 4 - 12
4 SETUP AND PREPARATION BEFORE OPERATION
MELSEC-A
POINT
• On this unit, use the Ver. 1.10-compatible CC-Link dedicated cable (FANC-
110SBH, CS-110, FA-CBL200PSBH).
You cannot use the Ver. 1.10-compatible CC-Link dedicated cables of other than
the above types, CC-Link dedicated cables and CC-Link dedicated, high-
performance cables.
• The shield cable of the CC-Link dedicated cable should be connected to "SLD" in
each module, and both ends should be grounded through "FG".
SLD and FG are connected inside the module.
The following shows how to connect the one-touch connectors and online connectors.
POINT
To connect or remove a one-touch connector to/from an online connector, refer to
the manual included with the online connector.
4 - 13 4 - 13
4 SETUP AND PREPARATION BEFORE OPERATION
MELSEC-A
4.9 Wiring
This section provides the instructions for wiring the AJ65VBTCU-68ADVN/ADIN and its
wiring with external equipment.
(2) Do not bundle or place with load carrying wires other than the main circuit line,
high voltage line or programmable controller. Noises, surges, or conductivity may
affect the system.
(3) Place a one-point grounding on the programmable controller side for the shielded
line or shielded cable. However, depending on the external noise conditions, it
may be better have a grounding externally.
(4) Smoke and fire may occur when an overcurrent flows intermittently for a long
period of time. To avoid this, configure a safety circuit, such as an external fuse, to
protect the product.
(1) AJ65VBTCU-68ADVN
CON8 CH.8
500k
1 CH.8 V+
2 CH.8 V- 500k
3 NC
4 SLD
1 Shield
AG
3
FG1
4 - 14 4 - 14
4 SETUP AND PREPARATION BEFORE OPERATION
MELSEC-A
(2) AJ65VBTCU-68ADIN
2
CON8 CH.8
500k
1 CH.8 I+
2 CH.8 I- 250 500k
3 NC
4 SLD
1 Shield
AG
3
FG1
POINT
• A/D conversion needs to be powered on 30 mintes prior to operation for
compliance to the specification (sccuracy).
• Do not insert the one-touch connector plug for I/O of the one-touch connector
type/connector type compact remote I/O unit into the one-touch connector for
analog I/O accidentally.
Doing so can cause the module to be damaged.
• In an unused channel, if terminals remain open, an erratic digital value may be
output.
To prevent this, take any of the following measures.
1. Select Prohibit in the A/D conversion enable/prohibit setting for the unused
channel.
Note that changing the setting from Enable to Prohibit will reduce the
sampling cycle.
2. Short-circuit the input terminals (terminal V+ and V-) of the unused channel.
3. Connect the AG terminal to the GND terminal of the external device.
4 - 15 4 - 15
4 SETUP AND PREPARATION BEFORE OPERATION
MELSEC-A
This section describes the way to wire the one-touch connector plug.
Refer to section 2.3 for more information on the types and specifications of the one-
touch connector plugs which conform to the AJ65VBTCU-68ADVN/ADIN.
4.10.1 Precautions for the transition wiring of the one-touch connector for power supply and
FG
When the power supply is connected in the transition wiring with the one-touch
connector for power supply and FG, a current flows in the inside of the module. At the
transition wiring, the maximum rated current must be lower than the following values.
Smoke and fire may occur when an overcurrent at the rated value or higher flows
intermittently for a long period of time. To avoid this, configure a safety circuit, such as
an external fuse, to protect the product.
Depending on the operation characteristics of the fuse etc., a current which exceeds
considerably the rating may flow. Therefore, in order to avoid the damage on the
module, make a selection with enough safety allowance, considering the following
maximum rated current.
No. Power supply port name Power supply port Maximum rated current
One-touch connector for power supply and FG (CONC-2, 3
1) Module power supply (IN) 7A*1
pin)
4 - 16 4 - 16
4 SETUP AND PREPARATION BEFORE OPERATION
MELSEC-A
System example
4 - 17 4 - 17
4 SETUP AND PREPARATION BEFORE OPERATION
MELSEC-A
The following are the wiring procedures for the one-touch connector.
Note: Do not push the plug cover into the plug body.
Once pressed, the plug cannot be used any more.
Metal contact
SLD
Termination
using soldering One-touch connector
plug for analog I/O
Connect the applicable
cable ( 1).
V+
V-
SLD
Termination using One-touch connector
crimping sleeves
plug for analog I/O
Example: Butt joint
Connect the applicable
cable ( 1).
4 - 18 4 - 18
4 SETUP AND PREPARATION BEFORE OPERATION
MELSEC-A
4 3 2 1
3) Insert the cable.
Lift the end of the plug cover and insert the cable until it almost
reaches the plug body (within 1mm from the other end of the
plug cover).
Insufficient cable insertion may cause improper press fitting.
Note: When inserting the cable, prevent the cable from sticking
out from the plug cover end.
Signal name
V+ / I+
V- / I-
NC
SLD
ss
r le
mmo
1
Metal contacts
4 - 19 4 - 19
4 SETUP AND PREPARATION BEFORE OPERATION
MELSEC-A
[Correct example] 7) Check the press-fit condition (viewing from the wiring side).
Viewing from the wiring side, check that the plug surface is
flush with the plug cover.
Do not allow the plug cover to protrude from the plug surface.
[Correct example] 8) Check the press-fit condition (viewing from the top).
Viewing from the top, check that there is no clearance between
the plug body and plug cover.
Note: Clearance may occur between the plug body and plug
cover when the latches do not engage securely as shown
in [Wrong example].
[Wrong example] Press the plug cover firmly with pliers until it looks like
[Correct example] condition illustrated on the left.
Latches
Latch
Clearance
(Wiring completed)
4 - 20 4 - 20
4 SETUP AND PREPARATION BEFORE OPERATION
MELSEC-A
This section provides the wiring procedures of the one-touch connector for
communication.
Plug body
Plug cover 1) Check the connector.
Check that the plug cover is attached to the plug body.
Note: Do not push the plug cover into the plug body.
Once pressed, the plug cannot be used any more.
Metal contact
Signal name
DA (Blue)
DB (White)
DG (Yellow)
SLD NC
Metal contacts
Pliers
6) Press both ends of the plug cover
Latches
After pressing the center part of the plug cover, press both ends
of the plug cover where latches are located.
Verify that the latches engage with the plug body.
[Correct example] 7) Check the press-fit condition (viewing from the wiring side).
Viewing from the wiring side, check that the plug surface is
flash with the plug cover.
0.2mm or less
The difference between the plug cover and the plug surface
must be 0.2mm or less.
[Correct example] 8) Check the press-fit condition (viewing from the top).
Viewing from the top, check that there is no clearance between
the plug body and plug cover.
Note: Clearance may occur between the plug body and plug
cover when the latches do not engage securely as shown
in [Wrong example].
Press the plug cover firmly with pliers until it looks like
[Wrong example]
[Correct example] condition illustrated on the left.
Latches
Latch
Clearance
(Wiring completed)
4 - 22 4 - 22
4 SETUP AND PREPARATION BEFORE OPERATION
MELSEC-A
4.10.4 Wiring procedures for the one-touch connector for power supply and FG
The following are the wiring procedures for the one-touch connector used for power
supply and FG.
Note: Do not push the plug cover into the plug body.
Once pressed, the plug cannot be used any more.
Metal contact
Signal name
FG
FG1 +24V (UNIT)
AG 24G(UNIT)
Metal contacts
For the one-touch connector for power supply and FG, use
adjustable pliers so that their jaws can be widely opened.
4 - 23 4 - 23
4 SETUP AND PREPARATION BEFORE OPERATION
MELSEC-A
[Correct example] 6) Check the press-fit condition (viewing from the wiring side).
Viewing from the wiring side, check that the plug surface is
flush with the plug cover.
0.2mm or less
Set the plug cover so that it protrudes 0.2mm or less from the
plug surface.
[Correct example] 7) Check the press-fit condition (viewing from the top).
Viewing from the top, check that there is no clearance between
the plug body and plug cover.
Note: Clearance may occur between the plug body and plug
cover when the latches do not engage securely as shown
in [Wrong example].
Press the plug cover firmly with pliers until it looks like
[Wrong example]
[Correct example] condition illustrated on the left.
Latches
Latch
Clearance
(Wiring completed)
4 - 24 4 - 24
4 SETUP AND PREPARATION BEFORE OPERATION
MELSEC-A
There are no special inspection items for the AJ65VBTCU-68ADVN/ADIN module, but
follow the inspections items describes in the programmable controller CPU User's
Manual so that the system can always be used in the best condition.
4 - 25 4 - 25
5 PROGRAMMING
MELSEC-A
5 PROGRAMMING
The programming procedure, basic read/write programs, and program examples for
the AJ65VBTCU-68ADVN/ADIN are described.
When utilizing the program example introduced in this chapter for an actual system,
fully verify that there are no problems in controllability in the target system.
Refer to the user's manual of the master module used for the master module, to
Section 3.6 for the remote registers, and to the AnSHCPU/AnACPU/AnUCPU/QCPU-A
(A mode) Programming Manual (Dedicated Instructions) for details of the dedicated
instructions.
START
No
Perform average processing?
Initial settings
Yes
END
When using the QCPU (Q mode), you can use the remote device station
initialization procedure registration function to make settings. When using the ACPU,
QCPU (A mode) or QnACPU, use the sequence program to make settings.
5-1 5-1
5 PROGRAMMING
MELSEC-A
The program examples in this section are created under the following conditions.
(1) System configuration
Programmable controller
CPU AJ65VBTCU-68ADVN
Master station (Station number 1)
(X0 to X1F/Y0 to Y1F)
I/O (Input 64 points)
(X20 to X5F)
I/O (Output 64 points)
(Y60 to Y9F)
In the program example (refer to Section 5.2.4) that uses the RRPA instruction (automatic refresh
parameter setting) with the ACPU/QCPU (A mode), RWr0 to RWr8 are assigned to D456 to D464.
5-2 5-2
5 PROGRAMMING
MELSEC-A
POINT
Some CPU modules may not accept the devices used in the program example in
this chapter. For the setting ranges of the devices, refer to the user's manual of the
CPU module used. For the A1SCPU, for example, devices X100, Y100 and later
are unusable. Use such devices as B and M.
5-3 5-3
5 PROGRAMMING
MELSEC-A
The program examples in this section are created under the following conditions.
GX Developer is used to set the network and automatic refresh parameters.
Using the remote device station initialization procedure registration function facilitates
initial settings.
5-4 5-4
5 PROGRAMMING
MELSEC-A
POINT
For the case where the remote device station initialization procedure registration
function is not used but a sequence program is used to make setting, refer to the
user's manual of the used master module.
5-5 5-5
5 PROGRAMMING
MELSEC-A
AJ65VBTCU-68ADVN
data link normal
AJ65VBTCU-68ADVN
data link abnormal
1, 2
1) Initialization procedure registration Turns off initialization
procedure registration
directive.
Turns on initialization
procedure registration
directive.
3
2) Changing of
C ƒ
ƒ
initial settings
j V
ƒ ƒ ‹ƒ Ý è ’ •Ï X A/D conversion enable/
Initial setting change
prohibit specification
(RWw0)
CH.1 to CH.4 input
range setting (RWw1)
Average processing
specification (RWw3)
CH.2 average time,
number of times setting
(RWw5)
Turns on initial data setting
request flag (RY19).
Turns off initial data setting
request flag (RY19).
Read of digital output values
Reads CH.1 digital
output value (RWr0).
5-6 5-6
5 PROGRAMMING
MELSEC-A
[System configuration]
[Corrected program]
Insert the remote READY and initial data processing request flags for all the
stations, to which the remote device station initialization procedure
registration has been made, into the program.
5-7 5-7
5 PROGRAMMING
MELSEC-A
[System configuration]
[Corrected program]
5-8 5-8
5 PROGRAMMING
MELSEC-A
(2) When using the program enclosed by the dotted line 1) in combination with
other remote device stations, correct the program as shown below.
[System configuration]
[Corrected program]
Note that the master module can register the initialization procedure of only
the specified station out of the multiple remote device stations.
The master module supporting this function is the QJ61BT11N which serial
No’s first 5 digits is 08032 or later.
For details, refer to the CC-Link System Master/Local Module User’s Manual.
*2 Before the communication program is executed with remote device stations, the
program enclosed by the dotted line 1) enables the initial setting by using the SB0D
(remote device station initialization procedure registration instruction) and SB5F
(completion status of remote device station initialization procedure). Initialization
processing can’t be made only by the parameter setting of GX Developer.
*3 The program enclosed by the dotted line 2) is necessary only when the initial
settings are changed.
5-9 5-9
5 PROGRAMMING
MELSEC-A
5 - 10 5 - 10
5 PROGRAMMING
MELSEC-A
AJ65VBTCU-68ADVN data
link normal
AJ65VBTCU-68ADVN data
link abnormal
Initial settings
A/D conversion enable/
prohibit specification
(RWw0)
CH.1 to CH.4 input
range setting (RWw1)
Average processing
specification (RWw3)
CH.2 average time,
number of times setting
(RWw5)
Turns on initial data
processing completion flag
(RY18).
Turns on initial data
setting request flag
(RY19).
Changing of initial settings
Initial setting change A/D conversion enable/
prohibit specification
(RWw0)
CH.1 to CH.4 input
range setting (RWw1)
Average processing
specification (RWw3)
CH.2 average time,
number of times setting
(RWw5)
Turns on initial data setting
request flag (RY19).
Processing at initial settings
Turns off initial data
processing completion flag
(RY18).
Turns off initial data setting
request flag (RY19).
Read of digital output values
Reads CH.1 digital
output value (RWr0).
Reads CH.2 digital
output value (RWr1).
Processing at error occurrence
The program enclosed by the dotted line is necessary only when the initial settings are changed.
5 - 11 5 - 11
5 PROGRAMMING
MELSEC-A
5.2.4 Program Example for Use of the ACPU/QCPU (A mode) (dedicated instructions)
A sequence program is used to set the network and automatic refresh parameters.
Sets "X".
Sets X400.
Sets 32 points.
Sets "Y".
Sets Y400.
Sets 32 points.
Sets "D".
Sets D200.
5 - 12 5 - 12
5 PROGRAMMING
MELSEC-A
Sets "B".
Sets B0.
Sets "W".
Sets W0.
Dedicated instruction
(RRPA)
Starting I/O number of
master module
Parameter storage
starting device
AJ65VBTCU-68ADVN
data link normal
AJ65VBTCU-68ADVN
data link abnormal
Initial settings
A/D conversion enable/
prohibit specification
(RWw0)
CH.1 to CH.4 input
range setting (RWw1)
Average processing
specification (RWw3)
CH.2 average time,
number of times setting
(RWw5)
Turns on initial data
processing completion
flag (RY18).
Turns on initial data setting
request flag (RY19).
5 - 13 5 - 13
5 PROGRAMMING
MELSEC-A
Error reset
Turns on error reset
request flag (RY1A).
Turns off error reset
request flag (RY1A).
The program enclosed by the dotted line is necessary only when the initial settings are changed.
5 - 14 5 - 14
5 PROGRAMMING
MELSEC-A
5.2.5 Program Example for Use of the ACPU/QCPU (A mode) (FROM/TO instructions)
5 - 15 5 - 15
5 PROGRAMMING
MELSEC-A
5 - 16 5 - 16
5 PROGRAMMING
MELSEC-A
The program examples in this section are created under the following conditions.
(1) System configuration
5 - 17 5 - 17
5 PROGRAMMING
MELSEC-A
5 - 18 5 - 18
5 PROGRAMMING
MELSEC-A
POINT
When using the AJ65VBTCU-68ADVN as the ver. 2 remote device station in the
normal mode, set the mode select switch to "3".
5 - 19 5 - 19
5 PROGRAMMING
MELSEC-A
The network parameters and automatic refresh parameters are set using GX
Developer.
Use of the remote device station initialization procedure registration function makes
initial setting easy.
5 - 20 5 - 20
5 PROGRAMMING
MELSEC-A
When the initial data processing request flag (RX18) turns ON and Remote
device station initialization procedure registration (SB0D) is set, the
following data are registered to the AJ65VBTCU-68ADI.
Procedure Execution Condition in AJ65VBTCU-68ADI Execution Data
A/D conversion enable/prohibit specification: Channel 1, 2: Enable
(RWw0 :0003H)
CH.1 to CH.4 input range setting : channel 1: 4 to 20mA
: channel 2: user range setting
(RWw1: 20H)
Average processing specification : channel 1: sampling processing
Initial data processing request flag (RX18) turns ON : Channel 2: Average processing, number
of times averaging
(RWw3: 200H)
CH. 2 average time, number of times setting: Channel 2: 16 times
(RWw5: 10H)
Initial data processing completion flag (RY18) is turned ON.
Initial data processing request flag (RY19) is turned ON.
Initial data processing request flag (RX18) turns OFF Initial data processing completion flag (RY18) is turned OFF.
Initial data setting completion flag (RX19) turns ON Initial data setting request flag (RY19) is turned OFF.
5 - 21 5 - 21
5 PROGRAMMING
MELSEC-A
When the initial data processing request flag (RX18) turns ON and Remote
device station initialization procedure registration (SB0D) is set, the
following data are registered to the AJ65VBTCU-68ADVN.
Procedure Execution Condition in AJ65VBTCU-68ADVN Execution Data
A/D conversion enable/prohibit specification: Channel 1, 2: Enable
(RWw0 :0003H)
CH. 1 to CH. 4 input range setting : Channel 1: 0 to 5V
: Channel 2: User range setting 1
(RWw1: 31H)
Average processing specification : Channel 1: Sampling processing
Initial data processing request flag (RX18) turns ON : Channel 2: Average processing, number
of times averaging
(RWw3: 200H)
CH. 2 average time, number of times setting: Channel 2: 16 times
(RWw5: 10H)
Initial data processing completion flag (RY18) is turned ON.
Initial data setting request flag (RY19) is turned ON.
Initial data processing request flag (RX18) turns OFF Initial data processing completion flag (RY18) is turned OFF.
Initial data setting completion flag (RX19) turns ON Initial data setting request flag (RY19) is turned OFF.
POINT
For the case where the remote device station initialization procedure registration
function is not used but a sequence program is used to make setting, refer to the
user's manual of the used master module.
5 - 22 5 - 22
5 PROGRAMMING
MELSEC-A
5 - 23 5 - 23
5 PROGRAMMING
MELSEC-A
5 - 24 5 - 24
5 PROGRAMMING
MELSEC-A
The program examples in this section are created under the following conditions.
(1) System configuration
Ver. 2 compatible
X150F to X1500 RX0F to RX00
X151F to X1510 RX1F to RX10
X152F to X1520
X153F to X1530
5 - 25 5 - 25
5 PROGRAMMING
MELSEC-A
5 - 26 5 - 26
5 PROGRAMMING
MELSEC-A
POINT
When using the AJ65VBTCU-68ADVN as the ver. 2 remote device station in the
normal mode, set the mode select switch to "3".
5 - 27 5 - 27
5 PROGRAMMING
MELSEC-A
The network parameters and automatic refresh parameters are set using GX
Developer.
Use of the remote device station initialization procedure registration function makes
initial setting easy.
5 - 28 5 - 28
5 PROGRAMMING
MELSEC-A
When the initial data processing request flag (RX18) turns ON and Remote
device station initialization procedure registration (SB0D) is set, the
following data are registered to the AJ65VBTCU-68ADI.
Procedure Execution Condition in AJ65VBTCU-68ADI Execution Data
A/D conversion enable/prohibit specification: Channel 1, 2: Enable
(RWw0 :0003H)
CH.1 to CH.4 input range setting : channel 1: 4 to 20mA
: channel 2: user range setting
(RWw1: 20H)
Average processing specification : channel 1: sampling processing
Initial data processing request flag (RX18) turns ON : Channel 2: Average processing, number
of times averaging
(RWw3: 200H)
CH. 2 average time, number of times setting: Channel 2: 16 times
(RWw5: 10H)
Initial data processing completion flag (RY18) is turned ON.
Initial data processing request flag (RY19) is turned ON.
Initial data processing request flag (RX18) turns OFF Initial data processing completion flag (RY18) is turned OFF.
Initial data setting completion flag (RX19) turns ON Initial data setting request flag (RY19) is turned OFF.
5 - 29 5 - 29
5 PROGRAMMING
MELSEC-A
When the initial data processing request flag (RX18) turns ON and Remote
device station initialization procedure registration (SB0D) is set, the
following data are registered to the AJ65VBTCU-68ADVN.
Procedure Execution Condition in AJ65VBTCU-68ADVN Execution Data
A/D conversion enable/prohibit specification: Channel 1, 2: Enable
(RWw0 :0003H)
CH. 1 to CH. 4 input range setting : Channel 1: 0 to 5V
: Channel 2: User range setting 1
(RWw1: 31H)
Average processing specification : Channel 1: Sampling processing
Initial data processing request flag (RX18) turns ON : Channel 2: Average processing, number
of times averaging
(RWw3: 200H)
CH. 2 average time, number of times setting: Channel 2: 16 times
(RWw5: 10H)
Initial data processing completion flag (RY18) is turned ON.
Initial data setting request flag (RY19) is turned ON.
Initial data processing request flag (RX18) turns OFF Initial data processing completion flag (RY18) is turned OFF.
Initial data setting completion flag (RX19) turns ON Initial data setting request flag (RY19) is turned OFF.
POINT
For the case where the remote device station initialization procedure registration
function is not used but a sequence program is used to make setting, refer to the
user's manual of the used master module.
5 - 30 5 - 30
5 PROGRAMMING
MELSEC-A
5 - 31 5 - 31
5 PROGRAMMING
MELSEC-A
5 - 32 5 - 32
5 PROGRAMMING
MELSEC-A
MEMO
5 - 33 5 - 33
6 TROUBLESHOOTING
MELSEC-A
6 TROUBLESHOOTING
The details of the errors which may occur when using the AJ65VBTCU-68ADVN/ADIN
and troubleshooting are described.
(1) If the average time/number of times setting error occurs, the "RUN" LED flickers at 6
intervals of 0.5s and A/D conversion processing is performed with the average
time or number of times used prior to error occurrence.
If the input range setting error occurs, the "RUN" LED flickers at intervals of 0.1s
and A/D conversion processing is not performed on all channels.
(2) If two or more errors occurred, the error code of the first error is stored and the
other errors are not stored.
(3) To reset the error code, turn on the error reset request flag RY(n+1)A.
6-1 6-1
6 TROUBLESHOOTING
MELSEC-A
This section explains how to check errors using the LED indications of the
AJ65VBTCU-68ADVN/ADIN.
Refer to the programmable controller CPU and master module user's manual for
issues regarding the programmable controller CPU and master module.
6-2 6-2
6 TROUBLESHOOTING
MELSEC-A
(5) When the AJ65VBTCU-68ADVN/ADIN "L ERR." LED flickers at fixed intervals
Check item Corrective action
Has the station number or transmission speed
After correcting the setting switch setting, switch
setting switch position been changed during normal
power on again.
operation?
If the "L ERR." LED has begun flickering though
Is the station number or transmission speed setting switch setting change was not made during
switch faulty? operation, the possible cause is a hardware fault.
Contact your nearest Mitsubishi representative.
(6) When the AJ65VBTCU-68ADVN/ADIN "L ERR." LED flickers at unfixed intervals
Check item Corrective action
Check whether the terminating resistor is fitted. If it
Have you forgotten fitting the terminating resistor? is not connected, connect it and switch power on
again.
Earth both ends of the shield wire of the CC-Link
dedicated cable to the protective earth conductor
Is the module or CC-Link dedicated cable affected via SLD and FG of the corresponding module.
by noise? Earth the FG terminal of the module without fail.
When carrying out wiring in piping, earth the pipe
without fail.
6-3 6-3
6 TROUBLESHOOTING
MELSEC-A
6-4 6-4
6 TROUBLESHOOTING
MELSEC-A
6.4 Troubleshooting for the Case where the "ERR." LED of the Master Station Flickers
6-5 6-5
6 TROUBLESHOOTING
MELSEC-A
1 2 3
N
Is the "L RUN" LED lit?
Y Are the
station number N
setting switches properly
(not overlapping with
other stations)?
Set the station number
setting switches properly
Y
Y
Set the correct transmission speed
Is the communication N
cable wired properlly ?
*1
Wire the communication
Y cable properly
Are the
station number N
setting switches properly
(not overlapping with
other stations)?
End
*1 Check for a short, reversed connection, wire breakage, terminal resistor, FG connection,
overall distance and station-to-station distance.
6-6 6-6
APPENDICES
MELSEC-A
APPENDICES
APPX - 1 APPX - 1
APPENDICES
MELSEC-A
Set the mode select switch of the module to the ver. 1 remote device
station and use the same station number.
POINT
To handle the AJ65VBTCU-68ADVN/ADIN according to the system, the mode
select switch of the module must be set, and at the same time, "mode setting" and
"station information (station type)" in the network parameters of GX Developer must
also be set.
Set the network parameters of GX Developer according to the system.
APPX - 2 APPX - 2
APPENDICES
MELSEC-A
Unit : mm
APPX - 3 APPX - 3
INDEX
I
[A] [G]
A/D conversion completion flag .................... 3-13 Gain value ........................................................ 3-3
A/D conversion enable/prohibit specification General specification ....................................... 3-1
....................................................................... 3-17 GX Developer Version 8.03D ................... 2-4,4-7
Absolute maximum input................................. 3-2
Accuracy .................................................... 3-2,3-6 [I]
Analog input..................................................... 3-2 I/O Conversion Characteristics........................ 3-3
Analog input points .......................................... 3-2 Initial data processing completion flag .......... 3-14
Applicable master modules ............................. 2-3 Initial data processing request flag ................ 3-13
Average processing ........................................ 3-9 Initial data setting completion flag ................. 3-13
Average processing specification ................. 3-19 Initial data setting request flag ....................... 3-14
Average time/number of times setting .......... 3-19 Input range changing function ......................... 3-8
Input range setting ......................................... 3-18
[C]
CC-Link dedicated cable ............................... 4-11 [M]
CC-Link dedicated instruction ......................... 2-4 Maintenance and inspection.......................... 4-25
Comparison, differences and compatibility Maximum resolution.................................. 3-2,3-6
between new and conventional models Mode select switch .......................4-1,4-4,4-6,4-7
..................................................................APPX-1 Mode setting........................................ 2-3,4-6,4-7
Conversion speed ........................................... 3-7
Current consumption ....................................... 3-2 [N]
Current input characteristics ........................... 3-5 Name of each part ........................................... 4-3
Cyclic transmission.......................................... 1-1 Number of occupied stations ........................... 3-2
[D] [O]
Data link cable wiring .................................... 4-11 Offset value ...................................................... 3-3
Digital output.................................................... 3-2 Offset/gain adjusting LED ................................ 4-4
Digital output value ........................................ 3-20 Offset/Gain Setting........................................... 4-8
DIN rail .................................................3-2,4-2,4-5 One-touch connector for analog I/O ................ 4-5
One-touch connector for communication ........ 4-5
[E] One-touch connector for power supply and FG
E2PROM write error flag ............................... 3-13 .......................................................................... 3-2
Error code ........................................................ 6-1 Operation status display LED .......................... 4-4
Error reset request flag ................................. 3-14
Error status flag ............................................. 3-14 [P]
Expanded cyclic transmission......................... 1-1 Parts sold separately ....................................... 2-5
External dimension diagram ....................APPX-3 Performance specification ............................... 3-2
External power supply ..................................... 3-2 Plug for one-touch connector .......................... 2-5
Pre-Operation procedure ................................. 4-1
[F] Precautions when handling ............................. 4-1
Facing direction of the module installation ... 4-10 Program example for use of the ACPU/QCPU
Function list ..................................................... 3-8 (A mode) (dedicated instructions) ................. 5-12
INDEX - 1 INDEX - 1
Program example for use of the ACPU/QCPU
(A mode) (FROM/TO instructions)................ 5-15
Program example for use of the QCPU (Q mode) I
(when remote net ver. 1 mode is used) .......... 5-4
Program example for use of the QnACPU ... 5-10
Programming procedure ................................. 5-1
[R]
Remote device station.................. 2-1,2-2,2-3,3-2
Remote I/O signal list .................................... 3-10
Remote net additional mode
.............................................. 1-3,2-2,2-3,4-7,5-25
Remote net ver. 1 mode ........ 1-3,2-1,2-3,4-7,5-2
Remote net ver. 2 mode ...... 1-3,2-2,2-3,4-7,5-17
Remote READY ............................................ 3-14
Remote register allocation ............................ 3-15
Resolution ........................................................ 3-6
[S]
Sampling processing ....................................... 3-9
SELECT/SET switch ....................................... 4-4
Station information ..............................2-3,4-6,4-7
Station number setting switch ......................... 4-5
[T]
Troubleshooting............................................... 6-1
Troubleshooting for the case where the
"ERR."LED of the master station flickers ....... 6-5
[U]
User range setting ...............................3-4,3-5,4-4
[V]
Ver. 1 remote device station
....................................... 2-3,3-2,3-11,4-4,4-6,4-8
Ver. 2 remote device station
....................................... 2-3,3-2,3-12,4-4,4-6,4-8
Voltage input characteristics ........................... 3-4
[W]
Weight .............................................................. 3-2
Wiring ............................................................. 4-14
Wiring of module with external equipment ... 4-14
INDEX - 2 INDEX - 2
MEMO
INDEX - 3 INDEX - 3
WARRANTY
Please confirm the following product warranty details before using this product.
1. Gratis Warranty Term and Gratis Warranty Range
If any faults or defects (hereinafter "Failure") found to be the responsibility of Mitsubishi occurs during use of the product
within the gratis warranty term, the product shall be repaired at no cost via the sales representative or Mitsubishi Service
Company.
However, if repairs are required onsite at domestic or overseas location, expenses to send an engineer will be solely at
the customer's discretion. Mitsubishi shall not be held responsible for any re-commissioning, maintenance, or testing
on-site that involves replacement of the failed module.
[Gratis Warranty Term]
The gratis warranty term of the product shall be for one year after the date of purchase or delivery to a designated place.
Note that after manufacture and shipment from Mitsubishi, the maximum distribution period shall be six (6) months, and
the longest gratis warranty term after manufacturing shall be eighteen (18) months. The gratis warranty term of repair
parts shall not exceed the gratis warranty term before repairs.
[Gratis Warranty Range]
(1) The range shall be limited to normal use within the usage state, usage methods and usage environment, etc., which
follow the conditions and precautions, etc., given in the instruction manual, user's manual and caution labels on the
product.
(2) Even within the gratis warranty term, repairs shall be charged for in the following cases.
1. Failure occurring from inappropriate storage or handling, carelessness or negligence by the user. Failure caused
by the user's hardware or software design.
2. Failure caused by unapproved modifications, etc., to the product by the user.
3. When the Mitsubishi product is assembled into a user's device, Failure that could have been avoided if functions
or structures, judged as necessary in the legal safety measures the user's device is subject to or as necessary by
industry standards, had been provided.
4. Failure that could have been avoided if consumable parts (battery, backlight, fuse, etc.) designated in the
instruction manual had been correctly serviced or replaced.
5. Failure caused by external irresistible forces such as fires or abnormal voltages, and Failure caused by force
majeure such as earthquakes, lightning, wind and water damage.
6. Failure caused by reasons unpredictable by scientific technology standards at time of shipment from Mitsubishi.
7. Any other failure found not to be the responsibility of Mitsubishi or that admitted not to be so by the user.
2. Onerous repair term after discontinuation of production
(1) Mitsubishi shall accept onerous product repairs for seven (7) years after production of the product is discontinued.
Discontinuation of production shall be notified with Mitsubishi Technical Bulletins, etc.
(2) Product supply (including repair parts) is not available after production is discontinued.
3. Overseas service
Overseas, repairs shall be accepted by Mitsubishi's local overseas FA Center. Note that the repair conditions at each FA
Center may differ.
4. Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:
(1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
(2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.
(3) Special damages and secondary damages whether foreseeable or not, compensation for accidents, and
compensation for damages to products other than Mitsubishi products.
(4) Replacement by the user, maintenance of on-site equipment, start-up test run and other tasks.
5. Changes in product specifications
The specifications given in the catalogs, manuals or technical documents are subject to change without prior notice.
INFORMATION AND SERVICES
For further information and services, please contact your local Mitsubishi Electric sales office or representative.
Visit our website to find our locations worldwide.
TRADEMARKS
The company names, system names and product names mentioned in this manual are either registered trademarks or
trademarks of their respective companies.
In some cases, trademark symbols such as '' or '' are not specified in this manual.
SH(NA)-080401E-I
SH(NA)-080401E-I(2412)MEE
MODEL: AJ65V-68ADN-U-SY-E
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
NAGOYA WORKS: 1-14, YADA-MINAMI 5-CHOME, HIGASHI-KU, NAGOYA 461-8670, JAPAN
When exported from Japan, this manual does not require application to the
Ministry of Economy, Trade and Industry for service transaction permission.