Viking 25 Original
Viking 25 Original
MANUAL
© Regulateurs Europa Ltd 2007
These instructions have been compiled to assist personnel responsible for the operation and
maintenance of equipment manufactured by Regulateurs Europa Ltd.
Care has been taken to ensure that the equipment has been accurately represented, but it should
be appreciated that, with the continued progress of design and the diversity of application, certain
items may differ in detail.
It should be noted that these instructions are issued for general information and do not constitute
a specification of the equipment.
Whilst reserving the right to make any alteration in design which they may consider advisable the
manufacturers absolve themselves from making any such alteration retrospective.
In addition to the information given herein, practical advice and assistance are always available
from our Service Department.
INSTALLATION NOTE
WARNING
The prime mover should be equipped with a separate overspeed shutdown device, to protect
against runaway or damage to the prime mover, with possible personal injury or loss of life,
should the governor/actuator fail.
SAFETY
Equipment supplied or manufactured by Regulateurs Europa Ltd may contain one or more of the
following:
i) Rotating parts
ii) High pressure oil
iii) Compressed air
iv) High voltages
v) Preloaded springs
vi) PCB’s
vii) Microprocessors
All of the above items represent a potential danger or hazard to operating personnel, therefore the
operator should be aware of the working principles and safety procedures involved with the
equipment being used. Before working on the equipment, the following points should be observed:
2. Ensure that the overall operator-in-charge is informed of the nature of work being
carried out
3. Display and secure warning notices at both local and remote control positions
5. Ensure that the equipment cannot be activated in any way from a remote position.
(In the case of keys operated equipment, all keys must be in the operators
possession.)
Finally, before the equipment is released for operation, ensure that relevant supplies are
reconnected, safety guards and all tools removed.
SAFETY OF PERSONNEL OPERATING & MAINTAINING EQUIPMENT MANUFACTURED BY
REGULATEURS EUROPA LTD
Before carrying out any repairs, adjustments or maintenance to any equipment by Regulateurs
Europa Ltd, it is essential the following safety precautions be observed:
1. General
i) High voltages
ii) Rotating parts
iii) High pressure oil
iv) Compressed air
v) Preloaded springs
vi) PCB’s
vii) Microprocessors
All of the above items represent a potential danger or hazard to operating personnel and the
operator should take care to make himself thoroughly familiar with the operating principles,
methods of adjustment and the dismantling and assembly procedures (where applicable)
concerning the equipment in his care.
1.1 Before carrying out any repairs, adjustments or maintenance to the equipment or unit, the
operator should ensure that any such unit or equipment cannot be activated from a remote
position. To achieve this condition, he should ensure that all electrical/pneumatic supplies to
the prime mover starter system are isolated at their incoming source and that all electrical
supplies to control systems are isolated by the withdrawal of the relevant fuses or by
disconnecting the incoming electrical supply at the control board. In addition to these
precautions, visual-warning notices should be prominently displayed by the equipment or unit
and also at any remote control positions. Where control cabinets and consoles are secured
with keys, all such keys should be in the possession of the operator carrying out the work.
Information regarding position, level and type of work to be carried out should also be made
available to the ‘Engineer in Charge’ of the installation to prevent attempted use of the
equipment or unit during breakdown.
1.2 In the case of electrical/electronic control systems, the operator should make careful
reference to the Instruction manual to ensure that he is aware of any special safety
precautions which are peculiar to that particular equipment or unit.
1.3 Before the equipment or unit is finally released for operation, operating personnel should
ensure that all tools and repair equipment has been removed and that all safety guards are
securely replaced (where applicable). All fuses should be replaced and operating mediums
(electrical and pneumatic supplies) should be opened or reconnected.
ELECTROSTATIC PRECAUTIONS
WARNING
This equipment contains components that are electrostatic sensitive. Electrostatic damage can
cause immediate failure or shortening of useful life.
Servicing PCBs at component level should be done at an electrostatic free workstation. If site work
cannot be avoided, the following precautions must be taken:
b) Personal wrist or ankle earth straps must be worn. To protect against personal
hazard, the resistance of the earth strap should be approximately 250k ohms.
Electrical Interference
a) All cable screens to be terminated and earthed at the entry to the equipment
To ensure prompt and satisfactory attention to customer’s enquiries, all communications should refer
to the UNIT TYPE and SERIAL NUMBER, as stamped on the nameplate.
In order to obtain the most efficient service it is recommended that all enquiries for service or spare
parts to be addressed to the manufacturer of the equipment to which the unit is fitted.
Customer training can be provided either in Colchester or Roden or on site. Contact below for
further details.
Regulateurs Europa b v
1e Energieweg 8
9301 LK
RODEN NETHERLANDS
FOR THE
OF
Abbreviations
Various abbreviations are used within this document and are listed below:
BCM. Viking Bank Control Module. Mounted on the inside of the ICAM
panel.
EFI Controller. Electronic Fuel Injection V25 Controller. Mounted in the ICAM
panel.
MAA Controller Monitoring And Alarm V25 Controller. Mounted in the ICAM
panel.
-2 -
Pub. 3580
INDEX
1 GENERAL DESCRIPTION...................................................................................... 6
1.1 Introduction ................................................................................................ 6
1.2 Engine Control Unit ................................................................................... 8
1.2.1 General Features ......................................................................................... 8
1.2.2 Panel Mounting Equipment.......................................................................... 8
1.2.3 Internal Equipment..................................................................................... 10
1.3 Integrated Control And Monitoring Enclosure ...................................... 11
1.3.1 General Features ....................................................................................... 11
1.3.2 Panel Mounted Equipment......................................................................... 11
1.3.3 Internal Equipment..................................................................................... 11
2 SETTING TO WORK............................................................................................. 14
2.1 Speed Switch............................................................................................ 14
2.1.1 General ...................................................................................................... 14
2.1.2 Layout ........................................................................................................ 15
2.2 ECU Multi-function Modules ................................................................... 16
2.3 Shutdown Module .................................................................................... 16
2.4 Shaft Speed Sensing Module.................................................................. 17
2.5 High H.T Water Temperature Trip Module ............................................. 17
2.6 Signal Conditioning Modules.................................................................. 18
3 SYSTEM OPERATION.......................................................................................... 20
3.1 Speed Sensing ......................................................................................... 20
3.2 Engine priming ......................................................................................... 20
3.3 Engine starting ......................................................................................... 21
3.4 Engine stopping ....................................................................................... 22
3.5 Engine Protections .................................................................................. 22
3.6 Engine Slowdowns .................................................................................. 25
3.7 Speed Setting ........................................................................................... 27
3.8 Control Transfer ....................................................................................... 28
3.9 Boost Bypass Valve Control ................................................................... 28
3.10 AVLOS Pump Control .............................................................................. 28
3.11 Fuel Module Pump Control ..................................................................... 28
3.12 Clutch Control .......................................................................................... 29
3.13 Oil Mist Temperature ............................................................................... 29
3.14 Shaft Speed Sensing ............................................................................... 29
3.15 Data Network ............................................................................................ 30
3.15.1 EFI/BCM CANBUS ...................................................................................... 30
3.15.2 EFI/MAA RS485......................................................................................... 30
3.15.3 EFI RS232.................................................................................................. 30
3.15.4 MAA/DI CANBUS....................................................................................... 30
3.15.5 MAA RS232 ............................................................................................... 30
3.15.6 DI/SCS RS485 ........................................................................................... 31
3.15.7 DI/SCS RS485 ........................................................................................... 31
3.16 Monitoring And Alarm ............................................................................. 33
-3 -
Pub. 3580
4 CONTROLLER FAILURES................................................................................... 35
4.1 V25 EFI Controller .................................................................................... 35
4.1.1 RS232 Operator Display Communication Link Failure. ............................. 35
4.1.2 BCM CANBUS Communication Link Failure. ............................................ 35
4.1.3 MAA RS485 Communication Link Failure. ................................................ 35
4.1.4 Controller Failure. ...................................................................................... 35
4.2 V25 DI Controller Failure ......................................................................... 35
4.2.1 SCS optional monitoring RS485 Communication Link Failure. ................. 35
4.2.2 SCS RS485 Communication Link Failure................................................. 35
4.2.3 MAA CANBUS Communication Link Failure ............................................. 36
4.2.4 Controller Failure. ...................................................................................... 36
4.3 V25 MAA Controller Failure..................................................................... 36
4.3.1 RS232 Operator Display Communication Link Failure. ............................. 36
4.3.2 DI CANBUS Communication Link Failure.................................................. 36
4.3.3 Controller Failure. ...................................................................................... 36
4.4 V25 Operator Interface............................................................................. 36
4.5 Back-up Mode........................................................................................... 38
6 GRAPHICAL DISPLAY......................................................................................... 46
6.1 Home Page................................................................................................ 46
6.2 Exhaust Menu........................................................................................... 48
6.3 Services Menu .......................................................................................... 49
6.4 Gearbox Menu .......................................................................................... 50
6.5 Bearings Menu ......................................................................................... 51
6.6 EFI Menu ................................................................................................... 52
6.7 Display Menu ............................................................................................ 53
6.8 Alarm Display ........................................................................................... 54
-4 -
Pub. 3580
9 DRAWINGS........................................................................................................... 66
-5 -
Pub. 3580
1 GENERAL DESCRIPTION
1.1 Introduction
1 off Engine Control Unit [ECU]. This is a bulkhead mounted panel with three
compartments containing the electronic Viking 25 Data Interface Digital
Controller, power supply distribution, signal conditioning modules and external
connection terminals. Access to the internal components is by two upper side
hinged doors and a lower lift off panel. Devices for operator interface are
provided on both doors. A gland plate and terminals enable connection of the
ships wiring and the engine mounted ICAM panel.
ENGINE SPEED
OPERATOR DISPLAY
Operator Interface
EFI OFF MAA
EMERGENCY STOP
CLUTCH CLUTCH
IN OUT PB3 START STOP
Regulateurs
Europa
-6 -
Pub. 3580
1 off Integrated Control And Monitoring [ICAM] enclosure. This is mounted on the
engine oil cooler and contains the signal conditioning modules, two Viking
Bank Control Modules, Viking 25 EFI and Monitoring And Alarm Digital
Controllers. Access to the internal components is by three lift off covers
opening upwards. Connections to the ECU and engine sensor rails are either
on the internal terminal rail or directly to the signal conditioning modules.
-7 -
Pub. 3580
The left hand side hinged door has a Viking 25 Operator Interface [membrane
keypad with integral 4 line message display], engine rpm indicator, hours run
recorder and operator interface controls. The right hand side hinged door is
fitted with an HMI display with touch screen controls, status indications and
push-button controls. The lower door is lift off and retained by six captive
fasteners. The hinged doors allow access to all internal components and are
fitted with door stays to hold them open.
A gland plate and terminals enable connection of the ships wiring, gearbox,
optional starter panel and the on engine ICAM enclosure. The panel
environmental rating is to a minimum of IP54.
This panel provides the central point of the control system. It enables the
engine and gearbox to be controlled locally by the operator using the controls
provided on the panel or remotely by the ships systems. The Viking HMI on
the left hand door enables the operator to interrogate either the EFI or MAA
controllers and view faults, display status information and modify system
parameters. The Graphical HMI display on the right hand door enables the
operator to view current alarms, status information and channel data from the
MAA system.
Internally are fitted the Viking 25 DI controller, shaft speed switch, signal
conditioning modules, interface relays and terminals.
Viking HMI:
Four line, 20 characters per line Vacuum Fluorescent display.
Membrane overlay with 12 buttons and four “hidden till lit” text panels.
RS232 serial communications link to the selected Viking 25 Digital
Controller.
To display any software detected faults and allow program variables to
be modified.
Instruments:
Hours Run recorder
Engine rpm indicator: 0-1200 rpm
-8 -
Pub. 3580
Control Pushbuttons:
HMI RESET [black]
Control Switches:
OPERATOR DISPLAY EFI/OFF/MAA [rotary – three position]
Graphical HMI with touch screen for the display of parameter values and
alarm status indication. The display is available providing the EFI controller is
selected to the operator display.
Indicators:
REMOTE CONTROL [white]
REMOTE CONTROL NOT ACCEPTED [yellow]
BACK-UP MODE [yellow]
ENGINE RUNNING [green]
ALARM ACTIVE [amber]
Control Pushbuttons:
EMERGENCY STOP [twist to release]
START ENGINE [green]
STOP ENGINE [red]
PROTECTION RESET [red - illuminated]
TEST LAMPS [yellow]
ALARM MUTE [white]
ALARM RESET [black]
CLUTCH IN [white - illuminated]
CLUTCH OUT [white - illuminated]
EFI CONTROLLER RESET [amber - illuminated]
EMERGENCY OVERRIDE ENABLED [amber – illuminated]
Control Switches:
Control station LOCAL/REMOTE [key operated]
Engine speed LOWER/N/RAISE [centre biased]
Manual alarm commission OFF/ON
-9 -
Pub. 3580
- 10 -
Pub. 3580
Lower Compartment
External terminals.
Gland plates are provided for cabling to the engine sensors and the ECU. The
panel environmental rating is to a minimum of IP54.
The main functions of the panel are to provide a central point on the engine for
interconnecting the engine sensor rails, condition the monitoring signals for
the internal MAA Controller, house the EFI Controls [BCM’s and EFI
Controller] and interface the engine with the ECU.
None fitted.
Two BCM’s.
These control the individual cylinder fuel pump solenoids and also
provide emergency back-up speed governing.
- 11 -
Pub. 3580
- 12 -
Pub. 3580
10 channels provided.
Selectable wire break detection on each channel.
Close on fault initiating contacts.
Contact for common protection operated indication on the ECU.
Individual shutdown and module healthy multiplexing interface for MAA
monitoring.
Back-up speed switch failure detection [engine running, no speed switch
50rpm level detection]. 50rpm level repeated to EFI Controller to
independently detect failure in normal operating mode.
- 13 -
Pub. 3580
2 SETTING TO WORK
2.1.1 General
The speed sensing module in the ICAM is a four channel level sensing unit
with 4-20mA tachometer drive. The speed switch monitors the signal from a
perception head that is mounted above the engine starter ring [304 teeth] or
gearbox output shaft gearwheel. The head may be either a passive or active
[powered] type and is set on links 1, 2, 7 and 8.
The speed switch module has additional links to select the full scale deflection
frequency range, 0-20 or 4-20 mA output, mA output power source and to
enable over speed test. The module detects the pulses from the perception
head input and converts them into an analogue speed reference signal. This
speed signal is used to drive a proportional mA output [for instrumentation]
and as a reference for four independently adjustable speed sensitive switches.
Each level switch is capable of being set within the range 5 to 105% of
tachometer FSD and operates when the reference signal exceeds the
channels set level.
A small toggle switch is mounted on the module for over speed testing and is
enable by link 5 being set to the A position. When operated, it has the effect of
lowering the level at which the over speed level [channel 2] operates by
approximately 50%. The purpose of this switch is to allow a simulated over
speed condition [approximately 575 rpm] without over stressing the engine to
ensure that the engine is shutdown.
To use the test switch, start the engine in LOCAL control. Place the toggle
switch in the TEST position [TEST LED4 is illuminated]. Raise the engine
speed using the control switch on the ECU and ensure that the OVER SPEED
alarm is initiated at the set level. Clear the ECU alarm and place the toggle
switch back in the NORMAL position.
The frequency range [scale] of the output is set by links 3 and 4 and is
calculated by:
Link Settings
- 14 -
Pub. 3580
Adjustments
2.1.2 Layout
- 15 -
Pub. 3580
Wire break monitoring, disabling channel blocking on selected channels and module
address are selected by jumpers mounted on the module as follows:
Notes: The block override links, if fitted, select the shutdown channel to be active at
all times [i.e. is not inhibited while the engine is stationary].
- 16 -
Pub. 3580
The speed sensing module in the ECU has a 4-20mA tachometer drive and monitors
the signal from a perception head that is mounted on the gearbox. The head is an
active [powered] type and the number of teeth being monitored will depend on the
type of gearbox.
The protection circuit for the H.T water temperature is monitored by a Pt1000 sensor
and this is converted by the module into 4-20mA representing 0 – 150°C. The
conditioned signal is then compared to out of range limits [3>mA>22] and an
adjustable trip level.
If the signal is out of range, or the power supply fails, relay 2 will de-energise. This will
disconnect a 15K resistor in the trip circuit causing a wire break alarm and the trip
output is inhibited.
Providing the out of range check is healthy [relay 2 energised], relay 1 will energise if
the sensor value exceeds the set trip level and close a contact to initiate engine
shutdown.
VR1 - Sensor calibration [to give 4.96v at 150°C measuring TP3 w.r.t TP2].
VR2 - Set to illuminate LED1 at required trip level [95°C rising].
- 17 -
Pub. 3580
There are two types of 16 channel signal conditioning modules fitted in the ICAM.
One is for Pt600/Pt1000 sensors [depending on build] and the other is for
thermocouples. It is also possible, on both types of module depending on the link
configuration, to set a channel to monitor either 4-20mA or digital signals. The digital
signal may also be fitted with a 15K resistor across its contact for wire break
detection.
Module channel scaling, address and link positions are listed on the appropriate
sheets of drawing L5473. Refer to section 9 of this manual.
- 18 -
Pub. 3580
- 19 -
Pub. 3580
3 SYSTEM OPERATION
Two perception heads are used by the EFI controller in the ICAM enclosure to
monitor 304 teeth on the engine flywheel. One head is active, the other acts as a
stand-by. If the active head should fail while the engine is running, an output is de-
energised that will illuminate the EFI CONTROLLER RESET push-button on the ECU
and the EFI controller will automatically switch to the standby head. The MAA
controller will detect the fault [via the communication links], provide an audible alarm
contact and make the information available to the ECU HMI and ships monitoring
systems via the DI controller communication links. If both perception head inputs fail
while the engine is running [without a stop initiated], an additional output will be de-
energised that will illuminate the BACK-UP MODE indicator and allow the BCM’s to
take direct control.
The EFI CONTROLLER RESET push-button must be operated to reset the fault.
Note that terminals are provided to permit a remote reset push-button to be
connected.
There is an analogue electronic speed switch mounted in the ICAM panel that in the
event of an engine over-speed will initiate a shutdown sequence independently of the
EFI digital controller.
For continuous priming, the lube oil pump will be run continuously to maintain the
engine in a primed state whenever the engine is stationary. Once priming pressure
has been achieved for a set time, or the engine had been running in the last set
minutes, the engine is considered available to start.
For pre-start prime the lube oil pump will only run when the engine start sequence is
initiated. Once priming pressure has been achieved for a set time the start sequence
will continue. Also, whenever the engine is stopped, the lube oil pump will start and
run for a set time.
- 20 -
Pub. 3580
Start Interlocks
The EFI controller monitors the start request signal from the station in control and the
following start block conditions:
i. Engine running.
ii. Stop sequence applied or timing out.
iii. Shutdown protection channel operated.
iv. Analogue speed setting above idle. Only applies if in REMOTE control,
signal healthy and digital speed control not selected.
v. Gearbox out of neutral.
vi. EFI pick-ups failed.
vii. Not primed [fail to prime if pre-start priming is selected].
viii. Barring gear engaged.
ix. Gearbox interlock [depending on gearbox type]
Providing that no start block is applied, on sensing a start request from the station in
control, the EFI controller will energise an output to start the fuel module pumps and
initiate a start sequence.
If the engine accelerates above firing speed within the set time, the start sequence is
cancelled and after a delay has expired, to enable engine pressures to stabilise, the
COMMISSION ALARMS output is energised. The commission alarms output will:
- 21 -
Pub. 3580
The EFI controller monitors the stop request signal from the station in control and the
shutdown module in the ECU. At the station in control, momentary operation of the
STOP push-button will latch the engine stop sequence in the EFI controller. A
permanent stop will be applied if a protection channel has operated, irrespective of
the control selector switch position.
When a stop sequence is initiated, the EFI controller will energise the fuel shut-off
valve solenoid and signal the BCM’s, via a communications link, that a stop is
applied. The stop signal will be latched for a preset time [to allow the engine to
become stationary] before resetting and permitting the engine to be restarted. If the
stop was initiated by a shutdown protection, the power supply to the EFI solenoids
will be isolated until the shutdown channel has been reset. The EFI controller will also
de-energise the fuel module pump start output once speed drops below engine
running rpm and cancel the COMMISSION ALARM output that will:
i. Energise the Jacket Water circulating pump and heater run demand.
ii. De-energise the crankcase extraction fan start demand.
iii. Remove fuel module circulating and supply pumps run overrides.
iv. Apply clutch trip demand and disable ECU and SCS controls.
v. Apply the alarm inhibit to the MAA controller.
vi. Apply slowdown alarm inhibit [selected channels].
vii. Apply shutdown alarm inhibit [selected channels].
viii. Extinguish ECU ENGINE RUNNING indicator and de-energise the
hours recorder.
ix. Open the SCS engine running contact.
Various shutdown protections are hardwired, the logic for which is housed in the
ICAM. The fault switches close to initiate shutdown with wire break detection fitted to
the following engine protection channels:
There are individual LED indicators on the module to identify the channel at fault and
a group wire break signal [module healthy] that is monitored by the MAA controller
multiplexing interface. In the event of a wire break or power supply failure an alarm is
given and the engine remains running but will be without the protection of the failed
channel. The MAA controller will continue to give a warning of a deteriorating
condition [1st stage fault].
- 22 -
Pub. 3580
To clear the fault, the initiating contact must be reset or inhibited if the engine is
stationary. The illuminated PROTECTION RESET push-button on the ECU can then
be momentarily operated to release the latch. This is confirmed once the push-button
indication is extinguished. The engine can then be restarted providing that other
interlocks are satisfied.
This input is inhibited if the engine is stationary and is only enabled by the EFI
controller after the engine has been running for a preset time or by the
operator using the MANUAL ALARM COMMISSION switch on the ECU in
LOCAL control. Activated by engine mounted pressure switch.
This input is inhibited if the engine is stationary and is only enabled by the EFI
controller when the engine is running above a set speed level. Activated by
engine mounted pressure switch.
The clutch oil pressure input is inhibited if the gearbox is at neutral and the lub
oil pressure input is inhibited if the engine is stationary. Both are activated by
gearbox mounted pressure switches and have individual delays to avoid
transient conditions initiating false shutdowns.
vi. Over-speed
The over-speed input is active at all times and is initiated by the electronic
speed switch in the ICAM.
- 23 -
Pub. 3580
A 50rpm level from the speed switch is used for checking correct operation. If
the EFI controller is healthy and senses that the engine is running and the
50rpm level from the speed switch is not present, then it will send a
discrepancy message to the MAA controller via the serial communication link
to initiate an alarm.
As a back up the shutdown module will also compare the 50rpm level to the
COMMISSION ALARMS status. If the alarms are commissioned and there is
no 50rpm level from the speed switch, a wire break alarm will be given. An
LED indicator on the module will illuminate to identify the fault and a group
wire break contact [module healthy] will open. This contact is monitored by the
MAA controller multiplexing interface to initiate an alarm.
This input is active at all times and is initiated by the MAA controller.
This input is active at all times and is initiated by the EFI controller if any two
of the following channels are valid:
This input is inhibited if the engine is stationary and is only enabled by the EFI
controller after the engine has been running for a preset time or by the
operator using the MANUAL ALARM COMMISSION switch on the ECU in
LOCAL control. Activated by engine mounted Pt1000 temperature sensor that
is processed by a trip amplifier mounted in the ICAM panel.
The trip amplifier provides outputs for high level exceeded [activates the
shutdown channel], and for module healthy [wire break alarm]. If the healthy
output is de-energised [power supply or sensor failure], it will inhibit the high
level output and initiate a wire break alarm by disconnecting an internal 15k
resistor.
x. Fire Detected
This input is active at all times and is initiated by a contact from the SCS.
When activated it will also close a contact to the EFI controller to inhibit the
lube oil pump from running.
- 24 -
Pub. 3580
Various parameters are monitored by the EFI controller in the ICAM that will initiate a
engine slowdown. These are either analogue transducers or fault switches that close
to initiate slowdown. Wire break detection is fitted to the following engine protection
channels:
In the event of a wire break [contact disconnected or transducer out of range], the
engine remains running but will be without the protection of the failed channel.
When a slowdown occurs [initiating contact closes or measured value exceeds set
level], the fault channel is latched, the EFI CONTROLLER RESET push-button is
illuminated and the fault is sent via the communications link to the MAA controller to
initiate an alarm.
To clear the fault, the condition must have returned to a healthy state or be inhibited if
the engine is stationary. The illuminated EFI CONTROLLER RESET push-button on
the ECU can then be momentarily operated to release the latch. This is confirmed
once the push-button indication is extinguished. The hold at idle interlock will be
removed and will enable the engine speed to be controlled over its full range.
- 25 -
Pub. 3580
In addition, the EFI controller will initiate a shutdown demand if two of the following
conditions are satisfied:
This input is active at all times. Initiated by the MAA controller and consists of
high H.T water engine outlet temperature [menu enabled], high exhaust
temperatures and if not selected as a shutdown, high main bearing
temperature. These inputs are inhibited if the engine is stationary and are only
enabled by the EFI controller after the engine has been running for a preset
time or by the operator using the MANUAL ALARM COMMISSION switch on
the ECU in LOCAL control.
This input is inhibited if the engine is stationary and is only enabled by the EFI
controller after the engine has been running for a preset time. The alarm level
is two stage and dependant on engine speed. Activated by engine mounted
pressure transducer.
This input is inhibited if the engine is stationary and is only enabled by the EFI
controller after the engine has been running for a preset time. Activated by
engine mounted pressure switch.
This input is active at all times and is initiated by an output from a grid switch
sensor on the engine.
The bearing oil splash temperatures are monitored and is only enabled by the
EFI controller after the engine has been running for a preset time. Activated by
any individual channel exceeding the average temperature of all other healthy
channels by a set level.
This input is active at all times and is initiated by a signal from the ships
control system.
This input is active at all times and is initiated by a signal from the ECU control
system. This is currently not used.
- 26 -
Pub. 3580
The analogue speed demand from the SCS is continually monitored by the EFI
controller to ensure that it is within the expected 4-20mA range. Should it fall outside
these limits and the FAULT – GO TO IDLE input is OFF, an output is de-energised to
illuminate the EFI CONTROLLER RESET push-button and the EFI controller will go
idle. The MAA controller will detect the SPEED TRANSDUCER FAILED fault [via the
communication links], provide an audible alarm contact and make the information
available to the ECU HMI and ships monitoring systems via the DI controller. This
does not effect digital speed control that may be selected by the SCS as a back-up
control. The EFI CONTROLLER RESET push-button must be operated to reset the
fault before analogue control can be reinstated. The alarm will not be given but the
engine will be instructed to go to idle if the FAULT- GO TO IDLE input is ON.
The EFI controller will switch an output ON whenever the engine is running and within
an idle speed band. This is provided for a clutch engagement interlock.
In the event of a serious fault with the EFI controller the BCM’s revert to back-up
mode. In this condition the engine will go to idle, the BACK-UP MODE indicator on
the ECU is illuminated, the contact to the SCS is closed and the digital controls at the
station in control must be used. If in remote control, the analogue reference can no
longer be used and the digital back-up controls must be selected. In this mode the
BCM’s provide basic speed control only. To enable the clutch to be engaged when
running in back-up mode, hardwired interlocks will override the EFI Controller clutch
interlock if the engine is running below a set rpm level [speed switch output] and the
back-up indication is ON.
- 27 -
Pub. 3580
When the ECU is switched to LOCAL control, the current speed setting will be
maintained for bump-less transfer and the digital speed controls on the ECU will be
enabled allowing adjustments to be made.
If the TAKE CONTROL input is linked out, and the matched band is set to maximum,
then transfer of control will be immediate.
The EFI controller provides a 24v dc signal to open the boost bypass valve when the
engine speed is within a preset speed band. Speed levels are menu adjustable.
Hysteresis is provided to prevent spurious switching.
The EFI controller will energise an output to run the AVLOS pump when the engine
speed is above a preset level and the gearbox is not at neutral. Speed level is menu
adjustable. Hysteresis is provided to prevent spurious switching.
The EFI controller will energise an output to run the fuel module circulating and
supply pumps whenever an engine start sequence is initiated or while the engine is
above running rpm and no stop sequence is applied.
Once the engine is running, the pump run demand is maintained by a hardwired
contact of the commission alarms relay. This ensures that in the event of an EFI
controller failure, the engine will continue to receive fuel.
- 28 -
Pub. 3580
Whenever the engine is stopped or stationary, the gearbox control valve will be
moved to the dis-engaged position by energising the clutch out solenoid. Only after
the engine has been started and the alarms commissioned can the gearbox be
clutched in from the selected control station. If at any time the engine is stopped,
either by a manual request or by a fault shutdown protection channel, the clutch out
signal is reapplied and operator controls are disabled.
Interlocks are provided to ensure that the gearbox can only be clutched in or out in a
controlled manner. A clutch in request is dependant on a permission signal from the
EFI controller [engine is running in the idle speed band] and the SCS [closes to block
engagement. When running in back-up mode [EFI Controller off-line], an output from
the speed switch provides the idle speed interlock.
The gearbox may be clutched in, providing the engine is running in the idle speed
band and the SCS interlock is healthy, by momentarily operating the appropriate
push-button at the selected control station. This will energise the clutch in solenoid on
the gearbox control valve. On the ECP, the CLUTCH OUT push-button will be
extinguished providing the gearbox control valve moves to the clutch in position. The
CLUTCH IN push-button will illuminate once full pressure has been applied to the
clutch.
The gearbox may be clutched out at any time by momentarily operating the
appropriate push-button at the selected control station. This will energise the clutch
out solenoid on the gearbox control valve. The CLUTCH OUT push-button will
illuminate to confirm the control valve has returned to the correct position and the
CLUTCH IN push-button will extinguished once pressure has been removed from the
clutch.
The EFI controller monitors the oil splash sensors mounted on the engine [one for
each crank space] and can initiate an alarm [sensor fault] or a slowdown [high oil
splash temperature deviation].
- 29 -
Pub. 3580
High speed link that enables data to be exchanged between the two BCM’s
and the EFI controller. A connector is provided on the EFI Controller in the
ICAM enclosure that enables the connection of a laptop for monitoring
purposes.
Point to point link between the EFI and MAA controllers. Enables the MAA
controller to receive status information on the EFI and BCM units.
Point to point link between the EFI controller and the ECU. This allows either
the panel mounted Viking HMI, or a laptop using the port provided inside the
ECU, to be connected. These can then access information or view/edit
parameters in the controller.
High speed link that enables data to be exchanged between the MAA and DI
controllers. A connector is provided on the MAA controller in the ICAM
enclosure that enables connection of a laptop for monitoring purposes. The
MAA reads off engine status information from the DI controller. This is
combined with engine parameters monitored by its own I/O modules and data
obtained from the EFI controller, processed and repeated back to the DI
controller. The DI controller enables the SCS to view this information.
Point to point link that enables an ECU panel mounted HMI device [Viking HMI
or graphical display] to be used to interrogate the MAA controller. The
graphical interface will display alarm information providing the Operator
Interface switch is selected to EFI. In this mode the graphical display requests
information from the MAA using MODBUS protocol. In the event that the
graphical display is not operational, or changes to the MAA configuration are
required, the ECU Viking HMI can be selected [operator interface switch to
MAA position] and the protocol mode automatically changes to support this
device. When the Operator Interface is selected to OFF, the SCS has access
to both the EFI and MAA controllers.
- 30 -
Pub. 3580
Point to point link between the DI controller and the ships management
system that enables monitoring data to be exchanged using MODBUS
protocol.
Point to point link between the DI controller and an optional monitoring system
that enables monitoring data to be exchanged using MODBUS protocol.
- 31 -
Pub. 3580
O PTIO NAL
SHIPS
M ONITORIN G
SYSTEM REM O TE VIKIN G
SYSTEM
VISION C ONNE CTION S
EF I M AA
RS485 RS485
[R S232] [RS2 32]
VIKIN G 25
DI
CON TRO LLER
SERIAL
C ANBUS RS23 2 CH ANGEOVER RS232
724901
R S232 R S232
VIKING GRAPH IC AL
HM I HMI
VIKIN G 25 VIKIN G 25
M AA R S485 EF I
CON TRO LLER CO N TROLLER
BC M BCM
'A' 'B'
BANK BANK
ICAM ENCLOSURE
[ENGINE MOUNTED]
The MAA controller processes data monitored by its own input conditioning modules
with that received on the CANBUS [DI controller] and RS485 [EFI controller]
communication links. A listing of the signals monitored is detailed in section 5 of this
document.
The MAA will process each signal individually using parameters held in its menu
system. These parameters can define high, low or deviation, operating level, delay,
block etc., according to the input being processed.
A block alarm input will close to inhibit specific channels from alarming when the
engine is stationary.
An audible alarm output will switch OFF and a changeover contact is provided to the
SCS whenever a new alarm has occurred.
An output will switch OFF to illuminate the ALARM ACTIVE indicator on the ECU and
a changeover contact provided to the SCS.
An ALARM MUTE push-button is provided to cancel the audible alarm output and an
ALARM RESET push-button to clear the fault providing the input has returned to a
healthy state.
The alarm can also be accepted or reset by the SCS over the serial communication
network.
Outputs will also switch ON to initiate a slowdown [high HT water engine outlet
temperature, high exhaust temperatures and if not selected as a shutdown, high main
bearing temperature] or shutdown [high main bearing temperature if not selected as a
slowdown]. Selection of high main bearing temperature as a slowdown or shutdown is
set in the MAA menu system.
Channel values and fault conditions are made available on the communication
networks for local and remote displays.
- 33 -
Pub. 3580
OPT IO NAL
SH IPS
M O NITORING
SYSTEM
SYSTEM
O FF EN GINE
ANALOG U E VIKI NG 25
EXPANSI ON DI
MO DUL E C ONTRO LLE R
H ARDW I RED ECU
SIG NALS
D IGITAL
EXPANSI ON
MO DUL E
RAW DATA FROM
BC M'S & EFI
R AW DA TA CO NTR OLLER
VIK ING 25
EFI
CO NTR OLLER
PRO C ESSED
D ATA
H ARDW I RED
SIG NALS PR OCESSED DAT A
VIKI NG 25
CON DIT IONING G R APHICAL
MAA
MO DU LE 1 H MI
C ONTRO LLE R
SETTINGS/
ALAR M BLO C K
HMI
MODIFI ED
CON DIT IONING
C O NFI GUR ATIO N
MO DU LE 4
PARAM ETERS
SH UTDO W N
MO DU LE 5
- 34 -
Pub. 3580
4 CONTROLLER FAILURES
The main functions of the EFI controller are to start/stop the engine, control the
engine speed, limit fuel demands and receive status information by a serial
communications link with the BCM’s and forward status information to the MAA
controller via a serial communication link.
i. MAA controller initiates link failure alarm and cannot update EFI/BCM
data.
The main functions of the DI controller are to collect ECU, off-engine fuel module and
starter panel status and forward this data onto the MAA for alarm processing.
Receive alarm information from the MAA and permit the SCS access to this
information.
- 35 -
Pub. 3580
The main functions of the MAA controller are to monitor the on-engine sensors,
combine this with data received on a communications link from the EFI [includes
BCM’s] and DI controllers. Process the raw data to provide scaled values, generate
alarms and allow any HMI [direct] and SCS [via the DI controller], access to this
information.
The EFI and MAA controllers generate a number of faults that are detected by the
software. A specific message for the failed sensor will be displayed on the ECU LCD
display [providing the ALARM menu LED is illuminated]. They are caused by the
system failing to sense a switch or analogue signal input, or not getting the expected
feedback to a control output. Two menus are available to aid fault finding which that
enable the operator to monitor inputs or switch outputs ON/OFF by means of the
keyboard.
- 36 -
Pub. 3580
The display is selected to the appropriate controller using the switch provided. To re-
establish communications the HMI RESET push-button on the ECU must be
momentarily operated.
Operator Interface
MENU RESET
SELECT ALARM
ALARM
EDIT CANCEL
DATA EDIT
SAVE FINISH
DATA EDIT
PRESET
ACCESS
DATA
To display current alarms, press the MENU SELECT key to cycle the display until the
ALARM LED is illuminated then use the UP and DOWN keys to move through the
alarm list.
Fail To Prime
Alarm 01 of 01
19:37:31 04/03/07
S 0RPM L –33.3%
- 37 -
Pub. 3580
The BACK-UP MODE indicator on the ECU is illuminated, and the two SCS contacts
closed, when the engine is running in BCM control. This can occur when a fault has
occurred with the EFI controller.
This is a basic governing mode where the BCM’s control the engine speed and
respond to the digital speed inputs from the station in control. Maximum running
speed will be limited to 80% of full speed in this mode. The engine may be started
[on-engine], protections commissioned [manually on the ECU using the switch
provided and LOCAL control is selected] and stopped [emergency stop].
Prior to starting it may be necessary to manually start the fuel module circulating and
supply pumps unless a sufficient head of fuel is available. Once the engine is
running, and the protections are commissioned, the pump run signals will be
maintained by the ECU until the engine is stopped.
Terminals are provided to enable the EFI controller to be reset remotely by the SCS,
providing the initiating fault has returned to a healthy condition, to restore normal
control.
- 38 -
Pub. 3580
5.1 General
The tables in section 5.2 list the sensors monitored and alarmed by the MAA
controller. Channels 1 to 56 are off engine inputs collected by the DI controller [ECU,
gearbox, optional starter panel and off engine sensors] and passed over the CAN
communications network to the MAA for processing. Channels 57 to 160 are direct
inputs from the engine to the MAA that are wired in the ICAM enclosure.
A full listing for the 20RK280 is given in section 5.2. For 12 and 16 cylinder versions,
the number of exhaust cylinder and bearing temperatures being monitored will be
reduced accordingly.
Parameters for scaling, units, alarm levels, delays etc. for the inputs are held in the
MAA controller. These may be edited using the panel mounted [ECU] Operator
display or by a laptop running Viking Vision software.
Processed values and alarm information is made available to the SCS and optional
monitoring system by RS485 Modbus RTU interfaces [via the DI controller] and to
either the V25 Operator Display or graphical HMI via a RS232 interface.
Internally generated software faults [signal/control failures] are not listed but are
processed and available on the communication links.
Locally on the ECU, operator controls consist of ALARM MUTE and ALARM RESET
push-buttons together with a ALARM ACTIVE indication. These functions are also
accessible by the SCS on the Modbus communication link. Clean changeover
contacts are provided in the ECU for AUDIBLE ALARM ACTIVE and ALARM ACTIVE
[MAA fault] for hardwired interfacing if required.
The display unit that is communicating with the MAA controller and actively updating
its information, is determined by the OPERATOR DISPLAY switch position on the
ECU as follows:
EFI - V25 Operator display communicating with the EFI Controller, graphical
HMI communicating with the MAA controller.
REMOTE – There are no communications to either the V25 Operator display or the
graphical HMI. EFI and MAA Controller Viking Vision interface is
switched to permit remote monitoring by the SCS.
MAA - V25 Operator display communicating with the MAA Controller, there are
no communications with the graphical HMI.
- 39 -
Pub. 3580
9
10
11
12
13
14
15
16
- 40 -
Pub. 3580
Ch. Tag Description Sensor Range Units Block Low High Alarm
No. No. Level Level Delay
41 Gearbox Clutch Oil Pressure 4-20mA 0-40 Bar @ 17 10
neutral
42 Gearbox Lub Oil Pressure 4-20mA 0-10 Bar Yes 0.4
43 Gearbox Oil Temperature Pt1000 0-150 °C Yes 95
44
45
46 Shaft Speed 4-20mA 0-600 rpm
47
48
- 41 -
Pub. 3580
- 42 -
Pub. 3580
Ch. Tag Description Sensor Range Units Block Low High Alarm
No. No. Level Level Delay
89 TE03 Charge Air Inlet Temperature Pt1000 0-150 °C 65
90 TE11 L.T Water L.O Cooler Inlet Temperature Pt1000 0-150 °C 59
91 TE54 Air Intake Temperature [A-Bank] Pt1000 0-150 °C 45
92 TE55 Air Intake Temperature [B-Bank] Pt1000 0-150 °C 45
93 TE08 L.T Jacket Water Inlet Temperature [pump Pt1000 0-150 °C 89
inlet]
94 TE09 H.T Water C.A Cooler Inlet Temperature Pt1000 0-150 °C 89
95 TE12 LTW LO Cooler Out Temperature Pt1000 0-150 °C 60
96 TE51 L.T Water Inlet Temperature [pump outlet] Pt1000 0-150 °C 45
Note:
Fuel filter blocked is detected by pressure difference between PT16 and PT08
- 43 -
Pub. 3580
Ch. Tag Description Sensor Range Units Block Low High Alarm
No. No. Level Level Delay
129 TE47 Main Bearing No.9 Temperature Pt1000 0-150 °C 110
130 TE48 Main Bearing No.10 Temperature Pt1000 0-150 °C 110
131 TE49 Main Bearing No.11 Temperature Pt1000 0-150 °C 110
132 PT01 Charge Air Pressure - T/C Out A-Bank 4-20mA 0-4 Bar 3.8
133 PT02 Charge Air Pressure - T/C Out B-Bank 4-20mA 0-4 Bar 3.8
134 PT11 L.T Water Pressure [L.O cooler outlet] 4-20mA 0-4 Bar 0.8/1.2
135 PT10 H.T Water Pressure [I/C outlet] 4-20mA 0-4 Bar 0.9/2.0
136 PT34 Sea Water Pressure 4-20mA 0-6 Bar 0.5/1.5
137
138
139 TE13 L.O Cooler Inlet Temperature Pt1000 0-150 °C
140 TE14 L.O Engine Inlet Temperature Pt1000 0-150 °C 78
141 PT14 Filter Inlet Lub Oil Pressure 4-20mA 0-10 Bar 1.0
142 PT15 Control Air Pressure 4-20mA 0-10 Bar 6.5 8.5
143 PT23 Lub. Oil Pressure [engine inlet] 4-20mA 0-10 Bar Yes 2/3.5
144 PT05 Lub. Oil Pressure [pump outlet] 4-20mA 0-10 Bar 9.0
- 44 -
Pub. 3580
Ch. Tag Description Sensor Range Units Block Low High Alarm
No. No. Level Level Delay
161 ST01 Speed Pick-up 1 Failed Pulse
162 ST02 Speed Pick-up 2 Failed Pulse
163 A Bank BCM communications Failed
164 B Bank BCM communications Failed
165
166 Speed Switch Failure
167 Fail To Prime
168 Speed Demand Input Failed
169 Fail To Start
170 Overload
171
172 PT12 Air manifold sensor fault
173 PT27 HT water pressure sensor fault
174 PT07 Lube oil pressure sensor fault
175
176
- 45 -
Pub. 3580
6 GRAPHICAL DISPLAY
When the unit is powered up, or if the HOME key is pressed to return from a sub-
menu, the main home page graphic is displayed. Refer to figure 6.1.1. For
communications to operate correctly the operator display switch on the ECU must be
in the EFI position.
Touch screen controls allow the operator to navigate the graphic pages and the latest
alarm status is displayed.
- 46 -
Pub. 3580
Note: The graphic pages shown in this section are for a 20 cylinder engine display.
The format of the 12 and 16 cylinder engines are the same except they only
show the relevant number of cylinders or bearings are displayed.
HOME
page
Gearb ox
Status
[DEFAU LT]
St art
EFI Status EFI Solenoid
V2 5 St at us B CM Stat us Int erloc k
[ DEF AULT] St atus
Statu s
For clarity, alarm lists are not shown although they can be accessed from all graphic
pages.
- 47 -
Pub. 3580
Touch screen controls allow the operator to navigate the graphic pages and the latest
alarm is displayed.
1. Parameter values.
2. Touch screen buttons to select alternative graphic pages i.e. bar graph
or turbo-charger. Depressed button indicates the selected page.
3. Touch screen button to HOME page.
4. Animated alarm window with touch screen button to display the alarm
page.
- 48 -
Pub. 3580
Touch screen controls allow the operator to navigate the graphic pages and the latest
alarm is displayed.
1. Animation that changes state when the parameter is in alarm. Text will
be black and background will go yellow [warning] or red [trip/shutdown] if
the alarm is activated.
2. Touch screen buttons to select alternative graphic pages i.e. fuel oil,
H.T/L.T water or air systems. Depressed button indicates the selected
page.
3. Parameter value.
4. Touch screen button to HOME page.
5. Animated alarm window with touch screen button to display the alarm
page.
- 49 -
Pub. 3580
This is selected from the home page and will only be shown if gearbox monitoring is
provided by the ECU and is also determined by the make and model of gearbox.
Touch screen controls allow the operator to navigate the graphic pages and the latest
alarm is displayed.
1. Animation that changes state when the parameter is in alarm. Text will
be black and background will go yellow [warning] or red [trip/shutdown] if
the alarm is activated.
2. Touch screen buttons to select alternative graphic pages. Not currently
used.
3. Parameter value.
4. Touch screen button to HOME page.
5. Animated alarm window with touch screen button to display the alarm
page.
- 50 -
Pub. 3580
Touch screen controls allow the operator to navigate the graphic pages and the latest
alarm is displayed.
1. Parameter value.
2. Touch screen buttons to select alternative graphic pages i.e. value or
bar graph. Depressed button indicates the selected page.
3. Touch screen button to HOME page.
4. Animated alarm window with touch screen button to display the alarm
page.
- 51 -
Pub. 3580
Touch screen controls allow the operator to navigate the graphic pages and the latest
alarm is displayed.
1. Parameter value.
2. Animation that will change state when the parameter is healthy or in
alarm. For a fault indication the background will go yellow [warning]. For
a status indication the background will go green [healthy].
3. Touch screen buttons to select alternative graphic pages i.e. injectors,
V25 controllers, Bank Control Modules or Start Interlocks status.
Depressed button indicates the selected page.
4. Touch screen button to HOME page.
5. Animated alarm window with touch screen button to display the alarm
page.
- 52 -
Pub. 3580
Touch screen controls allow the operator to navigate the graphic pages and the latest
alarm is displayed.
Password Protection
The time/date adjustment on the clock page, and the monitor/diagnostic buttons, are
password protected and when touched will display an alphabetical keypad. RK280
must be entered and acceptance will be displayed for a short time on the screen. The
required action can then be carried out. The password allowance will automatically
cancel after a delay has expired.
- 53 -
Pub. 3580
The last four alarm events are displayed in the alarm window at the bottom of all
graphic pages.
Alarms or events appearing in the window [item 1] are colour coded as follows:
Touching on the alarm window on any graphic screen will display the alarm overview
page as follows:
Touch screen controls allow the operator to filter or page through the alarm list.
- 54 -
Pub. 3580
Note that this is an information screen only. All alarms are accepted through the
Ships Control Link communication link [if enabled] or from the ECU using the push-
button provided.
- 55 -
Pub. 3580
7 ROUTINE MAINTENANCE
The best assurance against serious failures occurring is for regular inspection of the
equipment. This should include regular exercise of the control system [i.e. starting,
speed control and stopping of the engine] in all modes of control.
iv) That all indications illuminate using the test facilities provided.
- 56 -
Pub. 3580
8 FAULT FINDING
8.1 General
Any fault finding should be tackled in a methodical manner and taking suitable
precautions if working on live equipment.
The approach to tackling problems is to first identify whether the fault exists internal
or external to the panel. Cage clamp terminals are provided in each panel on printed
circuit boards, modules and connection to the ships wiring. These provide a
convenient location to disconnect wiring to isolate signals and/or for connecting a
multi-meter.
Modules, fuses and relays are fitted with LED indicators to aid fault finding. LED’s
fitted to fuse holders will illuminate if the fuse has blown. Those fitted on relays will
illuminate when there is a supply on the coil. On each module a GREEN LED will
illuminate to indicate the supply is healthy.
8.2 Sensors
A sensor failure will generally be detected and displayed by the monitoring system or
ECU.
There are generally five types of sensor used. A different method has to be employed
for each type.
- 57 -
Pub. 3580
iii). PT1000: This is a 1000 ohm resistance probe that will change its
resistive properties in response to the heat applied to its
junction. This is generally used for low temperature ranges
[i.e. water coolant]. Disconnect and measure using a multi-
meter set to ohm's range for continuity. To simulate the
sensor, connect a potentiometer or decade box across the
panel terminals where 1000R=0 °C and 1385R=100 °C. The
sensor is converted to 4-20mA on the module it is connected
to and will be fused before being processed.
iv). 4-20mA: These are output from electronic equipment that are
generally monitoring pressure [i.e. lub oil] or position [i.e.
speed demand]. They are usually powered from the panel
[with the exception of the ships speed setting demand] and
are fused on the module it is connected to before being
processed. When powered from the equipment, check for an
energising supply by measuring the output and return
terminal voltage with reference to the supply 0v. The multi-
meter must be set to a dc voltage range and a lower voltage
would be expected on the return. To check the current loop
disconnect one terminal and wire the multi-meter selected to
a mA range in series between the terminal and disconnected
wire. To simulate the sensor, either a mA source [unpowered
transmitter] or potentiometer [powered transmitter] will be
required.
v). Perception Head: This may be a passive type [magnetic pick up] or active [24v
dc supplied] which will give an output when a metallic object
passes [i.e. starter ring teeth]. Check that no swarth has
collected on the head and that is set to the required gap
between head and teeth. For a passive type, disconnect the
panel terminals and check continuity with a multi-meter set to
ohms range. For an active type, check that the energising
supply is present. To simulate the sensor, an oscillator and
counter will be required.
- 58 -
Pub. 3580
8.3.1 General
Alarms are detected by the EFI or MAA software generated and consist of a
number of fault conditions. In normal operation these will be displayed on the
graphical display and are caused by the system failing to sense a switch or
analogue signal input, or not getting the expected feedback to a control output.
As an aid to fault finding, the V25 Operator Display can be used. The display
is selected to the appropriate controller using the switch provided on the
panel. To establish communications to the selected controller the HMI RESET
push-button must be momentarily operated. Note that if any position other
than EFI is selected, the graphical interface communications will fail.
Three menus are available to aid fault finding that enable the operator to
monitor inputs [display], switch outputs ON/OFF or modify parameters by
means of the keyboard [edit] and view active faults [alarm]. Comprehensive
details on how to select and navigate these menus are given in the Viking
User Manual in section 10 of this publication.
To display current alarms on the selected controller, press the MENU SELECT
key to cycle the display until the ALARM LED is illuminated then use the UP
and DOWN keys to move through the alarm list.
Operator Interface
MENU RESET
SELECT ALARM
ALARM
EDIT CANCEL
DATA EDIT
SAVE FINISH
DATA EDIT
PRESET
ACCESS
DATA
- 59 -
Pub. 3580
Fail To Prime
Alarm 01 of 01
19:37:31 04/03/07
S 0RPM L –33.3%
To display the status of the digital and analogue hardware inputs and outputs,
press the MENU SELECT key to cycle the display until the DISPLAY LED is
illuminated. The arrowed keys can then be used to navigate through the menu
system to display the required channel as detailed in figure 8.1.
Operator Interface
EDIT CANCEL
DATA EDIT
SAVE FINISH
DATA EDIT
PRESET
ACCESS
DATA
- 60 -
Pub. 3580
Ent er select ed
menu using DOW N
k ey.
Select INPU T or
OUTPU T m enu use U P k ey t o m ov e
using left/ right up one menu.
arrow k ey s.
Ent er select ed
menu using DOW N
k ey.
Selec t required
channel u sing
left/right arrow k eys .
- 61 -
Pub. 3580
The module provides fourteen wire break detection channels selected using jumper
settings. Settings are listed in section 2 of this manual. The wire break circuitry
monitors the voltage on the positive side of the shutdown circuit relay to check the
continuity of the wiring from the engine. The circuit monitoring the engine mounted
switches requires a 15K bridging resistor across its contacts. When two switches are
connected in parallel [for example, engine emergency stop input], each must have a
33K bridging resistor across its contacts. If the switch becomes disconnected the
feedback voltage falls to zero, the green healthy LED is extinguished and a contact
opens to initiate an alarm via the multiplexing interface to the MAA controller.
On the shutdown module, the continuity of the EFI shutdown relay is also checked. A
small current is passed through the coil and the voltage drop across it monitored. If
the coil becomes disconnected the voltage will rise to 24v, the green healthy LED is
extinguished and a contact opens to initiate an alarm via the multiplexing interface to
the MAA controller.
LED's are provided to indicate the status of individual wire break monitored channels
and are listed in table 1. DIP switches are provided for each wire break channel that
can be used to test the wire break detection circuit. This will not effect the state of the
shutdown circuit being tested.
A speed switch failed circuit is incorporated into the wire break alarm. If the engine
protections are commissioned and there is no running output from the speed switch,
the green healthy LED is extinguished and a contact opens to initiate an alarm via the
multiplexing interface to the MAA controller. Warning of speed switch failure is very
important as this provides the only over-speed protection for the engine.
LED Location
- 62 -
Pub. 3580
In the event of a wire break alarm, determine the sensor from the list above. For
engine equipment ensure that the sensor is not unplugged and that connections are
terminated correctly [both on the device and in the ICAM]. For the SCS emergency
stop and fire detected inputs, check cabling from the ICAM to the ECU and the ships
wiring to the ECU.
For speed switch failure, if the rpm indicator on the panel is functioning, check that
the module idle speed LED6 is illuminated. If not then the speed switch has a fault. If
the indicator is not functioning, ensure that the speed switch module power supply is
healthy [green LED2 is ON] and that the engine mounted perception head is plugged
in.
WARNING
The wire break condition must be rectified as soon
as possible. Whilst this alarm is present, the engine
is not fully protected and could be seriously damaged
in the event of a deteriorating or major fault
condition.
- 63 -
Pub. 3580
ohm's
°C[t90] 0 1 2 3 4 5 6 7 8 9 °C[t90]
0 600.0 602.3 604.6 607.0 609.3 611.7 614.0 616.4 618.7 621.0 0
10 623.4 625.7 628.0 630.4 632.8 635.1 637.4 639.8 642.1 644.4 10
20 646.7 649.1 651.4 653.8 656.1 658.4 660.7 663.0 665.4 667.7 20
30 670.0 672.4 674.7 677.0 679.3 681.7 684.0 686.3 688.6 690.9 30
40 693.2 695.6 697.9 700.2 702.5 704.8 707.2 709.5 711.8 714.0 40
50 716.4 718.7 721.0 723.3 725.6 727.9 730.3 732.5 734.8 737.2 50
60 739.4 741.8 744.1 746.3 748.7 751.0 753.2 755.6 757.9 760.1 60
70 762.5 764.8 767.0 769.3 771.7 774.0 776.2 778.5 780.8 783.1 70
80 785.4 787.7 790.0 792.2 794.5 796.8 799.1 801.4 803.7 806.0 80
90 808.3 810.5 812.8 815.1 817.4 819.7 821.9 824.2 826.5 828.8 90
100 831.0 830.3 835.6 837.8 840.1 842.4 844.7 847.0 849.2 851.5 100
110 853.7 856.0 858.3 860.6 862.8 865.1 867.4 869.6 871.9 874.1 110
120 876.4 878.6 880.9 883.2 885.4 887.7 890.0 892.2 894.5 896.8 120
130 899.0 901.3 903.5 905.8 908.0 910.3 912.5 914.8 917.0 919.3 130
140 921.5 923.8 926.0 928.3 930.5 932.8 935.0 937.2 939.5 941.7 140
150 944.0 946.3 948.4 950.7 952.9 955.1 957.4 959.6 961.9 964.0 150
ohm's
°C[t90] 0 1 2 3 4 5 6 7 8 9 °C[t90]
0 1000.0 1003.9 1007.8 1011.7 1015.6 1019.5 1023.4 1027.3 1031.2 1035.1 0
10 1039.0 1042.9 1046.8 1050.7 1054.6 1058.5 1062.4 1066.3 1070.2 1074.0 10
20 1077.9 1081.8 1085.7 1089.6 1093.5 1097.3 1101.2 1105.1 1109.0 1112.9 20
30 1116.7 1120.6 1124.5 1128.3 1132.2 1136.1 1140.0 1143.8 1147.7 1151.5 30
40 1155.4 1159.3 1163.1 1167.0 1170.8 1174.7 1178.6 1182.4 1186.3 1190.1 40
50 1194.0 1197.8 1201.7 1205.5 1209.4 1213.2 1217.1 1220.9 1224.7 1228.6 50
60 1232.4 1236.3 1240.1 1243.9 1247.8 1251.6 1255.4 1259.3 1263.1 1266.9 60
70 1270.8 1274.6 1278.4 1282.2 1286.1 1289.9 1293.7 1297.5 1301.3 1305.2 70
80 1309.0 1312.8 1316.6 1320.4 1324.2 1328.0 1331.8 1335.7 1339.5 1343.3 80
90 1347.1 1350.9 1354.7 1358.5 1362.3 1366.1 1369.9 1373.7 1377.5 1381.3 90
100 1385.1 1383.8 1392.6 1396.4 1400.2 1404.0 1407.8 1411.6 1415.4 1419.1 100
110 1422.9 1426.7 1430.5 1434.3 1438.0 1441.8 1445.6 1449.4 1453.1 1456.9 110
120 1460.7 1464.4 1468.2 1472.0 1475.7 1479.5 1483.3 1487.0 1490.8 1494.6 120
130 1498.3 1502.1 1505.8 1509.6 1513.3 1517.1 1520.8 1524.6 1528.3 1532.1 130
140 1535.8 1539.6 1543.3 1547.1 1550.8 1554.6 1558.3 1562.0 1565.8 1569.5 140
150 1573.3 1577.0 1580.7 1584.5 1588.2 1591.9 1595.6 1599.4 1603.1 1606.8 150
Conversion method
°C = (°F - 32)
1.8
°F = 1.8°C + 32
- 64 -
Pub. 3580
emf/mV
°C[t90] 0 1 2 3 4 5 6 7 8 9 °C[t90]
0 0 39 79 119 158 198 238 277 317 357 0
10 397 437 477 517 557 597 637 677 718 758 10
20 798 838 879 919 960 1000 1041 1081 1122 1163 20
30 1203 1244 1285 1326 1366 1407 1448 1489 1530 1571 30
40 1612 1653 1694 1735 1776 1817 1858 1899 1941 1982 40
50 2023 2064 2106 2147 2188 2230 2271 2312 2354 2395 50
60 2436 2478 2519 2561 2602 2644 2685 2727 2768 2810 60
70 2851 2893 2934 2976 3017 3059 3100 3142 3184 3225 70
80 3267 3308 3350 3391 3433 3474 3516 3557 3539 3640 80
90 3682 3723 3765 3806 3848 3889 3931 3972 4013 4055 90
100 4096 4138 4179 4220 4262 4303 4344 4385 4427 4468 100
110 4509 4550 4591 4633 4674 4715 4756 4797 4838 4879 110
120 4920 4961 5002 5043 5084 5124 5165 5206 5247 5288 120
130 5323 5369 5410 5450 5491 5532 5572 5613 5653 5694 110
140 5735 5775 5815 5856 5896 5937 5977 6017 6058 6098 140
150 6138 6179 6219 6259 6299 6339 6380 6420 6460 6500 150
160 6540 6580 6620 6660 6701 6741 6781 6821 6861 6901 160
170 6941 6981 7021 7060 7100 7140 7180 7220 7260 7300 170
180 7340 7380 7420 7460 7500 7540 7579 7619 7659 7699 180
190 7739 7779 7819 7859 7899 7939 7979 8019 8059 8099 190
200 8138 8178 8218 8258 8298 8338 8378 8418 8458 8499 200
210 8539 8579 8619 8659 8699 8739 8779 8819 8860 8900 210
220 8940 8980 9020 9061 9101 9141 9181 9222 9262 9302 220
230 9343 9383 9423 9464 9504 9545 9585 9626 9666 9707 230
240 9747 9788 9828 9869 9909 9950 9991 10031 10072 10113 240
250 10153 10194 10235 10276 10316 10357 10393 10439 10480 10520 250
260 10561 10602 10643 10684 10725 10766 10807 10848 10889 10930 260
270 10971 11012 11053 11094 11135 11176 11217 11259 11300 11341 270
280 11382 11423 11465 11506 11547 11588 11630 11671 11712 11753 280
290 11795 11836 11877 11919 11960 12001 12043 12084 12126 12167 290
300 12209 12250 12291 12333 12374 12416 12457 12499 12540 12582 300
310 12624 12665 12707 12748 12790 12831 12873 12915 12956 12998 310
320 13040 13081 13123 13165 13206 13248 13290 13331 13373 13415 320
330 13457 13498 13540 13582 13624 13665 13707 13749 13791 13833 330
340 13874 13916 13958 14000 14042 14084 14126 14167 14209 14251 340
350 14293 14335 14377 14419 14461 14503 14545 14587 14629 14671 350
360 14713 14755 14797 14839 14881 14923 14965 15007 15049 15091 360
370 15133 15175 15217 15259 15301 15343 15385 15427 15469 15511 370
380 15554 15596 15638 15680 15722 15764 15806 15849 15891 15933 380
390 15975 16017 16059 16102 16144 16186 16228 16270 16313 16355 390
400 16397 16439 16482 16524 16566 16608 16651 16693 16735 16778 400
410 16820 16862 16904 16947 16989 17031 17074 17116 17158 17201 410
420 17243 17285 17328 17370 17413 17455 17497 17540 17582 17624 420
430 17667 17709 17752 17794 17837 17879 17921 17964 18006 18049 430
440 18091 18134 18176 18218 18261 18303 18346 18388 18431 18473 440
450 18516 18558 18601 18643 18686 18728 18771 18813 18856 18898 450
460 18941 18983 19026 19068 19111 19154 19196 19239 19281 19324 460
470 19366 19409 19451 19494 19537 19579 19622 19664 19707 19750 470
480 19792 19835 19877 19920 19962 20005 20048 20090 20133 20175 480
490 20218 20261 20303 20346 20389 20431 20474 20516 20559 20602 490
500 20644 20687 20730 20772 20815 20857 20900 20943 20985 21028 500
510 21071 21113 21156 21199 21241 21284 21326 21369 21412 21454 510
520 21497 21540 21582 21625 21668 21710 21753 21796 21838 21881 520
530 21924 21966 22009 22052 22094 22137 22179 22222 22265 22307 530
540 22350 22393 22435 22478 22521 22563 22606 22649 22691 22734 540
550 22776 22819 22862 22904 22947 22990 23032 23075 23117 23160 550
560 23203 23245 23288 23331 23373 23416 23458 23501 23544 23586 560
570 23629 23671 23714 23757 23799 23842 23884 23927 23970 24012 570
580 24055 24097 24140 24182 24225 24267 24310 24353 24395 24438 580
590 24480 24523 24565 24608 24650 24693 24735 24778 24820 24863 590
600 24905 24948 24990 25033 25075 25118 25160 25203 25245 25288 600
610 25330 25373 25415 25458 25500 25543 25585 25627 25670 25712 610
620 25755 25797 25840 25882 25924 25967 26009 26052 26094 26136 620
630 26179 26221 26263 26306 26348 26390 26433 26475 26517 26560 630
640 26602 26644 26687 26729 26771 26814 26856 26898 26940 26983 640
650 27025 27067 27109 21152 27194 27236 27278 27320 27363 27405 650
660 27447 27489 27531 27574 27616 27658 27700 27742 27784 27826 660
670 27869 27911 27953 27995 28037 28079 28121 28163 28205 28247 670
680 28289 28332 28374 28416 28458 28500 28542 28584 28626 28668 680
690 28710 28752 28794 28835 28877 28919 28961 29003 29045 29087 690
700 29129 29171 29213 29255 29297 29338 29380 29422 29464 29506 700
710 29548 29589 29631 29673 29715 29757 29798 29840 29882 29924 710
720 29965 30007 30049 30090 30132 30174 30216 30257 30299 30341 720
730 30382 30424 30466 30507 30549 30590 30632 30674 30715 30757 730
740 30798 30840 30881 30923 30964 31006 31047 31089 31130 31172 740
750 31213 31255 31296 31338 31379 31421 31462 31504 31545 31586 750
760 31628 31669 31710 31752 31793 31834 31876 31917 31958 32000 760
770 32041 32082 32124 32165 32206 32247 32289 32330 32371 32412 770
780 32453 32495 32536 32577 32618 32659 32700 32742 32783 32824 780
790 32865 32906 32947 32988 33029 33070 33111 33152 33193 33234 790
800 33275 33316 33357 33398 33439 33480 33521 33562 33603 33644 800
- 65 -
Pub. 3580
9 DRAWINGS
- 66 -
1 2 3 4 5 6 7 8 9 10
C
L
DRG. 'X'
No. AE6550 SHT1 975
90 200
875
SPACER PIECES PANEL FIXING CENTRES WITH NO AV MOUNTS FITTED
SUPPLIED LOOSE 40
[FITTED IF CUSTOMER CHOOSES 805
A NOT TO USE AV MOUNTS SUPPLIED] AV MOUNT FIXING CENTRES
16 40 41
9 40 41
15 40 41
102 20 42
100 LP6 LP9 LP1 LP8
B 82.5 21 42
31 42 43 PB5
1 ENGINE SPEED
6 111
OPERATOR DISPLAY
Operator Interface
2 HOLES EFI OFF MAA
PB6
DIA 11
22 43
SW4 LPB1
25 40 41 42
1 HOLE - 56mm DIA REQUIRED LPB3
MOUNTS TO BE INSTALLED IN 5 32 42
C ORIENTATION SHOWN ON SHEET 3 CONTROL STATION
LOCAL REMOTE
ENGINE SPEED
LOWER RAISE
MANUAL ALARM
OFF
COMMISSION
ON
EMERGENCY
OVERRIDE 2
28 33 40 41 42
ENCLOSURE LPB4
WASHER
CENTERING 18 42
C/L FIXING HOLES NO AV MOUNTS
CLUTCH CLUTCH
WASHER IN OUT PB3 START STOP
C/L FIXING HOLES NO AV MOUNTS
CUSTOMER
1600
34 35 36
AV MOUNT MOUNTING PB4
1560
BRACKET
27 40 41 42
1518
WASHER
23 42
D
NOTE :- SHEET No.1 GIVES LATEST ISSUE
NUMBER FOR DRAWING.
INDIVIDUAL SHEET ISSUE NUMBERS
AS GIVEN BELOW.
ISSUE No.
SHEET No.1 1 2
" No.2 1 2
" No.3 1 1
" No.4 1 2
" No.5 1 1
1
ALL DIMENSIONS IN MILLIMETRES
LAYER 3 MASKED
4 C
3
77
4 77 C
78 4
4 78
79 4 Regulateurs C
4 79
4 Europa C
DIA 14
11
CHECKED
ø
TITLE
MOUNTS TO BE INSTALLED IN
ORIENTATION SHOWN ON SHEET 3 100
G ENGINE CONTROL UNIT
190
55 865 55
GENERAL ARRANGEMENT
INSTALLATION NOTE:
BASE MOUNTS ARE DESIGNED TO TAKE THE FULL LOAD OF C/L MOUNTING HOLE FIXING CENTRES
THE PANEL. APPROVED DRAWING No.
ON INSTALLATION THE PANEL SHOULD THEREFORE BE SECURED
ON THE BASE MOUNTS FIRST. THE TOP CUSTOMER MOUNTING
DESIGN PRODUCTION
AE6550
BRACKETS CAN THEN BE FIXED IN THEIR FINAL LOCATION.
SHEET 1 OF 5 SHEETS
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged ,copied or reproduced without written authorisation of the company. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-20
1 2 3 4 5 6 7 8 9 10
DRG.
No. AE6550 SHT2
*
71 72 73 37 38 46 47
A 14 14 2 2
TRUNKING 25 X 60
ER10
ER11
*ER1
*ER2
*ER3
*ER4
*ER5
*ER6
*ER7
*ER8
*ER9
*MH
*ME
*MA
*AA
*PT
46 47 1 5 9 13 17 21 4 8 12 16 20 23 25 29 32 28 33
TRUNKING 43 X 60 6 6
3 7 11 15 19 2 6 10 14 18 22 24 27 30 26 31
B 50 51
5 5
13-14
[1-4]
[5-8]
9-12
ITEM 54 - FUSED TERMINAL
RC
RC
RD
5-8
CP
CP
CP
RS
TC
LS
45
BLOCK LAYOUT
53
1
WIRE BREAK RESISTOR
62 63
TRUNKING 43 X 60
5mm LOCAL TRUNKING 43 X 60 ACROSS GPT CONTACT
DIN PORT 1
2
EARTH POINT PROTOCOL
MODBUS
V25 VISION
GCT
GPT
GN
GE
EG
EB
EP
TRUNKING 25 X 60
VIKING 25 - DIN TRUNKING 25 X 60
CONTROLLER
62 63
97 98 117 14 1
C TRUNKING 25 X 60
121
121
121
122
122
122
123
123
127
167
168
438
2 SERIAL PORT 1 CANBUS
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8
86 87 88
ACTUATOR DIGITAL DIGITAL
SERIAL PORT 2 OUTPUTS INPUTS
OUTPUT
D1-9
C H9 -1 6
ENGINE SPEED
& ALARMS
VIKING 25 ALARM LEGEND
SEE MANUAL FOR RELEVANT
STORING
PARAMETERS 147
ALARM CODES
D
TRUNKING 43 X 60
3 7 11 15 19 2 6 10 14 18 22 24 27 30 26 31
108 93
TRUNKING 25 X 60
D TRUNKING 25 X 60
M722802
ANALOGUE 232
TRUNKING 43 X 60
OK
COND.
SF2
VM * * * SF1
PCB 1 A B C
SHAFT SPEED
90 105 SWITCH
TRUNKING 25 X 60
139
TRUNKING 25 X 60
142
125
143
LAYER 3 MASKED
123 TRUNKING 60 X 60 2
150 151 C
4
TB1 TB2 TB3 TB4 140 136 SEE NOTE
5mm LOCAL TB5 C
EARTH POINTS 2
DATE AND
ISSUE ALTERATION FILMED
COPYRIGHT C
DRAWN SCS
RK280 - ECU TYPE 3
CHECKED
This document is the exclusive property of Regulateurs Europa Ltd and is strictly confidential. C Regulateurs Europa Ltd 2006 REGULATEURS EUROPA FORM No
It must not be divulged ,copied or reproduced without written authorisation of the company. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-20
1 2 3 4 5 6 7 8 9 10
DRG.
No. AE6550 SHT3
E
LAYER 3 MASKED
C
F
1 C 23.05.06 ORIGINAL ISSUE
DATE AND
ISSUE ALTERATION FILMED
COPYRIGHT C
DRAWN SCS
RK280 - ECU TYPE 3
CHECKED
TITLE
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-10
1 2 3 4 5 6 7 8 9 10
DRG.
No. AE6550 SHT4
ITEM CIRCUIT PART No. DESCRIPTION No. OFF REMARKS LEGEND ITEM CIRCUIT PART No. DESCRIPTION No. OFF REMARKS LEGEND
A No. REF. No. REF.
1 ENCLOSURE 1 71 94-218/01 TOGGLE SWITCH 1 DIN PORT 1 : MODBUS/VIKING VISION
2 72 AE6509 SWITCH LEGEND 1
3 92 G 34 NAMEPLATE 1 73 AE6510 SWITCH MOUNTING PLATE 1
4 62 G 23B SERIAL NUMBER PLATE 1 74
5 97-041/01/02 HOURS RECORDER AND GASKET 1 75 92-281/58 M4 x 10 S.S SCREW 4
6 02-079/05 HMI 1 76 92-281/62 M5 x 10 S.S SCREW 110
7 06-006/01 INSTRUMENT : 0-1200 rpm 1 77 92-281/65 M2.5 x 12 S.S SCREW 8
8 78 92-281/67 M2.5 S.S SHAKEPROOF WASHER 8
9 LP6 83-245/35 INDICATOR - YELLOW 1 HIGHLAND - TYPE 04 ALARM ACTIVE 79 92-281/68 M2.5 FULL NUT 8
10 80 92-281/69 M5 x 20 S.S SCREW 6
11 81
12 82
B 13 LP9 83-245/35 INDICATOR - YELLOW 1 HIGHLAND - TYPE 04 REMOTE CONTROL NOT ACCEPTED 83
14 LP8 83-245/36 INDICATOR - GREEN 1 '' '' '' '' ENGINE RUNNING 84
15 LP1 83-245/38 INDICATOR - WHITE 1 '' '' '' '' REMOTE CONTROL 85
16 LP2 83-245/35 INDICATOR - YELLOW 1 '' '' '' '' BACK-UP MODE 86 DG1-5 94-172/52 SINGLE DECK TERMINAL : 4 CONDUCTOR 5 FITTED WITH 2 X IN4007 DIODE
17 87 DG6-9 94-172/53 SINGLE DECK TERMINAL : 4 CONDUCTOR 6 FITTED WITH 1 X IN4007 DIODE
18 PB2 83-245/39 PUSH BUTTON - RED 1 '' '' '' '' STOP 88 94-172/54 END PLATE 2
19 PB1 83-245/41 PUSH BUTTON - GREEN 1 '' '' '' '' START 89
20 PB5 83-245/43 PUSH BUTTON - WHITE 1 '' '' '' '' ALARM MUTE 90 EC416 FREE PART SOCKET SET 1 ANALOGUE CONDITIONING MODULE
21 PB6 83-245/43 PUSH BUTTON - WHITE 1 FITTED WITH BLACK DIFFUSER AE4541P24B ALARM RESET 91 EC417 FREE PART SOCKET SET 1 SERIAL CHANGEOVER MODULE
22 PB7 83-245/43 PUSH BUTTON - WHITE 1 FITTED WITH BLACK DIFFUSER AE4541P101B HMI RESET 92 EC418 FREE PART SOCKET SET 2 SLOWDOWN/SHUTDOWN MODULE
23 PB4 83-245/40 PUSH BUTTON - YELLOW 1 '' '' '' '' TEST LAMPS 93 EC419 FREE PART SOCKET SET 1 SPEEDSWITCH MODULE
C 24 LPB3 83-245/63 PUSH-BUTTON [ILLUM] : RED 1 '' '' '' '' PROTECTION RESET 94 EC420 FREE PART SOCKET SET 2 SERIAL CONNECTION PCB
25 LPB1 83-245/64 PUSH-BUTTON [ILLUM] :AMBER 1 '' '' '' '' EFI CONTROLLER RESET 95 EC421 FREE PART SOCKET SET 2 V25
26 LPB5 83-245/67 PUSH-BUTTON [ILLUM] :WHITE 1 '' '' '' '' CLUTCH IN 96
27 LPB6 83-245/67 PUSH-BUTTON [ILLUM] :WHITE 1 '' '' '' '' CLUTCH OUT 97 2500G061P2 VIKING 25 DIN 1
28 LPB4 83-245/64 PUSH-BUTTON [ILLUM] :AMBER 1 '' '' '' '' EMERGENCY OVERRIDE 98
29 SW1 83-245/100 LEVER OPERATED SWITCH 1 HIGHLAND TYPE 04 - OFF/ON CONTROL STATION LOCAL REMOTE 99
30 SW3 83-245/100 LEVER OPERATED SWITCH 1 HIGHLAND TYPE 04 - OFF/ON MANUAL ALARM COMMISSION 100 2500G024 OPERATOR DISPLAY 1
31 SW4 83-245/108 LEVER OPERATED SWITCH 1 HIGHLAND TYPE 04 - 3 POSITION VIKING INTERFACE SELECTION 101 ANALOGUE MULTIPLEXING MODULE 1
32 SW2 83-245/110 LEVER OPERATED SWITCH 1 HIGHLAND TYPE 04 - CENTRE BIASED ENGINE SPEED LOWER / RAISE 102 EC(M)724901 SERIAL CHANGEOVER MODULE 1
33 83-245/82 PROTECTIVE FLAP 1 HIGHLAND - TYPE 04 103
34 PB3 83-245/106 EMERGENCY STOP PUSHBUTTON 1 HIGHLAND TYPE 04 - TWIST TO RELEASE EMERGENCY STOP 104
35 83-245/107 EMERGENCY STOP PUSHBUTTON SHROUD 1 HIGHLAND - TYPE 04 105 EC(M)722802 ANALOGUE CONDITIONING 1
D 36 83-245/72 CONTACT BLOCK : 2 N/O [BUTT ACTION] 1 '' '' '' '' 106
37 ER1,2,3,4,5,6,7,8&9 97-040/07 RELAY 2P C/O 17 107
A,B,C,ME,MH,
38 MA,AA,PT 97-040/08 RELAY BASE 17 108 05-033/01 SPEEDSWITCH 1
39 109
40 97-219/01 LED : WHITE MBC 10 110
41 83-245/45 DIODE BLOCK 10 111 2500G022P05 HARNESS [GRAPHICAL HMI - SERIAL C/O MODULE] 1
42 83-245/21 CONTACT BLOCK : 2 N/O 13 HIGHLAND - TYPE 04 112 2500G022P06 HARNESS [APP CONT. - ANALOGUE COND. PCB] 1
43 83-245/23 CONTACT BLOCK : 1 N/O, 1N/C 4 '' '' '' '' 113 2500G022P07 HARNESS [APP CONT. - SERIAL C/O MODULE] 1
44 114 2500G022P08 HARNESS [SERIAL C/O MODULE - OP. DISPLAY] 1
45 EG 97-040/06 RELAY : BISTABLE 2P C/O 1 115 2500G022P09 HARNESS [SERIAL C/O MODULE - VIKING VISION PORT] 2
46 TC,RC1-4,RC5-8 97-040/02 RELAY : 24v dc 4P C/O 10 116 2500G022P10 RIBBON CABLE [DIN CONT. - ANALOGUE COND. PCB] 2
ER10,ER11,CP5-8,
47 97-040/04 RELAY BASE : 4P C/O 11 117 2500G022P15 RIBBON CABLE [I/O EXPANDER - SHUTDOWN MODULE] 5
E CP9-12, RD,GN,GE
48 118 2500G022P16 RIBBON CABLE [SHUTDOWN - SLOWDOWN MODULE] 3
49 97-040/05 RELAY CLIP 33 SUPPLIED AS PAIRS 119
50 LS,RS,CP, 97-040/01 RELAY : 24v dc 2P C/O 5 120 2500G022P18 HARNESS [APP CONT. - ANALOGUE COND. PCB] 1
EB,EP
51 97-040/03 RELAY BASE : 2p C/O 5 121
52 122
53 GPT,GCT 94-212/05 MULTI-FUNCTION TIMER : 1P C/O 2 123 EC[M]724601 DIGITAL INPUT MODULE 1
54 FS1-33 94-175/17 FUSEHOLDER : 5 X 20mm FUSE 33 WITH FUSE BLOWN INDICATION 124
55 94-175/09 END PLATE 2 125 EC[M]724502 ANALOGUE INPUT MODULE 1
56 94-175/11 ADJACENT JUMPER 16 126
57 FS7-10,15,16,25-29 94-030/05 FUSELINK : 1A 11 127
58 FS1-4,11,12,17,18,21,22 94-030/08 FUSELINK : 2A 6 128
2 C 20.02.07 AS BUILT
GENERAL ARRANGEMENT
1 C 23.05.06 ORIGINAL ISSUE APPROVED DRAWING No.
DATE AND
DESIGN PRODUCTION
AE6550
ISSUE ALTERATION FILMED
COPYRIGHT C SHEET 4 OF 5 SHEETS
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged ,copied or reproduced without written authorisation of the company. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-05
1 2 3 4 5 6 7 8 9 10
DRG.
No. AE6550 SHT5
F 189
190
191
192
193
C SCALE 1:4 CONTRACT :-
194
195 C DRAWN SCS
196
RK280 - ECU TYPE 3
C CHECKED
197
198 C TITLE
199
G C ENGINE CONTROL UNIT
200
C
GENERAL ARRANGEMENT
1 C 23.05.06 ORIGINAL ISSUE APPROVED DRAWING No.
DATE AND
DESIGN PRODUCTION
AE6550
ISSUE ALTERATION FILMED
COPYRIGHT C SHEET 5 OF 5 SHEETS
This document is the exclusive property of Regulateurs Europa Ltd.and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged ,copied or reproduced without written authorisation of the company. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-05
1 2 3 4 5 6 7 8 9 10
AE6552 sht 1
DRG.
No. 4 OFF 1360 x 190 x 18 INSULATION 127
SLOTTED LATCHES HEAT SHIELD FIXED IN 6 PLACES
WITH M6 SCREWS. 114.3 43
14.2
PER DOOR
EACH FIXING TO HAVE 2 OFF
WASHERS AND A 15mm
LG SPACER
A
48
63
52 53 54 8 9
3
DIA 4
6 12 6
1620 AE6551P11
50 1360 100 8 9 55 57
6 6 4
190
18
OIL COOLER
60
DETAIL OF WIRE ROPE
ANTI-VIBRATION MOUNT
70
(ITEM 70)
18.5
9.5
132
B
12
415
BEFORE POWER
ENSURE SKIRT
IS APPLIED
IS FITTED
665
WA R N I N G
28.528.5
!
DO NOT STAND DO NOT STAND DO NOT STAND
ON THIS SURFACE ON THIS SURFACE ON THIS SURFACE 57.15 57.15
65
SPACER
C (ITEM 69)
AE6551P13
111
9 8
6 6
3 OFF 2 OFF
1 LIFT OFF SIDE
DOORS MOUNTING
1770 PLATES
(1 OFF 55 57
EACH SIDE) 4
95
E
5
41 50
4 6
57 56
42 51
9 4 12
43 15
8 12
46 44 16 47
8 12
45
1070 350
8
8
4 OFF 1016 x 635 mm 49 48
3 OFF 8 CENTRE LINE
MOUNTING 9 WIRE ROPE SHEET OF OF ENGINE
PLATES 8 ANTI-VIBRATION 25 x 25 x 2 mm
MOUNTS STAINLESS STEEL
NOTE :- SHEET No.1 GIVES LATEST ISSUE
WELD MESH NUMBER FOR DRAWING.
FIXED TO BOTTOM INDIVIDUAL SHEET ISSUE NUMBERS
F OF ENCLOSURE AS GIVEN BELOW.
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-25
1 2 3 4 5 6 7 8 9 10
AE6552 sht 2
DRG.
No.
SKT1
MODULE 1 MODULE 4 26
SIGNAL CONDITIONING [16 CHANNELS] ACT UAT OR
SERIAL PORT 1 CANBUS
C H1 C H2 C H3 C H4
DIGITAL
C H5 C H6 C H7 C H8 C H1 C H2 C H3 C H4
DIGITAL
C H5 C H6 C H7 C H8
SIGNAL CONDITIONING [16 CHANNELS]
SERIAL PORT 2 OUT PUTS INPUTS
74
OUTPUT
D I GITAL OUTPUTS
C H9 - 1 6
ENGINE SPEED
& ALARMS STORING
VIKING 25 ALARM LEGEND PARAMETERS
SEE MANUAL FOR RELEVANT
ALARM CODES
67
D IGITAL INPUTS
C H9 - 1 6
26 PROCESSOR
16
HEALTHY
CONTROL MODULE
CONTROL MODULE
SIGNAL CONDITIONING [16 CHANNELS] REGULATEURS EUROPA SIGNAL CONDITIONING [16 CHANNELS] 13 14 15 16 17 18 19 20 21 22
22 21 20 19 18 17 16 15 14 13
24V
POWER SUPPLY
0V
ANALOGUE ANALOGUE SPEED
OUT PUTS INPUTS INPUTS
40 40 3 3 3
C H1 C H2 C H3 C H4 C H5 C H6 C H7 C H8 C H1 C H2 C H3 C H4 C H5 C H6 C H7 C H7 C H8 C H1 C H2
3 3 3 40 40
A BANK
B BANK
B 25
SKT1
MODULE 3 MODULE 9
25 SIGNAL CONDITIONING [16 CHANNELS] SERIAL PORT 1 CANBUS SHUTDOWN PROTECTIONS 29
C H1 C H2 C H3 C H4 C H5 C H6 C H7 C H8 C H1 C H2 C H3 C H4 C H5 C H6 C H7 C H8
D I GITAL OUTPUTS
C H9 - 1 6
ENGINE SPEED
& ALARMS STORING
VIKING 25 ALARM LEGEND PARAMETERS
SEE MANUAL FOR RELEVANT
ALARM CODES
D IGITAL INPUTS
C H9 - 1 6
PROCESSOR
HEALTHY
12
MOD. MODULE
MODULE
8
7 6 Viking 25
RTD MAA 24V
REGULATEURS EUROPA
SPEED POWER SUPPLY
TRIP SIGNAL
0V
ECU TERMINALS 1 - 80
ANALOGUE ANALOGUE SPEED
SWITCH C H1 C H2 C H3 C H4
OUT PUTS
C H5 C H6 C H7 C H8 C H1 C H2 C H3 C H4
INPUTS
C H5 C H6 C H7 C H7 C H8
INPUTS
C H1 C H2
AMP. CONDITION
TERMINALS
X01 - 16 25 x 60 TRUNKING
C
31 32 33 34 35 36 37 38 39 40 30 72 28 MAA CONTROLLER 24 64 65 73 31 32 33 34 35 36 37 38 39 40 12
4 4
INTERNAL LAYOUT IDENTIFYING THE MAIN CABLING ROUTES CROSS SECTION VIEW IDENTIFYING
INTERNAL SIDE WALL CABLE ROUTES
GLAND PLATES ON UNDER SIDE A BANK 62 B BANK GLAND PLATE ON UNDER SIDE
OF ICAM PANEL FOR ENGINE OF ICAM PANEL FOR ENGINE
WIRING HARNESSES. WIRING HARNESSES.
D 59
B-EXH
B BANK EXHAUST
SKT1
MODULE 1 MODULE 4
SOT SIGNAL CONDITIONING [16 CHANNELS] ACT UAT OR
OUTPUT
SERIAL PORT 1
SERIAL PORT 2
CANBUS
C H1 C H2 C H3 C H4
DIGITAL
OUT PUTS
C H5 C H6 C H7 C H8 C H1 C H2 C H3 C H4
DIGITAL
INPUTS
C H5 C H6 C H7 C H8
D I G ITAL OUTPUTS
OIL SPLASH
C H9 - 1 6
ENGINE SPEED
& ALARMS STORING
VIKING 25 ALARM LEGEND PARAMETERS
SEE MANUAL FOR RELEVANT
ALARM CODES
D IGITAL INPUTS
MBT
C H9 - 1 6
PROCESSOR
HEALTHY
MAIN BEARING
MODULE 2
Viking 25 MODULE 5 B-EFI
SIGNAL CONDITIONING [16 CHANNELS]
24V
POWER SUPPLY
0V
ANALOGUE
REGULATEURS EUROPA
ANALOGUE SPEED
SIGNAL CONDITIONING [16 CHANNELS] B BANK SOLENOIDS
OUT PUTS INPUTS INPUTS
C H1 C H2 C H3 C H4 C H5 C H6 C H7 C H8 C H1 C H2 C H3 C H4 C H5 C H6 C H7 C H7 C H8 C H1 C H2
A-EXH B-FWE-PRES
A BANK EXHAUST
ASSORTED SIGNALS
A-FWE-SEN SKT1
B-FWE-SEN
E ASSORTED SIGNALS MODULE 3 MODULE 9 PICK-UPS
SIGNAL CONDITIONING [16 CHANNELS] ACT UAT OR
SERIAL PORT 1
SERIAL PORT 2
CANBUS
C H1 C H2 C H3 C H4
DIGITAL
C H5 C H6 C H7 C H8 C H1 C H2 C H3 C H4
DIGITAL
C H5 C H6 C H7 C H8
SHUTDOWN PROTECTIONS
OUTPUT OUT PUTS INPUTS
D I G ITAL OUTPUTS
B-FE-PRES
C H9 - 1 6
A-EFI
A BANK SOLENOIDS MODULE MOD.
MODULE 6 Viking 25
8 7
MAA SIGNAL REGULATEURS EUROPA
OE-EFI
RTD
ECU [CABLE 2 - CONTROL]
24V
TRIP RTD/4-20mA
ANALOGUE
OUT PUTS
ANALOGUE
INPUTS
SPEED
INPUTS
SWITCH
C H1 C H2 C H3 C H4 C H5 C H6 C H7 C H8 C H1 C H2 C H3 C H4 C H5 C H6 C H7 C H7 C H8 C H1 C H2
AMP.
TERMINALS OE-COMM
X01 - 16 ECU [CABLE 1 - SIGNAL]
60
61
GLAND PLATE ON UNDER SIDE
F OF ICAM PANEL FOR ECU
INTERNAL LAYOUT IDENTIFYING THE MAIN CUSTOMER CABLING ROUTES WIRING HARNESSES.
W.R.T. EXTERNAL CONNECTIONS
C DRAWN S.N.G.
C CHECKED
C TITLE
RK280
INTEGRATED CONTROL
G C AND MONITORING ENCLOSURE
(ICAM) - TYPE 3
2 C 19.02.07 AS BUILT
LAYOUT/INSTALLATION
1 C 04.07.06 ORIGINAL ISSUE APPROVED DRAWING No.
DATE AND
DESIGN PRODUCTION
AE6552
ISSUE ALTERATION FILMED
COPYRIGHT C SHEET 2 OF 3 SHEETS
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-25
1 2 3 4 5 6 7 8 9 10
AE6552 sht 3
DRG.
No.
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-25
1 2 3 4 5 6 7 8 9 10
DRG.
No. L 5471 Sht 1
LINE No.
100
A
101
102 FS1-2A
109 109 117 121
109 +in +out
109 FILTER VIKING 25 DATA INTERFACE CONTROLLER
MCB1 109 FS2-2A LINE 218
110 110 SF1 118 122
103 25A 110 -in -out
DB1 110
101 1 2 105 110 2.5mm FS3-2A
+ TB5/1 8 123
NORMAL SUPPLY 110, s
+ -
VIKING 25 EFI CONTROLLER
104 24Vdc (18-32V) 102 3 4 106 A FS4-2A
- TB5/2 124 LINE 400
1
105
FS5-3A
109 125
B 106
110
FS6-3A
126
SHUTDOWN PROTECTIONS
LINE 600
MCB2
25A 2.5mm
107 DB2 FS7-1A
103 1 2 107 127
+ TB5/3 8 4mm
UPS SUPPLY + - CONTROLS
111, s B FS8-1A LINE 500
24Vdc (18-32V) 104 3 4 108 128
108 - TB5/4 1
4mm 4mm FS9-1A
129
121
109 COMMON INDICATIONS
FS10-1A LINE 750
104 130
3 4 309 24V DC NORMAL
A-1 SUPPLY HEALTHY
110 FS11-2A
107 131
3 4 310 24V DC UPS
DI SOLENOIDS
B-1 SUPPLY HEALTHY FS12-2A
CONTROLLER 132 LINE 600
111 124 LINE 314
C 3
C-1
4 311 EFI EQUIPMENT CONTROL
SUPPLY HEALTHY FS13-3A
133
312 PANEL CONTROL
112 12 CLUTCH CONTROL
11 VOLTAGE HEALTHY FS14-3A
134 LINE 868
14
1 VOLTS
113 MONITOR FS15-1A
3 VM1 135
GEARBOX SUPPLY
FS16-1A LINE 868
FS17-2A 136
114 165
TB2/81
FS18-2A NOT USED
166
TB2/82
115
FS19-3A
116
D FS20-3A NOT USED
117
167
LINE 629
120
168
LINE 626
121 MCB3
16A 2.5mm
FS23-3A
E 109 1 2 141
+in +out
145 2.5mm 153
TB4/3 13 'A' BANK CONTROL 24v
FILTER
122 FS24-3A
110 3 4 142 SF2 146 154
-in -out TB4/4 23 'B' BANK CONTROL 24v
FS25-1A
155
123 TB4/5 01 SENSOR 1 SET 24v
FS26-1A
156
8 1 TB4/6 05 SENSOR 1 SET 0v
C
124 FS27-1A C
2.5mm 157
TB4/7 07 SENSOR 2 24v
EFI EQUIPMENT CONTROL
FS28-1A C
SUPPLY STATUS 158
125 112, S TB4/8 11 SENSOR 2 SET 0v
FS29-1A C
159 BCM BACK-UP CONTROLS
LINE 322
126 601 601 FS30-6.3A
12 11 31 32 147 160 C
TB4/10 14 'A' BANK SOLENOID SUPPLY
D-1 D-2
F FS31-6.3A
161 2 C 21.02.07 ICAM INTERCONNECTING NUMBERS ADDED
127 TB4/11 16 'A' BANK 0V
FS32-6.3A 1 C 07.06.06 ORIGINAL
162
TB4/12 24 'B' BANK SOLENOID SUPPLY
128 FS33-6.3A DATE AND
163 ISSUE ALTERATION FILMED
TB4/13 26 'B' BANK 0V COPYRIGHT C
2.5mm
129 DRAWN RJN CONTRACT :-
SHEET 1 OF 10SHEETS
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-EL
1 2 3 4 5 6 7 8 9 10
DRG.
No. L 5471 Sht 2
LINE NO.
A 200
VIKING 25 DIN
201
EC[P]720501
88
89 SPEED
INPUT
90 CH1
202
NOT USED
203 91
92 SPEED
INPUT
93 CH2
204
HARNESS HARNESS
ANALOGUE
ANALOGUE 2500G022P10 2500G022P19 CONDITIONING
205
CONDITIONING
B EC[M]722802 64 + 42
SHIPS CONTROL SYSTEM
251 + SHAFT SPEED
206 26 ANALOGUE ANALOGUE 3 TB1/9
65 - 41 FS1 4 -20 mA
INPUT OUTPUT 2 REFER TO
CH1 CH1 252
27 66 0V 40 1 TB1/10 SHEET 10
207
67 + 45
201 253 +
TB1/19 29 +ve -ve ANALOGUE ANALOGUE 6 TB1/7 ENGINE SPEED
68 - 44 FS2
EC[P]722601
EC[P]722601
208 FS10 INPUT OUTPUT 5 4 -20 mA =
202 CH2 CH2 254 0 - 1200 RPM
TB1/20 30 69 0V 43 4 TB1/8
209 70 + 48
255
203 Pt1000/4-20mA ANALOGUE ANALOGUE 9 TB1/3
TB1/21 33 CONVERTOR 71 - 47 FS3 ENGINE SPEED
204 INPUT OUTPUT 8
TB1/22 32 [0-150°C] CH3 CH3 256 4-20mA=0-1200rpm
210 72 0V 46 7 TB1/4
122
16
21 B 51 A
17 CH.8 O/S TEST SWITCH DISABLED
22 A 52 B
1 18
220 CH.6 EXTERNAL LOOP POWER 23 A 53 B
4 19
H 104 24 B 54 B
PL8 20
PL5 L 105 CH.7 INTERNAL LOOP POWER 25 B 55 B
E 221 SERIAL PORT COM 106
21
26 B
CH3 3 27 B
CAN BN 361
121 H 107 28 B
37 +24v B 362 TO VIKING 25 MAA CONTROLLER
222 PWR PL6 L 108 LINE 330 29 B
122 COM 109 30 B
38 0v
3 3
243
121
122
223
A 98 TB1/15 RS485 MODBUS
244
PL3 B 99 TB1/16 COMMUNICATION
245 TO SHIP C
SERIAL PORT COM 100 TB1/17
224 CH2 TB1/18
RS485 C
A 101
PL4 B 102
C
COM 103
225 SG
LINE 301 4
C
3 W 239
RS485 MODBUS
SERIAL PORT TB1/11
F 226 CH1 PL1 2
R
BK
240
241
TB1/12 COMMUNICATION
TO OPTIONAL
2 C 21.02.07 ANALOGUE COND. PART No. AMENDED
RS232 TB1/13 MONITORING SYSTEM
5
TB1/14 1 C 07.06.06 ORIGINAL
227 SERIAL
CONECTION ISSUE
DATE AND
ALTERATION FILMED
COPYRIGHT C
EC[M]723101
228 GRAPHICAL HMI
DISPLAY DRAWN RJN CONTRACT :-
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-EL
1 2 3 4 5 6 7 8 9 10
DRG.
No. L 5471 Sht 3
LINE No.
300
121
122
302 20 DI 0v
TB2/41 4
NOT USED 301 DO-1
TB2/42 21 DI-1 5
303 6
SPARE DO-2
23 DI-2 7
I/P
8
304 SPARE DO-3
25 DI-3 9
PORT 1 I/P
MODBUS PROTOCOL 10
304 DO-4
27 DI-4 11
305 SW5
12
SPARE DO-5
29 DI-5 13
I/P
TB2/83 14
NOT USED DO-6
B 306 TB2/84
306
31 DI-6 15
16
SPARE DO-7
33 DI-7 17
307 I/P
18
SPARE DO-8
35 DI-8 19
I/P
308
122
309 2500G022P23
ANALOGUE PL6 PL1
STATUS INPUTS LINE 804
2500G022P22
V25 I/O
310 DIG I/P MODULE PL6
STATUS INPUTS LINE 907
PL8 EXPANDER
EC[P]722201
ANALOGUE PL4 2500G022P33
311 CONTROL LINES LINE 805 PL2
C DIGITAL PL5
CONTROL LINES LINE 909
312
DIGITAL DIGITAL
COMMON CONNECTION CONNECTION
313 EC[P]722501 EC[P]722501
24V DC NORMAL 309
SUPPLY HEALTHY 110 DI-9 127
DO-9 119
24V DC UPS 310
314 LINE 111 111 DI-10
SUPPLY HEALTHY
DO-10 120
EFI EQUIPMENT CONTROL 311
112 DI-11
SUPPLY HEALTHY
315 DO-11 121
PANEL CONTROL 312
113 DI-12
VOLTAGE HEALTHY
627 DO-12 122
6 5 313
316 MAA CONTROLLER HEALTHY 114 DI-13
MH-2
DO-13 123
D EMERGENCY OVERRIDE ENABLED
10
410
2 314
115 DI-14
ER11-2
317 407 DO-14 124
6 5 315
EFI CONTROLLER HEALTHY 116 DI-15
ER8-2 DO-15 125
SPARE 117 DI-16
318 I/P
DO-16 126
118
319
320
121
122
321
E
322 LINE 812
FS29
323 ICAM
159
502
4 12 8 [ON-ENGINE]
503
8 357 12 359 LS-2 TERMINALS
324 159
506 RS-2 8 TB4/15 33 +VE SUPPLY C
12
13 L R 14 352
4 358
RC-8 TB4/16 34 LOWER SPEED C
325
353
TB4/17 35 RAISE SPEED C
23 24 SW2
LINE 401 354
326 TB4/18 36 START C
13 14
PB1
F LINE 406
13 14
355
TB4/19 37 STOP 2 C 21.02.07 ICAM INTERCONNECTING NUMBERS ADDED
327 PB2
DG6
DG7
DG8
DG9
LINE 404
4
356
TB4/20 39 CHECK LOCAL PANEL 1 C 07.06.06 ORIGINAL
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-EL
1 2 3 4 5 6 7 8 9 10
DRG.
No. L 5471 Sht 4
A 400
ICAM [ON-ENGINE]
123
124
TERMINALS TERMINALS
123 124
TB4/21 41 42 TB4/38
401 EFI 0v
5 401 CONTROLLER
REMOTE CONTROL 507 TB4/22 43 451 8 ER 1 START FUEL PUMPS
9 LINE 326 DO-09 119 TB4/39 520, 523
1
1 410 13 14 411 1 4 402
402 LOWER SPEED TB4/27 111 DI-10
RC-1 412 2 452 8 1
ER CONTROL STATIONS MATCHED
DG1 DO-10 120 TB4/40
2 715, 506
403 413 1 4 403
RAISE SPEED 43 44 TB4/28 112 DI-11 453 8 ER 1 RUNNING AT IDLE
L R SW2 414 2 DO-11 121 TB4/41
DG2
3 861, s
LINE 327
404 13 14 415 1 4 404 454 8 ER 1 START L.O PUMP
STOP TB4/26 110 DI-09 DO-12 122 TB4/42
416 2 4 525, s
PB2
LINE 764 DG3
455 8 ER 1 STOP
405 ENABLE/DISABLE 13 14 417 1 4 405 D0-13 123 TB4/43
TB4/23 44 5 604, 614
EMERGENCY OVERIDE
B LINE 326
LPB4
418 2
DG4
456 8 ER 1
DO-14 124 TB4/44 COMMISSION ALARMS
419 1 4 406 6 614, s
406 START TB4/30 114 DI-13
PB1 420 2
DG5 457 8 ER 1 EFI CONTROLLER FAULT
502 D0-15 125 TB4/45
7 762, s
9 5
407
503 LS-1 458 8 ER 1 EFI CONTROLLER ON-LINE
DO-16 126 TB4/46
9 5 8 608, 317
408 RS-1
459 8 ER 1
47 TB4/47 START AVLOS PUMP
9
527, s
SHIPS CONTROL
409 SYSTEM 460 14 ER 13
48 TB4/48 IN GOVERNOR MODE
TB3/49 TB3/50 10
761, 718, 861, 712
TB3/51 461 14 ER 13
410 49 TB4/49 EMERGENCY OVERRIDE ENABLED
11
TB3/52 764, 317, 721, s
C
411
WATER JET
FAULT - GO TO IDLE/RAMP RATE 431
SELECT [SOFTWARE SELECTABLE] TB3/1 TB3/2 TB4/25 46
412
508
10 6 432
REMOTE DIGITAL SPEED TB4/24 45
CONTROL RD-2 LINE 762
413
13 14 433
EFI CONTROLLER RESET TB4/29 113 DI-12
LPB1
414
WATER JET
TB3/25 TB3/26
415
853
D GEARBOX AT NEUTRAL
9
GN-1
5 434
TB4/31 115 DI-14
416
GEARBOX START RELEASE DETERMINED BY GEARBOX 435
TB2/73 REFER TO SHEET 10 TB2/74 TB4/32 116 DI-15
417
E 421
EFI
SHIPS CONTROL SYSTEM CONTROLLER
422 SET ENGINE + 441
TB1/1 TB1/43 14
SPEED
4-20mA= 442
IDLE-1000rpm TB1/2 TB1/44 13
423
C
424 C
C
425
C
1 C 07.06.06 ORIGINAL
427
DATE AND
ISSUE ALTERATION FILMED
COPYRIGHT C
428
DRAWN RJN CONTRACT :-
430
TITLE
ENGINE CONTROL PANEL
SCHEMATIC
G 431 EFI CONTROLLER INTERFACE
NOTES:
1. ENGINE SHOWN STATIONARY AND ALL RELAY DE-ENERGISED.
432 APPROVED DRAWING No.
2. SPARE WIRE NUMBERS : 400, 407-409, 421-430, 439-440, 443-450, 462-490, 493-499
3. USE CABLE PART No. 02-002/02 DESIGN PRODUCTION L 5471
SHEET 4 OF 10SHEETS
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-EL
1 2 3 4 5 6 7 8 9 10
DRG.
No. L 5471 Sht 5
LINE NO.
500
A
FS7 FS8
501
127
128
502 WATER JET
TB3/5 TB3/6
501 14
LS
13 LOWER SPEED SERIAL CHANGEOVER
407, 324 EC[M]724901
503 502 14 13 RAISE SPEED GRAPHICAL HMI DISPLAY
TB3/7 RS PL5
407, 324 SERIAL PORT
LINE 229
7
C 511 13 14
SW4
509 4 RL
1 8
510 5 RL RL3
512 2
23 24
RL
LINE 632 3
513
ICAM
514 [ON-ENGINE]
PL1
3
W 552
515 3 TB1/51 3 RS232 Tx
R 551
EFI 2 TB1/52 2 RS232 Rx EFI
BK 553 CONT'R
5 TB1/53 5 RS232 COM
D 516
TB1/54 RS232 SCREEN
SERIAL
CHANGEOVER
517 MODULE
LINE 506 3
W 555
3 TB1/55 3 RS232 Tx
518 R 554
MAA 2 TB1/56 2 RS232 Rx MAA
BK 556 CONT'R
5 TB1/57 5 RS232 COM
519 TB1/58 RS232 SCREEN
PL3
520 401
3 4
11
621
3 523
STARTER
TB2/15 PANEL START JACKET WATER HEATER
CP-7 C
524 CIRCULATING PUMP
403 TB2/16
3 4 524 C
TB2/17
ER4-1
525 START LUBE OIL PRIME PUMP
TB2/18 C
525
TB2/19
START C/CASE EXTRACTION FAN C
526 TB2/20
408
F 3 4 526
TB2/21
2 C 21.02.07 ANALOGUE COND. PART No. AMENDED
ER9-1 START AVLOS PUMP
527 TB2/22 1 C 07.06.06 ORIGINAL
127
128
DATE AND
528 ISSUE ALTERATION FILMED
COPYRIGHT C
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-EL
1 2 3 4 5 6 7 8 9 10
DRG.
No. L 5471 SHT 6
LINE NO.
A HD
601 13 14 601 A1 A2 EFI SHUTDOWN 651
D
ISOLATE SOLENOID SUPPLY
125
131
132
126
23 24 602
126, 126
605 655
15K
TB3/43 TB3/44
611 661
C EMERGENCY STOP
15K 610
TB3/45 TB3/46 TB4/57 65 FIRE DETECTED
612 662
EMERGENCY
LINE 505 PROTECTION
COMMISSION
613 663
21 L R 22 13OFF-ON 14 612
TB4/58 66 COMMISSION LATCH
SW1 611 SW3
126
TB4/64 72 PROTECTION -VE SUPPLY
620 670
- SLAVE [13-14] 13 14
CP
856, 709
621 671
- SLAVE [9-12] 13 14
E s, 719, 630, 758
CP
622 672
- SLAVE [5-8] 13 14 617
CP TB4/65 73 COMMISSION PROTECTIONS
521, 522, 524, 864
623 673
1 8 618
723, 757 PT TB4/66 74 PROTECTION TRIPPED
624 674 C
621
TB1/41 79
TO ENGINE SPEED INDICATOR
4 - 20 mA = 0 - 1200 RPM C
625 622 675
LINE 770 TB1/42 80
C
24V DC SUPPLY -VE
626 LINE 120 676 C
1 8 624
UNIT HEALTHY MH TB4/71 53
F s, 316
1 8 625
2 C 21.02.07 ICAM INTERCONNECTING NUMBERS ADDED
627 ALARM ACTIVE MA TB4/72 54 677
763, 701 1 C 07.06.06 ORIGINAL
1 8 626
AUDIBLE AA TB4/73 55
628 s, 703 678 DATE AND
ISSUE ALTERATION FILMED
COPYRIGHT C
24V DC SUPPLY +VE MAA
LINEV 120 CONTROLLER
629 13 14 628 679 DRAWN RJN
ALARM RESET TB4/75 21 DI-1 CONTRACT :-
PB6
CHECKED RK280 - ECU TYPE 3
630 11 622 3 629 680
ALARM BLOCK TB4/76 23 DI-2
CP-11
ALARM MUTE
13 14 630
TB4/77 25 DI-3
TITLE
ENGINE CONTROL PANEL
631 PB5
LINE 513
681
SCHEMATIC
G NOTES: SHUTDOWN PROTECTIONS
2/13 2/14 631
632 SELECT MODBUS TB4/78 29 DI-5 682 1. ENGINE SHOWN STATIONARY AND ALL RELAYS DE-ENERGISED.
PROTOCOL SW4
2. SPARE WIRE No.'s : 600, 605-610, 618-620, 632-699
APPROVED DRAWING No.
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-EL
1 2 3 4 5 6 7 8 9 10
DRG.
No. L 5471 Sht 7
LINE NO.
LINE NO.
750
700
A FS9 FS10
5 701 751
TB3/63
701 6 627
129
130
7 702
TB3/64 ALARM ACTIVE
MA-2 752
702 703
TB3/65
5 704 753
TB3/66
703 6 628
7 705
TB3/67 AUDIBLE ALARM
AA-2 754
704 706
TB3/68
854
10 6 707 755
TB3/13
705 GE-2 13 14 752
ENGAGED
708 PB4
TB3/14
B 10
853
6 709
756 TEST LAMPS
706 TB3/15
GN-2 LPB3
DISENGAGED 623 RED
710 757 6 5 753 PROTECTION OPERATED
TB3/16
707 PT-2 X2 X1 RESET PUSH-BUTTON
860
12 8 711 LP8
TB3/17 622 GREEN
EP-2 758 12 8 754
ENGINE AT IDLE SPEED ENGINE RUNNING
708 712 CP-12 X2 X1
TB3/18
+
621 hr HOURS RUN
12 4 713 WATER JET 759
TB3/19 LP1
709 CP-14
ENGINE STOPPED 506 WHITE
714 12 8 755
TB3/20 REMOTE CONTROL
760 RC-4 X2 X1
507
710 11 7 715 LP2
TB3/21 409 AMBER
RC-7 9 1 756
REMOTE CONTROL BACK-UP MODE
716 761 ER10-1 X2 X1
C 711 409
TB3/22
407
LPB1
12 4 717 3 2 757 AMBER
TB3/23 EFI CONTROLLER RESET
ER10-4 762 ER7-1 X2 X1
IN BACK-UP MODE
712 718 LP6
TB3/24 627 AMBER
3 2 758
ALARM ACTIVE
763 MA-1 X2 X1
713 LPB4
410 AMBER
9 5 759
EMERGENCY OVERRIDE ENABLED
764 ER11-1 X2 X1
D 716
10
507
6 725 12
853
8 762
LPB6
WHITE
TB3/33 CLUTCH OUT
RC-6 767 GN-4 X2 X1
REMOTE CONTROL
717 726
TB3/34
409
10 2 727 768
TB3/35 DIODES MOUNTED ON REAR
718 ER10-2 ENGINE RPM
IN BACK-UP MODE [DIGITAL DISPLAY] OF LAMPHOLDER
728
TB3/36
769 129 130
622 SHIPS 9 10
719 10 6 729
TB3/37 CONTROL
CP-10 621
ENGINE RUNNING SYSTEM 1 ENGINE RPM
730 770
TB3/38 4-20mA=0-1200 RPM
720 622 LINE 624
410 2
11 7 731
TB3/39
ER11-3 EMERGENCY OVERRIDE 771
721 732 ENABLED
E 504
TB3/40
10 6 733 772
TB3/53 CONTROL STATION
722 TC-2
DISCREPANCY
734 ALARM
TB3/54
623 773
723 3 4 735
TB3/59
PT-1 PROTECTION TRIP
736 [ANY SHUTDOWN]
TB3/60 774 C
724 854
12 8 737
TB3/61 C
EG-4 775
GEARBOX ENGAGED
725 738
TB3/62 C
776 C
726
F 2 C 21.02.07 EG4 AND RPM INDICATOR DETAILS ADDED
777
727 1 C 07.06.06 ORIGINAL
SHEET 7 OF 10SHEETS
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-EL
1 2 3 4 5 6 7 8 9 10
DRG.
No. L 5471 Sht 8
LINE NO.
LINE NO.
850
LINE 628
800 ANALOGUE INPUT
A MODULE
851
127
128
801
EC[M]724502
ADDRESS LINKS 25 & 26 = A
ALL OTHERS = A
852
802 801
TB2/47 1 +ve -ve
FS1 AICH1 851 14 13 GEARBOX AT NEUTRAL
802 853 TB2/65 GN
TB2/48 2 415, 706, 855, 767
803 TB2/66
803 854
TB2/49 4 +ve -ve 852 14 13 GEARBOX ENGAGED
804 GEARBOX TB2/67 GE
FS2 AICH2 766, 705, 904, 725
REFER TO SHEET 10 TB2/50
804
5 TB2/68
2500G022P23 PL1 855 GEARBOX
805 PL6 LINE 308 853 GEARBOX LOW CLUTCH
805 Pt1000/4-20mA
REFER TO SHEET 10 TB2/69
853 11 3 854 A1
GC A2 OIL PRESSURE SHUTDOWN
TB2/45 19 CONVERTOR GN-3 T TYPE E-10sec
B TB2/46
806
20
[0-150°C] AICH7
2500G022P33 PL2
856 TB2/70 616
806 FS7 PL4 LINE 311 621
20 855 9 5 856 A1 A2 GEARBOX LOW LUB
TB2/71 GP OIL PRESSURE SHUTDOWN
857 CP-13 T
Pt1000/4-20mA TYPE E-10sec
807 22 TB2/72 617
CONVERTOR PL7
[0-150°C] AICH8
23 FS8 858
808
PL5
859
809 7 S.C.S
SPARE INPUT 857 14 13 ENABLE GEARBOX ENGAGEMENT
AICH3 TB3/57 TB3/58 EB
8 863, 905
860
810 403
3 4 858 14 13 ENGINE AT IDLE, ENGAGEMENT PERMITTED
EP
813 ER3-1 863, 707
12 861
C 811 814
FS4 AICH4 11
409
3 3
618
2 WATER JET
11 24V DC 859
LINE 320 ER10-3 ME-1 TB3/9 TB3/10
862
25 121 862
812 TB3/11 TB3/12 D10
13 28 122
SPARE INPUT AICH5 PL3 863 5 LPB5 861 860
860 9 507 864 9 5 865 9 5 866
813 14
621 8 EP-1 EB-1 14 13
RC-5 1
12 CLUTCH IN
864 LPB6 EG CLUTCH IN/OUT
814 16 CP-8 863 [LATCHING RELAY]
4
SPARE INPUT AICH6 871, 906
CLUTCH OUT 867 12 9
17 865
815
866 D11
D 816
867
817
SPEEDSWITCH
813 868
-I MODULE
818 T401 FS15 FS16 FS13 FS14
814
+I
869
3
819 R 815 121
TB2/51 +V +24V
GEARBOX W 816 122
TB2/52 SIGN 0V
REFER TO SHEET 10 TB2/53
BK 817
0VS 870 TB2/75
135
820 PE 136
sh TB2/76
LINE 913
GEARBOX 869 5 864
871 TB2/77
821
REFER TO SHEET 10 10 133
E TB2/79
870 1
EG-1
SHAFT SPEED MONITORING 872 TB2/78
134
822
873
823
874
824
C
875
825 C
876 C
826
F 2 C 21.02.07 ANALOGUE COND. PART No. AMENDED
877
827 1 C 07.06.06 ORIGINAL
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-EL
1 2 3 4 5 6 7 8 9 10
DRG.
No. L 5471 SHT 9
LINE No.
DIGITAL INPUT
900 MODULE 950
A EC[M]724601
ADDRESS LINKS 1 TO 4 =B
901 951
901
TB2/54 33
902 900 952
TB2/55 34 DICH25
902
GEARBOX TB2/56 35
903
REFER TO SHEET 10 903 953
TB2/59 1
904 DICH1
TB2/60 3
854
904 11 7 905 954
G/B ENGAGED 4
GE-3 DICH2
911 961
C LUBE OIL PRIMING
PUMP TRIPPED
TB2/27
922
11
DICH9
928 37 978
DICH26 DATE AND
ISSUE ALTERATION FILMED
38 COPYRIGHT C
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-EL
1 2 3 4 5 6 7 8 9 10
DRG.
No. L 5471 SHT 10
1000
TYPE P01 GEARBOX INTERFACE
A
1001 CLUTCH OIL + 801
PRESSURE TB2/47 BLOCK ALARM
0-40BAR IF ENGAGE DEMAND
ALARM <17BAR 802 INPUT 4 IS ON
1002 TB2/48
805
1004 LUBE OIL TB2/45
TEMPERATURE BLOCK ALARM IF
ALARM >95°C 806 ENGINE IS NOT RUNNING
[PT1000] TB2/46
1005
+ 815
TB2/51
SIG
B 1006 SHAFT SPEED
-
TB2/52
816
817
TB2/53
1007
901
+ TB2/54
LOW LUBE OIL 900
LEVEL S- TB2/55
902
1008 - TB256
903
1009 FILTER BLOCKED TB2/59
904
TB2/60
1010
851
1011 TB2/65
C AT NEUTRAL 127
+VE
TB2/66
1012
852
TB2/67
ENGAGED
TB2/68
1013
123
1016 TB2/73
CLOSE FOR START
D RELEASE TB2/74
435
1017 135
+ TB2/75 FS15-1A
24V DC SUPPLY FOR
136
SENSORS - TB2/76 FS16-1A
1018 869
CLUTCH IN TB2/77
134
TB2/78
1019 870
CLUTCH OUT TB2/79
1020
1021
E
1022
1023
1024 C
C
1025
C
1026 C
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-EL
1 2 3 4 5 6 7 8 9 10
DRG.
No. L 5472 sht 1
THE FOLLOWING RECOMMENDATIONS MUST BE APPLIED WHEN WIRING THE EQUIPMENT TO REDUCE THE POSSIBILITY
OF ELECTRICAL INTERFERENCE. THESE SHOULD BE APPLIED IN ADDITION TO GOOD STANDARD WIRING PRACTICES
REGARDING SEGREGATION OF CABLES, SAFETY, GLANDING, TERMINATION, IDENTIFICATION etc.
A 1. ALL CONTACTS ARE SHOWN WITH THE ENGINE COLD, STATIONARY AND ISOLATED,
BARRING GEAR AND GEARBOX DISENGAGED.
2. ALL SIGNAL CABLES ARE TO HAVE AN OVERALL SCREEN AROUND ITS CORES FOR SHIELDING. THIS
SCREEN MUST HAVE AN OUTER INSULATING SHEATH.
THE LOW LEVEL SENSITIVE SIGNAL CABLES TERMINATED IN TB1 MUST HAVE
TWISTED PAIRS, AN INDIVIDUAL SCREEN AND OUTER INSULATING SHEATH.
3. TO MINIMIZE THE EFFECT OF ELECTRICAL NOISE, SCREENS MUST BE EARTHED AS SHOWN AT THE
ENGINE CONTROL UNIT ONLY. THIS SHOULD BE BY THE USE OF SUITABLE CABLE GLANDS
THAT TERMINATE THE SCREEN TO ITS BODY GIVING 360 DEGREE GROUNDING TO THE GLAND PLATE.
ON NO ACCOUNT ARE SCREENS TO BE TAKEN INTO THE PANEL COMPARTMENTS FOR TERMINATION.
4. WHEN CONNECTING TO EXTERNAL EQUIPMENT, THE CABLE SCREEN MUST BE TERMINATED AS SHOWN.
HOWEVER, IN CERTAIN INSTANCES IT MAY NOT BE POSSIBLE TO TERMINATE THE SCREEN IN
A PARKING TERMINAL. IF THIS IS THE CASE, THE SCREEN MUST BE PROTECTED WITH AN APPROPRIATE
INSULATING SLEEVE TO PREVENT IT COMING INTO CONTACT WITH GROUND AND DEGRADING THE SHIELDING.
IT IS ESSENTIAL THAT THE EXTERNAL SCREENING OF SENSITIVE CABLING CONNECTED TO THE LEFT HAND SIDE
FOR PERCEPTION HEADS AND SPEED REFERENCES, IS CARRIED THROUGH USING
THE TERMINALS PROVIDED IN THE EXTERNAL PANELS AND ENGINE TERMINAL BOX.
5. CABLES TO THE PANEL SHOULD NOT BE RUN IN PARALLEL WITH OTHER SHIPS CABLING CARRYING
B HIGH VOLTAGES OR HIGH CURRENTS. WHERE THESE CABLE RUNS MUST CROSS, THEY SHOULD DO
SO AT RIGHT ANGLES TO MINIMIZE THE EFFECT OF ELECTRICAL INTERFERENCE.
C
ENGINE CONTROL UNIT
[E.C.U]
TB1
SCREENS TO BE EARTHED ON GLAND PLATE UNLESS SHOWN OTHERWISE
FUTURE
FUTURE
4-20mA
SPARE
SPARE
SPARE
SPARE
SPARE
INPUT
INPUT
SPARE
RTD
TB5
+
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
10
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
11
1
2
3
4
5
6
7
8
9
1
2
3
4
D
ENGINE FUEL/LOAD
ENGINE SPEED
OE-COMM
6mm
CONTINUED ON
SHEET 4
OE-COMM/01
OE-COMM/02
OE-COMM/03
OE-COMM/04
OE-COMM/05
OE-COMM/06
OE-COMM/07
OE-COMM/08
OE-COMM/09
OE-COMM/10
OE-COMM/12
OE-COMM/11
SIGNALS FOR
CLIENTS USE
ADDITIONAL
+
-
+
-
79
80
E
24v 30A dc UPS SUPPLY
+
24v 30A dc NORMAL SUPPLY
107
108
14
13
COM
COM
Rx 3
Tx 2
COM 5
Rx 3
Tx 2
COM 5
A
B
A
B
CAN+
CAN-
+
-
MONITORING SYSTEM
NOTE: FOR USE WITH
CONTROLLER PL1]
CONTROLLER PL1]
OPTIONAL COCOS
[DIRECT TO MAA
[DIRECT TO MAA
SPEED SETTING
[DIRECT TO EFI
CONTROLLER]
ENGINE RPM
SHAFT RPM
RS232
RS232
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-EL
1 2 3 4 5 6 7 8 9 10
DRG.
No. L 5472 sht 2
C
ENGINE CONTROL UNIT
[E.C.U]
TB2
FUTURE
DIG. I/P
SPARE
SPARE
SPARE
SPARE
SPARE
81
82
83
84
85
86
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
10
12
13
14
15
16
17
18
19
20
11
1
2
3
4
5
6
7
8
D
GEARBOX INTERFACE
REFER TO SHEET 5 FOR
CONNECTION DETAILS
36
32
33
34
31
40
41
42
43
44
45
46
47
49
48
51
52
53
54
55
56
57
IS SUPPLIED BY REGULATEURS
EUROPA Ltd.
E
FUEL SUPPLY PUMP TRIPPED
FUEL CIRC. PUMP TRIPPED
J.W CIRC. PUMP & HEATER
C
SOLENOID - SOV4
CRANKCASE FAN
AVLOS PUMP ON
FUEL SHUT-OFF
J.W HEATER ON
TEMPERATURE
COMMON -VE
AVLOS PUMP
C
FUEL OIL
C
FUEL SYSTEM STARTER PANEL
F 2 C 13.07.06 F.O TEMPERATURE SENSOR NOW 2 WIRE
1 C 12.06.06 ORIGINAL
DATE AND
ISSUE ALTERATION FILMED
COPYRIGHT C
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-EL
1 2 3 4 5 6 7 8 9 10
DRG.
No. L 5472 sht 3
C
ENGINE CONTROL UNIT
[E.C.U]
TB3
SPARE
SPARE
SPARE
10
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
67
68
11
1
2
3
4
5
6
7
8
9
AUDIBLE ALARM/
ALARM ACTIVE
NEW ALARM
E
*
*
*
CONTROL SYSTEM RESET
[SOFTWARE SELECTABLE]
FAULT - GO TO IDLE/RAMP
CONTROL DISCREPANCY
EMERGENCY OVERRIDE
EMERGENCY OVERRIDE
[LINK OUT IF NOT USED]
REMOTE CONTROL IND.
ENGINE @ IDLE SPEED
PROTECTION TRIPPED
[MOMENTARY OFF/ON]
IN REMOTE CONTROL
GEARBOX ENGAGED
MATCHED CONTROL
EMERGENCY STOP
ENABLE GEARBOX
IN BACK-UP MODE
IN BACK-UP MODE
ENGINE STOPPED
ENGINE RUNNING
[ANY SHUTDOWN]
SPEED CONTROL
SELECT DIGITAL
FIRE DETECTED
INITATE ENGINE
C
TAKE CONTROL
LOWER SPEED
ENGAGEMENT
DISENGAGED
RATE SELECT
RAISE SPEED
CLUTCH OUT
SLOWDOWN
CLUTCH IN
ENGAGED
C
ENABLED
START
STOP
DATE AND
ISSUE ALTERATION FILMED
COPYRIGHT C
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-EL
E
F
B
D
A
G
No.
DRG.
OE-COMM
FROM SHEET 1
1
2.5mm
1.5mm
OE-PROT/01
51 1
MAA POWER SUPPLY OE-PROT/02
52 2
OE-EFI/01
'A' BANK CONTROL 24v 13 3
OE-EFI/02
'B' BANK CONTROL 24v 23 4
OE-EFI/03
SENSOR 1 SET 24v 1 5
OE-EFI/04
SENSOR 1 SET 0v 5 6
OE-EFI/05
SENSOR 2 24v 7 7
OE-EFI/06
SENSOR 2 SET 0v 11 8
9 SPARE
OE-EFI/07
'A' BANK SOLENOID SUPPLY 14 10
OE-EFI/08
L 5472 sht 4
'A' BANK 0V 16 11
OE-EFI/09
'B' BANK SOLENOID SUPPLY 24 12
OE-EFI/10
'B' BANK 0V 26 13
14 SPARE
OE-EFI/11
2
OE-COMM/18
GEARBOX AT NEUTRAL 115 31
OE-COMM/19
GEARBOX START RELEASE 116 32
33 SPARE
OE-COMM/20
DIRECT SLOWDOWN COMMON 35 34
OE-COMM/21
TO EFI APPLY SLOWDOWN [SCS] 36 35
I/O MODULE OE-COMM/22
APPLY SLOWDOWN [FUTURE] 39 36
37 SPARE
OE-EFI/22
EFI CONTROLLER -VE 42 38
OE-COMM/23
START FUEL PUMPS 119 39
OE-COMM/24
STATIONS MATCHED 120 40
OE-COMM/25
RUNNING AT IDLE 121 41
TB4
OE-COMM/26
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential.
DIRECT START L.O PUMP 122 42
TO EFI OE-COMM/27
CONTROLLER STOP 123 43
OE-COMM/28
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd.
COMMISSION ALARMS 124 44
C
PROTECTION +VE 70 62
5
OE-PROT/15
450RPM LEVEL 71 63
OE-PROT/16
PROTECTION -VE 72 64
ENGINE CONTROL UNIT
OE-PROT/17
COMMISSIONED 73 65
OE-PROT/18
PROTECTION TRIPPED 74 66
67
68
69 SPARE
70
OE-PROT/19
MAA HEALTHY 53 71
OE-PROT/20
OE-PROT
OE-COMM
7
CABLE CORES TO BE A
SPECIFIED OTHERWISE.
MINIMUM OF 0.75mm UNLESS
ISSUE
DESIGN
TITLE
C
C
C
C
C
C
DRAWN
CHECKED
DATE AND
APPROVED
08.08.06
9
28.07.06
22.09.06
12.06.06
13.07.06
20.02.07
RJN
PRODUCTION
COPYRIGHT C
CONTRACT :-
DRAWING No.
ORIGINAL
ALTERATION
CORE SIZES UPDATED
SHEET 4 OF
L 5472
10
FORM No
A1SHT-EL
5 SHEETS
FILMED
1 2 3 4 5 6 7 8 9 10
DRG.
No. L 5472 sht 5
TB2
A 45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
B
+
+
s
s
-
+
-
CLUTCH OIL PRESSURE
PRESSURE SHUTDOWN
PRESSURE SHUTDOWN
LUB OIL TEMPERATURE
TRANSDUCER SUPPLY
LUBE OIL PRESSURE
START RELEASE
SHAFT SPEED
CLUTCH OUT
LOW LUB OIL
AT NEUTRAL
CLUTCH IN
ENGAGED
[PT1000]
24V DC
C
GEARBOX
1 C 12.06.06 ORIGINAL
DATE AND
ISSUE ALTERATION FILMED
COPYRIGHT C
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-EL
1 2 3 4 5 6 7 8 9 10
DRG.
No. L 5473 Sht 1
LINE No.
100
A
101 ECU
FS25
155
TB4/5
102 SENSOR 1 SET FS26
24V DC SUPPLY 156
TB4/6
103
FS27
157
TB4/7
104 SENSOR 2 SET FS28
24V DC SUPPLY 158
TB4/8
105
B 106
01
107 + 02
191
CRANK SHAFT POSITIONER S- 03 CRANK SENSOR 1
CCM A BANK 192
108 ST3 CAM SENSOR 1
- A BANK CONTROL MODULE
04 193 LINE 530
CRANK SENSOR 2
05
109 194
CAM SENSOR 2
+
+
114
CAM SHAFT POSITIONER S- 12
CCM [OUTER]
ST10
115 -
116
D
117
118
119
120
121
E
122
123
124 C
C
125
C
126 C
SHEET 1 OF 10SHEETS
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-EL
1 2 3 4 5 6 7 8 9 10
DRG.
No. L 5473 Sht 2
LINE NO.
A 200
PERCEPTION
VIKING 25 EFI
201
HEADS EC[P]720501
90
ST1 - 88 SPEED
INPUT
SIG 89 CH1
202
FLYWHEEL
304 TEETH 93
ST2 - 91 SPEED
203 INPUT
SIG 92 CH2
204
ANALOGUE
205 CONDITIONING
B +
EC[P]725301
64 + 42
1 +ve -ve
206 AIR MANIFOLD PRESSURE [AFTER I/C] 65 ANALOGUE ANALOGUE - 41
PT12 FS1 INPUT OUTPUT
[0-4Bar=4-20mA] 2 66 CH1 CH1 0V 40
207
+ 67 + 45
3 +ve -ve
HT WATER PRESSURE [I/C OUTLET] 68 ANALOGUE ANALOGUE - 44
208 PT27 FS2 INPUT OUTPUT
[0-4Bar=4-20mA] 4 69 CH2 CH2 0V 43
209 70 + 48
6
SPARE 71 ANALOGUE ANALOGUE - 47
INPUT FS3 INPUT OUTPUT
5 72 CH3 CH3 0V 46
210
C 73 + 51
211 8 ANALOGUE ANALOGUE
74 - 50
SPARE INPUT OUTPUT V25 CONTROL UNIT
INPUT FS4 CH4 CH4
75 0V 49 LINK SETTINGS
7
212 LINK LINK LINK
No. POSITION No. POSITION No. POSITION
+ 76 + 54
9 +ve -ve 1 A 31 B
LUB OIL PRESSURE 77 ANALOGUE ANALOGUE - 53
L725301 ANALOGUE COND. MODULE 2 A 32 B
213 INPUT OUTPUT LINK SETTINGS
PT07 FS5 3 B 33 B
[0-10Bar=4-20mA] 10 78 CH5 CH5 0V 52 LINK SETTING DESCRIPTION 4 B 34 B 64 B
A B No.
214 5 B 35 B 65 B
79 + 57 1
12 ANALOGUE CH.1 INTERNAL LOOP POWER 36 B 66 B
INPUT ANALOGUE 2
SPARE 80 - 56 7 A 37 B 67 A
INPUT FS6 CH6 OUTPUT 3
215 CH6 CH.2 INTERNAL LOOP POWER 8 A 38 B 68 A
11 0V 55 4
ECU 81 9 NO 39 B 69 A
5
10 NO 40 B 70 A
D + 14
82 + 60 6
CH.3 EXTERNAL LOOP POWER
11 NO 71 A
216 ANALOGUE 7
SPEED SETTING 83 INPUT ANALOGUE - 59 CH.4 EXTERNAL LOOP POWER 12 NO 72 A
DEMAND 4-20mA FS7 CH7 OUTPUT 8
CH7 13 NO 43 B 73 A
- 13 84 0V 58 9
217 CH.5 INTERNAL LOOP POWER 14 NO 74 A
10
15 NO 75 A
85 + 63 11
16 CH.6 EXTERNAL LOOP POWER 16 NO 76 A
ANALOGUE ANALOGUE 12
SPARE 86 - 62 17 B 47 A 77 A
218 INPUT OUTPUT 13
INPUT FS8
CH8 CH8 CH.7 EXTERNAL LOOP POWER 18 B 48 A 78 A
15 87 0V 61 14
19 B 49 A 79 A
15
219 CH.8 EXTERNAL LOOP POWER 20 A 50 A 80 A
16
21 B 51 A
FS3
FS9 22 A 52 B
TB4/21 41 1
220 23 B 53 B
FS4 4
H 104 2 24 B 54 B
TB4/38 42 PL4 BN 295
PL5 L 105 TO VIKING BCM - A BANK 25 B 55 B
E 221 SERIAL PORT COM 106
B 296
LINE 524 26 B
CH3 2 27 B
CAN BN 295
123 H 107 TO VIKING BCM - B BANK 28 B
36 +24v B 296
LINE 574
222 PL6 L 108 29 B
37 +24v
PWR COM 109 30 B
124 2
38 0v BN 291
223
A 98 RS485 MODBUS
39 0v B 292 COMMUNICATION
123
124
PL3 B 99
BK 293 TO MAA CONTROLLER C
COM 100
SERIAL PORT LINE 623
224 CH2
RS485 C
A 101
PL4 B 102
C
COM 103
225 SG
LINE 301 C
3 RS232 MODBUS
SERIAL PORT
F 226 CH1 PL1 2
COMMUNICATION
TO ECU
2 C 20.02.07 ECU INTERCONNECTING NUMBERS ADDED
RS232
5
1 C 07.06.06 ORIGINAL
227 SERIAL
CONECTION ISSUE
DATE AND
ALTERATION FILMED
COPYRIGHT C
228 EC[M]723101
DRAWN RJN CONTRACT :-
230
TITLE
INTEGRATED CONTROL &
MONITORING PANEL [ICAM]
G 231 SCHEMATIC
1. ENGINE SHOWN STATIONARY AND ALL RELAY DE-ENERGISED. DESIGN PRODUCTION L 5473
2. USE CABLE PART No. 02-002/02
SHEET 2 OF 10SHEETS
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-EL
1 2 3 4 5 6 7 8 9 10
DRG.
No. L 5473 Sht 3
LINE No.
A VIKING 25 EFI
123
124
301
X01
EC[P]720501
BARRING GEAR DIS-ENGAGED
XS6
302 X02 20 DI 0v
4 START SOLENOID
391 DO-1
21 DI-1 5 LINE 1052
303 ECU
6 BOOST BYPASS VALVE SOLENOID
401 DO-2
REMOTE CONTROL TB4/22 43 23 DI-2 7 LINE 1052
LINE 1007 8 2 FROM 3 SLOWDOWNS
304 29 30 392 DO-3 LINE 1028
SPEEDSWITCH >50 RPM 25 DI-3 9
LINE 1032 10 ENABLE L.O.P HI SPEED SHUTDOWN
62 63 393 DO-4 LINE 1031 ECU
FIRE DETECTED 27 DI-4 11
305 459
LINE 1029 12 47 TB4/47 START AVLOS PUMP
55 56 394 DO-5
SHUTDOWN OPERATED 29 DI-5 13 399
SHUTDOWN
MODULE 14 DISENGAGE BACKUP MODE LINES 529/579
DO-6
B 306 ENABLE/DISABLE O/R TB4/23 44
405
31 DI-6 15
159
+VE LINE 526
460
16 48 TB4/48 IN GOVERNOR MODE
431 DO-7
33 DI-7 17
307 461
18 49 TB4/49 EMERG. O/R ENABLED
REMOTE DIGITAL 432 DO-8
TB4/24 45 35 DI-8 19
SPEED CONTROL
308 FAULT-GO TO IDLE/ TB4/25 46
124
RAMP RATE SELECT
309 2500G022P30
ANALOGUE PL10 PL1
STATUS INPUTS LINE 405
V25 I/O
310 PL8 EXPANDER
EC[P]722201
ANALOGUE PL8 2500G022P28 123
311 PL2
CONTROL LINES LINE 406
C
312
DIGITAL DIGITAL
CONNECTION CONNECTION
313 EC[P]722501 EC[P]722501
STOP TB4/26 110 DI-9 127
DO-9 119 TB4/39 START FUEL PUMPS
314 LOWER SPEED TB4/27 111 DI-10
DO-10 120 TB4/40 CONTROL STATIONS MATCHED
RAISE SPEED TB4/28 112 DI-11
315 DO-11 121 TB4/41 RUUNING AT IDLE SPEED
RESET TB4/29 113 DI-12
DO-12 122 TB4/42 START LUB OIL PUMP
316 START TB4/30 114 DI-13
DO-13 123
D GEARBOX AT NEUTRAL TB4/31 115 DI-14
TB4/43 STOP APPLIED
320
321
123
124
E
322
LINE 412
323
324 C
C
325
C
326 C
TITLE
INTEGRATED CONTROL &
331
MONITORING PANEL [ICAM]
G NOTES: SCHEMATIC
332 1. ENGINE SHOWN STATIONARY AND ALL RELAY DE-ENERGISED.
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-EL
1 2 3 4 5 6 7 8 9 10
DRG.
No. L 5473 Sht 4 L725202 ANALOGUE INPUT MODULE
LINE NO. LINK SETTINGS
LINE NO.
450 LINK SET FUNCTION
400 10 C
A ANALOGUE INPUT 11 B
ADDRESS SETTING
MODULE 1 12 A CONTROL LINE SUPPLY
451
401
EC[M]725202
CH CHANNEL LINK SETTING
452 No. 1 2 3 4 5 6 7 8
402 Pt600/4-20mA 1 A A A A A A A A
2
1 CONVERTOR 2 A A A A A A A A
CRANKCASE OIL SPLASH No.1 [0-120°C] AICH1
1 3 A A A A A A A A
TE60 2 453
403 4 A A A A A A A A
5 A A A A A A A A
Pt600/4-20mA 454 6 A A A A A A A A
2
4 CONVERTOR 7 A A A A A A A A
404 [0-120°C] AICH2
CRANKCASE OIL SPLASH No.2 1 8 A A A A A A A A
TE61 5
455 9 A A A A A A A A
2500G022P30 PL1
405 PL10 LINE 309 10 A A A A A A A A
Pt600/4-20mA 11 A A A A A A A A
2
7 CONVERTOR
B CRANKCASE OIL SPLASH No.3
TE62 1
[0-120°C] AICH3
2500G022P28 PL2
456 12
13
B
B
B C B B B B A
B C B B B B A
406 8 PL8 LINE 311 14 B B C B B B B A
457 15 B B C B B B B A
407 Pt600/4-20mA 16 B B C B B B B A
2
10 CONVERTOR PL9
CRANKCASE OIL SPLASH No.4 [0-120°C] AICH4
1
TE63 11 458
408
Pt600/4-20mA PL7
2 459
13 CONVERTOR
409 [0-120°C] AICH5
CRANKCASE OIL SPLASH No.5 1
TE64 14
460
410
Pt600/4-20mA
2
16 CONVERTOR
[0-120°C] AICH6 461
C 411
CRANKCASE OIL SPLASH No.6
TE65
1
17 24V DC
LINE 322
FS2 3 123 462
412 Pt600/4-20mA
2
CONVERTOR 1 124
19
CRANKCASE OIL SPLASH No.7 [0-120°C] AICH7 PL11
1
TE66 20 463
413
Pt600/4-20mA 464
2
22 CONVERTOR
414 [0-120°C] AICH8
CRANKCASE OIL SPLASH No.8 1
TE67 23
465
415
Pt600/4-20mA
2
25 CONVERTOR
[0-120°C] AICH9 466
CRANKCASE OIL SPLASH No.9
D 416 TE68
1
26
467
417 Pt600/4-20mA
2
28 CONVERTOR
CRANKCASE OIL SPLASH No.10 [0-120°C] AICH10
1
TE69 29 468
418
Pt600/4-20mA 469
31 CONVERTOR
419 [0-120°C] AICH11
32
470
420
ECU FS1L
TB4/34 35 +
AICH12 471
421 15K -
E APPLY SLOWDOWN TB4/35 36
[SCS]
472
422 FS1M
38 +
AICH13
15K - 473
APPLY SLOWDOWN
423 [RESERVED] TB4/36 39
15K
FS1N 474
41 +
424 AICH14
HIGH CRANKCASE -
PRESSURE SLOWDOWN C
PS30 42 475
425 15K C
FS1O
44 +
METAL PARTICLE AICH15 476 C
426 DETECTED SLOWDOWN -
F MPD1
15K
45 2 C 20.02.07 ECU INTERCONNECTING NUMBERS ADDED
477
703 FS1P
427 4 5 491 1 C 19.06.06 ORIGINAL
47 +
MAA/DO-1 AICH16
MAA INITIATED SLOWDOWN -
LINE 703 478 DATE AND
492 ISSUE ALTERATION FILMED
428 48 COPYRIGHT C
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-EL
1 2 3 4 5 6 7 8 9 10
DRG.
No. L 5473 Sht 5
LINE NO. BANK CONTROL MODULE LINE NO. BANK CONTROL MODULE
[A BANK] [B BANK]
500 550
A
SKTB SKTB
501 + 551 +
1 1
C1 PUMP C1 PUMP
11 11
502 552
+ +
2 2
503 C2 PUMP 553 C2 PUMP
12 12
504 + 554 +
3 3
C3 PUMP C3 PUMP
13 13
505 555
+ +
4 4
B C4 PUMP
14
C4 PUMP
14
506 556
+ +
5 5
507 C5 PUMP 557 C5 PUMP
15 15
508 + 558 +
25 25
C6 PUMP C6 PUMP
35 35
509 559
+ +
24 24
C7 PUMP C7 PUMP
510 34 560 34
+ +
C 511 C8 PUMP
23
561 C8 PUMP
23
33 33
512 + 562 +
22 22
C9 PUMP C9 PUMP
32 32
513 563
+ +
21 21
C10 PUMP C10 PUMP
514 31 564 31
515 565
SKTA SKTA
ECU ECU
FS23 153 FS24 154
2 2
D 516
TB4/3 13 153
MODULE 24V 566
TB4/4 23 154
MODULE 24V
SHUTDOWN MODULE B C
2040
FS29 ECU 15 CAN L 15 CAN L
TB4/15 33 C
526 LINE 306 13 CAN SCN 576 13 CAN SCN
a a
F DECREASE SPEED TB4/16 34
352
28 DECREASE SPEED
352
28 DECREASE SPEED 2 C 20.02.07 ECU INTERCONNECTING NUMBERS ADDED
b 353 b 353
527 INCREASE SPEED TB4/17 35 18 INCREASE SPEED 577 18 INCREASE SPEED
c c 1 C 19.06.06 ORIGINAL
354 354
START TB4/18 36 8 START 8 START
d 355 d 355 DATE AND
528 STOP TB4/19 37 38 STOP 578 38 STOP ISSUE ALTERATION FILMED
COPYRIGHT C
38 e 356 e 356
9 CHECK LOCAL PANEL 9 CHECK LOCAL PANEL
CHECK LOCAL PANEL TB4/20 39
399 399 DRAWN RJN CONTRACT :-
529 LINE 306 37 DISENGAGE BACK-UP 579 LINE 306 37 DISENGAGE BACK-UP
191
6 CRANK SENSOR 1
191
6 CRANK SENSOR 1 CHECKED RK280 - ECU TYPE 3
192 192
530 16 CAM SENSOR 1 580 16 CAM SENSOR 1
LINE 108 193
7 CRANK SENSOR 2
LINE 111 193
7 CRANK SENSOR 2
TITLE
INTEGRATED CONTROL &
531
194
17 CAM SENSOR 2 581
194
17 CAM SENSOR 2 MONITORING PANEL [ICAM]
G SCHEMATIC
532 0.62mm 582 0.62mm
APPROVED DRAWING No.
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-EL
1 2 3 4 5 6 7 8 9 10
DRG.
No. L 5473 Sht 6
LINE NO.
A 600
VIKING 25 MAA
601
PERCEPTION
HEADS
EC[P]720501
90
ST6 88 SPEED
A BANK INPUT
TURBO- 89 CH1
602 CHARGER
603 93
ST7 91 SPEED
B BANK INPUT
92 CH2
TURBO-
604 CHARGER
HARNESS
ANALOGUE
ANALOGUE 2500G022P27 CONDITIONING
605
CONDITIONING
B EC[M]722801 64 + 42
+
606 26 +ve -ve ANALOGUE ANALOGUE 3
LUB OIL PRESSURE FILTER INLET 65 - 41
PT14 FS9 INPUT OUTPUT 2
[0-10Bar=4-20mA] 27 66 CH1 CH1 0V 40 1
607
67 + 45
29 +ve -ve ANALOGUE ANALOGUE 6
68 - 44
EC[P]722601
SPARE INPUT OUTPUT 5
608 INPUT FS10
30 69 CH2 CH2 0V 43 4
609
2 70 + 48
33
Pt1000/4-20mA ANALOGUE ANALOGUE 9
CONVERTOR 71 - 47
L.O COOLER INLET INPUT OUTPUT 8
TE13 1 [0-150°C] CH3 CH3
610 32 72 0V 46 7
C 2
36
73 + 51
611 Pt1000/4-20mA PL2 ANALOGUE ANALOGUE PL1 12
L.O ENGINE INLET CONVERTOR 74 - 50
INPUT OUTPUT 11 V25 CONTROL UNIT
TE14 1 [0-150°C]
35 75 CH4 CH4 0V 49 10 LINK SETTINGS
612 LINK LINK LINK
No. POSITION No. POSITION No. POSITION
76 + 54
38 1 A 31 B
ANALOGUE ANALOGUE 15 L722801 ANALOGUE COND. MODULE
613 SPARE 77 - 53 2 A 32 B
FS13 INPUT OUTPUT 14 LINK SETTINGS
INPUT CH5 CH5 3 B 33 B
39 78 0V 52 13 LINK SETTING DESCRIPTION 4 B 34 B 64 B
A B No.
614 5 B 35 B 65 B
+ 79 + 57 1 CH.8 O/S TEST SWITCH DISABLED
40 +ve -ve ANALOGUE 36 B 66 B
INPUT ANALOGUE 18 2
CONTROL AIR PRESSURE 80 - 56 7 A 37 B 67 A
PT15 FS14 CH6 OUTPUT 17 3
615 CH6 8 A 38 B 68 A
[0-10Bar=4-20mA] 41 0V 55 16 4 CH.3 RTD INPUT SELECTED
81 9 NO 39 B 69 A
5
10 NO 40 B 70 A
D + 82 + 60 6
11 NO 71 A
616 44 +ve -ve ANALOGUE 21 7
LUB OIL PRESSURE [ENGINE INLET] 83 INPUT ANALOGUE - 59 12 NO 72 A
PT23 FS15 CH7 OUTPUT 20 8
[0-10Bar=4-20mA] CH7 13 NO 43 B 73 A
45 84 0V 58 19 9 CH.4 RTD INPUT SELECTED
617 14 NO 74 A
10
15 NO 75 A
+ 85 + 63 11
46 +ve -ve 16 NO 76 A
LUB OIL PRESSURE [PUMP OUTLET] ANALOGUE ANALOGUE 24 12
618 PT05 86 - 62 17 B 47 A 77 A
FS16 INPUT OUTPUT 23 13
[0-10Bar=4-20mA] CH8 CH8 18 B 48 A 78 A
48 87 0V 61 22 14 CH.5 RTD INPUT NOT SELECTED
19 B 49 A 79 A
15
619 20 A 50 A 80 A
16
21 A 51 A
17 CH.8 O/S TEST SWITCH DISABLED
22 A 52 B
1 18
620 ECU CH.6 EXTERNAL LOOP POWER 23 B 53 B
4 19
FS21 H 104 24 B 54 B
PL8 20
TB4/1 51 PL5 L 105 CH.7 INTERNAL LOOP POWER 25 B 55 B
E 621 FS22 SERIAL PORT COM 106
21
26 B
TB4/2 52 CH3 27 B
CAN BN
167 H 107 CANBUS COMMUNICATION 28 B
36 +24v B
TO ECU [DI CONTROLLER]
622 PL6 L 108 29 B
37 +24v
PWR COM 109 30 B
168 2
38 0v BN 291
623
A 98 RS485 MODBUS
39 0v B 292 COMMUNICATION
PL3 B 99
BK 293 TO EFI CONTROLLER C
167
168
COM 100
SERIAL PORT LINE 223
624 CH2
RS485 C
A 101
PL4 B 102
C
COM 103
625 SG
LINE 701 C
3 BN
RS485 MODBUS/RS232 VIKING 25
SERIAL PORT
F 626 CH1 PL1 2
B
BK
COMMUNICATION
TO ECU
2 C 20.02.07 ECU INTERCONNECTING NUMBERS ADDED
RS232
5
1 C 19.06.06 ORIGINAL
627 SERIAL
CONECTION ISSUE
DATE AND
ALTERATION FILMED
COPYRIGHT C
628 EC[M]723101
DRAWN RJN CONTRACT :-
630
TITLE
INTEGRATED CONTROL &
MONITORING PANEL [ICAM]
G 631 SCHEMATIC
1. ENGINE SHOWN STATIONARY AND ALL RELAY DE-ENERGISED. DESIGN PRODUCTION L 5473
2. USE CABLE PART No. 02-002/02
SHEET 6 OF 10SHEETS
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-EL
1 2 3 4 5 6 7 8 9 10
DRG.
No. L 5473 Sht 7
LINE No.
700
167
168
702 20 DI 0v
ECU 4 SLOWDOWN DEMAND TO EFI CONTROLLER ECU
DO-1
ALARM RESET TB4/75 21 DI-1 5 LINE 428 -VE
703 6
DO-2 625
ALARM BLOCK TB4/76 23 DI-2 7 54 TB4/72 ALARM ACTIVE
8
704 DO-3 624
ALARM MUTE TB4/77 25 DI-3 9 53 TB4/71 HEALTHY
10
SPARE DO-4 626
SELECT MODBUS TB4/78 27 DI-4 11 55 TB4/73 AUDIBLE
705 I/P
12 H.M.B.T SHUTDOWN
DO-5
29 DI-5 13 LINE 1027
14
DO-6
B 706 SPARE
I/P
31 DI-6 15
16
SPARE DO-7
33 DI-7 17
707 I/P
18
SPARE DO-8
35 DI-8 19
I/P
708
168
709 2500G022P35
ANALOGUE PL10 PL1
STATUS INPUTS LINE 955
2500G022P34
V25 I/O
710 DIGITAL PL13
STATUS INPUTS LINE 1021
PL8 EXPANDER
EC[P]722201
SHUTDOWN PL11 2500G022P29
711 CONTROL LINES LINE 1024 PL2
C ANALOGUE PL8
CONTROL LINES LINE 956
712
DIGITAL DIGITAL
CONNECTION CONNECTION
713 EC[P]722501 EC[P]722501
110 DI-9 127
DO-9 119
714 111 DI-10
DO-10 120
112 DI-11
715 DO-11 121
113 DI-12
SPARE DO-12 122
I/P's
716 114 DI-13
DO-13 123
D 115 DI-14
717 DO-14 124
116 DI-15
DO-15 125
718 117 DI-16
DO-16 126
118
719
720
721
E
167
168
722
LINE 810
723
724 C
C
725
C
726 C
TITLE
INTEGRATED CONTROL &
731
MONITORING PANEL [ICAM]
G NOTES: SCHEMATIC
732 1. ENGINE SHOWN STATIONARY AND ALL RELAY DE-ENERGISED.
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-EL
1 2 3 4 5 6 7 8 9 10
DRG.
No. L 5473 Sht 8
LINE NO.
LINE NO. L725101 ANALOGUE INPUT MODULE
850 LINK SETTINGS
800 ANALOGUE INPUT ANALOGUE INPUT
A MODULE 2 MODULE 3
LINK SET FUNCTION
851 10 C
EC[M]725101 EC[M]725203 ADDRESS SETTING
801 11 B
12 A CONTROL LINE SUPPLY
852
802 TC/6-20mA Pt1000/4-20mA CH LINK SETTING
1 2
1 CONVERTOR 1 CONVERTOR No. 1 2 3 4 5 6 7 8
EXHAUST CYLINDER A1 [0-800°C] AICH1 [0-150°C] AICH1
TE16 2 CHARGE AIR - ENGINE INLET 1 1 A A A B A A A A
2 853 2
TE03
803 2 A A A B A A A A
3 A A A B A A A A
TC/6-20mA 854 Pt1000/4-20mA 4 A A A B A A A A
1 2
4 CONVERTOR 4 CONVERTOR 5 A A A B A A A A
804 EXHAUST CYLINDER A2 [0-800°C] AICH2 [0-150°C] AICH2
TE17 2 L.T WATER L.O COOLER INLET 1 6 A A A B A A A A
5 TE11 5
855 7 A A A B A A A A
2500G022P37 PL11
805 PL11 LINE 905 PL10 8 A A A B A A A A
TC/6-20mA Pt1000/4-20mA 9 A A A B A A A A
1 2
7 CONVERTOR 7 CONVERTOR
B EXHAUST CYLINDER A3 2
[0-800°C] AICH3
2500G022P36 PL9
856
AIR INTAKE [A BANK] 1
[0-150°C] AICH3
10
11
A
A
A A B A A
A A B A A
A
A
A
A
806 TE18 8 PL9 8 PL8
LINE 906 TE54
12 A A A B A A A A
857 13 A A A B A A A A
807 TC/6-20mA Pt1000/4-20mA 14 B B B A B A B B
1 2500G022P32 2
10 CONVERTOR PL10 a 10 CONVERTOR PL9 15 A A B B B A B B
EXHAUST CYLINDER A4 [0-800°C] AICH4 [0-150°C] AICH4
TE19 2 AIR INTAKE [B BANK] 1 16 A A B B B A B B
11 858 11 a
TE55
808
2500G022P31 L725203 ANALOGUE INPUT MODULE
TC/6-20mA PL8 b Pt1000/4-20mA PL7 LINK SETTINGS
1 859 2
13 CONVERTOR 13 CONVERTOR b
809 EXHAUST CYLINDER A5 [0-800°C] AICH5 [0-150°C] AICH5
2 H.T JACKET WATER [PUMP INLET] 1
TE20 14 14 LINK SET FUNCTION
TE08
860 10 A
ADDRESS SETTING
810 11 D
TC/6-20mA 24V DC Pt1000/4-20mA 12 A CONTROL LINE SUPPLY
1
CONVERTOR LINE 722 2
CONVERTOR
16 861 16
[0-800°C] AICH6 [0-150°C] AICH6
C 811
EXHAUST CYLINDER A6
TE21
2
17
FS2 3 167
H.T WATER C.A COOLER INLET
TE09
1
17
FS2 3 891 CH LINK SETTING
1 168 1 892 No. 1 2 3 4 5 6 7 8
PL13 862 PL12 1 A A A A A A A A
812 TC/6-20mA Pt1000/4-20mA 2 A A A A A A A A
1 2
19 CONVERTOR 19 CONVERTOR 3 A A A A A A A A
EXHAUST CYLINDER A7 [0-800°C] AICH7 [0-150°C] AICH7
2 L.T WATER L.O COOLER OUTLET 1 4 A A A A A A A A
TE22 20 3 891 863 20 3 893
TE12
813 5 A A A A A A A A
1 892 1 894
6 A A A A A A A A
PL12 PL11
1 TC/6-20mA 864 Pt1000/4-20mA 7 A A A A A A A A
2
22 CONVERTOR 22 CONVERTOR 8 A A A A A A A A
814 EXHAUST CYLINDER A8 [0-800°C] AICH8 [0-150°C] AICH8 LINE 910
2 L.T WATER INTLET 1
TE23 9 A A A A A A A A
23 TE51 23
865 10 A A A A A A A A
815 11 A A A A A A A A
1 TC/6-20mA Pt1000/4-20mA 12 B A B C B B B A
2
25 CONVERTOR 25 CONVERTOR 13 B A B C B B B A
EXHAUST CYLINDER A9 [0-800°C] AICH9 866 FUEL OIL SUPPLY RAIL [0-150°C] AICH9
2
TEMPERATURE
D 816 TE24
26 TE15
1
26
14
15
B
B
A B C B B
A B C B B
B
B
A
A
867 16 B A B C B B B A
817 1 TC/6-20mA Pt1000/4-20mA
2
28 CONVERTOR 28 CONVERTOR
EXHAUST CYLINDER A10 [0-800°C] AICH10 FUEL OIL RETURN RAIL [0-150°C] AICH10
2 1
TE25 868 TEMPERATURE
29 TE52 29
818
+
FS1N 874 FS1N
40 + +
824 AICH14 FUEL PRESSURE BEFORE FILTER 41 +
FUEL LEAKAGE - - PT16 AICH14
41 -
LS01 [0-10Bar=4-20mA] C
SIG
42 875 42
825 C
+
FS1O +
FS1O
43 + 876 44 +
SUMP LEVEL HIGH FUEL OIL PRESSURE ENGINE SUPPLY RAIL AICH15 C
826 - AICH15 PT08 -
LS02a
F 44
[0-10Bar=4-20mA] 45 2 C 20.02.07 ECU INTERCONNECTING NUMBERS ADDED
877
827 FS1P FS1P 1
+ + C 19.06.06 ORIGINAL
START AIR PRESSURE 46 + AIR MANIFOLD PRESSURE [AFTER I/C] 47 +
AICH16
PT09 - AICH16 878 PT24 -
[0-40Bar=4-20mA] [0-4Bar=4-20mA] DATE AND
828 47 48 ISSUE ALTERATION FILMED
COPYRIGHT C
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-EL
1 2 3 4 5 6 7 8 9 10
DRG.
No. L 5473 Sht 9
LINE NO.
LINE NO.
L725101 ANALOGUE INPUT MODULE
LINK SETTINGS
950
900 ANALOGUE INPUT ANALOGUE INPUT
A MODULE 4 MODULE 5
LINK SET FUNCTION
10 D
951 ADDRESS SETTING
901
EC[M]725101 EC[M]725203 11 A
12 A CONTROL LINE SUPPLY
952
TC/6-20mA Pt1000/4-20mA CH LINK SETTING
902 1 2
EXHAUST CYLINDER B1 1 CONVERTOR 1 CONVERTOR No. 1 2 3 4 5 6 7 8
TE26 2 [0-800°C] AICH1 1 [0-150°C] AICH1
MAIN BEARING No.1 1 A A A B A A A A
2 953 2
TE39 2 A A A B A A A A
903
3 A A A B A A A A
TC/6-20mA Pt1000/4-20mA 4 A A A B A A A A
1 954 2
4 CONVERTOR 4 CONVERTOR 5 A A A B A A A A
904 EXHAUST CYLINDER B2 AICH2 AICH2
2 [0-800°C] 1 [0-150°C] 6 A A A B A A A A
TE27 MAIN BEARING No.2
5 5
TE40 7 A A A B A A A A
2500G022P37 PL11 955 2500G022P35 PL1
PL11 PL10 8 A A A B A A A A
905 LINE 805 LINE 709
TC/6-20mA Pt1000/4-20mA 9 A A A B A A A A
1 2
EXHAUST CYLINDER B3 7 CONVERTOR 7 CONVERTOR 10 A A A B A A A A
B TE28 2 [0-800°C] AICH3
2500G022P36 PL9
956
MAIN BEARING No.3 1 [0-150°C] AICH3
2500G022P29 PL2 11 A A A B A A A A
906 8 PL9 8 PL8
LINE 806 TE41 LINE 711 12 A A A B A A A A
13 A A A B A A A A
957
TC/6-20mA Pt1000/4-20mA 14 A A B B B A B B
907 1 2
10 CONVERTOR PL10 2500G022P32 10 CONVERTOR PL9 15 A A B B B A B B
EXHAUST CYLINDER B4 a
2 [0-800°C] AICH4 1 [0-150°C] AICH4
TE29 MAIN BEARING No.4 16 B B B B B A B B
11 958 11 a
TE42
908
2500G022P31
L725203 ANALOGUE INPUT MODULE
PL8 b PL7 LINK SETTINGS
1 TC/6-20mA 2 Pt1000/4-20mA
13 959 13
CONVERTOR CONVERTOR b
909 EXHAUST CYLINDER B5 2 [0-800°C] AICH5 1 [0-150°C] AICH5
14 MAIN BEARING No.5 14 LINK SET FUNCTION
TE30 TE43
10 B
960 ADDRESS SETTING
11 C
910
TC/6-20mA 24V DC Pt1000/4-20mA 12 A CONTROL LINE SUPPLY
1 2
16 CONVERTOR LINE 864 16 CONVERTOR
EXHAUST CYLINDER B6 AICH6 961 AICH6
[0-800°C] [0-150°C]
C 911
TE31 2
17
FS2 3 893
MAIN BEARING No.6
TE44
1
17
FS2 3 991 CH LINK SETTING
1 894 1 992 No. 1 2 3 4 5 6 7 8
PL13 PL12 1 A A A A A A A A
962
TC/6-20mA Pt1000/4-20mA 2 A A A A A A A A
912 1 2
19 CONVERTOR 19 CONVERTOR 3 A A A A A A A A
EXHAUST CYLINDER B7 AICH7 AICH7
2 [0-800°C] 1 [0-150°C] 4 A A A A A A A A
TE32 MAIN BEARING No.7
20 3 991 963 20 3 993
TE45 5 A A A A A A A A
913 1 992 1 994 6 A A A A A A A A
PL12 PL11 7 A A A A A A A A
1 TC/6-20mA 964 2 Pt1000/4-20mA
22 CONVERTOR 22 CONVERTOR 8 A A A A A A A A
914 EXHAUST CYLINDER B8 2 [0-800°C] AICH8 [0-150°C] AICH8 LINE 1018
MAIN BEARING No.8 1 9 A A A A A A A A
TE33 23 23
TE46 10 A A A A A A A A
965
11 A A A A A A A A
915
1 TC/6-20mA Pt1000/4-20mA 12 B A B C B B B A
2
25 CONVERTOR 25 CONVERTOR 13 B A B C B B B A
EXHAUST CYLINDER B9 AICH9 966 AICH9
2 [0-800°C] MAIN BEARING No.9 1 [0-150°C] 14 B A B C B B B A
TE34
D 916 26 TE47 26
15 B A B C B B B A
16 B A B C B B B A
967
917
1 TC/6-20mA 2 Pt1000/4-20mA
28 CONVERTOR 28 CONVERTOR
EXHAUST CYLINDER B10 AICH10 AICH10
2 [0-800°C] MAIN BEARING No.10 1 [0-150°C]
TE35
29 968 TE48 29
918
1 TC/6-20mA 969
2 Pt1000/4-20mA
31 CONVERTOR 31 CONVERTOR
919 TURBOCHARGER INLET A BANK 2 [0-800°C] AICH11 1 [0-150°C] AICH11
32 MAIN BEARING No.11 32
TE06 TE49
970
920
1 TC/6-20mA +
FS1L
34 CONVERTOR 35 +
TURBOCHARGER OUTLET B BANK AICH12 971 CHARGE AIR PRESSURE [T/C OUT A BANK] AICH12
2 [0-800°C] -
TE07 PT01
921 35
E [0-4Bar=4-20mA] 36
972
922 1 TC/6-20mA +
FS1M
37 CONVERTOR 38 +
[0-800°C] AICH13 CHARGE AIR PRESSURE [T/C OUT B BANK] AICH13
CHARGE AIR - T/C OUTLET B BANK 2 -
38 973 PT02
TE02
[0-4Bar=4-20mA] 39
923
+
FS1N 974 +
FS1N
40 + 41 +
924 FUEL PRESSURE ENGINE RETURN RAIL AICH14 LT WATER PRESSURE [L.O COOLER OUTLET] AICH14
- PT11 -
PT22 C
[0-10Bar=4-20mA] [0-4Bar=4-20mA] 42
41 975
925 C
+
FS1O +
FS1O
43 + HT WATER PRESSURE [I/C OUTLET] 44 +
AICH15 976 AICH15 C
SUMP LEVEL LOW - PT10 -
926 [0-4Bar=4-20mA]
LS02b
F 44 45
2 C 20.02.07 ECU INTERCONNECTING NUMBERS ADDED
977
927 FS1P +
FS1P
46 + 47 + 1 C 19.06.06 ORIGINAL
AICH16 SEA WATER PRESSURE [PUMP OUTLET] AICH16
BOOST BYPASS VALVE OPEN - PT34 -
978 DATE AND
XS04 [0-6Bar=4-20mA]
928 48 48 ISSUE ALTERATION FILMED
COPYRIGHT C
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-EL
1 2 3 4 5 6 7 8 9 10
DRG.
No. L 5473 SHT 10
LINE NO.
ECU
FS11 DIODES MOUNTED INSIDE TERMINAL
1000 131 1050 131
SOL +VE SUPPLY TB4/51 59
FS12
A SOL -VE SUPPLY TB4/52 60
132 132
125
126
1
67 126
31 2
1005 1055
RS-2 32
RL1 3 NOT
132
68 USED
4
B 1006 1056
HIGH H.T WATER
2
9
TEMPERATURE RL2 15K
SHUTDOWN 1 125
1007 1002 1057 TE56 10 RL1 5 INPUT
b 33 HS 123 HIGH
29 SPEEDSWITCH 1006
LINE 1061 RS-3 RUNNING LEVEL 6 LINE 1025
1001 392
a 34 RS 30 304
1008 1058
131 41
X03 6 SPEEDSWITCH 125
1009 1059 1
ENGINE
601 43 MODULE 8
X04 SR1-4 126
EMERGENCY 33K 125
7 SD-1 EC[M]723003 4
STOP X05 8 SR2-4 44
1010 PUSH-BUTTON
XS2
1003 45
1060 ECU
X06 SR3-4 616
9 SD-4 MAX. ENGAGE [450 RPM] TB4/63 71 18 CH3 MAX. ENGAGE [450 RPM/2280Hz]
46
SR4-4 1001
1011 1061 17
C ENGINE
EMERGENCY SR5-4
47
LINE 1007
a CH2 RUNNING [50 RPM/253.3Hz]
33K 601 1002
STOP 25 CH 13 WIRE BREAK 48 b 16 CH1 OVERSPEED [1150 RPM/5807Hz]
1012 PUSH-BUTTON SR6-4 1062
XS3 26 CH 14 WIRE BREAK 49
SR7-4 621
50 TB4/41 79 12
1013 SR8-4 1063 ENGINE SPEED
125 4 - 20 mA = 0 - 1200 RPM 622
1 51 TB4/42 80 13
SR9-4
ECU 51
1014 612 SR11-4 1064
LATCH COMMISSION TB4/58 66 5
FS5 52
125 CP-4 SD-5
+VE SUPPLY TB4/62 70
1015 FS6 53 1065
126 WB-2 FLYWHEEL 10
-VE SUPPLY TB4/64 72 3
304 TEETH 8 FSD = 6080 Hz [1200 RPM]
617
COMMISSION PROTECTIONS TB4/65 73 10 9
1016 1066 ST8
613
D COMMISSION TB4/59 67 11
SD-2
Lo SPEED X10 16 9
1022 CP-1 4 1072 OUTPUT POWER SOURCE INTERNAL
PS26 10
LK20 PL12
L724402 SHUTDOWN MODULE - LINK SETTINGS
1023 SR 1073 LINK SETTING LED
17 DESCRIPTION
CP-2 5 A B No. SENSING No. COLOUR
2500G022P29 CONTROL LINES PL2
LK21 PL10 1 ON EMERGENCY STOP 1 RED
LINE 711
1024 1074 2 ON EMERGENCY STOP [ENGINE] 2 RED C
HIGH H.T WATER 125
TEMPERATURE 13 3 ON LOW OIL PRESSURE - Hi SPEED 3 RED
SHUTDOWN 1006 SR 4 ON LOW OIL PRESSURE - Lo SPEED 4 RED C
18 6 14
1025 LINE 1057 CP-3 SPARE INPUTS 1075 5 ON GEARBOX LOW OIL PRESSURE 5 RED
15
LK22 16 6 ON HIGH H.T WATER TEMPERATURE 6 RED C
7 ON HIGH MAIN BEARING TEMPERATURE 7 RED
1026 1007 SR 1076 8 OFF 2 FROM 3 SLOWDOWN INITIATED S/D 8 RED C
19 7
9 OFF OVERSPEED 9 RED
F 15K
705
10 OFF NOT USED 10 RED 2 C 20.02.07 ECU INTERCONNECTING NUMBERS ADDED
1027 HIGH MAIN BEARING 12 13 1008 SR 1077 11 ON FIRE DETECTED 11 RED
TEMPERATURE 20 8
[IF SELECTED IN MAA] MAA/DO-5 12 ON SPEEDSWITCH 12 RED 1 C 19.06.06 ORIGINAL
13 ON EFI SHUTDOWN CIRCUIT 13 RED
1028 304 1078 14 ON - - DATE AND
2 FROM 3 SLOWDOWNS 8 9 SR CHANNEL 13 -VE WIRE BREAK ISSUE ALTERATION FILMED
INITIATED SHUTDOWN 21 9 123 15 ON - - COPYRIGHT C
EFI/DO-03 56 ANY SHUTDOWN
+ 394 LINE 305 16 OFF NOT USED 14 RED
1029 HS-1 55 1079
SD-3 ECU 17 ON
CHANNEL 14 -VE WIRE BREAK
- - DRAWN RJN CONTRACT :-
618
ANY Ch.
OPERATED
SD 58 74 TB4/66 PROTECTION TRIPPED
-
18
-
ON
- WIRE BREAK CIRCUIT HEALTHY
-
15
-
GREEN CHECKED
RK280 - ECU TYPE 3
125
1030 57 1080 19 OFF COMMISSION OVERRIDE - -
SD-6
LK28 SR 355 20 OFF COMMISSION OVERRIDE - -
23
11 60
159
ANY SHUTDOWN TO BCM
LINE 525 21 ON COMMISSION OVERRIDE - -
TITLE
INTEGRATED CONTROL &
1031
ENABLE HI SPEED
305 SD-7
59 1081 22 OFF COMMISSION OVERRIDE - - MONITORING PANEL [ICAM]
G LOW L.O PRESSURE
10
EFI/DO-04
11 1009
12 CH 62
123
FIRE DETECTED TO EFI CONTROLLER
A
A
23
24
-
-
BOARD ADDRESS
BOARD ADDRESS
-
-
-
- SCHEMATIC
SHUTDOWN
1032 DISABLE 393 LINE 304 1082 25 ON 12V PULL UP - -
SPEED SWITCH 61 63
SR11-3 26 ON POWER RAIL - -
CHECK APPROVED DRAWING No.
[NOT USED] 27 ON SR11 SELECTED AS SHUTDOWN - -
28 ON SR11 LATCHED - - DESIGN PRODUCTION L 5473
29 ON - -
125
126
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-EL
E
F
B
G
A
111
No.
119
118
117
116
115
114
113
112
110
132
131
130
129
128
127
126
125
124
123
122
121
120
109
108
107
106
105
104
103
102
101
100
DRG.
LINE No.
1
CABLES
" No.3
" No.2
SOT
A-EFI
A-EXH
AS GIVEN BELOW.
L 5474 Sht 1
A BANK
GLAND PLATE
ISSUE No.
TE17/1
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential.
FPS04/1 16 H.T WATER C.A 16
BOOST BYPASS VALVE X15 TE09/2 TE22/1 TE65/2 CRANKCASE OIL
S0V2/2 4 + 17 COOLER I/L TE09 19 17
SOLENOID SOV2 FPS04/2 C4 PUMP EXHAUST CYLINDER SPLASH No.6 TE65
X16 14 - TE12/1 TE22/2 TE66/1
A7 TE22
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd.
19 L.T WATER L.O 20 19
TE12/2 TE23/1 TE66/2 CRANKCASE OIL
20 COOLER O/L TE12 22 EXHAUST CYLINDER 20 SPLASH No.7 TE66
FPS05/1 TE51/1 TE23/2 TE67/1
5 + A8 TE23
4
OVER
C6 PUMP
SPEED
TE52/1 TE25/1
SWITCH
35 - 28 FUEL OIL RETURN RAIL 28 TE69/1 28
[A BANK]
EXHAUST CYLINDER CRANKCASE OIL
MODULE 8
TE52/2 TEMPERATURE TE52 TE25/2 TE69/2
29 29 A10 TE25 29 SPLASH No.10 TE69
FPS07/1 TE04/1
24 + 31
FPS07/2 C7 PUMP TURBOCHARGER I/L
34 - TE10/1 TE04/2
31 H.T WATER C.A 32 A BANK TE04 31
TE10/2 TE05/1
TE56/1 32 COOLER O/L TE10 34 TURBOCHARGER O/L 32
9 FPS08/1 TE05/2
TE56/2 23 + 35 A BANK TE05
10 FPS08/2 C8 PUMP PT04/1 OE-COMM/20
TRIP
33 - 35 35
HT WATER PRESSURE APPLY SLOWDOWN
PT04/2 TE01/1 OE-COMM/21
MODULE 7
AMPLIFIER
H.J.W.T S/D
36 [PUMP OUTLET] PT04 37 CHARGE AIR - T/C O/L 36 [SCS]
FPS09/1 PT06/1 TE01/2
22 + 38 38 A BANK TE01 38 APPLY SLOWDOWN
FPS09/2 C9 PUMP LT WATER PRESSURE
32 - PT06/2 OE-COMM/22 [RESERVED]
39 [PUMP OUTLET] PT06 39
PT16/1 LS01/+ PS30/1
FPS10/1 41 FUEL PRESSURE 40 41 HIGH CRANKCASE
INJECTOR BANK CONTROL MODULE
PT14/1 21 + PT16/2 BEFORE FILTER PT16 LS01/- FUEL LEAKAGE PS30/2 PRESSURE PS30
L.I FILTER I/L 26 FPS10/2 C10 PUMP 42 41 42
PT14/2 PT08/1 LS01/s LS01 MPD1/1
C
PRESSURE PT14 27 31 - 44 FUEL OIL PRESSURE 42 44
5
38
39
OE-COMM
A-FE-TEMP
B-FE-PRES
B-FWE-PRES
B-FWE-SEN
SHEET 2
SHEET 2
SHEET 2
SHEET 2
SHEET 2
CONTINUED ON
CONTINUED ON
CONTINUED ON
CONTINUED ON
CONTINUED ON
8
ISSUE
DESIGN
TITLE
C
C
C
C
DRAWN
CHECKED
DATE AND
COPYRIGHT
RJN
C 27.07.06
C 20.02.07
9
APPROVED
PRODUCTION
C
CONTRACT :-
DRAWING No.
ORIGINAL
ALTERATION
SHEET 1 OF
PT14 NOW CONNECTED TO 26/27 [WAS 38/39]
10
L 5474
RK280 - ECU TYPE 3
FORM No
A1SHT-EL
EXTERNAL CONNECTIONS - A BANK
3 SHEETS
FILMED
1 2 3 4 5 6 7 8 9 10
DRG.
No. L 5474 Sht 2
LINE No.
OE-COMM/07
OE-COMM/08
OE-COMM/09
200
A
201
BN
BK
B
202
5
203
20
21
23
25
27
29
31
33
35
10
12
13
14
15
16
17
18
19
11
4
5
6
7
8
9
OE-COMM
COMMUNICATION
FROM
RS232 MODBUS
204 SHEET 1
OE-COMM/23
119
OE-COMM/24
120
205 OE-COMM/25
121
PL1
OE-COMM/26
122
OE-COMM/27
123
B 206 124
OE-COMM/28
OE-COMM/29
125
OE-COMM/30
126
207 127 INTERNAL WIRING
OE-COMM/13
EFI CONTROLLER 110
OE-COMM/14
111
208 OE-COMM/15
PERCEPTION
PERCEPTION
116
HEAD ST01
HEAD ST02
FLYWHEEL
FLYWHEEL
117
210 118
C 211
88
89
90
91
92
93
212
10
12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
213
OE-COMM/04
OE-COMM/03
214
PT12/1
PT12/2
PT27/1
PT27/2
PT07/1
PT07/2
ST01/1
ST01/2
ST02/1
ST02/2
B-FWE-SEN CONTINUED ON
215 SHEET 3
B-FE-PRES CONTINUED ON
216 SHEET 3
D B-FWE-PRES CONTINUED ON
SHEET 3
217
FROM
B-FWE-SEN OE-COMM CONTINUED ON
218 SHEET 1 SHEET 3
OE-COMM/10
OE-COMM/12
OE-COMM/05
OE-COMM/06
OE-COMM/11
FROM
B-FE-PRES
SHEET 1
INTERNAL
219
OE-COMM/31 WIRING
220
OE-COMM/32
OE-COMM/33
OE-COMM/34
BN
BK
B
221
107
108
E
3
222
20
21
23
25
27
29
31
33
35
10
12
13
14
15
16
17
18
19
11
4
5
6
7
8
9
COMMUNICATION
RS232 MODBUS
223 110
111
112
PL1
224 C
113
114
C
115
225 116
C
A-FE-TEMP 117
FROM
SHEET 1 118
C
226
MAA CONTROLLER 119
F 120
121
2 C 20.02.07 EFI CONT. T110-127 POSITION CORRECTED
B-FWE-PRES
227 FROM 122
SHEET 1 1 C 27.07.06 ORIGINAL
123
124
228 DATE AND
PERCEPTION
PERCEPTION
HEAD ST07
126
127
DRAWN RJN
T/C B
T/C A
229 CONTRACT :-
230
TITLE
INTEGRATED CONTROL &
231 MONITORING PANEL [ICAM]
ST06/1
ST06/2
ST07/1
ST07/2
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential. C Regulateurs Europa Ltd. 2006 REGULATEURS EUROPA Ltd. FORM No
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd. PORT LANE, COLCHESTER. CO1 2NX. UK. A1SHT-EL
E
F
B
G
A
No.
311
332
331
330
329
328
327
326
325
324
323
322
321
320
319
318
317
316
315
314
313
312
310
309
308
307
306
305
304
303
302
301
300
DRG.
LINE No.
1
FROM
FROM
FROM
FROM
SHEET 2
SHEET 2
SHEET 2
SHEET 2
OE-EFI/03
1
ST3/+
2
ST3/s
L 5474 Sht 3
3
ST3/-
4
OE-COMM
OE-EFI/04 ST5/+
B-FE-PRES
5
B-FWE-SEN
ST5/s
B-FWE-PRES
6
OE-EFI/05 ST5/-
7
ST4/+
2
8
ST4/s
9
ST4/-
10
OE-EFI/06 ST10/+
11
ST10/s
12
OE-EFI/01 ST10/-
13
OE-EFI/07
14
15
OE-EFI/08
16
17
18
19
20
XS04/2
21 BOOST BYPASS 48
PT34/2 XS04/1
22 SEA WATER PRESS. 48 VALVE OPEN XS04 46
OE-EFI/02 PT34/1 LS02B/2
23 [PUMP OUTLET] PT34 47 SUMP LEVEL LOW 44
3
This document is the exclusive property of Regulateurs Europa Ltd. and is strictly confidential.
35 FPS14/1 TURBOCHARGER I/L 32
OE-EFI/14 4 + TE48/2 TE06/1
36 MAIN BEARING No.10 29 A BANK TE06 31
OE-EFI/15 FPS14/2 C4 PUMP TE48/1 TE35/2
14 - TE48
It must not be divulged, copied or reproduced without written authorisation of Regulateurs Europa Ltd.
37 28 EXHAUST CYLINDER 29
TE47/2 TE35/1
38 MAIN BEARING No.9 26 B10 TE35 28
OE-EFI/16 FPS15/1 TE47/1
5 + TE47
4
39 FPS15/2 C5 PUMP 25
15 - TE46/2 TE34/2
40 MAIN BEARING No.8 23 EXHAUST CYLINDER 26
OE-EFI/17 TE46/1 TE34/1
41 TE46 22 B9 TE34 25
OE-EFI/22 FPS16/1 TE45/2 TE33/2
42 25 + 20 23
FPS16/2 C6 PUMP MAIN BEARING No.7 EXHAUST CYLINDER
OE-EFI/18 35 - TE45/1 TE33/1
43 TE45 19 B8 TE33 22
[B BANK]
OE-EFI/19 TE44/2 TE32/2
44 FPS17/1 MAIN BEARING No.6 17 EXHAUST CYLINDER 20
OE-EFI/20 24 + TE44/1 TE32/1
45 TE44 16 B7 TE32 19
OE-EFI/21 FPS17/2 C7 PUMP
46 34 -
OE-EFI/23 TE44/2 TE31/2
47 FPS18/1 MAIN BEARING No.5 14 EXHAUST CYLINDER 17
OE-EFI/24 23 + TE44/1 TE31/1
48 TE43 13 B6 TE31 16
OE-EFI/25 FPS18/2 C8 PUMP TE43/2 TE30/2
49 33 - 11 14
MAIN BEARING No.4 EXHAUST CYLINDER
TE43/1 TE30/1
50 TE42 10 B5 TE30 13
OE-PROT/01 FPS19/1 TE42/2 TE29/2
51 22 + 8 11
FPS19/2 C9 PUMP MAIN BEARING No.3 EXHAUST CYLINDER
OE-PROT/02 32 - TE41/1 TE29/1
52 TE41 7 B4 TE29 10
OE-PROT/19
53 FPS20/1
INJECTOR BANK CONTROL MODULE
C
55 31 - TE40 4 B3 TE28 7
5
TE27/2
56 EXHAUST CYLINDER 5
TE39/2 TE27/1
57 MAIN BEARING No.1 2 B2 TE27 4
TE39/1 TE26/2
58 TE39 1 EXHAUST CYLINDER 2
OE-PROT/03 TE26/1
59 B1 TE26 1
OE-PROT/04
60
OE-PROT/05
61
OE-PROT/06
62
OE-PROT/07
63
OE-PROT/08
64
OE-PROT/09
71
OE-PROT/16
72
OE-PROT/17
73
OE-PROT/18
74
75
76
77
78
MAA CONTROLLER INTERFACE
MAA CONTROLLER INTERFACE
OE-COMM/01
79
OE-COMM/02
80
B BANK SIGNAL CONDITIONING MODULE 5
B BANK SIGNAL CONDITIONING MODULE 4
7
BAR
EARTH
B BANK
GLAND PLATE
CABLES
EARTH BAR FOR
ON-ENGINE SENSOR
8
OE-EFI
OE-COMM
B-FE-PRES
B-FWE-PRES
B-FWE-SEN
B-EXH
OE-PROT
MBT
B-EFI
ISSUE
DESIGN
TITLE
C
C
C
C
DRAWN
CHECKED
DATE AND
COPYRIGHT
RJN
C 20.02.07
C 27.07.06
9
APPROVED
PRODUCTION
C
CONTRACT :-
DRAWING No.
ORIGINAL
ALTERATION
XS04 CONNECTION UPDATED
SHEET 3 OF
10
L 5474
RK280 - ECU TYPE 3
FORM No
A1SHT-EL
EXTERNAL CONNECTIONS - B BANK
3 SHEETS
FILMED
Pub. 3580
10 ASSOCIATED LITERATURE
- 67 -
INSTRUCTION
MANUAL
© Regulateurs Europa Ltd 2007
These instructions have been compiled to assist personnel responsible for the operation and
maintenance of equipment manufactured by Regulateurs Europa Ltd.
Care has been taken to ensure that the equipment has been accurately represented, but it should
be appreciated that, with the continued progress of design and the diversity of application, certain
items may differ in detail.
It should be noted that these instructions are issued for general information and do not constitute
a specification of the equipment.
Whilst reserving the right to make any alteration in design which they may consider advisable the
manufacturers absolve themselves from making any such alteration retrospective.
In addition to the information given herein, practical advice and assistance are always available
from our Service Department.
INSTALLATION NOTE
WARNING
The prime mover should be equipped with a separate overspeed shutdown device, to protect
against runaway or damage to the prime mover, with possible personal injury or loss of life,
should the governor/actuator fail.
SAFETY
Equipment supplied or manufactured by Regulateurs Europa Ltd may contain one or more of the
following:
i) Rotating parts
ii) High pressure oil
iii) Compressed air
iv) High voltages
v) Preloaded springs
vi) PCB’s
vii) Microprocessors
All of the above items represent a potential danger or hazard to operating personnel, therefore the
operator should be aware of the working principles and safety procedures involved with the
equipment being used. Before working on the equipment, the following points should be observed:
2. Ensure that the overall operator-in-charge is informed of the nature of work being
carried out
3. Display and secure warning notices at both local and remote control positions
5. Ensure that the equipment cannot be activated in any way from a remote position.
(In the case of keys operated equipment, all keys must be in the operators
possession.)
Finally, before the equipment is released for operation, ensure that relevant supplies are
reconnected, safety guards and all tools removed.
SAFETY OF PERSONNEL OPERATING & MAINTAINING EQUIPMENT MANUFACTURED BY
REGULATEURS EUROPA LTD
Before carrying out any repairs, adjustments or maintenance to any equipment by Regulateurs
Europa Ltd, it is essential the following safety precautions be observed:
1. General
i) High voltages
ii) Rotating parts
iii) High pressure oil
iv) Compressed air
v) Preloaded springs
vi) PCB’s
vii) Microprocessors
All of the above items represent a potential danger or hazard to operating personnel and the
operator should take care to make himself thoroughly familiar with the operating principles,
methods of adjustment and the dismantling and assembly procedures (where applicable)
concerning the equipment in his care.
1.1 Before carrying out any repairs, adjustments or maintenance to the equipment or unit, the
operator should ensure that any such unit or equipment cannot be activated from a remote
position. To achieve this condition, he should ensure that all electrical/pneumatic supplies to
the prime mover starter system are isolated at their incoming source and that all electrical
supplies to control systems are isolated by the withdrawal of the relevant fuses or by
disconnecting the incoming electrical supply at the control board. In addition to these
precautions, visual-warning notices should be prominently displayed by the equipment or unit
and also at any remote control positions. Where control cabinets and consoles are secured
with keys, all such keys should be in the possession of the operator carrying out the work.
Information regarding position, level and type of work to be carried out should also be made
available to the ‘Engineer in Charge’ of the installation to prevent attempted use of the
equipment or unit during breakdown.
1.2 In the case of electrical/electronic control systems, the operator should make careful
reference to the Instruction manual to ensure that he is aware of any special safety
precautions which are peculiar to that particular equipment or unit.
1.3 Before the equipment or unit is finally released for operation, operating personnel should
ensure that all tools and repair equipment has been removed and that all safety guards are
securely replaced (where applicable). All fuses should be replaced and operating mediums
(electrical and pneumatic supplies) should be opened or reconnected.
ELECTROSTATIC PRECAUTIONS
WARNING
This equipment contains components that are electrostatic sensitive. Electrostatic damage can
cause immediate failure or shortening of useful life.
Servicing PCBs at component level should be done at an electrostatic free workstation. If site work
cannot be avoided, the following precautions must be taken:
b) Personal wrist or ankle earth straps must be worn. To protect against personal
hazard, the resistance of the earth strap should be approximately 250k ohms.
Electrical Interference
a) All cable screens to be terminated and earthed at the entry to the equipment
To ensure prompt and satisfactory attention to customer’s enquiries, all communications should refer
to the UNIT TYPE and SERIAL NUMBER, as stamped on the nameplate.
In order to obtain the most efficient service it is recommended that all enquiries for service or spare
parts to be addressed to the manufacturer of the equipment to which the unit is fitted.
Customer training can be provided either in Colchester or Roden or on site. Contact below for
further details.
Regulateurs Europa b v
1e Energieweg 8
9301 LK
RODEN NETHERLANDS
This guide contains general instructions for the installation of a Viking 25 Digital
Governor Control Unit. Considerations include power supply requirements,
environmental precautions and location to determine the best position for the Control
Unit. The guide also covers connections, cabling and procedures for use in
electro-magnetically noisy environments. As with all electronic equipment, attention
to good practice at the installation stage is essential for reliable operation.
Avoid electrically noisy environments. Where this cannot be done EMC precautions
must be taken, as detailed in the wiring recommendations.
An external connection diagram is supplied for each application of the Viking 25, as
the use of the Input/ Output capacity may be unique to that application. Always refer
to this drawing.
WARNING
IMPORTANT
READ THIS AND ALL OTHER DOCUMENTS AND ASSOCIATED
PUBLICATIONS CONCERNING INSTALLATION, OPERATION & SERVICING
OF THIS EQUIPMENT CAREFULLY.
FAILURE TO FOLLOW INSTRUCTIONS COULD CAUSE PERSONAL INJURY
AND/OR DAMAGE TO THE PRIME MOVER.
WARNING
CAUTION
CAUTION
CAUTION
Components are not necessarily protected against electrostatic discharge when they
are mounted on boards. When boards are removed from their protective packaging
prior to assembly or for servicing, they should be laid on conductive anti-static mats.
Metallic surfaces must be avoided and components should not be touched. To
prevent damage to these parts observe the following precautions:
2 Do not touch the PCB inside the control unit with hands or conductive
devices. If it is necessary to remove the PCB, handle it only by its edges.
3 Avoid all materials around the Control Unit that can store and/or generate
static charges (for example plastics, vinyl, styrofoam etc).
The Viking has various features that are designed to minimise EMC (Electro
Magnetic Compatibility) problems. It is important that these should be maintained for
the life of the product.
CAUTION
1 Perception Head wiring must be shielded for normal use. Use 2 or 3 core
0.5mm CSA insulation, overall screened.
3 The actuator driveline should be shielded, and have a capacity of not less
than 2 amps. Use 2 core 1mm CSA insulated, overall screened.
4 The power supply line should be shielded, and have a capacity of not less
than 2 amps. Use 2 core 1mm CSA insulated, overall screened.
NOTE: Supply plus actuator cable lengths should have a loop, resistance
of less then 2 ohms inclusive, e.g. a maximum loop length of 100
meters of 1mm CSA.
7 Inputs should be from clean contacts fed from the internal or clean supply.
Use multicore 0.5mm CSA insulated overall screened cable. Where there
are high noise levels, all inputs used should be capacitively coupled to
earth.
NOTE: For some installations the minimum wiring CSA may be dictated
by the specification.
8 The Control Unit case must be connected to a clean exclusive earth point,
or at least an instrumentation earth point. The unit must not share an earth
with a high-energy device, such as a generator frame ground.
10 External cables to the Control Unit should not be run alongside of, or in the
same conduit as high voltage/current cables or cables where voltage
spikes could cause spurious signals to be induced in the Control Unit
cables. Control Unit cables should be separated from other cables by
distance of at least 300mm. If these cables have to cross high
voltage/current cables they must cross at 90 degrees to minimise cross
talk.
NOTE: The indicated cable sizes are recommended for loop lengths up to
100 metres. For greater lengths, an intermediate run of larger
sizes to local junction boxes might be necessary to achieve less
than 2 ohms loop resistance.
CAREFULLY check the destination of ALL wires before connecting power to the
Control Unit. Putting the supply voltage onto some signal lines can disrupt the
calibration. CONNECTION OF SUPPLY LEVEL VOLTAGE TO THE ACTUATOR
CIRCUIT CAN CAUSE PERMANENT DAMAGE TO THE ACTUATOR.
The minimum signal level required to trigger the governor is 400mV peak to peak.
This minimum signal must be generated at cranking speed otherwise the engine will
not start. In practice this level is easily exceeded and care must be taken that the
signal level is not so high that imperfections on the flywheel are seen as markers. If
using markers on the face of the flywheel, it is advisable to use studs of 10mm
diameter projecting at least 15mm from the face. This ensures that marks on the
flywheel are out of range of the perception head.
Pre-made leads for perception heads can be supplied by Regulateurs Europa Ltd.
SETTING TO WORK
CAUTION
Ensure that the Viking 25 governing system is installed according to this document
and wired as shown on the external connection drawing. Before applying power to
the controller the following checks should be carried out:-
1. Actuator
1.2 Check linkage and fuel racks are free from backlash and move smoothly.
Ensure fuel rack position corresponds to the following actuator calibration.
CAUTION
1.3 Before switching the supply on, check the loop resistance of the actuator drive
cable between control unit terminals 3(+) and 2 is as follows:
2. Speed Pick Up
2.2 Check loop resistance when disconnected from control unit terminals is 340
ohms ± 20%.
3. Control Unit
24V dc power can now be applied to the control unit. The specific input and output
connections to the controller should now be checked. Refer to the external
connection drawing for details.
VIKING 25
Engine Management System
‘Viking Vision’ can be left running for simple monitoring. VIKING 25 Engine Management System
FEATURES
• Complete engine management system • Controls diesel, dual fuel and spark ignition engines
• Controls actuators or electronic fuel injection • Suitable for power generation, propulsion or traction
applications
• 2 ‘RS’ ports plus 3 CANbus ports supporting both
industry standard and project specific protocols • Parameters can be edited or displayed on a PC in
(Modbus, CANOpen, Device Net) real time as graphs, gauges and bar charts, for fast
service support.
• Easy configuration with ‘Viking Vision’ Windows
PC software
VIKING 25
Engine Management System
SPECIFICATION
VIKING VIKING
BCM BCM TRICAN2
VIKING25 MAA (CANBUS)
(MONITORING
& ALARM)
BCMBUS
(CANBUS)
IVC2
VIKING25 (RS485)
EFI
PROPULSION PANEL
SHUTDOWN
PROTECTION
STATUS
OFF-ENGINE I/O
TRICAN2
VIKING25 DI (CANBUS)
(DATA
INTERFACE)
VMM07 VMM07
(MODBUS RS485) (MODBUS RS485)
SHIPS SHIPS
SYSTEM SYSTEM
(A) (B)
1. OVERVIEW OF SYSTEM
c) Interfacing to Viking BCMs to send fuel quantity and injection timing demands and to receive
diagnostic status information relating to Viking BCM and solenoid operation.
h) Load variable gain function applied to any combination of the proportional, integral and
derivative terms.
x) Priming.
z) Start interlocks
On start up a ‘Use CCF Parameters’ and a ‘Save’ will need to be carried out to set all the preset
menu parameters. The save must be performed without perception head signals being present.
3. INPUTS
CHANNEL DESCRIPTION
1 Spare
2 Spare
3 Spare
4 Spare
5 Spare
6 Spare
7 Spare
8 Spare
Speed measuring is by two speed pickups. The number of teeth / markers is dependent on the
selected engine type. The number of teeth / markers for any of the engine types can be set via
Viking Vision. The preset is for two high speed inputs using 304 teeth on the flywheel.
Note:- If any changes are made to the engine types or a new type is selected a full save,
followed by a power down, is required to allow these changes to be initialised prior to use.
a) The master speed pickup, number 1, is high frequency from the flywheel teeth.
b) The slave speed pickup, number 2, is high frequency from the flywheel teeth.
The primary speed pickup signal is from the master. If this fails then the slave is automatically
selected. The message No Signal will be displayed in the ‘Pickup 1’ alarm menu item and the
governor fault output will be energised.
If the slave speed pickup fails the message No Signal will be displayed in the Pickup 2 alarm
menu item and the governor fault output will be energised.
If both speed pickups fail then the message Pickups Failed will be displayed in the Pickup fault
alarm menu item, the governor fault output will be energised and the engine will revert to backup
mode governing.
If a difference in speed of greater than 2 rpm is measured between speed inputs, the software
automatically selects the highest measured speed as the one for use. In this instance the
message Warning will be displayed in the ‘Pickup Change’ alarm menu item and the governor
fault output will be energised. This functionality can be disabled via the ‘Change Over Enable’
menu item in the ‘Pickups’ menu. Setting this to ‘Disabled’ prevents a change of pickup on a 2
rpm speed difference. The pickups will also not change over below ‘Change Over Speed’ menu
item unless the active pickup fails.
Each speed pickup has a set of speed control gain parameters associated with it. The master
speed pickup uses the parameters in the Dynamics 1 menu and the slave uses the parameters
in the Dynamic 2 menu.
The Engine Status menu will display the messages ‘Pickup 1’ or ‘Pickup 2’ in the ‘Pickup In Use’
menu item to indicate the speed pickup in use.
6. START UP AND INITIAL RUN-UP
The engine can be started by energising the Start digital input or a comms based start request
via the IVC2 interface. In order for a start to be allowed, the following conditions must be met:
If any one of the above conditions is not met then the start sequence will be inhibited.
If the start function proceeds, the Air Start output is energised. In order that an auto start cannot
occur if a speed signal is not present, a stop is activated as soon as the Air Start output is
applied. As soon as a perception head signal is detected, the stop is deactivated and the
fuelling is set to the ‘Start Fuel Limit’ level. This minimises the possibility of air still being applied
to the air start motor, whilst the engine is actively running (the speed being un-detected by the
electronics).
When the speed reaches ‘Running Speed’ the Air Start output is de-energised and locked out.
If the engine speed does not reach ‘Idle Speed’ within ‘Start Time’ and a perception head signal
has not been detected a ‘Pickups Failed’ message will be displayed in the Pickup Fault alarm
menu item, the Controller Fault output will be energised, the Stop output will be energised, the
Air Start output removed and the start sequence will be terminated. If perception head signals
had been detected then a warning will be displayed in the ‘Fail To Start’ alarm menu item, the
Controller Fault output will be energised, the Stop output will be energised, and the start
sequence will be terminated. A reset will be required to remove the ‘Fail To Start’ alarm.
When setspeed has been achieved, the start fuel limit function is released so that normal
governing can proceed.
7. SPEED SETTING
According to the status of the Remote Control /Local Control digital input, the setspeed can be
adjusted either remotely or locally. Both analogue and digital speed setting modes are available
remotely, and digital speed setting mode locally:-
The speed is adjustable between the ‘Minimum Speed’ and ‘Maximum Speed’ range
(Digital Config. Menu) via the raise and lower digital inputs.
The speed can be adjusted between ‘Minimum Speed’ and ‘Maximum Speed’ range
(Analogue Config. Menu) in this mode using the speed setting analogue input.
The speed is adjustable between the ‘Minimum Speed’ and ‘Maximum Speed’ range
(Digital Config. Menu) via the raise and lower digital inputs.
It is possible to transfer from analogue to digital speed setting mode at any time as the setspeed
is frozen at the point of transfer. However in order to transfer from digital to analogue, the
analogue setspeed signal must first match the current engine speed so that the error between
them does not exceed +/- ‘Station Match Band’. When the error is less than this value and a
stop is not active and the engine is not running in cooldown mode, the Control Stations Matched
output will operate to indicate that it is possible to transfer mode. The hardware will then permit
transfer.
The ‘Engine Status’ menu will display whether local or remote control is active and also whether
the control is digital or analogue.
There is one further mode of operation – ‘backup mode’ which is used when the speed control
fails to backup mode. In this situation the setspeed is continuously set to the actual engine
speed in order to provide ‘bumpless’ switch back to normal governing mode when required.
If a slowdown is active the set speed will ramp to the Idle Speed setting, the Governor Fault
output will be energised and a Go To Idle alarm will be displayed in the alarm menu.
If, however, the Emergency Override Enable input is operated then the go to idle function will be
inhibited.
Operation of the Emergency Override Enable digital input is on a toggle basis, i.e. the function is
enabled by energising and then de-energising the input. Energising and then de-energising the
input again then disables the function.
The setspeed will be ramped to its new demand (either using digital inputs or analogue speed
setting input) using the adjustable curve shown below.
Speed
R1/R2 Speed
Up 'Down
Ram p 1' Ram p 2'
Idle Speed
Minimum Speed
Time
t1 t2 t3 t4
Two sets of two upward and two downward ramp rates are provided to provide ramped speed
setting suited to the application.
Five adjustable parameters make up the core of the speed setting ramp rate function:
v) ‘R1/R2 Speed’ Speed at which ramp rate changes from Ramp1 to Ramp2.
Via these parameters it is possible to vary the speed ramps independently and to alter the
speed at which the ramp changes from Ramp1 to Ramp2. It should be noted that the
programmed speed ramp is functional in all modes of speed setting.
If digital input 7 is configured as a Ramp Rate Select digital input and it is is energised then the
second set of ramp rates will be used (suffix ‘B’ in the menu), otherwise the first set (suffix ‘A’ in
the menu) will be used.
The ‘Engine Status’ menu will display which set of ramp rates are actively in use.
7.5 Cooldown Timer
If the engine speed is greater than ‘Running Speed’ and a normal stop is operated, the engine
speed will ramp down to idle where it will be held for a period of ‘Cooldown Time’. Once this time
has expired the engine will be stopped.
If a normal stop operates with the engine speed below ‘Running Rpm’, it will be treated as an
immediate stop signal.
If a shutdown is requested during the cooldown period, the engine will immediately shutdown.
If digital input 7 is configured to act as a fault – go to idle input via the menu parameter ‘Dig IP 7
Config’ in the Speed Setting menu, then when it is operated, the engines speed will be taken to
idle, but only if the engine is operating in remote analogue speed setting mode.
If the speed setting signal has fallen below 2mA or exceeds 21mA then the speed setting
transducer is assumed to have failed. The speed setting input will be set to 0%. A Set Speed
Trans. Fail alarm will be displayed in the ‘Transducer’ alarm menu and the governor fault output
will be energised. The signal fault has to be reset before the speed setting transducer input is
again available for use.
8. FUEL LIMITATION
Boost pressure and torque fuel limitation functions can be enabled and disabled via the
individual menus enable items.
Note :- Setting all the data points of any fuel limitation function to Maximum Fuel Qty value, will
prevent any limitation even if Enabled is selected for that function.
If boost pressure or torque fuel limitation are limiting the available fuel then the’ Engine Status’
menu will indicate the fuel limitation in control.
Boost pressure fuel limit is a control of fuelling as a function of boost pressure. The relationship
has been preset to give the supplied curve, but can be adjusted on a running engine by editing
Data Points 0-10. The parameters Maximum Boost mA and Minimum Boost mA are the
transducer current output representing maximum boost and no boost for scaling purposes.
10000
Fuel
Quantity
Parameters
(mm3/str)
Data Pt 0 to 10
Boost Pressure
0 100
(% of range)
Torque fuel limit is a control of fuelling as a function of actual engine speed. The relationship
has been preset to give the supplied curve, but can be adjusted on a running engine by editing
Data Points 0-10. It should be noted that the Torque Limit speed range is determined by the
High RPM and Low RPM settings under the Torque Limit menu.
10000
Fuel
Quantity
Parameters
(mm3/str)
Data Pt 0 to 10
At start up the fuelling rate can be controlled to a level independent of the boost and torque
functions by programming start fuel limit in the Systems menu. When set speed is reached the
start fuel limit is unlatched.
If the boost pressure fuel limit is enabled in the menu and the output of the boost transducer has
fallen below 2mA then the boost transducer is assumed to have failed. The boost input will be
set to 100% to prevent any limiting. A CAP PT12 Trans. Fail alarm will be displayed in the
‘Transducer’ alarm menu and the governor fault output will be energised. This fault has to be
reset before the boost pressure transducer input is again available for use.
9. LOAD VARIABLE GAIN
The load variable gain is a control of fuel as a function of engine load (actuator position). The
relationship has been preset to give the supplied curve, but can be adjusted on a running engine
by editing Data Points 0-10 in the Load Variable Gain menu.
The load variable gain can be applied to any combination of the proportional, integral and
derivative terms. This can be selected via the Proportional Enable, Integral Enable and
Derivative Enable menu items.
The modification acts as a multiplier to the Prop.Gain, Integ.Gain and Deriv.Gain items in the
currently selected Dynamics menu. Setting the data points to 100.0% will multiply these gains
by 1. Setting the data points to 50.0% will multiply the gains by 0.5.
100.0
Parameters
Gain Data Pt 0 to 10
Modifier
0 Actuator Position 10
Actuator positions below 0 will be treated the same as 0, actuator positions above 10 will be
treated the same as 10.
Note: the actuator position used to determine the gain modifiers is taken before any fuel limits
or fuel derates have been applied.
10. SPEED VARIABLE GAIN 1
The speed variable gain 1 is a control on fuel as a function of engine speed. The relationship
has been preset to give the supplied curve, but can be adjusted on a running engine by editing
Data Points 0-10.
The speed variable gain 1 can be applied to any combination of the proportional, integral and
derivative terms. This can be selected via the speed variable gain 1 menu.
The modification acts on the Prop.Gain, Integ.Gain and Deriv.Gain items in the currently
selected Dynamics menu. Setting the data points to 100.0% will multiply these gains by 1.
Setting the data points to 50.0% will multiply the gains by 0.5.
100.0
Modification
to selected
PID terms Parameters
(%) Data Pt 0 to 10
The speed variable gain 2 is a control on fuel as a function of engine speed. The relationship
has been preset to give the supplied curve, but can be adjusted on a running engine by editing
Data Points 0-10.
The speed variable gain 2 can be applied to any combination of the proportional, integral and
derivative terms. This can be selected via the speed variable gain 2 menu.
The modification acts on the Prop.Gain, Integ.Gain and Deriv.Gain items in the currently
selected Dynamics menu. Setting the data points to 100.0% will multiply these gains by 1.
Setting the data points to 50.0% will multiply the gains by 0.5.
100.0
Modification
to selected
PID terms Parameters
(%) Data Pt 0 to 10
The non-linear gain is a control on fuel as a function of the error between the set speed and the
actual speed. Above the first Error Range percentage speed error the control is linear. The
relationship has been preset to give the supplied curve, but can be adjusted on a running engine
by editing Data Points 0-10. The non-linear gain can be enabled via the non-linear gain menu.
If 0 ≤ speed error ≤ Error Range, the function will retrieve a value from the 11 point curve. This
value will directly replace the original speed error.
Note: If the Error Range is adjusted the data points will need to be scaled to match the new
value.
10
Parameters
New Speed Data Pt 0 to 10
Error
0
Speed Error
0 Error Range
(%)
13. SYSTEMS FUNCTIONS
If the engine is available for a start then the 'Ready To Start' message will be given in the Engine
Status display menu. The conditions for this message are that the engine is not running, there
is no stop signal, the governor is healthy and no faults are present.
A pickup fault is registered if the controller detects that a speed measurement, having previously
been present and above Running Speed, reduces below the speed pickup detection speed
without a stop having been initiated. This would occur if the pickup signal was lost whilst the
engine was running but could also be due to an engine stall. A Pickup Fault error will be
displayed in the alarm menu, the Governor Fault output will be energised and the engine will
revert to backup mode governing.
13.3 Stop
When a stop command is received, the cooldown function will operate after which the fuel
demand is driven to the stop position, the Governor Shutdown output is energised and the stop
timer is started.
When the Fault Shutdown digital input is energised the fuel demand is driven to the stop
position, the Governor Shutdown output is energised, the set speed is taken to idle and a ‘Fault
Shutdown’ alarm will be displayed in the alarm menu. A reset is required with the engine
stationary to remove the shutdown condition.
When the stop button in the Viking Vision program is clicked the fuel demand is driven to the
stop position, the Governor Shutdown output is energised, the set speed is taken to idle and a
‘Vision Stop’ will be displayed in the alarm menu. A reset is required with the engine stationary
to remove the shutdown condition.
If a stop has been initiated and the engine is still running after a period of ‘Stop Time’ has
expired then the Controller Fault digital output will be energised, the stop is latched in and the
‘Fail To Stop’ alarm will be displayed in the Stops alarm menu.
A reset is required with the engine stationary to remove the stop and alarm condition.
13.7 Governor Healthy Digital Output
The Governor Healthy output is always energised via the software. If the Viking25 fails the
output will be de-energised.
The Governor Fault output will be energised in the event of any alarm occurring. The alarm
menu will indicate the fault that has occurred.
13.9 Overload
If the global fuelling demand exceeds ‘Overload Level’ for a continuous period of time equal to
‘Overload Delay’ then the governor fault output will be energised and an ‘Overload’ alarm will be
displayed in the ‘General’ alarm menu.
A digital output ‘Commission Alarms’ is provided to commission alarms external to the Viking25
EFI unit.
The output will energise when the engine speed has exceeded ‘Comms. Alarm Speed’ for a
continuous period of time equal to ‘Comms. Alarm Delay’. The output will de-energise when the
engine speed has fallen below (‘Comms. Alarm Speed’ – ‘Comms. Alarm Hyst’), or if a stop is
active.
A digital output ‘Enable low LOP high speed shutdown’ is provided to commission the Low LOP
high speed shutdown function external to the Viking25 EFI unit.
The output will energise when the engine speed has exceeded ‘HS LOP SD Speed’ and will de-
energise when the engine speed falls below ‘HS LOP SD Speed’ – ‘HS LOP SD Hyst.’
A digital output ‘Running at idle speed’ is provided. The output will de-energise when the engine
speed is below ‘Running at idle Lev.’ and energise when the speed falls below ‘Running at idle
Lev.’ – ‘Running At Idle Hyst’
14. BOOST BYPASS CONTROL
When the engine speed is between ‘Boost Bypass Low’ and ‘Boost Bypass High’ the Open
Boost Bypass Valve digital output will be energised. When the engine speed is outside of this
range the Open Boost Bypass Valve digital output will be de-energised.
A hysteresis band of ‘Boost Bypass Hyst’ is applied to the speed levels to prevent toggling of the
valve at the limits of the speed band.
The function can be disabled via the ‘Boost Bypass’ menu item. When the function is disabled
the Open Boost Bypass Valve digital output will be de-energised.
All parameters are adjustable from the ‘Boost Bypass Valve’ menu.
valve de-energised
valve de-energised
Boost
Bypass
Hyst
Boost Bypass High
INCREASING DECREASING
SPEED SPEED
valve energised
valve energised
valve de-energised
valve de-energised
15. AVLOS (AIR VALVE LUBRICATING OIL SYSTEM) PUMP CONTROL
When the engine speed is below ‘AVLOS Level’ – ‘AVLOS Hyst.’, or the Gearbox At Neutral
input is energised, the Start AVLOS Pump digital output will be de-energised to drain the oil.
When the engine speed is above ‘AVLOS Level’ and the Gearbox At Neutral input is de-
energised the Start AVLOS Pump digital output will be energised for lubrication.
All parameters are adjustable from the ‘AVLOS Pump ‘edit menu.
16 FUEL MODULE CONTROL DIGITAL OUTPUT
The Start Fuel Pumps digital output will be energised on initiation of a start attempt and will be
maintained at all times above firing speed.
The software will monitor the status of the engine speed after a time period equal to ‘Time
Delay’ from when the Air Start digital output is energised. If the engine has not achieved ‘Firing
Speed’ by the end of this delay then the Start Fuel Pumps digital output will be de-energised.
The value of firing speed (‘Firing Speed’) and the time delay to get firing speed (‘Time Delay’)
from start can be edited in the ‘Fuel Module’ edit menu.
17 ENGINE SLOWDOWNS
Engine slowdowns can be instigated by the following analogue and digital sources.
If the engine speed exceeds ‘Commission Speed’ for a continuous period of time exceeding
‘Commission Delay’ then the slowdowns are commissioned. If the engine speed falls below
‘Commission Speed’ – ‘Commission Hyst’ then the slowdowns are instantly decommissioned.
The status of the slowdown commissioning is displayed in each of the slowdown menus.
Ten oil splash temperature inputs (PT600) are supported by the Viking25 EFI. The temperature
sensed by each is displayed in the Slowdowns > Oil Splash Temp. > Measured Value menu.
(Note:- Oil splash temperatures will continue to be displayed even when a transducer failure
alarm is active in order to assist with the calibration of signal conditioning.)
The hardware configuration for each sensor can be adjusted in the Slowdowns > Oil Splash
Temp. > Hardware edit menu. The range in terms of electrical and measured signal can be set.
The slowdown configuration for each sensor can be adjusted in the Slowdowns > Oil Splash
Temp. > Slowdown Config. edit menu. Each sensor can either be set to ‘Disabled’ in which case
the temperature is displayed but slowdown or transducer error is inhibited, or it can be set to
‘Enabled’ in which case both slowdown and transducer error will be generated if conditions
arise.
If a channel is active and has no transducer failure alarm then it will contribute towards the
average oil splash temperature reading displayed as ‘OS Mean’. Once slowdowns are
commissioned then if any channel deviates by more than ‘Channel SLD Dev.’ In a positive or
negative direction for a continuous period of time exceeding ‘Channel SLD Delay’ then the
channel will instigate an ‘OSx TE6X SLD’ alarm and the engine speed will be taken to idle.
A reset is required with the measured temperature in a healthy condition for the engine speed to
return to normal demand.
If a particular oil splash temperature signal has fallen below 2mA or exceeds 21mA and the
sensor is active, then the oil splash temperature transducer is assumed to have failed. The oil
splash temperature input will continue to display temperature, but the slowdown functionality
associated with it will be disabled. An ‘OSx TE6x Trans. Fail’ alarm will be displayed in the
‘Transducer’ alarm menu and the governor fault output will be energised. The signal fault has to
be reset before the oil splash temperature transducer input is again available for use.
17.3 Mean Oil Splash Temperature Slowdowns
The mean temperature slowdown configuration can be adjusted in the Slowdowns > Oil Splash
Temp. > Slowdown Config. edit menu. The mean slowdown ‘Mean Config.’ menu item can either
be set to ‘Disabled’ in which case the temperature slowdown is inhibited, or it can be set to
‘Enabled’ in which case the slowdown will be generated if conditions arise.
Once slowdowns are commissioned then if any channels are active and the mean oil splash
temperature exceeds ’Mean SLD Level’ for a continuous period of time exceeding ‘Mean SLD
Delay’ then an ‘OS Mean SLD’ alarm will be instigated and the engine speed will be taken to
idle.
A reset is required with the mean oil splash temperature in a healthy condition for the engine
speed to return to normal demand.
17.4 HT Water Pressure Slowdown
An HT water pressure sensor input is supported by the Viking25 EFI. The pressure sensed is
displayed in the Slowdowns > HT Water Pressure menu.
The hardware configuration for the sensor can be adjusted in the Slowdowns > HT Water
Pressure > Hardware edit menu. The range in terms of electrical and measured signal can be
set.
The slowdown configuration can be adjusted in the Slowdowns > HT Water Pressure >
Slowdown Config. edit menu. The sensor can either be set to ‘Disabled’ in which case the
pressure is displayed but slowdown or transducer error is inhibited, or it can be set to ‘Enabled’
in which case both slowdown and transducer error will be generated if conditions arise.
Once slowdowns are commissioned then if the HT water pressure channel is active and the HT
water pressure drops below ‘Lo HTWP LS PT27 Lev.’ for a continuous period of time exceeding
‘Lo HTWP Delay’, or the engine speed is above ‘Low HTWP HS Speed’ and the HT water
pressure drops below ‘Lo HTWP HS PT27 Lev.’ for a continuous period of time exceeding ‘Lo
HTWP Delay’, then a ‘Lo HTWP PT27 SLD’ alarm will be instigated and the engine speed will be
taken to idle.
A reset is required with the HT water pressure in a healthy condition for the engine speed to
return to normal demand.
If the HT water pressure signal has fallen below 2mA or exceeds 21mA and the sensor is active,
then the HT water pressure transducer is assumed to have failed. The HT water pressure input
will display maximum pressure, but the slowdown functionality associated with it will be disabled.
An ‘HTWP PT27 Trans. Fail’ alarm will be displayed in the ‘Transducer’ alarm menu and the
governor fault output will be energised. The signal fault has to be reset before the HT water
pressure transducer input is again available for use.
17.5 SCS Slowdown
An SCS Slowdown input is supported by the Viking25 EFI. Wirebreak detection is supported for
this input. The status of the input and the input’s wirebreak sensing are displayed in the
Slowdowns > Digitals menu.
The slowdown configuration can be adjusted in the Slowdowns > Digitals > Slowdown Config.
edit menu. The sensor (‘SCS Config.’) can either be set to ‘Disabled’ in which case the
slowdown is inhibited, or it can be set to ‘Enabled’ in which case the slowdown will be generated
if conditions arise.
If the SCS slowdown channel is active and the SCS Slowdown input is energised (> 2.45V) for a
period of time that exceeds ‘Digital SLD Delay’ then a ‘SCS SLD’ alarm will be instigated and the
engine speed will be taken to idle.
A reset is required with the SCS slowdown channel in a healthy condition for the engine speed
to return to normal demand.
The wirebreak configuration can be adjusted in the Slowdowns > Digitals > Wirebreak Config.
edit menu. The wirebreak sensing (‘SCS WB Config.’) can either be set to ‘Disabled’ in which
case the the wirebreak alarm is inhibited, or it can be set to ‘Enabled’ in which case the
wirebreak alarm will be generated if conditions arise.
If the SCS slowdown channel is active and the SCS Slowdown input is sensed as being open
circuit (< 0.5V) for a period of time that exceeds ‘Digital WB Delay’ then a ‘SCS SLD WB’ alarm
will be instigated.
A reset is required with the SCS slowdown channel in a connected condition for the wirebreak
alarm to be cleared.
17.6 Oil Mist Slowdown (Optional)
An Oil Mist Slowdown input is supported by the Viking25 EFI. Wirebreak detection is supported
for this input. The status of the input and the input’s wirebreak sensing are displayed in the
Slowdowns > Digitals menu.
The slowdown configuration can be adjusted in the Slowdowns > Digitals > Slowdown Config.
edit menu. The sensor (‘OMD1 Config.’) can either be set to ‘Disabled’ in which case the
slowdown is inhibited, or it can be set to ‘Enabled’ in which case the slowdown will be generated
if conditions arise.
If the oil mist slowdown channel is active and the Oil Mist Slowdown input is energised (> 2.45V)
for a period of time that exceeds ‘Digital SLD Delay’ then a ‘OMD1 SLD’ alarm will be instigated
and the engine speed will be taken to idle.
A reset is required with the Oil Mist slowdown channel in a healthy condition for the engine
speed to return to normal demand.
The wirebreak configuration can be adjusted in the Slowdowns > Digitals > Wirebreak Config.
edit menu. The wirebreak sensing (‘OMD1 WB Config.’) can either be set to ‘Disabled’ in which
case the the wirebreak alarm is inhibited, or it can be set to ‘Enabled’ in which case the
wirebreak alarm will be generated if conditions arise.
If the Oil Mist slowdown channel is active and the Oil Mist Slowdown input is sensed as being
open circuit (< 0.5V) for a period of time that exceeds ‘Digital WB Delay’ then a ‘OMD1 SLD WB’
alarm will be instigated.
A reset is required with the Oil Mist slowdown channel in a connected condition for the
wirebreak alarm to be cleared.
17.7 High Crankcase Pressure Slowdown
A High Crankcase Pressure Slowdown input is supported by the Viking25 EFI. Wirebreak
detection is supported for this input. The status of the input and the input’s wirebreak sensing
are displayed in the Slowdowns > Digitals menu.
The slowdown configuration can be adjusted in the Slowdowns > Digitals > Slowdown Config.
edit menu. The sensor (‘Hi CP PS30 Config.’) can either be set to ‘Disabled’ in which case the
slowdown is inhibited, or it can be set to ‘Enabled’ in which case the slowdown will be generated
if conditions arise.
Once slowdowns are commissioned then if the High Crankcase Pressure Slowdown channel is
active and the High Crankcase Pressure Slowdown input is energised (> 2.45V) for a period of
time that exceeds ‘Digital SLD Delay’ then a ‘Hi CP PS30 SLD’ alarm will be instigated and the
engine speed will be taken to idle.
A reset is required with the High Crankcase Pressure slowdown channel in a healthy condition
for the engine speed to return to normal demand.
The wirebreak configuration can be adjusted in the Slowdowns > Digitals > Wirebreak Config.
edit menu. The wirebreak sensing (‘Hi CP PS30 WB Config.’) can either be set to ‘Disabled’ in
which case the the wirebreak alarm is inhibited, or it can be set to ‘Enabled’ in which case the
wirebreak alarm will be generated if conditions arise.
If the High Crankcase Pressure Slowdown channel is active and the High Crankcase Pressure
Slowdown input is sensed as being open circuit (< 0.5V) for a period of time that exceeds ‘Digital
WB Delay’ then a ‘Hi CP PS30 SLD WB’ alarm will be instigated.
A reset is required with the High Crankcase Pressure Slowdown channel in a connected
condition for the wirebreak alarm to be cleared.
17.8 Metal Particles Detected Slowdown
A Metal Particles Detected Slowdown input is supported by the Viking25 EFI. Wirebreak
detection is supported for this input. The status of the input and the input’s wirebreak sensing
are displayed in the Slowdowns > Digitals menu.
The slowdown configuration can be adjusted in the Slowdowns > Digitals > Slowdown Config.
edit menu. The sensor (‘MPD1 Config.’) can either be set to ‘Disabled’ in which case the
slowdown is inhibited, or it can be set to ‘Enabled’ in which case the slowdown will be generated
if conditions arise.
If the Metal Particles Detected Slowdown channel is active and the Metal Particles Detected
Slowdown input is energised (> 2.45V) for a period of time that exceeds ‘Digital SLD Delay’ then
a ‘MPD1 SLD’ alarm will be instigated and the engine speed will be taken to idle.
A reset is required with the Metal Particles Detected Slowdown channel in a healthy condition
for the engine speed to return to normal demand.
The wirebreak configuration can be adjusted in the Slowdowns > Digitals > Wirebreak Config.
edit menu. The wirebreak sensing (‘MPD1 WB Config.’) can either be set to ‘Disabled’ in which
case the the wirebreak alarm is inhibited, or it can be set to ‘Enabled’ in which case the
wirebreak alarm will be generated if conditions arise.
If the Metal Particles Detected Slowdown channel is active and the Metal Particles Detected
Slowdown input is sensed as being open circuit (< 0.5V) for a period of time that exceeds ‘Digital
WB Delay’ then a ‘MPD1 SLD WB’ alarm will be instigated.
A reset is required with the Metal Particles Detected Slowdown channel in a connected condition
for the wirebreak alarm to be cleared.
17.9 Viking25 MAA Slowdown
A Viking25 MAA Slowdown input is supported by the Viking25 EFI. Wirebreak detection is
supported for this input. The status of the input and the input’s wirebreak sensing are displayed
in the Slowdowns > Digitals menu.
The slowdown configuration can be adjusted in the Slowdowns > Digitals > Slowdown Config.
edit menu. The sensor (‘MAA Config.’) can either be set to ‘Disabled’ in which case the
slowdown is inhibited, or it can be set to ‘Enabled’ in which case the slowdown will be generated
if conditions arise.
If the Viking25 MAA Slowdown channel is active and the Viking25 MAA Slowdown input is
energised (> 2.45V) for a period of time that exceeds ‘Digital SLD Delay’ then a ‘MAA SLD’
alarm will be instigated and the engine speed will be taken to idle.
Note:- A reset is not required for the engine speed to return to normal demand – this will
automatically occur as soon as the Viking25 MAA Slowdown channel becomes inactive.
The wirebreak configuration can be adjusted in the Slowdowns > Digitals > Wirebreak Config.
edit menu. The wirebreak sensing (‘MAA WB Config.’) can either be set to ‘Disabled’ in which
case the the wirebreak alarm is inhibited, or it can be set to ‘Enabled’ in which case the
wirebreak alarm will be generated if conditions arise.
If the Viking25 MAA Slowdown channel is active and the Viking25 MAA Slowdown input is
sensed as being open circuit (< 0.5V) for a period of time that exceeds ‘Digital WB Delay’ then a
‘MAA SLD WB’ alarm will be instigated.
A reset is required with the Viking25 MAA Slowdown channel in a connected condition for the
wirebreak alarm to be cleared.
17.10 2 From 3 Shutdown
If any two of the following conditions arise then a 2 From 3 shutdown will be instigated.
The 2 From 3 shutdown will self-reset when the trigger slowdowns are in a healthy condition.
18. PRIMING
The software supports both pre-start and continuous priming modes of operation, the selection
of which is via the ‘Prime Operation’ menu parameter in the Priming > General menu.
In this mode the software will enable the priming to take place when a start sequence is initiated.
An engine start will only follow if the priming cycle has been successful. For the rest of the time
when the engine is stationary the prime pump is de-energised.
However, there is an exception to this - if the engine has been running and then stops, the prime
pump will energise when the engine speed falls below ‘Pump On Speed’ and will continue to run
for a period of time (‘Post-Run Prime Time’) during which the engine can be immediately started
again (assuming prime pressure remains healthy). This enables a quick start without the
requirement for a further priming cycle to have been exercised first.
If the engine has been stationary for a period of time greater than ‘Post-Run Prime Time’, the
engine will be inhibited from starting, the ‘Prime Not Achieved’ menu parameter will show
‘active’, and the priming pump will be de-energised. When a start command is received and no
stops are active, the priming pump will be energised. If a healthy priming pressure (‘Prime
Healthy’) is then established for a continuous period of ‘Pre-Run Prime Time’, the engine will be
permitted to start and the ‘Prime Not Achieved’ menu parameter will change top show ‘inactive’.
The prime pump will remain energised until the engine speed exceeds ‘Pump Off Speed’ unless
one of the following situations arises:
a) If the priming pump is energised and the priming pressure falls below ‘Prime Healthy’ –
‘Prime Healthy Hyst’ for a period of time exceeding ‘Prime Fail Time’ then a Fail To Prime
alarm will be activated, the priming pump will be de-energised and the engine will be
inhibited from starting. The ‘Prime Not Achieved’ menu parameter will change to show
‘active’. This condition will remain until an alarm reset is operated at which point the priming
sequence will be reset to the point where the software is awaiting an engine start initiation.
b) If the engine is stationary and a new stop is operated or a fire is detected then the priming
sequence will be reset to the point where the software is awaiting an engine start initiation,
and the priming pump will be de-energised. The sequence will continue only when no fire is
detected and no new stop is active.
18.2 Continuous Priming
In this mode the software will enable the priming to take place whenever the engine is
stationary, but an engine start will still only follow if the priming is successful.
If the engine has been running and then stops, the prime pump will energise when the engine
speed falls below ‘Pump On Speed’ and will continue to run for a period of time (‘Post-Run
Prime Time’) during which the engine can be immediately started again (assuming prime
pressure remains healthy). This enables a quick start without the requirement for further priming
to have been exercised first.
If the engine has been stationary for a period of time greater than ‘Post-Run Time’, the engine
will be inhibited from starting and the ‘Prime Not Achieved’ menu parameter will show ‘active’. If
a healthy priming pressure (‘Prime Healthy’) is then established for a continuous period of
‘Prime Time’ and no stops are active, the engine will be permitted to start and the ‘Prime Not
Achieved’ menu parameter will change top show ‘inactive’.
The prime pump will remain energised until the engine speed exceeds ‘Pump Off Speed’ unless
one of the following situations arises:
a) If the priming pump is energised and the priming pressure falls below ‘Prime Healthy’ –
‘Prime Healthy Hyst’ for a period of time exceeding ‘Prime Fail Time’ then a Fail To Prime
alarm will be activated, the priming pump will be de-energised and the engine will be
inhibited from starting. The ‘Prime Not Achieved’ menu parameter will change to show
‘active’. This condition will remain until an alarm reset is operated at which point the priming
sequence will be reset to the point where the software is awaiting a healthy priming
pressure (‘Prime Healthy’) to be established for a continuous period of ‘Prime Time’.
b) If the engine is stationary and a new stop is operated or a fire is detected then the priming
sequence will be reset to the point where the software is awaiting a healthy priming
pressure (‘Prime Healthy’) to be established for a continuous period of ‘Prime Time’, and
that the priming pump will be de-energised. The sequence will continue only when no fire is
detected and no new stop is active.
19. ENGINE TYPE SELECTION
The engine type is selected and configured via the menu system.
With the exception of Flywheel Rotation (CCW or CW), the parameters within the Engine Types
menu are pre-configured for the RK280 range of engines and will not require adjustment.
20. DROOP / ISOCHRONOUS OPERATION
The unit will operate in droop mode. Setting the droop to 0% will enable isochronous operation.
21. TEMPERATURE LOGGING
The temperature of the board is constantly monitored and displayed in the ‘Temperature’ menu.
This also displays the maximum and minimum values since the last reset of the temperature
measuring function. The maximum and minimum values are stored in memory when changed
from previous values.
The ‘Status’ menu item shows the status of the saving operation. If the maximum and minimum
values have not changed ‘Not Required’ will be shown. If awaiting a save, due to the engine
running or the timer not having expired, ‘Awaiting Save’ will be shown. If a save is in progress
‘Saving’ will be shown.
21.2 Power Up
When the unit is powered up the stored values are read from memory. If these are corrupted
the maximum and minimum will be set to the current temperature, the ‘Calib. Memory Error’
alarm will be displayed in the alarm menu and the data will be logged to memory as soon as the
engine is not running. This alarm can be removed with a reset.
When the ‘Reset’ menu item is saved and the ‘Save All Edited Data’ is saved the unit will reset
the maximum and minimum values to the current temperature and log the values to memory,
provided the engine is stopped.
If the maximum and minimum change, the ‘Reset’ menu item is activated or an error occurs
reading the memory at power up the maximum and minimum values are logged to memory.
NOTE :- During normal use, no reset and no errors, the logging to memory is prevented
from happening within 4 hours of the last save. In this circumstance the Status
display will show ‘Awaiting Save’.
The logging to memory will not occur when the engine is running. In this
circumstance the Status display will show ‘Awaiting Save’.
22.1.1 Communications
The CAN communications between the Viking25 and the Viking Bank Control Modules (BCMs)
uses CAN 2.0B with a baud rate of 500 KBit/second running BCMbus protocol. The Viking25 is
designated to be the Master unit, the two Viking BCMs the slaves.
When the system is first powered up the Viking25 will de-energise the Disengage Backup Mode
digital output for at least 30ms prior to energising it. The BCMs will move out of backup mode
on the rising edge and start looking for the Master Message 1 transmission from the Viking25.
The communications will then proceed as specified in the BCMbus protocol definition document.
If the Viking BCMs fail to see three consecutive Master Message 1 frames they will enter backup
mode and ignore any further Viking25 communications.
If the Viking25 fails to see three consecutive responses from any BCM it will stop
communications, the governor fault output will be energised, the Disengage Backup Mode digital
output will be de-energised and a ‘Communication Fail’ alarm will be displayed in the ‘CAN’
alarm menu.
A reset will be required to restore the communications. This will energise the Disengage
Backup Mode digital output to indicate to the BCMs to move out of backup mode.
Communications will also be stopped if the IVC comms has failed. In this instance IVC comms
must return to healthy before comms to the BCM can be re-established and transfer of
governing to the Viking occurs.
When the Viking BCMs are in backup mode and the Viking25 has indicated a ‘Communication’
alarm the engine will be controlled by the BCMs to idle. The BCMs will now respond to raise /
lower digital inputs external to the Viking25.
The BCMs will require a start digital input signal prior to starting the engine to trigger the startup
fuelling sequence.
22.1.4 Communications
It is possible to disable the communications from the Viking25 for test purposes. Setting the
‘CAN Communications’ menu item to ‘disable’ will suspend the communications.
The ‘Wrong Messages’ menu item is incremented each time a message frame is received that
was not expected from the BCMs. This can be used as a diagnostic feature in the event of
errors.
The ‘Communications’ display menu item in the ‘EFI General’ menu will show the status of the
communications. If the communications are disabled or an error occurs this will read ‘Halted’
otherwise it will read ‘Operating’.
Note:- The timing and mask registers for the CAN Port 1 menu should not be altered.
22.2 FUEL CONTROL
22.2.1 Calibration
It is possible to adjust the fuel demand values to allow for differences in performance between
engines by means of a fuelling compensation function. The fuelling volume in the ‘0% Load At’
menu item should be set to give full speed no load running conditions. The fuelling volume in the
‘100% Load At’ menu item should be set to give full speed full load running conditions.
The fuel quantity demand is transmitted on the CAN bus to all Viking BCM units. This defines
the global fuel quantity demand for fuel injection
The Maximum Fuel Qty value defines the maximum volume of fuel that can be demanded.
The fuel pump solenoid timing demand is transmitted on the CAN bus to all Viking BCM units.
This defines the global timing demand for fuel injection.
The fuel pump solenoid timing demand is derived from the engine speed and load with the use
of a mapping table. The relationship has been preset to give the supplied surface, but can be
adjusted on a running engine by editing data points Speed 0-100% in the Load 0-100% data
tables.
+100.0
Fuel Pump
Solenoid
Timing
0
(from TDC)
-100.0
Parameters
High Load Data Pt 0 to 10
(Load 100%) En
gi
ne
Lo
ad
%
Low Load
(Load 0%)
Low Engine Speed % High
Speed Speed
(Speed 0%) (Speed 100%)
The fuel pump solenoid timing speed range is determined by the Low Speed and High Speed
settings under the Configuration menu. The fuel pump solenoid timing demand load range is
determined by the Low Load and High Load settings under the Configuration menu.
A value of 100.0 degrees in the data table will result in a 100.0 degrees crankshaft angle offset
before TDC, a value of –100.0 degrees will result in a 100.0 degrees crankshaft angle offset
after TDC.
It is possible to adjust the fuel quantity and pump start for each cylinder. This is achieved using
the ‘Fuel Adjustment’ menu. The values for each component can be changed between +/-
100%. The value is a multiplier against global demand. Therefore a value of 25% means that
the demand will be reduced by 75%.
Adjustment of the parameters "'A' Bank Running" and "'B' Bank Running" allows each engine
bank to be individually shutdown. A value of ‘Enable’ will operate the bank, a value of ‘Disable’
renders the bank shutdown.
WARNING: Due care and attention should be given to adjustment of these parameters. Only
authorised experienced personnel should change the settings.
In the Cylinder Adjustment – Isolation menu, a menu parameter is provided for each cylinder to
allow it be independently shutdown. A value of ‘Enable’ will operate the cylinder, a value of
‘Disable’ renders the cylinder shutdown.
WARNING: Due care and attention should be given to adjustment of these parameters. Only
authorised experienced personnel should change the settings.
If the crank sensor is positioned incorrectly resulting in an offset of timing, correction can be
made using the ‘Timing Adjustment’ menu parameter. This parameter allows an offset of +/- 15
degrees to be made to the global solenoid start timing demands.
Note: this parameter should only be used to compensate for minor positional errors.
WARNING: Due care and attention should be given to adjustment of these parameters. Only
authorised experienced personnel should change the settings.
A menu parameter ‘Blowover Mode’ is provided to allow the engine to be turned with fuelling
inhibited. A value of ‘Enable’ will inhibit fuelling; a value of ‘Disable’ will permit normal fuelling.
.
22.3 BACKUP MODE
When either the Viking BCMs have detected that CANbus communications have ceased or the
Viking25 does not see valid CANbus responses from both BCMs, each BCM will enter into
Backup Mode Operation. In this mode, each BCM will run independently in droop mode
controlling the engine speed.
If either of these conditions have occurred with the result being that the BCMs are in backup
mode, operating a Reset can restore remote mode operation (but only if the CANbus
communications can be established again and there is no active IVC comms failure alarm).
For the purpose of testing, the BCMs can be forced into Backup Mode through disablement of
the CANbus communications via setting the parameter ‘BCM Communications’ to ‘disable’ in the
EFI/General menu.
In order to re-establish remote control of the BCMs again, the parameter ‘BCM Communications’
should be set to ‘enable’.
Each BCM unit will transmit via the CANbus its fuelling level, timing and setspeed for backup
governing. These can be found in the menu EFI/BCM/x Bank.
In addition to the display of individual fuel quantities per BCM, the average fuelling of both BCMs
is displayed in the EFI/General menu as ‘Average B.M. Fuelling’.
22.4 EFI / VIKING BCM DIAGNOSTICS
Each BCM will transmit via the CANbus diagnostic information about the characteristics of the
fuel pump solenoid. The information can be found in the EFI/Cylinder/Solenoid Diagnostics
menu.
Where:
In the situation where a fault does arise, the Viking25 will latch the fault as an alarm, displaying it
in the EFI/Cylinder alarm menu. A reset will be required to clear the fault when the solenoid is
healthy.
The Viking25 sends information about the exhaust temperature for each cylinder to the Viking
BCMs in order to improve the BCMs ability to diagnose solenoid faults.
Each BCM will transmit via the CANbus diagnostic information about the status of the cam and
crank sensor signals. This information is displayed in the EFI/BCM/x Bank menu. The display
will either show ‘Healthy’ or ‘Fault’ against the relevant sensor.
When communications are not healthy ‘No comms’ is shown.
In the situation where a fault does arise, the Viking25 will latch the fault as an alarm, displaying it
in the EFI/BCM alarm menu. A reset will be required to clear the fault when the sensor is
healthy.
22.4.3 Data Limiting Status
Each BCM will transmit via the CANbus diagnostic information about its limitation placed on
Viking25 demands. The information can be found in the EFI/Cylinder/Parameter Limitation
menu.
In certain circumstances, the BCM will limit the demand for fuel quantity and timing, which can
be seen in the menu.
PUMP INJECTOR
FUEL
START START
MESSAGE DISPLAYED QUANTITY COMMENT
TIMING TIMING
LIMITED
LIMITED LIMITED
‘None’ No limitation
‘FQ’ √
‘P’ √
‘P+FQ’ √ √
Where:
Each BCM will transmit via the CANbus its power supply voltage level measurement of the
supply to the processor and to the driver stage circuitry. This can be seen in the EFI/BCM/x
Bank menus.
When communications are not healthy a value of zero is shown.
If either BCM transmits a processor supply voltage that falls below the menu parameter Proc
Sup Alarm Level in the EFI/General menu, the Viking25 will latch the fault as a Power Supply
alarm, displaying it in the EFI/BCM alarm menu. A reset will be required to clear the fault when
the voltage is healthy.
If either BCM transmits a solenoid supply voltage that falls below the menu parameter Sol Sup
Alarm Level in the EFI/General menu, the Viking25 will latch the fault as a Power Supply alarm,
displaying it in the EFI/BCM alarm menu. A reset will be required to clear the fault when the
voltage is healthy.
Each BCM will transmit via the CANbus its temperature measurement at the processor. This can
be seen in the EFI/BCM/x Bank menus..
When communications are not healthy a value of zero is shown.
If either BCM transmits a temperature that exceeds the menu parameter Temp Alarm Level in
the EFI/General menu, the Viking25 will latch the fault as an x Bank Temperature alarm,
displaying it in the EFI/BCM alarm menu. A reset will be required to clear the fault when the
temperature is healthy.
22.4.6 BCM Configuration Monitoring
Each BCM will transmit via the CANbus information about its configuration regarding number of
cylinders, BCM position (A Bank or B Bank) and engine rotation. This can be seen in the
EFI/BCM/x Bank menus.
The Viking 25 will compare engine rotation and number of cylinder information from the BCMs
against its own engine configuration set in the menu. If the two sets of information do not agree
then the Viking25 will latch the fault as an x Bank Config alarm, displaying it in the EFI/BCM
alarm menu. The engine will also be prevented from running as a safety measure. A reset will
be required to clear the fault when configuration of the Viking25 and the Viking BCMs match.
22.5 MISCELLANEOUS FUNCTIONALITY
Each BCM will transmit via the CANbus its own embedded software version. This can be seen
in the EFI/BCM/x Bank menus..
When communications are not healthy a value of zero is shown.
Each BCM will transmit via the CANbus its own engine speed measurement. This can be found
in the menu EFI/BCM/x Bank.
When communications are not healthy a value of zero is shown.
Each BCM will transmit via the CANbus its own operating mode. This can be found in the menu
EFI/BCM/x Bank.
MODE DESCRIPTION
Local stop The BCM is in backup mode and stop is enabled.
Local crank The BCM is in backup mode and an instruction to start has been given to it
Local run The BCM is in backup mode and no stop is enabled.
Remote stop The BCM is responding to commands from the Viking25 and a stop is enabled.
Remote run The BCM is responding to commands from the Viking25 and no stop is enabled.
No comms There are no communications to the BCM.
23. VIKING HMI
The Viking HMI is used to display and reset alarms and edit or display the contract data. For
ease of access to the data three menus are used. The alarm menu holds any alarms that are
present in a list format. The display menu holds all of the display menu items and is in a tree
format. The edit menu holds all of the editable menu items and is in a tree format.
Example of the tree format used for part of the edit menu :-
Serial Actuator
The current menu that is being displayed is shown by the lit MENU area text on the Viking HMI.
The Viking25 EFI is able to respond from commands from an external system via the IVC2 interface.
Supported commands are:-
• Alarm reset
• Start the engine
• Stop the engine
In order to ensure that these signals are used safely, the facility to enable / disable their operation is
provided via the menu parameters “Allow IVC2 Reset’, ‘Allow IVC2Start’ and ‘Allow IVC2 Stop’ in the
systems menu.
25. DISPLAY MODULE ALARM MESSAGES
ALARM
DESCRIPTION
CODE
A1 CAP PT12 Trans. Fail
A2 Set Speed Trans.Fail
A3 OS1 TE60 Trans.Fail
A4 OS2 TE61 Trans.Fail
A5 OS3 TE62 Trans.Fail
A6 OS4 TE63 Trans.Fail
A7 OS5 TE64 Trans.Fail
A8 OS6 TE65 Trans.Fail
A9 OS7 TE66 Trans.Fail
A10 OS8 TE67 Trans.Fail
A11 OS9 TE68 Trans.Fail
A12 OS10 TE69 Trans.Fail
A13 HTWP PT27 Trans.Fail
A14 LOP PT7 Trans.Fail
A15 Error Status
A16 Last Error Code
A17 Communications Fail
A18 Pickup Fault
A19 Pickup 1 Fail
A20 Pickup 2 Fail
A21 Pickup Change
A22 Fail To Stop
A23 Viking Vision Stop
A24 Fault Shutdown
A25 2 From 3 Shutdown
A26
A27 External Flash Fail
A28 Speed Switch Failed
A29 Fail To Start
A30 Go To Idle
A31
A32 IVC_Comms_Fail
A33 Internal Temperature
A34 EFI Config
A35 Fail To Prime
A36 Overload
A37 A Bank Crank1 Fault
A38 A Bank Crank2 Fault
A39 A Bank Cam1 Fault
A40 A Bank Cam2 Fault
A41 B Bank Crank1 Fault
A42 B Bank Crank2 Fault
A43 B Bank Cam1 Fault
A44 B Bank Cam2 Fault
A45 A Bank Temperature
A46 B Bank Temperature
A47 Power Supply
A48 A Bank Cam2 Fault
A49 B Bank Crank1 Fault
A50 Cylinder A1 Fault
ALARM
DESCRIPTION
CODE
A51 Cylinder A2 Fault
A52 Cylinder A3 Fault
A53 Cylinder A4 Fault
A54 Cylinder A5 Fault
A55 Cylinder A6 Fault
A56 Cylinder A7 Fault
A57 Cylinder A8 Fault
A58 Cylinder A9 Fault
A59 Cylinder A10 Fault
A60 Cylinder B1 Fault
A61 Cylinder B2 Fault
A62 Cylinder B3 Fault
A63 Cylinder B4 Fault
A64 Cylinder B5 Fault
A65 Cylinder B6 Fault
A66 Cylinder B7 Fault
A67 Cylinder B8 Fault
A68 Cylinder B9 Fault
A69 Cylinder B10 Fault
A70 O.Splash 1 TE60 SLD
A71 O.Splash 2 TE61 SLD
A72 O.Splash 3 TE62 SLD
A73 O.Splash 4 TE63 SLD
A74 O.Splash 5 TE64 SLD
A75 O.Splash 6 TE65 SLD
A76 O.Splash 7 TE66 SLD
A77 O.Splash 8 TE67 SLD
A78 O.Splash 9 TE68 SLD
A79 O.Splash 10 TE69 SLD
A80 OS Mean SLD
A81 SCS SLD
A82 OMD1 SLD
A83 Hi CP PS30 SLD
A84 MPD1 SLD
A85 MAA SLD
A86 Lo HTWP PT27 SLD
A87 SCS SLD WB
A88 OMD1 SLD WB
A89 Hi CP PS30 SLD WB
A90 MPD1 SLD WB
A91 MAA SLD WB
A92
A93
A94
A95
A96
A97
A98
A99
26. VIKING VISION ALARM MESSAGES
Dynamics 1 [ ]
Non-Linear Gain [ ]
Boost Menu [ ]
Systems Menu [ ]
Serial Port 1 – VV [ ]
CANbus – BCMbus [ ]
Pickups [ ]
Temperature [ ]
Memory [ ]
Configuration [ ]
Selection [ ]
12RK280 [ ]
16RK280 [ ]
General [ ]
AVLOS Pump [ ]
Fuel Module [ ]
When engine speed is measured from markers on the flywheel in order to minimise cyclic
effects, the number used depends on :
1) Number of cylinders
2) V angle
In some instances the software should be set to read Every Other marker as ½ a marker is not
possible.
In Line 4 Stroke
V Angle 4 Stroke
Link Settings
DIGITAL OUTPUTS
LINK CONTRACT
CHANNEL POSITION (NO) POSITION (NC) POSITION
No.
1 16 Normally open Normally closed x
2 15 Normally open Normally closed x
3 14 Normally open Normally closed x
4 13 Normally open Normally closed x
5 12 Normally open Normally closed x
6 11 Normally open Normally closed x
7 10 Normally open Normally closed x
8 9 Normally open Normally closed x
ANALOGUE INPUTS
LINK CONTRACT
CHANNEL POSITION (A) POSITION (B) POSITION
No.
79 0-5V range 0-10V range A
1
80 mA input mode Voltage input mode A
77 0-5V range 0-10V range A
2
78 mA input mode Voltage input mode A
75 0-5V range 0-10V range A
3
76 mA input mode Voltage input mode A
73 0-5V range 0-10V range A
4
74 mA input mode Voltage input mode A
71 0-5V range 0-10V range A
5
72 mA input mode Voltage input mode A
69 0-5V range 0-10V range A
6
70 mA input mode Voltage input mode A
67 0-5V range 0-10V range A
7
68 mA input mode Voltage input mode A
20 0-5V range 0-10V range A
8
21 mA input mode Voltage input mode A
Continued
ANALOGUE OUTPUTS
LINK CONTRACT
CHANNEL POSITION (A) POSITION (B) POSITION
No.
64 0-5V range 0-10V range B
1 65 Voltage output mode mA output mode B
66 Voltage output mode mA output mode B
38 0-5V range 0-10V range B
2 39 Voltage output mode mA output mode B
40 Voltage output mode mA output mode B
35 0-5V range 0-10V range B
3 36 Voltage output mode mA output mode B
37 Voltage output mode mA output mode B
32 0-5V range 0-10V range B
4 33 Voltage output mode mA output mode B
34 Voltage output mode mA output mode B
29 0-5V range 0-10V range B
5 30 Voltage output mode mA output mode B
31 Voltage output mode mA output mode B
26 0-5V range 0-10V range B
6 27 Voltage output mode mA output mode B
28 Voltage output mode mA output mode B
23 0-5V range 0-10V range B
7 24 Voltage output mode mA output mode B
25 Voltage output mode mA output mode B
17 0-5V range 0-10V range B
8 18 Voltage output mode mA output mode B
19 Voltage output mode mA output mode B
MEAN LOAD
LINK CONTRACT
POSITION (A) POSITION (B) POSITION
No.
47 Normal analogue mode Mean load mode A
48 Normal analogue mode Mean load mode A
49 Normal analogue mode Mean load mode A
SERIAL PORTS
LINK CONTRACT
CHANNEL POSITION (A) POSITION (B) POSITION
No.
RS485/422 mode
8 RS232 mode A
RS485/422 mode
50 RS232 mode A
1 RS485/422 mode
51 RS232 mode A
RS232 mode/not
43 RS485/422 terminated B
terminated
RS485/422 mode
52 RS232 mode B
RS485/422 mode
53 RS232 mode B
2 RS485/422 mode
55 RS232 mode B
RS232 mode/not
7 RS485/422 terminated A
terminated
CANBUS PORT
LINK CONTRACT
POSITION (A) POSITION (B) POSITION
No.
5 Terminated Unterminated B
28. FUSES
FS1
CAP PT12 Trans Fail Error Status Pickup Fault Fail To Stop External Flash Fail
Set Speed Trans. Fail Last Error Code Pickup 1 Fail Vision Stop Speed Switch Failed
OS1 TE60 Trans Fail Communications Fail Pickup 2 Fail Fault Shutdown Fail To Start
A Bank Crank1 Fault Cylinder A1 Fault OS1 TE60 SLD SCS SLD Lo HTWP PT27 SLD SCS SLD WB
A Bank Crank2 Fault Cylinder A2 Fault OS2 TE61 SLD OMD1 SLD OMD1 SLD WB
A Bank Cam1 Fault Cylinder A3 Fault OS3 TE62 SLD Hi CP PS30 SLD Hi CP PS30 SLD WB
A Bank Cam2 Fault Cylinder A4 Fault OS4 TE63 SLD MPD1 SLD MPD1 SLD WB
B Bank Crank1 Fault Cylinder A5 Fault OS5 TE64 SLD MAA SLD MAA SLD WB
Cylinder B4 Fault
Cylinder B5 Fault
Cylinder B6 Fault
Cylinder B7 Fault
Cylinder B8 Fault
Cylinder B9 Fault
Speed P Gain Boost Menu Torque Limit Menu Last Saved Date Inputs
Speed I Gain Boost PT12 Engine Speed Last Saved Month Value
Speed D Gain Boost PT12 Engine Load Last Saved Year Input 1
Input 8
Input 9
Input 10
Input 11
Input 12
Input 13
Input 14
Input 15
Input 16
A0047 DISPLAY MENU STRUCTURE (SHEET 2 OF 6)
Output 10 Input 9
Output 11 Input 10
Output 12 Input 11
Output 13 Input 12
Output 14 Input 13
Output 15 Input 14
Output 16 Input 15
Maximum Wrong Messages IVC2 Comms Messages Fuel Quantity Speed Speed
Status IVC2 Comms CRC Err Demand Set Speed Processor Supply Processor Supply
Identity Identity
Solenoid Diagnostics Parameter limitation Glob. Fuel Quantity Selection Saving Status Stop Active
B1 Pump Diag. B1
B2 Pump Diag. B2
B3 Pump Diag. B3
B4 Pump Diag. B4
B5 Pump Diag. B5
B6 Pump Diag. B6
B7 Pump Diag. B7
B8 Pump Diag. B8
B9 Pump Diag. B9
Boost Bypass Valve AVLOS Pump Fuel Pump Oil Splash Temp
OS Mean OS Mean
Slowdowns
A0047 DISPLAY MENU STRUCTURE (SHEET 6 OF 6)
OMD1 SLD WB
Hi CP PS30 SLD
Hi CP PS30 SLD WB
MPD1 SLD
MPD1 SLD WB
MAA SLD
MAA SLD WB
Slowdowns
A0047 EDIT MENU STRUCTURE (SHEET 1 of 14)
Fuel Control
Droop Non-Linear Gain Speed Variable Gain1 Speed Variable Gain2 Load Variable Gain Boost
Droop Null Data Point 0 Data Point 0 Data Point 0 Data Point 0 Data Point 0
Prop. Gain Data Point 1 Data Point 1 Data Point 1 Data Point 1 Data Point 1
Integ. Gain Data Point 2 Data Point 2 Data Point 2 Data Point 2 Data Point 2
Deriv. Gain Data Point 3 Data Point 3 Data Point 3 Data Point 3 Data Point 3
Data Point 4 Data Point 4 Data Point 4 Data Point 4 Data Point 4
Data Point 5 Data Point 5 Data Point 5 Data Point 5 Data Point 5
Data Point 6 Data Point 6 Data Point 6 Data Point 6 Data Point 6
Data Point 7 Data Point 7 Data Point 7 Data Point 7 Data Point 7
Data Point 8 Data Point 8 Data Point 8 Data Point 8 Data Point 8
Data Point 9 Data Point 9 Data Point 9 Data Point 9 Data Point 9
Data Point 10 Data Point 10 Data Point 10 Data Point 10 Data Point 10
Error Range High RPM High RPM Proportional Enable Boost Limit Enable
NLG Enable Low RPM Low RPM Integral Enable Maximum Boost (mA)
System Hardware
Force 11
Force Value 11
Force 12
Force Value 12
Force 13
Force Value 8
Force Value 13
Force 9
Force 14
Force Value 9
Force Value 14
Force 10
Force 15
Force Value 10
Force Value 15
Force 16
Force Value 16
A0047 EDIT MENU STRUCTURE (SHEET 4 of 14)
Configurat ion Port 1 - VV Port 2 - IVC Bit Timing Force Mode Channel A (standard)
Force 4 Type 6
Force 5 Type 8
Force Value 5
Force 6
Force Value 6
Force 12
Force 7
Force Value 12
Force Value 7
Force 13
Force 8
Force Value 13
Force Value 8
Force 14
Force 9
Force Value 14
Force Value 9
Force 15
Force 10
Force Value 15
Force Value 10
Force 16
Force 11
Force Value 16
Force Value 11
A0047 EDIT MENU STRUCTURE (SHEET 5 of 14)
Outpu ts
Value 10
Enable 11
Value 11
Enable 12
Value 12
Enable 13
Value 13
Enable 14
Enable 9
Value 14
Value 9
Enable 15
Enable 10
Value 15
Enable 16
Value 16
A0047 EDIT MENU STRUCTURE (SHEET 6 of 14)
EFI
Enable 7
Value 7
Enable 8
Value 8
A0047 EDIT MENU STRUCTURE (SHEET 7 of 14)
Load 10% Load 20% Load 30% Load 40% Load 50% Load 60%
Speed 10% Speed 10% Speed 10% Speed 10% Speed 10% Speed 10%
Speed 20% Speed 20% Speed 20% Speed 20% Speed 20% Speed 20%
Speed 30% Speed 30% Speed 30% Speed 30% Speed 30% Speed 30%
Speed 40% Speed 40% Speed 40% Speed 40% Speed 40% Speed 40%
Speed 50% Speed 50% Speed 50% Speed 50% Speed 50% Speed 50%
Speed 60% Speed 60% Speed 60% Speed 60% Speed 60% Speed 60%
Speed 70% Speed 70% Speed 70% Speed 70% Speed 70% Speed 70%
Speed 80% Speed 80% Speed 80% Speed 80% Speed 80% Speed 80%
Speed 90% Speed 90% Speed 90% Speed 90% Speed 90% Speed 90%
Speed 100% Speed 100% Speed 100% Speed 100% Speed 100% Speed 100%
A0047 EDIT MENU STRUCTURE (SHEET 8 of 14)
Cylinder Adjustment
Load 70% Load 80% Load 90% Load 100% Low Load A1
Speed 10% Speed 10% Speed 10% Speed 10% Low Speed A3
Speed 20% Speed 20% Speed 20% Speed 20% High Speed A4
Speed 30% Speed 30% Speed 30% Speed 30% EFI System Type A5
Speed 40% Speed 40% Speed 40% Speed 40% Timing Adjustment A6
B3
B4
B5
B6
B7
B8
B9
B10
A0047 EDIT MENU STRUCTURE (SHEET 9 of 14)
Configurat ion
Timing Isolation Working Load Range Fuel Calib. Table 'A' Bank Running Engine Type
A5 A5 Data Point 4
A6 A6 Data Point 5
A7 A7 Data Point 6
A8 A8 Data Point 7
A9 A9 Data Point 8
B1 B1 Data Point 10
B2 B2 High Fuel
B3 B3 Low Fuel
B4 B4 Calibration Enable
B5 B5
B6 B6
B7 B7
B8 B8
B9 B9
B10 B10
A0047 EDIT MENU STRUCTURE (SHEET 10 of 14)
Every Other Every Other Every Other Every Other Every Other Every Other
Pickup 1 Type Pickup 1 Type Pickup 1 Type Pickup 1 Type Pickup 1 Type Pickup 1 Type
Pickup 2 Type Pickup 2 Type Pickup 2 Type Pickup 2 Type Pickup 2 Type Pickup 2 Type
Actuator Mode Actuator Mode Actuator Mode Actuator Mode Actuator Mode Actuator Mode
Crankcase Offset Crankcase Offset Crankcase Offset Crankcase Offset Crankcase Offset Crankcase Offset
Not Available Not Available Not Available Not Available Not Available Not Available
Every Other Every Other Every Other Every Other Every Other Every Other
Pickup 1 Type Pickup 1 Type Pickup 1 Type Pickup 1 Type Pickup 1 Type Pickup 1 Type
Pickup 2 Type Pickup 2 Type Pickup 2 Type Pickup 2 Type Pickup 2 Type Pickup 2 Type
Actuator Mode Actuator Mode Actuator Mode Actuator Mode Actuator Mode Actuator Mode
Crankcase Offset Crankcase Offset Crankcase Offset Crankcase Offset Crankcase Offset Crankcase Offset
A0047 EDIT MENU STRUCTURE (SHEET 12 of 14)
Priming
General General
Not Available Not Available Not Available Not Available Save All Edited Data Prime Operation
Every Other Every Other Every Other Every Other Pump Off Speed
Pickup 1 Type Pickup 1 Type Pickup 1 Type Pickup 1 Type Pump On Speed
Pickup 2 Type Pickup 2 Type Pickup 2 Type Pickup 2 Type Minimum Pressure
Actuator Mode Actuator Mode Actuator Mode Actuator Mode Minimum Pressure
Pre Start Priming Continuous Priming Boost Bypass Low AVLOS Level Time Delay Oil Splash Temp
Post-Run Prime Time Post-Run Time Boost Bypass High AVLOS Hyst Firing Speed Slowdown Config
OS3 Config
OS4 Config
OS5 Config
OS6 Config
OS7 Config
OS8 Config
OS9 Config
OS10 Config
Mean Config
Return to Sheet 1
Hardware Slowdown Config Wirebreak Config Slowdown Config Hardware Slowdown Config
OS1 Maximum SCS Config SCS WB Config Lo HTWP PT27 Config Maximum Pressure Commission Speed
OS1 Minimum OMD1 Config OMD1 WB Config Lo HTWP LS PT27 Lev Minimum Pressure Commission Delay
OS1 Maximum Hi CP PS30 Config Hi CP PS30 WB Config Lo HTWP HS PT27 Lev Maximum Pressure Commission Hyst
OS1 Minimum MPD1 Config MPD1 WB Config Lo HTWP HS Speed Minimum Pressure
OS2 Maximum
OS2 Minimum
OS3 Maximum
OS3 Minimum
OS3 Maximum
OS3 Minimum
OS4 Maximum
OS8 Maximum
OS4 Minimum
OS4 Maximum
OS4 Minimum
OS5 Maximum
OS5 Minimum
OS5 Maximum
OS5 Minimum
OS6 Maximum
OS6 Minimum
OS10 Minimum