Calibrationbox TAHCK

The document provides a step-by-step guide for calibrating the Calibrationbox TAHCK duct system, including instructions for zero point calibration and amplification. It details the necessary preparations, sensor adjustments, and the use of specific gases during the calibration process. The procedure ensures accurate readings and proper maintenance of the sensors within the duct system.

Uploaded by

ahmadbensliman90
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
24 views1 page

Calibrationbox TAHCK

The document provides a step-by-step guide for calibrating the Calibrationbox TAHCK duct system, including instructions for zero point calibration and amplification. It details the necessary preparations, sensor adjustments, and the use of specific gases during the calibration process. The procedure ensures accurate readings and proper maintenance of the sensors within the duct system.

Uploaded by

ahmadbensliman90
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Calibrationbox TAHCK duct system

STARTING
- Remove the protective cap from the sensor beside cable input
- Pull out the sensor from the duct and let them cool out handwarm
- Plug in the calibration box measuring cable and lock it in position
ZERO POINT
- Press the key
- After date, time and software version are shown in display, press key
- For information, you get next function an default (CAL) alarm at device, maybe your
system is stopping ( or make a bridge between default alarm )
- Move the cursor to the function MAINTENANCE and press
- Go to CALIBR: ZERO and confirm with
- Take the bottle synthetic air 20% oxygen and screw the pressure adapter briefly at the
minican, before look that the valve is closed
- Set the ball of the flow meter from calibration set into the middle of the glass
- Hold on the sensor in position it is mounted into the duct
- At display you see APPLY ZERO GAS TO SENSOR than press
- You see the LEL% value and ADJUST, go with cursor to Y and
- Now you see a value between 1000 and 1700 MV, when the value is constant

- Close the valve of the calibration set


- At calibration box you see again the LEL concentration, say N and
- Make to come to display MAINTENANCE
- If you have more sensors and one flow meter, make all sensors with zero point but
remove the calibration box only at maintenance or off situation
- After finish remove the flow meter from the minican bottle
AMPLIFICATION
- Go again to MAINTENANCE and confirm CALIBR. GAIN with
- At display you see CALGAS = PROPAN, SAMPGAS = (Your solvents ),
RESPONSE = ( factor difference Calibration to solvent gas )
-
- CALGAS = SAMP GAS, now change with cursor the CALGAS value to:
17 with 0,3% C3H8 propane ( see minican bottle )
Depending of response you see another Sampgas value
- When the CALGAS concentration is at 17,
- Take the bottle 0,3% C3H8 propane and screw the pressure adapter briefly at the
minican, before look that the valve is closed
- Set the ball of the flow meter from calibration set into the middle of the glass
- Hold on the sensor in position it is mounted into the duct
- At display you see APPLY CALGAS TO SENSOR than press
- You see the LEL% value and ADJUST, go with cursor to Y and
- Now you see a value between 200 and 400 MV, when the value is constant
- Close the valve of the calibration set
- At calibration box you see again the LEL concentration, say N and
- Make to come to display MAINTENANCE
- If you have more sensors make all calibrations
- When you see MAINTENANCE go with cursor down (next page) to END and
to make off the calibration box
- After finish remove the flow meter from the minican bottle