LAB INFRA TECH PVT.LTD.
Lalitpur Metropolitan-11, Lalitpur Nepal
Email : Labinfratech21@gmail.com
9851017354 , 9847486908
DETERMINATION OF SPECIFIC GRAVITY AND WATER ABSORPTION (IS 1386-3)
Name of Project :-Upgradting Construction and performance based maintenance Worke of dolalghat-phalate-kolati-Dhakhake-pokhari-Gurse Road.
Client :-Rural Connectivity Improvement Project.
Contract No :-RCIP-AF/Bagmati/Works/OCB-06/2079/80
Contractor :-Bandan Bhagwati Niramn sewa pvt.ltd.
Testing Date :-2081-07-21
Specimen No. 1
Weight of Basket + Sample in water gm 1266.4
Weight of Basket in water gm 712.2
Weight of Sample in Water ( C ) gm 554.2
Weight of Sample Saturated Surface Dry ( B ) gm 887.6
Weight of Sample Oven Dry ( A ) gm 881.4
Water Absorption = 100 (B - A)/A % 0.70
Apparent Specific Gravity = A/(A - C) 2.69
Bulk Specific Gravity = B/(B - C) 2.66
Result: From above test of Boulder Stone
following results are observed:
Apparent Specific Gravity = 2.69
Bulk Specific Gravity = 2.66
Water Absorption = 0.70
Note : Information & test sample provided By The Contractor.
Test By Checked By
LAB INFRA TECH PVT.LTD.
Lalitpur Metropolitan-11, Lalitpur Nepal
Email : Labinfratech21@gmail.com
9851017354 , 9847486908
DETERMINATION OF SPECIFIC GRAVITY AND WATER ABSORPTION (IS 1386-3)
Name of Project :-Upgradting Construction and performance based maintenance Worke of dolalghat-phalate-kolati-Dhakhake-pokhari-Gurse Road.
Client :-Rural Connectivity Improvement Project.
Contract No :-RCIP-AF/Bagmati/Works/OCB-06/2079/80
Contractor :-Bandan Bhagwati Niramn sewa pvt.ltd.
Testing Date :-2081-07-21
Specimen No. 1
Weight of Basket + Sample in water gm 1271.6
Weight of Basket in water gm 712.2
Weight of Sample in Water ( C ) gm 559.4
Weight of Sample Saturated Surface Dry ( B ) gm 896.4
Weight of Sample Oven Dry ( A ) gm 889.4
Water Absorption = 100 (B - A)/A % 0.79
Apparent Specific Gravity = A/(A - C) 2.70
Bulk Specific Gravity = B/(B - C) 2.66
Result: From above test of crushed Aggregate
following results are observed:
Apparent Specific Gravity = 2.70
Bulk Specific Gravity = 2.66
Water Absorption = 0.79
Note : Information & test sample provided By The Contractor.
Test By Checked By
LAB INFRA TECH PVT.LTD.
Lalitpur Metropolitan-11, Lalitpur Nepal
Email : Labinfratech21@gmail.com
9851017354 , 9847486908
SIEVE ANALYSIS OF SAND
Name of Project :-Upgradting Construction and performance based maintenance Worke of dolalghat-phalate-kolati-Dhakhake-pokhari-Gurse Road.
Client :-Rural Connectivity Improvement Project.
Contract No :-RCIP-AF/Bagmati/Works/OCB-06/2079/80
Contractor :-Bandan Bhagwati Niramn sewa pvt.ltd.
Testing Date :-2081-07-21
Sieve Size Weight Cum. Wt. Cum. % % Specified requirement
mm Retained Retained Retained Passing Min. Max.
10.00 0.00 0.00 0.00 100.00 100.00 100.00
4.75 72.00 72.00 7.33 92.67 90.00 100.00
2.36 144.00 216.00 22.00 78.00 75.00 100.00
1.18 195.00 411.00 41.85 58.15 55.00 90.00
0.60 188.00 599.00 61.00 39.00 35.00 59.00
0.30 165.00 764.00 77.80 22.20 8.00 30.00
0.150 141.00 905.00 92.16 7.84 0.00 10.00
Pan 77.00
Total WT.GM. 982.00
100
90
80
70
% Passing by weight
Series1
60 Series2
Series3
50
40
30
20
10
0
0.01 0.10 1.00 10.00 100.00
Sieve size, mm
Note: Infarmation & Test sample provided By Contractor.
Test By Checked By
LAB INFRA TECH PVT.LTD.
Lalitpur Metropolitan-11, Lalitpur Nepal
Email : Labinfratech21@gmail.com
9851017354 , 9847486908
Sieve Analysis of Coarse Aggregate Material
Name of Project :-Upgradting Construction and performance based maintenance Worke of dolalghat-phalate-kolati-Dhakhake-pokhari-Gurse Road.
Client :-Rural Connectivity Improvement Project.
Contract No :-RCIP-AF/Bagmati/Works/OCB-06/2079/80
Contractor :-Bandan Bhagwati Niramn sewa pvt.ltd.
Testing Date :-2081-07-21
Sieve Size Retained Cum.Ret. Cum. % % passing Specification Limit
in mm Wt (gm) Wt (gm) Retained by Wt Min Max
20 0 0 0.00 100.00 100 100
16 519.00 519 9.21 90.79 90 100
10 2855.00 3374 59.90 40.10 30 70
4.75 1854.00 5228 92.81 7.19 0 10
Pan 405.00
Total Wt in
5633
(gm)
100
90
80
70
60
% of passing
Series1
50
Series2
40 Series3
30
20
10
0
1 Sieve size in10
mm 100
Note: Infarmation & Test sample provided By Contractor.
Test By Checked By