GL309 Manual
GL309 Manual
T&D
© 2007 AREVA T&D Inc. One Power Lane – Charleroi, PA 15022 – Tel.: 724-483-7308 – Fax: 724-483-7771
Type GL309 Circuit Switchers
Revision History
Revision Record Description Revised by Date
Chapter 2 Safety
Addendum A Sulfur Hexafluoride (SF6)
Attachment A MSDS for SF6
Revision History
Revision Record Description Revised by Date
Chapter 1
Introduction
Contents
1.0 Introduction .....................................................................................................3
1.1 Using this Instruction Manual ...........................................................................3
1.2 Confidentiality ..................................................................................................4
1.3 Device Descriptions .........................................................................................4
1.3.1 Pole Unit ................................................................................................6
1.3.2 Operating Mechanism .............................................................................6
1.3.3 SF 6 Gas Monitoring System ....................................................................6
1.3.4 SF 6 Gas Density Monitor .........................................................................6
1.3.5 SF 6 Gas Policy .......................................................................................7
1.4 Technical Data .................................................................................................8
List of Figures
Figure 1-1: Switcher General Outline (Rigid Conduit Option Not Shown) .....................5
Figure 1-2: SF 6 Pressure Curves ...............................................................................7
Figure 1-3: Example Nameplate (values may differ) ..................................................11
List of Tables
Table 1-1: Technical Data for the GL309 ....................................................................8
Table 1-2: Technical Data for the FK3-1 Operating Mechanism ...................................9
Table 1-3: Technical Data for the Control Circuits.......................................................9
Table 1-4: Acceptance Criteria – GL309 ...................................................................10
Revision History
Revision Record Description Revised by Date
1.0 Introduction
AREVA T&D bases its position as a global leader in circuit breaker and circuit switcher development on
the operating experience that we have accumulated from the more than 60,000 circuit breakers and
circuit switchers with spring and hydraulic operating mechanism that are in operation throughout the
world. SF6 circuit switchers from AREVA T&D demonstrate a high level of reliability on a daily basis.
Even under extreme conditions such as those that prevail in areas with high seismic activity or in the
tropical regions of the world, our customers can count on AREVA T&D circuit switchers.
All circuit switchers described in this manual are factory tested and designed to meet specific customer
requirements and all applicable ANSI, IEEE, IEC, and NEMA standards at the time of manufacture.
There is no assurance that these products meet all state and local codes because the code
requirements vary so greatly.
An ISO 9001:2000 certified quality management system and ISO 14001-certified environmental
management govern the entire development and production process for AREVA T&D high voltage
circuit switchers. This guarantees a high quality product as well as compliance with the rated values
obtained in type tests.
NOTE
Our technical research has shown that the highest achievable reliability while in service is attained
when these instructions are followed properly. Due to continual design innovations and improvements
in technology, the data and information contained within this manual may have changed since its
publication. This information and data does not guarantee the performance or characteristics of the
product; it serves only to describe the product.
The instructions contained in this manual do not claim to cover all variations of this product, nor do
they claim to provide for every contingency of installation, operation, or maintenance. If you need
further information or directions to install or maintain this product, please contact:
We expressly decline liability for damages that occur due to any improper operation or unsuitable
handling of the equipment, even if this instruction manual does not contain specific indication in this
respect. We emphasize the fact that you use only AREVA T&D spare parts as replacements.
GL309 type circuit switchers are uncomplicated in design yet advance which yields minimal switcher
maintenance. However, maintenance is still required to help ensure trouble-free operation. Develop
good maintenance procedures for all personnel involved directly or indirectly with the installation,
operation, or maintenance of circuit switchers and their associated equipment. Carry out maintenance
and reconditioning according to the guidelines in this manual. The maintenance and reconditioning
recommended encompasses only those parts that are subject to wear and aging.
IMPORTANT
AREVA specialists should carry out major maintenance and reconditioning. Your service personnel
can be thoroughly trained in courses offered by AREVA.
Local environment and switcher applications must be considered in your maintenance and
reconditioning programs, including such variables as ambient temperatures, actual continuous current,
number of operations, type of interrupting duty, and any unusual local conditions such as corrosive
atmosphere or major insect problems. The AREVA maintenance program considers these variables by
offering appropriate inspection, maintenance and reconditioning intervals.
! DANGER
This circuit switcher contains charged springs, and high-pressure SF6 gas. Before performing any
service on this equipment, read the applicable sections of the instruction manual – particularly Chapter
2, Safety.
When operating equipment in extreme ambient conditions, we advise that you increase the frequency
of inspection and maintenance intervals. Such conditions include:
• Permanent high ambient temperature
• Abrasive dust in the atmosphere
• High dust content atmosphere
• Permanent high humidity
• Corrosive gas or vapors in the atmosphere
1.2 Confidentiality
This publication is a copyrighted work. No part of this manual may be transmitted to a third party or
duplicated without written permission from AREVA T&D Inc.
AREVA reserves the right to amend these instructions if required by ongoing engineering
developments. No claims can be asserted from the statements, figures, or descriptions in this manual.
Figure 1-1: Switcher General Outline (Rigid Conduit Option Not Shown)
1 Pole Columns 4 Auxiliary Controls Cabinet
2 Base Frame 5 Supports
3 Spring Operating Mechanism 6 Interconnection Cables
If a customer requested non-temperature compensated pressure gauge is provided with the SF6 gas
monitoring system, the chart shown in Figure 1-2 must be used to determine the proper SF6 gas
pressure at a given temperature.
In addition, if a customer requested the -40°C rating option, the temperature-compensated gas
monitoring system is furnished with alternate alarm and lockout pressure settings. The internal
electrical contacts will provide an alarm when the SF6 gas density in the pole units falls below 3.6 bar
(52.2 psig at 20°C), and to lockout the switcher at 3.3 bar (47.9 psig at 20°C).
SF6 in the gaseous state will show a change in pressure as its temperature is changed. This is
represented by the curve shown in Figure 1-2. The graph shows the normal SF6 pressure in the circuit
switcher over the rated temperature range of the circuit switcher.
T (°F)
-58 -40 -22 -4 14 32 50 68 86 104 122 140 158 176
9.0 130.5
6 1
8.0 116.0
2
7.0 101.5
6.0 3 87.0
P (psig)
P (bar)
5.0 4 72.5
4.0 58.0
5
3.0 43.5
2.0 29.0
1.0 14.5
-50 -40 -30 -20 -10 0 10 20 30 40 50 60 70 80
T (°C)
AREVA designs, manufactures and tests circuit breakers, circuit switchers, and gas-insulated
switchgear to be free of leaks. AREVA warrants a gas leakage rate of less than 1% per year on all SF6
equipment. If leaks develop in service, take appropriate action to locate and eliminate SF6 gas leaks.
Switcher Travel
Stroke mm 105 ± 4
Overtravel - Closing mm ≤6
Overtravel - Opening mm N/A
Closing Velocity m/s 2.6 – 3.4
Opening Velocity m/s 3.3 – 3.9
Switcher Pressure
SF6 – Nominal Pressure (pe @ 20°C) bar 6.4 psig 92.8
SF6 – Alarm Pressure (pe @ 20°C) bar 5.4 psig 78.3
SF6 – Lockout Pressure (pe @ 20°C) bar 5.1 psig 74.0
SF6 – Alarm Pressure (pe @ 20°C, -40°C applications) bar 3.6 psig 52.2
SF6 – Lockout Pressure (pe @ 20°C, -40°C applications) bar 3.3 psig 47.9
Chapter 2
Safety
Contents
2.0 Safety Symbols ................................................................................................3
2.1 Safety Precautions – General ...........................................................................3
2.2 Safety Precautions – Specific ...........................................................................4
2.3 Handling SF 6 Gas ............................................................................................4
2.4 Protective Gear for Handling SF 6 Gas...............................................................5
Revision History
Revision Record Description Revised by Date
! DANGER
Indicates there is an immediate threat of danger, potentially leading to death or serious injuries.
! WARNING
Signifies there is a very high probability of a dangerous situation, possibly leading to severe injury
and/or damage to the equipment.
! CAUTION
There is a possibility of a dangerous situation leading to possible injury and/or damage to the
equipment.
IMPORTANT
Reported information gives instructions for avoiding product damage, application tips, and useful
details.
NOTE
Presents instructions, practical tips, comments, or background information.
! DANGER
When dealing with circuit switchers, it is critical to remember that you are dealing with high voltages,
high gas pressures, toxic by-products, and moving machine parts. Do not take shortcuts or ignore
safety warnings and practices!
a) Do Not work on an energized switcher! If work has to be performed on the switcher, take it out
of service, open the switcher, open the disconnect switches at each side of the switcher, then
discharge the springs and ground each phase.
b) Do Not work on any part of the de-energized switcher until you disconnect all control and heater
power.
c) Do Not disassemble any portion of the gas system of the de-energized switcher until that
portion of the system has had the pressure reduced to ambient pressure by utilizing proper gas
handling equipment. After reducing the gas pressure to zero, cautiously remove covers, tubes,
fittings, etc.
d) To prevent over pressurizing the switcher, always use an SF6 regulator when filling or adding
SF6 to the switcher. Take precautions to protect personnel against sudden gas release from
accidental breakage of adjacent parts.
e) Never invert the gas bottle: this will release liquid SF6 into the switcher, will over pressurize the
switcher, and may cause the pressure relief device to release, requiring service and
replacement of parts.
f) Only skilled and knowledgeable personnel are permitted to service the operating mechanisms.
Take particular care to keep personnel clear of mechanisms that are to be operated or
discharged. This instruction manual provides information on mechanism operations.
! CAUTION
The circuit switcher is equipped with a stored energy mechanism for opening and closing operations.
In the closed state, the mechanism stores enough energy for an O-C-O operating sequence. To
remove stored energy from the mechanism, remove all control voltage from the motor. Then open and
close the switcher until all stored energy is released.
g) If there is any evidence of deterioration in the switcher dielectric capability, de-energize the
switcher by remote switching of back-up circuit switchers and isolated by disconnect switches.
h) Make Operational tests and checks after switcher maintenance to ensure that the switcher is
capable of properly operating. The extent of such tests and checks must be consistent with the
level of maintenance performed.
! CAUTION
Never intentionally release SF6 into the atmosphere.
(Refer to Addendum A for detailed information about SF6)
When opening an SF6 filled pole, consider the following while handling SF6 gas:
1. Sulfur Hexafluoride (SF6) is a colorless and odorless gas. Pure SF6 is non-poisonous; therefore,
no risk classification needs to be followed. Refer to the Material Safety Data Sheet (MSDS) in
Attachment A for complete details.
2. The maximum allowable concentration at a place of work, assuming that a person spends 8
hours per day there, is 1000 PPM (or 0.1%) by volume. This low value is the standard adopted
for all gases considered harmless, but not normally present in the atmosphere.
3. Under the influence of an arc, SF6 decomposes into products, which have varying toxicities.
They may irritate mucous membranes, respiratory tracts, or other unprotected skin. You can
recognize even the smallest amounts of gaseous decomposition products almost immediately
by their strongly pungent, sulfurous odor, generally before the danger of contamination arises.
4. It is necessary for maintenance personnel to follow these safety precautions in addition to all
safety regulations prescribed by their employer.
5. Do not agitate SF6 decomposition by-products unnecessarily.
6. Remove SF6 decomposition by-products immediately after opening the switcher (pole) to
prevent moisture combining with the by-products.
7. Use a suitable vacuum cleaner with dust filter, and wipe off the remaining decomposition by-
products with a piece of lint free cloth.
8. To neutralize SF6 by-products on desiccant and used cleaning cloths, soak them in a 3% soda
solution for 24 hours, or dispose of them as hazardous materials.
! WARNING
Sulfur hexafluoride (SF6) is potentially dangerous because of the toxicity of the gas by-products and
possible suffocation in low-lying places in enclosed areas.
1. Eating, drinking, or smoking, as well as food storage, are strongly discouraged inside rooms
with SF6 installations. These activities are prohibited during maintenance work, when the
interrupter enclosures are opened.
2. Only maintenance personnel who are necessary to carry out the work are allowed to be in the
work area.
3. Avoid direct contact with parts that were in contact with the insulating gas.
4. Do not allow the powdery decomposition products to touch exposed skin.
5. Ensure more than “sufficient” room ventilation.
6. Maintenance personnel handling used SF6 gas, must be equipped with the following personal
safety gear:
• Appropriate gas mask or breathing equipment. The best choices are a full gas mask or a
gas mask, breathing equipment, and gas-tight safety glasses.
• Dust tight acid resistant protective overalls (disposable).
• Rubber gloves or disposable gloves.
• Rubber boots or disposable boots.
7. After completing the gas handling procedure, thoroughly wash the gas mask and breathing
equipment, safety glasses, rubber boots and rubber gloves with water.
Addendum A
Instructions on Handling Sulfur
Hexafluoride Gas and By-products
Contents
A.1 SF 6 Gas Overview............................................................................................3
A.2 Properties of SF 6 Gas ......................................................................................3
A.3 Health Risks for Pure SF 6 .................................................................................4
A.4 Decomposition Products of SF 6 ........................................................................5
A.5 Safety Precautions – Ventilation .......................................................................6
A.6 Recommended Equipment for SF 6 Handling......................................................6
A.7 Occupying and Entering Rooms with SF 6 Switchgear Installed ..........................7
A.8 Working on SF 6 Switchgear ..............................................................................7
A.8.1 Fundamental Rules .................................................................................7
A.8.2 Removal of SF 6 Gas from Equipment ......................................................8
A.8.3 SF 6 and the Environment ........................................................................8
A.8.4 Opening the Apparatus ...........................................................................9
A.9 Summary of Important Safety Instructions.........................................................9
List of Figures
Figure A-1: Sulfur Hexafluoride Liquefaction Curve ....................................................4
List of Tables
Table A-1: SF 6 Neutralizing Agents ............................................................................8
Revision History
Revision Record Description Revised by Date
! WARNING
Outdoor use of pure SF6 is safe. However, SF6 decomposition products require special protective
measures.
! CAUTION
The maximum permissible moisture content in SF6 gas must not exceed 125 ppmv upon filling.
Moisture can react with SF6 under the influence of electrical discharges to form toxic and corrosive
compounds through hydrolysis.
exceed 1% per year. SF6 installations can meet this requirement, and any more stringent standards
that may propagate in the future by using appropriate handling procedures and on-site monitoring,
reclamation and incineration equipment now available.
! WARNING
There is danger of suffocation due to lack of oxygen if the SF6 concentration exceeds 35 percent by
volume in air. Such concentrations can occur in non-ventilated open SF6 installations, and at ground
level of narrow compact rooms, as well as in spaces below ground level (e.g. basements, cable
ducts). If SF6 gas escapes without being able to mix turbulently with ambient air, it may, because of its
high density, accumulate at floor level and enter lower located rooms. Once SF6 gas has mingled with
air it will not collect in low areas.
Pure sulfur hexafluoride (SF6) gas is chemically very stable, inert, almost water insoluble, non-
flammable, non-poisonous, odorless, colorless and heavier than air (approximately 5X by weight). SF6
is an insulating and cooling gas of high thermal stability and dielectric strength.
SF6 is nontoxic; therefore, no risk classification needs to be specified. Refer to Attachment A, the
Material Safety Data Sheet (MSDS), for complete details.
The maximum allowable SF6 concentration at a place of work, assuming that a person spends 8 hours
per day there, is 1000 ppm (or 0.1 %) by volume. This very low value is the standard value adopted for
all gases considered harmless, but not normally present in the atmosphere. In the case of SF6, it is
more than two orders of magnitude lower than the danger level.
Clean, pure SF6 gas contains no contaminants, which are detrimental to health; however, there exists a
risk of asphyxiation as discussed above.
! WARNING
SF6 decomposition products are toxic in various ways. They can result in skin, eye and mucous
membrane irritations, and, when handled in large amounts, will lead to laryngeal and lung failure,
heart and circulatory collapse, as well as blackouts. Gaseous decomposition products, even in small
amounts, provide certain warning symptoms within seconds (for example, unpleasant, piercing odors,
and nasal, mouth, and eye irritations), before any actual poisoning takes place, which enables
personnel to withdraw to safety in time.
Under the influence of an arc, decomposition products are created which are partly toxic. The amounts
of decomposition products formed are proportional to the magnitude and duration of the arc, the degree
of the temperature increase, the design materials of the equipment and contaminants present such as
air and moisture.
Due to the resilient properties of SF6, a large part of the decomposed gas recombines, upon cooling.
Reactions may occur, however, with other materials present in the equipment (e.g. with vaporizing
arcing contact material). This results in the formation of gaseous sulfur fluoride and solid metallic
fluoride powder. In the presence of oxygen or moisture, the development of hydrogen fluoride and
sulfur dioxide may occur. Solid byproducts, when present, can be observed in the form of white, grey,
or tan powders, and are irritating to exposed skin.
If moisture is present, corrosive electrolytes may form from the primary and secondary decomposition
products of SF6. These electrolytes may cause damage and operational failure in electrical equipment,
particularly to insulating surfaces such as glass and porcelain. Therefore, it is recommended to perform
circuit switcher maintenance on rain free days and days with low ambient humidity.
Adsorption can reduce moisture and SF6 decomposition products inside equipment to acceptable
levels. Materials such as alumina, lime, molecular sieves or combinations thereof are suitable for this
purpose. They adsorb the gaseous acid products effectively and practically irreversibly, and at the
same time ensure that the gas maintains a low dew point temperature.
! WARNING
With an SF6 concentration exceeding 35 percent by volume in air, there is danger of suffocation due to
lack of oxygen. Such concentrations can occur in unventilated open SF6 installations, and at ground
level of narrow compact rooms, as well as in spaces below ground level (for example, basements or
cable ducts). If SF6 gas escapes without being able to mix turbulently with ambient air, it may,
because of its high density, accumulate at floor level and enter lower located rooms. Once SF6 gas
has mingled with air, it will not collect in low areas.
In installations located at ground level, intermingling of SF6 and air produced by natural circulation is
adequate. About 50% of the ventilating airflow cross-section should be located as close as possible to
ground level. In the case of breakdowns, provide forced ventilation.
In installations located below ground level, mechanical ventilation (forced ventilation) is required. The
volume of gas, the gas losses, and the size of the room could result in SF6 collecting in sufficient
quantities to cause asphyxiation. In the case of forced ventilation, SF6 contaminated air must be
collected as close to ground level as possible.
Spaces lying below SF6 switchgear installations (for example, shafts, cable ducts, sumps, and pits)
which are connected to rooms of the installation must be adequately ventilated or sealed-off in such a
manner that SF6 cannot collect in dangerous amounts.
! CAUTION
If there is an unpleasant, piercing odor from SF6 decomposition products in a room with SF6
switchgear installed, vacate the room immediately. Do not enter the room unless you are wearing
suitable oxygen masks or after thoroughly ventilating the room.
If there is a disturbance in the installation and you encounter concentrations of SF6 gas in hazardous
amounts (risk of suffocation) due to the gas volume and size of the room, enter the room only after
thoroughly airing it. Entrance is only permitted to persons wearing oxygen masks operating
independent of the ambient air, or alternatively, after establishing that the ambient air contains at least
17% oxygen.
Rooms located below the switchgear installation and associated with the plant may only be entered by
a team wearing suitable oxygen masks or after thoroughly ventilating the room.
The above table reflects currently published data. The treatment methods suggested differ widely with
respect to neutralizing fluid formulation and treatment time.
! CAUTION
There is a possibility of a dangerous situation leading to possible injury and/or damage to the
equipment.
! CAUTION
Before opening the apparatus, use an HF monitor to sample the switcher gas to detect possible
toxins.
• Open the SF6 switchgear only after evacuating the gas and reducing the pressure inside the
apparatus to atmospheric pressure.
• Either place the ventilation system in operation or ensure that fresh air circulates in some other
manner (for example, natural turbulence) when switchgear containing decomposition products is
opened.
• Wear a suitable fresh air breathing apparatus if there is even the slightest possibility that
personnel working on the equipment may be in danger through inhalation of hazardous amounts
of gas or vapor from powdery decomposition products. (For example, wide-range masks, type
72 (RIVA) with filter B2P2 from AGA Company or equivalent from “Draeger”). Monitor the levels
of the oxygen content to avoid the danger of asphyxiation)!
• Wear hooded, disposable, non-permeable, acid resistant coveralls, made of paper with a nylon
type reinforcement material, when working on open SF6 switchgear that contains powdery
decomposition products. After completing work remove coveralls and dispose of as prescribed.
• Avoid stirring-up dust and powder from SF6 switchgear. Difficult-to-remove dust can be removed
with dry non-fibrous rags. Use a vacuum cleaner to remove loose dust. The vacuum cleaner
filter should be able to retain particles of at least 1µm in size.
• Items (such as rags, vacuum cleaner and filter, disposable coveralls, gloves, etc.) which come
in contact with the decomposition products must be collected and neutralized so that the dust
cannot be transferred, before disposing of these items. Or they may be disposed of as
hazardous materials. (Note: California requires special permits to treat hazardous waste.)
• Under all circumstances ensure that the decomposition products do not come in contact with
skin, eyes, clothes, or that they are not swallowed or inhaled. Pay special attention to personal
hygiene, clothes and work bench. Dust or powder that comes in contact with skin must be
washed away with plenty of clean water. It is advisable to wash face, neck, arms, and hands
with soap and plenty of clean water before work breaks and after stopping work.
• Avoid eating, drinking, smoking, or storing foods in rooms or outdoors near to opened SF6
switchgear, which may contain arc-decomposed powder.
! CAUTION
Although pure, non-contaminated SF6 gas is non-poisonous, electrical discharges and fault-switching
arcs will give rise to different grades of toxic decomposition products. In small amounts gaseous
decomposition products – within seconds and before any poisonous effects can take place – produce
warning symptoms, such as an unpleasant piercing odor or nasal, mouth and eye irritations, which
enable working personnel to withdraw to safety.
Solid decomposition products (powdery residues from switching) can cause skin irritations. SF6 is about
five times heavier than air, and in the absence of turbulence, results in the gas collecting just above
ground level. It may cause suffocation through oxygen deprivation when working indoors or in areas
where the gas can accumulate.
Therefore, observe the following instructions while performing maintenance work or inspection in SF6
substations and on SF6 switchgear:
• As soon as an unpleasant, piercing odor from decomposition products becomes perceptible,
immediately leave the substation room. Enter the room only after thorough ventilation or when
wearing suitable oxygen breathing masks (with filtering or forced air devices).
• After disturbances, enter the substation room only after having thoroughly ventilated the room,
or when wearing oxygen breathing masks that operate independent of ambient air. Alternatively,
after verifying by measurement that the ambient air contains at least 17% oxygen by volume,
especially if one has to reckon with the concentration of SF6 in hazardous amounts.
• Enter rooms located below, and connected with the substation-rooms after thorough ventilation
only, or when wearing oxygen breathing masks which operate independent of the ambient air,
or alternatively, after having verified by measurement that the ambient air contains at least 17%
oxygen by volume.
• Ensure that the room ventilation operates satisfactorily while performing maintenance on SF6
switchgear (discharging and filling of gas, opening and cleaning of equipment).
• Before entering SF6 switchgear enclosures, which contain powder deposits, wear dust-proof
(non-permeable) protective coveralls and suitable oxygen breathing masks (operating
independent of ambient air or, after having verification from measurement that there is adequate
oxygen, masks containing a filter device) as well as protective spectacles.
• When working on opened SF6 switchgear, protect skin against contact with decomposition
residue and avoid swallowing or inhaling gas. Ensure body, clothing, and workbench
cleanliness. Wear disposable work-coveralls, and after completing work, discard appropriately.
• Wash skin that comes in contact with powder deposits with plenty of water. Before work-breaks
and after work, wash your face, neck, arms and hands thoroughly with soap and plenty of water.
• Do not stir up powder deposits resulting from arc switching. Remove sticky powder with dry
rags. Use suitable vacuum cleaner with paper-filter to remove loose powder. Handle the powder
such that the deposits do not spread. Before discarding used items and filter-bags, neutralize
the contaminated items.
• Items (such as rags, vacuum cleaner and filter, disposable coveralls, gloves, etc.) that come in
contact with the decomposition products must be collected and neutralized so that the dust
cannot be transferred. Before disposing of these items, neutralize them in a 3 percent soda
solution for 24 hours. To verify the degree of neutralization after 24 hours, add additional soda
to the solution. If the solution is neutralized it will not effervesce, if it does, the neutralization
process is to be repeated. (Note: California requires permits to treat hazardous waste.)
! CAUTION
1. Do not eat, drink, store foods, or smoke inside rooms with SF6 installations, especially during
maintenance work, when the interrupter enclosures are opened.
2. Avoid direct contact with parts that were in contact with the insulating gas.
3. Do not allow the powdery decomposition products to touch exposed areas of the body.
4. Ensure sufficient ventilation of the room.
5. Only maintenance personnel who are necessary to carry out the work should be in the work area.
6. When handling used SF6 gas, maintenance personnel should be equipped as follows:
• Appropriate gas mask or breathing equipment. The best choice is full-face gas mask, or a gas
mask and breathing equipment plus gas-tight safety glasses.
• Dust tight, acid resistant protective coveralls (disposable).
• Rubber gloves or disposable gloves
• Rubber boots or disposable boots
• After completing work, wash the gas mask and breathing equipment, safety glasses, rubber
boots and rubber gloves thoroughly with neutralizing solution and drinkable water.
Attachment A
Revision History
Revision Record Description Revised by Date
Chapter 3
General Characteristics
Contents
3.1 Component Descriptions ..................................................................................3
3.1.1 Pole Unit ................................................................................................3
3.1.2 Interrupters ............................................................................................4
3.1.3 Base Frame............................................................................................4
3.1.4 Operating Mechanism .............................................................................4
3.1.5 Auxiliary Controls Cabinet.......................................................................4
3.2 SF 6 Gas Monitoring System..............................................................................4
3.2.1 SF 6 Gas Density Supervision ..................................................................4
3.2.2 SF 6 Gas Density Monitor .........................................................................5
3.2.3 SF 6 Gas Policy .......................................................................................5
3.3 Electrical Operation..........................................................................................5
3.3.1 Closing Operation ...................................................................................5
3.3.2 Opening Operation .................................................................................6
3.4 Mechanical Operation ......................................................................................6
3.4.1 Closing Operation ...................................................................................6
3.4.2 Opening Operation .................................................................................7
3.5 Control Circuits ................................................................................................7
List of Figures
Figure 3-1: General Circuit Switcher Outline (Rigid Conduit Option Not Shown) ..........3
Revision History
Revision Record Description Revised by Date
Figure 3-1: General Circuit Switcher Outline (Rigid Conduit Option Not Shown)
1 Pole Columns 4 Auxiliary Controls Cabinet
2 Base Frame 5 Supports
3 Spring Operating Mechanism 6 Interconnection Cables
3.1.2 Interrupters
The GL309 circuit switcher design incorporates interrupters housed in each pole unit that utilize third-
generation auto-puffer, energy-optimized, self-blasting principle. This allows for the optimization in the
use of the arc energy and enables the operation to be driven by a low energy spring mechanism
In the opening operation, the main contact system opens first. Then the arcing contacts open and an
arc forms. In the case of high current operations, the pressure for arc blow out in the pressure chamber
volume is generated by the arc itself in accordance with the self-blast principle. Immediately after the
contact rod leaves the nozzle restriction, SF6 gas flows out of the pressure chamber and thus quenches
the arc at the next current zero. The circuit switcher is now in the open position. In the case of low
current operations, the auxiliary puffer volume serves to generate the necessary quenching pressure.
Valves in the stationary piston and in the bottom of the pressure chamber volume control the type of
pressure generation.
The Interrupter unit is maintenance free for up to 10,000 operations or 40 years. No need for
replacement parts for over 40 years under normal conditions.
! CAUTION
Refer to Chapter 2 for comprehensive safety information on handling SF6.
The Intergovernmental Panel on Climate Change identified SF6 as a “greenhouse gas” with the
potential to contribute to global warming. Never deliberately release SF6 gas to the atmosphere.
Carefully follow gas-handling procedures described in this instruction book to limit the release of SF6
gas over the life of the circuit switcher. Use gas-handling and reclaiming equipment.
AREVA designs, manufactures and factory tests circuit switchers to be free of leaks. AREVA warrants a
gas leakage rate of less than 1% per year on SF6 insulated equipment. If leaks develop in service, take
appropriate action to locate and eliminate SF6 gas leaks.
NOTE
When a separate low pressure lock-out relay is used for Trip #1 and Trip #2, both trip circuits must be
enabled in order to pickup both lock-out relays for a closing operation (applies to normally energized
relays only).
5. For as long as the Close signal is maintained, the anti-pumping relay is sealed in through the
“52b” auxiliary contact locking in the anti-pumping relay, and thus preventing further energizing
of the closing coil.
6. When the Close signal is removed, the anti-pumping relay will be de-energized.
7. The main contacts will move to the full closed position. If a trip signal is present, the switcher will
then move to the full open position, demonstrating the “Trip-Free” function of the mechanism.
! CAUTION
Interrupt current through the coils immediately by the switcher auxiliary switch contacts to avoid
damage to the coils.
! CAUTION
Only use the manual trip when the SF6 gas system is above minimum pressure.
A caution plate is located near the control as a reminder of the conditions for operation.
! CAUTION
Never operate the maintenance charging handle for manually charging the closing spring unless you
removed the control power.
! CAUTION
Do not operate the switcher unless SF6 gas pressure is above lockout (73.8 psig or 5.1 bar for -30°C
applications and 47.7 psig or 3.3 bar for -40°C applications).
For maintenance operation, push levers to Trip / Close.
Alarm circuits and other control arrangements are provided for specific switchers. Please refer to the
drawings in Chapter 7 (customer drawings and documentation) for a complete description of the
controls for your individual switcher.
Chapter 4
Receiving, Handling, & Storage
Contents
4.1 Transportation Methods....................................................................................3
4.1.1 Transportation ........................................................................................3
4.1.2 Inspecting for Shipping Damage..............................................................3
4.1.3 Contents of Shipment .............................................................................3
4.2 Lifting by Crane ...............................................................................................4
4.3 Lifting the Circuit Switcher with a Fork Truck ....................................................5
4.4 Storage............................................................................................................5
List of Figures
Figure 4-1: Lifting the Switcher by Crane ...................................................................4
Figure 4-2: Routing Lifting Harnesses outside of the Shipping Timbers .......................5
Revision History
Revision Record Description Revised by Date
4.1.1 Transportation
For deliveries and destinations where practical, AREVA GL309 circuit switchers ship from the factory by
truck to North American destinations or by container for international delivery. A list of the shipping
components is below:
1. Circuit Switcher Assembly
2. Operating Mechanism
3. Support Structure Legs
4. Auxiliary Controls Box
5. Crated SF6 Gas Bottle (Optional)
The remaining assembly components and optional accessories are packaged either inside the control
cabinet, mounted to the pallet of the support structure legs, or packaged in a crate attached to the base
frame. Refer to the switcher outline drawing in Chapter 7 for the total weight of the assembled switcher.
Packaging was designed to support the field installation sequence and provide easy identification of the
components. A switcher outline drawing is provided for each installation to show the proper alignment
of switcher components (See drawings enclosed in Chapter 7).
The switcher ships as a single unit with the gas system charged with SF6, to a slight positive pressure
of 2.9 to 7.3 psig (0.2 to 0.5 bar). Optional high voltage terminal pads (if ordered) are removed.
A gas fill hose (if ordered) connects the circuit switcher gas system (DILO DN8) to the customer’s SF6
gas regulator. (An SF6 gas regulator is not provided unless specifically ordered.) Refer to Chapter 2
and IEC 61634 Annex B for information on SF6 decomposition products.
IMPORTANT
It is especially important that you report any damage or missing parts discovered as soon as possible
to ensure prompt delivery of replacement parts.
! CAUTION
The circuit switcher may slip or shift on the forks if it is not positioned properly, or if the operator
makes abrupt movements with the forklift. Use straps to secure circuit switcher to the forks.
Equipment damage or personal injury may result.
4.4 Storage
! CAUTION
The transport packaging is not suitable for long-term storage.
• Maximum period of outdoor storage in transport packaging: Two months from the date of
shipment
• Maximum period storage in a dry room in transport packaging: Four months from the date of
shipment
• Unpacked switchers can be stored as long as required in dry areas.
• Unpacked switchers can be stored outdoor or in a shed as long as required, if the operating
mechanism is mounted to the base frame and the anti-condensation heaters are energized
(avoidance of condensation and resultant corrosion damage.).
• When stored outdoors, place the switcher on its legs or leave it on its wooden shipping
supports.
• Make sure that the ventilation screens in the control cabinet are free of obstruction.
• Store the switcher with a positive SF6 pressure only.
Chapter 5
Assembly, Installation, & Commissioning
Contents
5.0 General Instructions .........................................................................................5
5.1 Circuit Switcher Assembly ................................................................................5
5.2 Materials and Equipment to Be Provided by Customer ......................................6
5.2.1 Materials ................................................................................................6
5.2.2 Tools and Hoisting Equipment .................................................................6
5.2.3 Testing and Measuring Equipment ..........................................................6
5.2.4 Indirect Materials and Supplies ...............................................................6
5.3 Installation Procedures.....................................................................................7
5.3.1 Unpacking the Crates .............................................................................7
5.3.2 Installing the Support Legs on the Foundation .........................................7
5.3.3 Mounting the Auxiliary Controls Box on the Support.................................9
5.3.4 Lifting the Circuit Switcher by Crane......................................................10
5.3.5 Mounting the Circuit Switcher on to the Support Structure......................11
5.3.6 Connecting the High Voltage Terminals .................................................14
5.4 Checking the SF 6 Gas System for Tightness ................................................... 15
5.4.1 Leak Detection Procedure .....................................................................15
5.4.2 Procedures if a Leak is Detected...........................................................15
5.4.3 Vacuum Evacuation Procedure .............................................................16
5.5 Filling the Circuit Switcher with SF 6 Gas ......................................................... 19
5.6 Grounding the Circuit Switchers and Enclosures ............................................. 20
5.7 Manually Charging the Spring Mechanism ...................................................... 21
5.8 Operating the Switcher ................................................................................... 21
5.9 Checking the Anti-Condensation Heater.......................................................... 23
5.10 Wiring the Supply Voltages ............................................................................ 23
5.11 Optional Installation Procedures ..................................................................... 23
5.11.1 Checking the Circuit Switcher System Pressure ...............................23
5.11.2 Density Monitor Switch Settings ......................................................23
5.11.3 Checking the Closing Spring Charging Time ....................................24
5.11.4 Timing Tests ...................................................................................24
List of Figures
Figure 5-1: Support Structure Installation .................................................................. 8
Figure 5-2: Auxiliary Control Box Mounting Brackets .................................................. 9
Figure 5-3: Mounting the Auxiliary Control Box to the Support Structure ................... 10
Figure 5-4: Lifting the Switcher by Crane ................................................................. 11
Figure 5-5: Routing Lifting Harnesses outside of the Shipping Timbers..................... 11
Figure 5-6: Assembling the Circuit Switcher to the Support Structure ....................... 12
Figure 5-7: Connecting Auxiliary Cabinet Cabling .................................................... 13
Figure 5-8: Connecting Auxiliary Cabinet Cabling with Rigid Conduit ........................ 13
Figure 5-9: Mounting the High Voltage Terminal Pads.............................................. 15
Figure 5-10: WIKA SF 6 Density Monitor Gauge Dial ................................................. 18
Figure 5-11: Standard SF 6 Gas Monitoring System .................................................. 20
Figure 5-12: Quick Connect Valve ........................................................................... 22
List of Tables
Table 5-1: Commissioning Checklist ........................................................................ 26
Revision History
Revision Record Description Revised by Date
! CAUTION
Do Not charge the operating mechanism or operate the switcher until the mechanism is connected
and the switcher is charged with more than 73.8 psig (5.1 bar) of SF6 gas at 20°C for -30°C
applications or 47.7 psig (3.3 bar) of SF6 gas at 20°C for -40°C applications
• When the switcher is shipped completely assembled, the switcher pole units have been filled
with SF6 gas for transportation, approximately 2.9 to 7.3 psig (0.2 to 0.5 bar).
• The manufacturer has already made all adjustments. The drive rod of the mechanism has been
adjusted and locked with a locking compound.
• Pole columns and mechanism ship in the open position. The closing spring of the mechanism is
discharged.
• In the spring operating mechanism, the opening latch assembly has been secured for shipping
by a cable tie.
• Whenever the instructions call for "bolt and locking adhesive," always use the liquid locking
adhesive Loctite (blue).
NOTE
In the following sections, the side of the circuit switcher on which the mechanism is located is referred
to as the "front."
! CAUTION
Fasteners (bolts, nuts, coupling pins, etc.) that do not have the required strength may fail during
installation, commissioning, or operation and cause serious damage or injury.
• Use only the fasteners supplied with the circuit switcher.
• Always use the proper grade and type of fastener (refer to the drawings supplied in this
chapter and Chapter 7).
• Tighten the bolts and nuts to the correct torque with a torque wrench as specified in
Attachment B – AREVA Specification TS-00007 (lubricate bolt threads per specifications).
! DANGER
Improper handling can result in serious damage or injury caused by falling loads.
• Standing under suspended loads is prohibited.
• Assigned personnel must wear protective headgear (hard hats).
5.2.1 Materials
• Foundation
• Grounding connections and fasteners
If not included with order:
• Anchor bolts, nuts, and washers
• Supports in accordance with AREVA specifications (already attached to the foundation)
• High voltage terminal pads and fasteners
IMPORTANT
For standard insulation height, 8-½ ft. to lowest ungrounded (2591 mm), the required crane height is
20 ft. (6 m).
• For different insulation heights, please refer to the dimension drawing.
IMPORTANT
The following instructions do not claim to cover all variations of this product, nor do they claim to
provide for every contingency of installation, operation or maintenance.
If you need further information or direction to prepare this product for installation or maintenance,
please contact AREVA T&D Inc. at:
724-483-7308 or 1-877-257-8661; Fax 724-483-7771.
1
4
5
4
2
3
Assembling Assembling
Standard Optional
Bracket Bracket
Assembled
Section Views
Assembling Assembling
Standard Optional
Bracket Bracket
Assembled
Figure 5-3: Mounting the Auxiliary Control Box to the Support Structure
1 Auxiliary Cabinet
2 Washer, (Chapter 4, Crate 1, Bag C1)
3 Bolt, (Chapter 4, Crate 1, Bag C1)
4 Nut, (Chapter 4, Crate 1, Bag C1)
! WARNING
Use four slings.
Do Not “basket” the circuit switcher, as it may roll.
Use four slings attached to the lifting lugs (specified in Section 5.2.2) located on the base frame (Figure
5-4). Route slings around the outside of wooden shipping timbers (Figure 5-5). The nameplate indicates
the weight of the circuit switcher.
Due to the weight of the mechanism, the center of gravity is offset. Refer to the outline drawings in
Chapter 7 for specific center of gravity information.
IMPORTANT
Aluminum oxidizes quickly; it is imperative you complete the preceding step even if the surface looks
clean.
3. Clean tin or silver plated contact surfaces with care to ensure that the surface of the plating is
not broken. Alternatively, you can clean the plated surfaces with a solvent that will not damage
the plating.
4. Immediately apply a thin layer of contact grease such as Penetrox A to all contact surfaces to
prevent further oxidation of the contact surfaces. Brush contact grease onto contact surfaces
with a wire brush or pad.
5. Apply a thin layer of anti-seize compound to the threaded surfaces of fasteners prior to
assembly (Chapter 4, Crate 1, Bag H2 if ordered).
6. Place a washer under the bolt and another under the nut.
7. Fasten the high voltage terminal pads with the accompanying bolts and tighten them to a
torque.
8. Torque the fasteners according to Attachment B within 5 minutes of completing grease
application.
9. Remove excess contact grease leaving a small bead around the outside edge of the joint to
prevent water infiltration.
10. Clean any dirt or debris, which the preparation of the HV terminals creates, from the bushings.
! CAUTION
ALWAYS use a pressure-regulating device when filling the switcher. Refer to safety precautions in
Chapter 2 for proper SF6 handling.
IMPORTANT
The SF6 density monitor (Figure 5-10) is a temperature compensated pressure gauge, that is, the
ambient temperature is already considered.
! CAUTION
ALWAYS use a pressure-regulating device when filling the switcher. Refer to the safety precautions in
Chapter 2 for proper SF6 handling.
IMPORTANT
Never move a switcher with more than 0.3 to 0.7 bar (4 to 10 psig) SF6 pressure.
Never store switchers with a vacuum.
IMPORTANT
For long-term storage, switchers should have 0.3 to 0.7 bar (4 to 10 psig) SF6.
Do not fill the switcher until it is installed on a permanent foundation and all high voltage connections
are made.
Some discoloration may occur to metal surfaces when using a liquid detergent, like dishwashing
liquid, for a leak test. Wash away all soap residues with clean water.
! DANGER
Improper transport or handling can result in damage to the pole columns. If this is the case, pole
columns may burst when they are being filled to rated pressure.
• To avoid serious accidents, carry out a visual inspection for damage before filling the switcher.
• While filling the switcher with SF6, all personnel must be in a protected location or at a
sufficient distance from the equipment.
IMPORTANT
The nameplate indicates the rated pressure. If the nameplate is missing, the marking on the density
monitor (black dot at the end of the green field on the dial) indicates the rated pressure.
• If there is any doubt about SF6 quality (when using unsealed SF6 cylinders, for example),
check the dew point of the SF6 gas after the filling operation, as described in Chapter 6.
• The density monitor can be checked against the pressure curve in Chapter 1 by using a test
manometer and a thermometer.
NOTE
If the piping has been opened or a pole coplumn has been dissasembled, a vacuum must be pulled on
the entire switcher prior to filling the switcher with gas, per Section 5.4.3.
Carefully follow all safety precautions. Refer to Chapter 2 of this manual for health risks associated with
SF6. For proper SF6 handling, use a gas handling and reclaiming cart. If a handling unit is unavailable,
always use an SF6 gas regulator when filling from the cylinder. Use only SF6 gas filling equipment that
has not been exposed to contaminating moisture, or SF6 by-products.
The SF6 gas density monitor (Figure 5-10) is a temperature compensated pressure gauge, that is, the
ambient temperature is already considered in the measurement. Due to the temperature compensating
mechanism of the gauge, the density monitor will not respond to normal changes in gas pressure due
to temperature fluctuations, and will only respond to changes in density of the SF6 gas system.
The switcher has been leak tested at the factory and determined to have a leak rate of less than 1% per
year.
1. Connect the filling hose to the gas-filling device (SF6 gas cylinder with pressure reducing
regulator or SF6 gas cart).
2. Evacuate the fill hose of all air.
3. If filling from a cylinder, flush the filling hose with a minimal amount of SF6 gas to displace the air
in the hose. Ensure that the hose is moisture-free and that there are no particles, dirt or oil
inside the hose or any fittings.
4. Connect the fill hose to the SF6 fill port (DILO DN8) on the circuit switcher. Refer to Figure 5-11
for the location of the filling port on the circuit switcher.
5. Fill up to the rated density, which the black dot at the upper limit of the green segment of the
density monitor indicates.
IMPORTANT
In order to be able to fill all of the switchers with the amount of SF6 gas supplied, start filling with the
gas cylinder that contains the least amount of gas. After using it completely, fill with the next emptiest
cylinder, etc. If you do not follow this procedure, the amount of gas supplied will not be enough.
! CAUTION
DO NOT invert the gas cylinder because this will fill the switcher with liquid SF6. The resulting over-
pressurization may burst the pressure relief device.
IMPORTANT
To prevent freezing of the gas cylinder or the filling equipment during SF6 charging, set the charging
pressure to no more than 1 to 2 psig (0.1 to 0.2 bar) above the nominal fill pressure of the switcher,
94.1 psig (6.5 bar).
6. After a temperature equalization period of approximately one hour, check again and correct the
SF6 pressure if necessary. After filling the switcher, remove the hose and replace the fill port
cap.
Three colored areas divide the dial of the WIKA gas density monitor: Green, Yellow and Red. The
position of the needle indicates the SF6 gas density at any ambient temperature.
If not completed at the factory, install the copper ground bar in the control cabinet using the hardware
supplied so that it protrudes through the bottom of the cabinet.
NOTE
Some orders may request additional grounding points on the exterior of the auxiliary controls cabinet
and the mechanism cabinet. Check these cabinets for stickers that point out additional grounding
locations. If there is a sticker on the mechaism cabinet, there should be one on the auxlilary cabinet.
Connect the two cabinets at the points indicated by the stickers.
Connect a ground cable to the control cabinet ground bar to ensure a proper ground for the control
cabinet and the associated control circuits.
IMPORTANT
Refer to Chapter 8 for additional information on spring-operated mechanisms.
! CAUTION
When operating the switcher manually, make sure that:
• Gas pressure is greater than the Lockout set point.
• All tools are removed and personnel are clear of the operating mechanism.
• Control power is removed.
• Only use the manual charge handle when all local control power has been de-energized.
• Do not operate the Manual control switch unless all of the above are observed
! CAUTION
Operating the system with less than the acceptable indicated gas pressure may damage the
interrupter parts. Observe the warning tag below, which is attached to the mechanism.
WARNING
Hazardous: Moving parts inside. No maintenance or other work should
be performed until all electrical power has been removed from the system.
Read the applicable sections of the instruction book, particularly the
section on "safety".
2. Operate the switcher remotely to ensure that the control circuits, motor circuit, and alarms are
functional.
3. You can check low SF6 alarms and lockout settings by slowly bleeding the pressure by means of
the three-way valve (optional) at the gas system manifold block. If a three-way valve is not
provided, follow the procedure below to simulate a gas leak.
! CAUTION
If the control scheme calls for the switcher to open and lockout at low pressure, the switcher will open.
Quick-connect
Valves
! DANGER
Before installing the supply and control cables, make sure the circuit switcher is not energized.
! CAUTION
As soon as you apply the supply voltage and you turn on the motor protection switch, the motor will
charge the closing spring.
• Before applying voltage or turning on the motor protection switch, make sure there are no
objects or parts of the body in the charging system area.
When you apply supply voltage, the anti-condensation heater will be hot. It can burn skin or clothing.
• Do not touch the heater.
Insert all supply and control cables through cable glands and connect them to the terminals in
accordance with the schematic diagram in Chapter 7.
IMPORTANT
Take these readings early in the morning, to avoid inaccuracies caused by solar heating of the circuit
switcher during the day.
• Take a temperature reading of the pole tank to get a close estimation of the SF6 gas
temperature.
• Attach a calibrated pressure gauge to the fill port of the circuit switcher.
• Consult the rated pressure curve in Chapter 1, to find the proper pressure at the recorded
temperature.
• Reduce pressure slowly to ensure that contacts operate at the proper alarm and lockout values.
• See switcher specific drawings for accurate densities (refer to Chapter 7).
• The contacts of the WIKA density meter are not adjustable. If you find that the density meter is
out of calibration, notify AREVA T&D Inc.
! CAUTION
Never operate the switcher with an SF6 gas density below the lockout value.
NOTE
The closing time is the time from energizing the close coil to contact touch.
The opening time is the time from energizing the trip coil to contact separation.
IMPORTANT
In the event of any warranty claim, the absence of this checklist may result in reduction of the claim.
Please note:
1. General information such as name of the user, name of substation, type of switcher, serial
number and the year of manufacture must always be filled in.
2. Each commissioning checklist is only valid for one switcher. Treat the Commissioning form in the
manual as a master and photocopy it whenever commissioning or recommissioning the switcher.
3. Note the serial number of the switcher on each page.
4. Carry out all work described in previous sections and initial the corresponding sections of the
checklist.
5. After completing the commissioning process, the commissioning engineer must sign and date the
commissioning checklist.
6. Return one copy to:
AREVA T & D Inc., Attention: QA,
One Power Lane,
Charleroi, PA 15022, USA.
Checked by _______________________________
Signed _______________________________
Date _______________________________
Return to: AREVA T&D Inc., Attn: QA, One Power Lane, Charleroi, PA 15022, USA
92
89
152
EP O-RING SEAL
30
HOLE THRU -
TO BE SPECIFIED
DIECAST BY CUSTOMER
ALUMINUM
ENCLOSURE
56
129
MEMBRANE VENT
42
70
NOT TO SCALE
PRESSU RE PORT - DIMENSIONS IN
48 G 1/2 A INCHES
0/800 0/25 0/2500 SW 316 stainless steel 316 stainless steel C-Tube Vac/600 ⁄4 & 1⁄2(2)
1
0/1000 0/40 0/4000 SW 316 stainless steel 316 stainless steel Helical 800/15,000 ⁄4 & 1⁄2(2)
1
Addendum:
3-Way Valve
MULT-IM ALSTOM T&D INC.
Part I, Page 2 INSTRUCTION MANUAL-ADDENDUM Rev 0 (03/28)
Contents:
List of Figures:
3-way valves are optionally provided as part of the gas system to enable the
customer to test and verify the alarm and lock-out points of the gas monitoring
device. The 3-way valve provides isolation from the interrupting chamber gas
system for testing or replacement of the gas monitoring device.
The 3-way valve is a ball valve that has a center-off orientation. The 3-way ball
valve is coupled with a mud dauber. The mud dauber acts as a vent and has a
screen to prevent insect from entering the valve. A normal-test nametag (See figure
1) is mounted with the 3-way valve to display the position of operation. The
orientation of the valve handle (with respect to the tag) depicts the corresponding
flow of the gas system.
Due to gas system variations from differences in breaker or switcher design, the 3-
way valve may be oriented differently. Refer to the nametag associated with the 3-
way valve on your equipment for proper handle orientation.
MULT-IM ALSTOM T&D INC.
Part I, Page 4 INSTRUCTION MANUAL-ADDENDUM Rev 0 (03/28)
When the handle on the 3-way valve is turned to the normal operating
position (refer to fig 2), the gas flow in the system interrupting chamber is
permitted to flow unrestricted to the gas density monitoring system.
When the handle of the 3-way valve is rotated 90 degrees from the normal
position (refer to fig 3), the gas density monitor is isolated from the gas
system.
When the handle of the 3-way valve is turned beyond the center-off position
(refer to fig 4), the density monitor can be evacuated (reduction of pressure)
of gas to alarm and lockout points for testing and verification of proper
function.
4.0 Procedure
• After testing is completed, remove reclamation cart and reinstall mud dauber to
3-way valve.
• Rotate the valve handle back to the normal position.
WARNING
Make certain to return handle of 3-way valve to normal position prior to putting
equipment into operation. Failure to do this will prevent the gas monitoring system
from operating correctly, and may result in improper equipment function or failure.
Be sure not to completely evacuate gas from the system. It is imperative that the
internal pressure is greater than ambient, so that moisture is unable to enter the
gas system of the equipment.
WARNING
SF6 possesses powerful greenhouse gas characteristics. It possesses a global
warming potential of approximately 24,000 times that of carbon dioxide over a
100-year time horizon, with an atmospheric residency of more than 3,000 years. It
is important for participants to recognize the importance of responsible use and
careful management of SF6 gas.
AREVA T&D Circuit Switchers Attachment B Rev. 0
Type GL309 Technical Specification TS-00007
Attachment B
Revision History
Revision Record Description Revised by Date
1. CONTENTS
2. PURPOSE AND SCOPE
3. DERIVATION, GENERAL REQUIREMENTS
This document defines the technical requirements for torque values for externally threaded
mechanical fasteners. These requirements are intended to serve as a general reference for
Areva personnel, as well as customers and suppliers, in the design, fabrication and repair of
Areva T&D Inc. products. This specification is a supplement to the assembly drawings from
which it is referenced and is subordinate to any specific values that are designated on the
respective drawings. The development-engineering department will control this document.
The torque values that are provided in the following table have been calculated to pre-stress
the fastener between 65-80% of tensile yield. A 0.20 (empirical) torque coefficient has been
assumed in the computation of the resulting values. Listed values are nominal. Tolerance is
± 20%.
NOTE: Metric fasteners threaded into cast aluminum shall not exceed torque
values listed for ASTM F 568M Property Class 5.6.
NOTE: Standard fasteners threaded into cast aluminum shall not exceed torque
values listed for SAE Grade 2.
Chapter 6
Maintenance and Troubleshooting
Contents
6.0 General ...........................................................................................................5
6.1 Recommended Maintenance Schedule .............................................................5
6.1.1 Maintenance Walk-by – Class M1 Service ...............................................5
6.1.2 Inspections – Class M2 Service...............................................................5
6.1.3 Overhaul – Class M3 to M5 Service.........................................................5
6.2 M1 Service – Annual Maintenance Walk-by.......................................................6
6.2.1 General Condition of Equipment..............................................................7
6.2.2 SF 6 Gas Pressure and Quality.................................................................7
6.2.3 Air Vents and Anti-Condensation Heater Operation..................................8
6.2.4 Operation Counter ..................................................................................8
6.2.5 Functional Check of the Electrical Control Circuits ...................................8
6.3 M2 Service – 6 Year Inspections ......................................................................8
6.3.1 Tightening High Voltage Terminals ..........................................................9
6.3.2 SF 6 Density Monitor Set Points ...............................................................9
6.3.3 Tightening Mounting Hardware................................................................9
6.3.4 Relay Operation .....................................................................................9
6.3.5 Resistance Measurement ........................................................................9
6.3.6 Bushing Insulators ..................................................................................9
6.3.7 Measuring Operating Times for Poles and Auxiliary Contacts .................10
6.4 M3 Service – 12 Year Overhaul ...................................................................... 10
6.4.1 Discharging the Closing Spring .............................................................10
6.5 M4 Service – 24 Year Overhaul ...................................................................... 11
6.6 M5 Service – Electrical Wear Overhaul ........................................................... 11
6.6.1 Electrical Wear Limits – Permissible Number of C-O Operations ............11
6.6.2 Application of Lubricants .......................................................................13
6.6.3 Provisions ............................................................................................13
6.6.4 Replacement of the Arcing Contacts......................................................15
6.6.5 Disassembly of Support Porcelain and Crankcase .................................21
6.7 Recommissioning a Reconditioned Circuit Switcher ........................................ 29
List of Figures
Figure 6-1: Permissible Number of C-O Operations.................................................. 12
Figure 6-2: Fixed Arcing Contact Removal ............................................................... 16
Figure 6-3: Fixed Arcing Contact Disassembly ......................................................... 17
Figure 6-4: Replacing the Base / Interrupter Assembly ............................................. 18
Figure 6-5: Reconditioning the Base ........................................................................ 19
Figure 6-6: Replacing the Adsorption Filter .............................................................. 20
Figure 6-7: SF 6 Piping............................................................................................. 21
Figure 6-8: Cover Panel Removal ............................................................................ 22
Figure 6-9: Disconnecting the Linkage..................................................................... 23
Figure 6-10: Disassembling of the Pole Column from the Base Frame ...................... 24
Figure 6-11: Setting the Tools ................................................................................. 25
Figure 6-12: Replacement of the Opening Springs ................................................... 26
Figure 6-13: Crankcase........................................................................................... 27
Figure 6-14: Disassembly of the Insulating Rod Assembly........................................ 28
Figure 6-15: Typical Swagelok ® Fitting .................................................................... 30
Figure 6-16: Reassembly of a Typical Swagelok ® Fitting .......................................... 30
List of Tables
Table 6-1: Acceptance Criteria – GL309 .................................................................... 6
Table 6-2: SF 6 Gas Quality ....................................................................................... 8
Table 6-3: Lubricants for Type GL309 Circuit Switchers ........................................... 13
Revision History
Revision Record Description Revised by Date
6.0 General
These maintenance directives incorporate measures for avoiding the hazards involved in the
application of SF6 gas to switchgear. Such directives are protective measures and recommendations
for the user of SF6 switchgear.
Any personnel performing maintenance or inspection on SF6 switchgear should read this section and
comply with these instructions as well as the safety precautions prescribed by their employer. Failure to
observe the safety precautions described herein, and those defined by the employer, may result in
bodily harm or asphyxiation.
IMPORTANT
In the case of service under extreme conditions, i.e.,
• continuously high ambient temperatures,
• presence of abrasive dust or grit,
• heavy dust accumulation,
• continuously high humidity,
• presence of aggressive gases or vapors,
Shorten the inspection and maintenance intervals.
Under normal service conditions, the maintenance program can be summarized as follows:
reached before 24 years of operations. However, if the switcher does reach it, it is necessary to
replace the breaking elements, Contact AREVA T&D customer Service for assistance. [Class
M5 Maintenance]
IMPORTANT
The time intervals given above are based on empirical values determined over many years of field
experience. Regionally applicable standards and regulations may specify shorter intervals.
Perform switcher overhaul maintenance as soon as any one of the above events occurs. Inspect the
circuit switcher used most often and then, depending on the results observed, adapt the maintenance
program for the other switchers.
Table 6-1: Acceptance Criteria – GL309
M1 Maintenance Walk-by (At least once a year)
M2 Inspection (Every 6 years)
M3 Overhaul Based on Service Time: 12 years
M4 Overhaul Based on Service Time: 24 years
M5 Overhaul Based on Electric Wear: See Section 6.6
§# M1 M2 M3 M4 M5 Action
6.2.1 9 9 9 9 9 Check the general visual appearance of switchgear:
(corrosion, paint, etc.).
6.2.2 9 9 9 9 9 Check SF6 pressure.
6.2.3 9 9 9 9 9 Check the condition of air vents and heater
operation.
6.2.4 9 9 9 9 9 Read and record the operating counter figures.
6.2.5 9 9 9 9 9 Perform two Open-Close duty cycles
6.3.1 c 9 9 9 9 Verify the tightness of the terminal block hardware
(c Six months after commissioning).
6.3.2 9 9 9 9 Check the switch points of the SF6 density meter.
6.3.3 9 9 9 9 Verify the tightness of the enclosures and hardware.
6.3.4 9 9 9 9 Check the relay operation.
6.3.5 9 9 9 9 Check resistance
6.3.6 9 9 9 9 Inspect the bushing insulators.
6.3.7 9 9 9 9 Measure the operating times of poles and auxiliary
contacts, at rated voltage and pressure.
6.6.2 9 Replace the operating contacts.
§ Refers to following section numbers
! CAUTION
During maintenance operations, take all safety precautions to protect personnel working on the
equipment; particularly read Chapter 2.
At least once a year, with the circuit switcher operating normally, perform a visual inspection of the
switcher and the operating mechanism. Inspections are to be performed only by trained personnel.
Follow the relevant safety precautions. Dismantling the circuit switcher poles is not necessary for the
following recommended inspections.
• Visually inspect for damage, especially to bushings.
• Check for corrosion or damage to metal parts and piping. Especially notice the condition of the
bolted flanges.
• Check for clear air vents in the base frame and in the mechanism and controls cabinets.
• Check cable connections.
• Functional check the anti-condensation heaters.
• Check the SF6 density (the SF6 density monitor must indicate in the green sector on the WIKA
gauge).
• Check the SF6 gas quality.
! CAUTION
Chapter 5 describes in detail the procedure for filling the circuit switcher with SF6.
Check the SF6 gas quality with respect to the moisture content, SF6 content, and acidity. Reference
values are:
! DANGER
Follow all regional and operator-specified safety precautions. In addition, observe the following
instructions:
• Isolate the switcher.
• Closing spring position indicator must show "spring discharged."
• Ground the switcher.
• Disconnect the supply and motor voltages. (Voltages are required for the procedures
described in 6.2.2 and 6.2.5.)
Every six years, de-energize the circuit switcher and inspect the switcher pole units and operating
mechanism without dismantling either the sub-assemblies or the interrupting chambers. Clean the
equipment and verify all connections, gas, and fluid levels are correct. Maintenance is to be performed
only by trained personnel or AREVA service technicians. It is not necessary to dismantle the switcher
pole for the following maintenance:
1. Take the circuit switcher out of service.
2. Perform all inspection items described in Section 6.2 preceding.
3. Check the terminal connections inside the control mechanism and the spring mechanism
enclosures.
4. Check the linkage bolts torques.
NOTE
Always lubricate the threads to prevent galling.
NOTE
The opening time is the time from energizing the trip coil to separation of the main contacts.
The closing time is the time from energizing the close coil to contact touch.
! CAUTION
NEVER use Molykote lubricants on any internal areas in contact with SF6.
• Coat all flanges and areas exposed to water with Dow 111 silicone grease to prevent moisture
penetration and to lubricate the O-rings and O-ring grooves. Apply lubricants or grease by hand.
• Do not use brushes or any device for applying lubricants because they may introduce particles
during lubrication. While applying lubricants by hand, if you feel any particles, thoroughly clean
the areas and reapply the proper lubricants or grease. Take care lubricating gaskets, seals, etc.;
verify that there is no damage and that no particles are present that would prevent a gas tight
seal.
• Clean all functional elements with a lint free wiper that has been soaked in denatured alcohol.
Grease the parts according to the greasing instructions. Replace parts when necessary.
• If you removed bolted connections during work, reinstall all hardware. Replace damaged
hardware if there is any visual damage.
• Replace the absorption filter (desiccant), refer to Section 6.6.4.6, whenever a pole unit has been
opened to the environment for long periods or if it is contaminated with SF6 decomposition by-
products. Do not remove the replacement absorption filter (desiccant) from its protective
container or install it until the switcher pole unit is completely assembled and ready for pulling
vacuum.
∑ Arms
2
⋅ t arc
2000
1000
100
N
15
10
1
1 2 10 25 31.5
I [kA]
6.6.3 Provisions
1. Tools
a. Torque wrenches 8 – 400 N·m
b. Socket wrenches 4 – 36 mm
c. Box-end wrenches 10 – 41 mm
2. Special Tools
Tool-No. Description Illustration Part No.
T100 Assembly tool for coupling bolt 2018905
3. Accessories
a. Loctite blue (242)
b. Molykote BR2 plus
c. Molykote PG 54 grease
d. DOW 111 Grease
e. Scotch abrasive pad
f. Cleaning alcohol
4. Replacement Parts
a. For disassembly and reconditioning of interrupter chamber
No. Description Qty. Per Pole
1.102 Fixed arcing contact 1
1.3 Interrupter unit 1
1.4 Gasket for chamber insulator 2
1.5.2 PTFE guide strip 1
1.5.3 PTFE guide strip 1
1.5.4 PTFE guide strip 2
1.7 Gasket for support porcelain 2
1.8.02 Coupling pin, 12 x 35 1
1.8.04 Adsorption filter 1
1.8.36 O-ring, 66.27 x 3.53 1
b. For disassembly of support porcelain and crankcase
No. Description Qty. Per Pole
1.4 Gasket for chamber insulator 2
1.7 Gasket for support porcelain 2
1.8.02 Coupling pin, 12 x 35 1
1.8.04 Adsorption filter 1
1.8.15 O-ring, 34.52 x 3.53 1
1.8.32 O-ring, 12.37 x 2.62 1
1.8.35 O-ring, 38.82 x 5.33 2
1.8.36 O-ring, 66.27 x 3.53 2
! CAUTION
Keep exposure of SF6 gas compartments to the atmosphere to a minimum. Protect from water (rain) in
all circumstances. Follow Chapter 2 instructions for handling SF6 and the absorption filter.
6.6.4.2 Procedure
First, ensure that:
• Disconnect the supply voltage to the motor
• Discharge the closing and opening springs. This state is reached when the position indicator
shows OPEN and the spring position indicator is on "discharged." The following operations are
required to reach this state, depending on the starting situation:
Switcher Position State of the Closing Spring Operations to Be Executed
CLOSED Charged O-C-O
CLOSED Discharged O
OPEN Charged C-O
OPEN Discharged No operation required
• Store the SF6 gas in a service unit and evacuate the columns. Then ventilate the pole columns.
5
L1
1
L2
3
! CAUTION
Do not let the fixed contact move horizontally while removing the bolts or lifting out the fixed contact,
as this could result in damage to the porcelain.
2. Lift the fixed contact out of the chamber porcelain, place on dry surface and clean all surfaces to
remove any dust particles that might be adhering to them.
3. Loosen bolt (Figure 6-3, Item 3) and replace fixed arcing contact (Figure 6-3, Item 2).
L7
1 2
L2
3
2
L1 4
L7
12
10
9
13
L1
L2
11
5
Figure 6-4: Replacing the Base / Interrupter Assembly
1 Chamber insulator 8 Bolt
2 Interrupter unit 9 Bolt
3 Gasket for chamber insulator 10 Washer
4 Base 11 Gasket for support insulator
5 Support porcelain 12 Coupling bolt
6 Washer 13 Cover
7 Bolt
2. Lift out the chamber porcelain (Figure 6-4, Item 1), place on a dry surface and clean the inside
surfaces to remove any dust particles.
3. Remove cover (Figure 6-4, Item 13) and two bolts (Figure 6-4, Item 9).
4. Detach the interrupter unit (Figure 6-4, Item 2) by pulling out the coupling bolt (Figure 6-4, Item
12). For this purpose, use tool T100, AREVA Order No. 2018905.
5. Remove two bolts (Figure 6-4, Item 8) and lift up subassembly base / interrupter unit.
4
6 L7
L7
L7
L7
! CAUTION
Do not forget the contact system (Figure 6-5, Item 6).
2. Detach the filter lids (Figure 6-6, Item 5) and remove the filter chambers (Figure 6-6, Item 2).
3. Remove the filter bags (Figure 6-6, Item 1) from the filter chambers, insert a new bag, and slide
the filter chambers back into the crankcases.
4. Replace the O-ring (Figure 6-6, Item 6).
5. Reinstall the lid and torque the screws to Attachment B specifications.
6. Reinstall all levers.
! CAUTION
• When reinstalling the levers, make sure the levers match up with the pole columns.
• Match up the position markings on the levers and shafts.
7. Evacuate the switcher, fill it with SF6 to rated pressure, (as described in Chapter 5) and carry
out commissioning operations.
8. Check all pole column flange connections that were opened during inspection and the SF6
piping for leak-tightness using the SF6 leak detector.
2 1 6 5 3 4
! DANGER
Follow the safety precautions given in Chapter 2.
6.6.5.1 Requirements
1. Disconnect the interrupter chamber from the support porcelain, as described in Section 6.6.3.
2. The following items shall be provided:
a. Tools listed in Section 6.6.3.
b. Indirect materials and factory supplies listed in Section 6.6.3.
c. Replacement parts listed in Section 6.6.3.
3. Disconnect the SF6 piping at the crankcases using the quick-connect valves, Figure 6-7.
Figure 6-10: Disassembling of the Pole Column from the Base Frame
1 Nut
2 Washer
3 Bolt
4 Extra Thick Washer
! CAUTION
Avoid damaging the insulating rod during disassembly.
C
T106
L3
2
L3
6. Remove bolts (Figure 6-12, Item 7) and locking plates (Figure 6-12, Item 6).
7. Release handle C, Figure 6-11, and turn handle B, Figure 6-11, carefully downwards. During
this operation, the opening spring (Figure 6-12, Item 2) recharges completely.
8. Proceed in reverse sequence for reassembling the opening spring.
L1
1
L3 2 12
10 14
5 10
L2 9
9
8
13
L1 16
11
3
L3 15
14
12
4
L1 5
7
6
2. Remove the insert bearing (Figure 6-13, Item 16) and the outer ring of the cylindrical roller
bearing (Figure 6-13, Item 3)
3. Remove the torque shaft (Figure 6-13, Item 8) and the inner ring of the roller bearing.
! CAUTION
Do not damage the sealing surfaces during disassembly.
4. Lift the assembly consisting of insulating rod (Figure 6-14, Item 1), spring seat (Figure 6-14,
Item 3) and inner lever (Figure 6-14, Item 4) up out of the crankcase.
L3
L3 3
L3 4
IMPORTANT
The following instructions must be followed when assembling the parts:
• Follow the lubrication specifications for contact and joining surfaces and for static and dynamic
seals.
• Replace all seals and gaskets.
• Then, while reassembling the unit, do not forget the sleeve (Figure 6-13, Item 9).
• Do not install a new filter until right before evacuating the assembled pole column.
• The tightening torques are given in Attachment B.
5. Mount the interrupter chamber as specified in Section 6.6.4 and re-commission the switcher as
described in Chapter 5.
6.8 Troubleshooting
Before beginning any troubleshooting, disconnect the switcher from the high voltage system and
ground it in accordance with the applicable company safety regulations.
1 Body
2 Front Ferrule
3 Back Ferrule
4 Nut
quantity required and, if possible, the number of the purchase order on which the switcher was
originally furnished.
All spare parts should be stored in a clean, dry location and out of the sunlight for maximum life
expectancy.
Depending on the geographical location of the equipment, a Service Contract may be available from
AREVA. For more information, contact your local AREVA representative.
Special tools
22.07.2004 48.020.190E/2
© AREVA 2004 1/7
Special tools
FK 3-X motor-wound spring operating mechanism
Special tools
Type of
No. operating Article-No. Drawing Name, application
mechanism
FK3-06 48.123.298-01
FK3-1 48.123.298-01 Closing latch disabling device
FK3-1/131 48.123.298-01
FK3-2 48.119.298-01 The closing latch disabling
70.71 device prevents the closing
FK3-3 48.119.298-01 latch working while manual
FK3-4 48.123.298-01 operations are being
FK3-5 48.123.298-01 performed.
FK3-12 48.128.298-01
FK3-06 48.123.299-01
FK3-1 48.123.299-01
FK3-1/131 48.123.299-01
FK3-4 48.127.299-01
FK3-5 48.127.299-01
Slow-movement device
FK3-2 48.119.299-01
FK3-3 48.119.299-01 The slow-movement device is
70.72
used in the manual operations
of slow closing and slow
opening.
FK3-12 48.128.299-01
22.07.2004 48.020.190E/2
© AREVA 2004 2/7
Special tools
FK 3-X motor-wound spring operating mechanism
22.07.2004 48.020.190E/2
© AREVA 2004 3/7
Special tools
FK 3-X motor-wound spring operating mechanism
FK3-06 48.119.470-01
FK3-1 48.119.470-01
FK3-1/ 48.119.470-01
131
AIS
FK3-2 48.119.470-01
FK3-3 48.119.470-01
FK3-4 48.127.470-01 Hand crank
FK3-5 48.127.470-01
70.53 The hand crank is used in the
FK3-1 48.119.270-01 manual operation of charging
the closing spring..
FK3-1/ 48.119.270-01
131
GIS
FK3-2 48.119.270-01
FK3-3 48.119.270-01
FK3-4 48.127.470-02
FK3-5 48.127.470-02
FK3-06 8.094449
FK3-1 8.094449
FK3-1/131 8.094449
FK3-2 8.094480
FK3-3 8.094480
Counter-wrench
FK3-4 8.094516
FK3-5 8.094516 The counter-wrench is used to
71.03 immobilise the distance sleeve
so that the lock nut on the
spring socket can be loosened
or tightened.
FK3-12 8.094550
22.07.2004 48.020.190E/2
© AREVA 2004 4/7
Special tools
FK 3-X motor-wound spring operating mechanism
FK3-06 8.094448
FK3-1 8.094448 Extension socket
FK3-1/131 8.094448
71.19 FK3-2 8.094479 The extension socket, fitted on
conventional ratchet drives, is
FK3-3 8.094479
used to turn the adjusting nut in
FK3-4 8.094517 the spring socket.
FK3-5 8.094517
22.07.2004 48.020.190E/2
© AREVA 2004 5/7
Special tools
FK 3-X motor-wound spring operating mechanism
FK3-06 48.123.296-01
FK3-1 48.123.296-01
FK3-1/131 48.123.296-01
FK3-4 48.123.296-01
FK3-5 48.123.296-01
71.20
The disabling feature of
FK3-12 48.128.714-01
undervoltage release is
necessary to immobilise the
undervoltage release magnet..
FK3-2 48.119.812-01
FK3-3 48.119.812-01
22.07.2004 48.020.190E/2
© AREVA 2004 6/7
Special tools
FK 3-X motor-wound spring operating mechanism
22.07.2004 48.020.190E/2
© AREVA 2004 7/7
AREVA T&D Circuit Switchers Chapter 7 Rev. 0
Type GL309 Drawings & Test Reports
Chapter 7
Drawings & Test Reports
Revision History
Revision Record Description Revised by Date
TERMINAL BLOCK
DENSITY MONITOR
(AUXILIARY)
THERMAL
OVERLOAD
3 3
TOGGLE SWITCH
72.5kV, 1200A, 31.5kA, 48VDC STOCK CODE: 0451030 M. Marino D. Muetzel 10/20/06 AREVA T&D Inc.
One Power Lane
LEGEND ENG. REVIEW DATE Charleroi, PA 15022 DRAWING No.: GL09C0003 SHT 1 OF 11
A B C D
A B C D
CLOSE CIRCUIT TRIP 1 CIRCUIT
TB1 FA TB2 SPARE TRIP COIL
1 1 2 1 2 41 TB3
SA 16A B9
14S
B3 LIGHT FOR TRIP PB2
CN
AND CLOSED IND. 52T1
CUSTOMER CLOSE
14P
CIRCUIT 2 TB1
9R 1
ME
TB1 TB1 TB3 52TC2
5 7R 51
17 15 2
TB3 ER1
1 B11 43M MA2
SET RECLOSER PB1 5
AT NO LESS 52C 52-2
16 a
THAN 20 CYC.
6
2 TB1
1 9
DT MA2
13 11 49 8 52-2
ER1 TB3 a
6S
16-20A
CN
43M B12
7
13S
15P
2
6P
OPTIONAL CUST
CN
12 3 DT
LOCKOUT
CN
49 3W
13P
AT2
15S
FIELD REMOVABLE
TB1 16-20A
3D
7
7
2 JUMPER
4 3NO 3NC a B10
2
10S
8 52-1
TB1 EGA TB3
MA1
CN
8 CN 63G
1S 1P
10P
74 psig 6
1 MB 3C a
88LS 52-1
8S
31 ES 4D 5
CN
52Y
a
AT2 MA1
48VDC 2
8P
4W
32
13 ES 1 MA1 T1 1. ALL DEVICES SHOWN IN DE-ENERGIZED POSITION
7P
52-1 DM
52Y 2. BREAKER IN OPEN POSITION
CN
a 88 2
21 EA MA1 3. SF6 GAS SYSTEM SHOWN AT ZERO PRESSURE
7S
14 2 13
63TX1 52TC1
52-1 4. (MAINTENANCE/NORMAL) SWITCH (43M) SHOWN IN NORMAL POSITION
22 b T2 MD 1 5. CLOSING SPRING SHOWN IN CHARGED POSITION
CN 14 MB
12P
2S 2P 3 A1 6. SPRING OPENED AND SPRING CLOSED MAIN CONTACTS
3S
88LS EA
CN
CN
a 63TX1
9P
4
3P
12S
11P
CUSTOMER USE ONLY
CN
1 A2
MC
CN
9S
52CC
11S
TB1
5.6 OHM 5 13
2 DT
3 9 MA1
52-1
37 35
ER1
49
16-20A 3
b 43M
10 6 32
A1 ES
52Y 36 63TX1
9 MB 31 EA
88LS A2
b
10
4P
CN
4S
TB1
TB1 3 4 3 4 14 TB1
2 SA FA TB3 10
16A
TB1 B6
6
7 ADDED CUSTOMER INFORMATION W. Holt D. Muetzel 01/29/07 CUSTOMER: SALT RIVER PROJECT AREVA JOB #
6 CORRECTED PRESSURE SWITCH NUMBER W. Holt D. Muetzel 01/22/07 CUSTOMER ORDER No.: SRP-0000208655, SRP-0000217237 J12079, J12381, J12382, J12383,
5 REVISED RATINGS NAMEPLATE W. Holt D. Muetzel 01/18/07 SUBSTATION:
4 CHANGED TO 24 POINT GROUND BAR W. Holt D. Muetzel 01/16/07 J12384, J12385, J12386, J12387,
SERIAL No.: 12079A-GL09, 12079B-GL09, 12079C-GL09, 12381A-GL09. 12381B-GL09
4 3
2
CORRECTED CONNECTION OF MA1-13,14
CHANGED ALL WIRE FROM SIS VW1 TO TEFZEL
D. Muetzel
W. Holt
D. Muetzel
D. Muetzel
01/07/06
12/08/06
12382A-GL09, 12382B-GL09, 12383A-GL09, 12383B-GL09, 12384-GL09
12385-GL09, 12386-GL09, 12387-GL09, 12388-GL09, 12389-GL09
J12388, 12389
AREVA ORDER #
4
REV. DESCRIPTION ENG. REVIEW DATE BREAKER TYPE: 72.5kV, 1200A, LT CIRCUIT SWITCHER CX03714, CX03841
72.5kV, 1200A, 31.5kA, 48VDC STOCK CODE: 0451030 M. Marino D. Muetzel 10/20/06 AREVA T&D Inc.
One Power Lane
CONTROL WIRING SCHEMATIC ENG. REVIEW DATE Charleroi, PA 15022 DRAWING No.: GL09C0003 SHT 2 OF 11
A B C D
A B C D
ER1
Contacts
Switch Position
43M
SPARE TERMINAL BLOCKS
Deck Front End Normal Maint. NORMAL
FOR CUSTOMER USE SPARE AUXILIARY SWITCHES FOR CUSTOMER USE
11
X MAINTENANCE
12
TB2 TB3 TB3
X TB7
1 1
13
1 15
X
B5 52 B13 B18 TB5 TB4 TB4 TB4 TB5 TB5 TB5
16 71 59 61 63 65 67 69
17
X
TB3 TB3 TB7 TB7 TB7 TB7
22S
X
40S
44S
36S
32S
20S
28S
21
B14 B15 108 109 B16 B17
CN
22
X
CN
CN
CN
CN
CN
CN
23
22P
X MA2 11 MA1
40P
44P
36P
32P
20P
28P
25
15 1 MA2 11 MA2 13 MA2
26
27
X TB7 52-2 52-1 52-2 52-2 52-2 1 MA3 9 MA3 MA3 11 MA3 MA3 MA3 MA3
B19 b b 52-3 52-3 3 52-3 13 5 15
a b b 52-3 52-3 52-3 52-3
32
31
X 16 12 2 12 14 a b a b b a b
33
X 2 10 4 12 14 6 16
3 X
45P
37P
33P
21P
29P
35
41P
23P
36
37
X
CN
CN
CN
CN
CN
CN
CN
45S
37S
33S
21S
29S
41S
23S
MAINTAINED CONTACTS
30S
2 2
48S
34S
16S
43M
42S
52S
50S
CN
46S
38S
CN
CN
CN
CN
CN
CN
CN
CN
22
30P
48P
34P
TB2 TB2 TB4
16P
42P
52P
50P
TB3 MA4
46P
38P
B4 23 53 9 7 MA3 11 MA4
TB7 TB7 B7 52-4 52-3 52-4 1 MA4 13 MA4 3 MA4 15 MA4 MA4 MA4
104 106 TB2 TB4 TB4 b 52-4 52-4 52-4 52-4 5 7
B2 55 57 a b 52-4 52-4
10
58S
8 12 a b a b a a
60S
2 14 4 16
49P
54S
56S
31P
6 8
CN
35P
CN
17P
CN
CN
47P
39P
18S
CN
CN
43P
53P
51P
58P
CN
60P
CN
CN
CN
49S
54P
56P
31S
5W
CN
CN
CN
CN
AT2
35S
24S
17S
1W
26S
47S
39S
18P
MB MB AT2
43S
53S
51S
13 5 5D 3 MA1
CN
EA
CN
88LS 88LS 4NO 4NC 1D 13 74 76 78
b a 63TX1 52-1
24P
2NO 2NC TB5 TB5 TB6 80 82 84 86 88 92
26P
14 6 EGA a 33 31
63G EGA 14 4 ER1 9 MA2 3 MA2 TB6 TB6 TB6 TB6 TB6 TB7
52-2 52-2
19P
74 psig 63G 43M
55P
57P
4C 78 psig b a
10 4
CN
CN
2C 32
AT2 2D AT2
19S
25P
27P
55S
57S
6W 2W
59P
CN
CN
61P
105 107
25S
27S
CN
3 3
CN
TB7 TB7
59S
61S
72.5kV, 1200A, 31.5kA, 48VDC STOCK CODE: 0451030 M. Marino D. Muetzel 10/20/06 AREVA T&D Inc.
One Power Lane
CONTROL WIRING SCHEMATIC ENG. REVIEW DATE Charleroi, PA 15022 DRAWING No.: GL09C0003 SHT 3 OF 11
A B C D
A B C D
1 1
HEATER CIRCUIT
TB2 1 2
35 FE
62S
16A 1
TH1
CN
62P
110 DEG F
1W 2
AT3
1D 7D
AT2
1 H2 1W EGA 7W
240 VAC HT1 G
64P
60Hz 63G
1D
95 W
CN
1 H1
2 2
2 600 OHM
64S
95 W
2D 600 OHM
AT3 2
GND
2W 2D
HT1
63S 63P
2W
CN
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
TB2 3 4
36
FE
16A
3 3
7 ADDED CUSTOMER INFORMATION W. Holt D. Muetzel 01/29/07 CUSTOMER: SALT RIVER PROJECT AREVA JOB #
6 CORRECTED PRESSURE SWITCH NUMBER W. Holt D. Muetzel 01/22/07 CUSTOMER ORDER No.: SRP-0000208655, SRP-0000217237 J12079, J12381, J12382, J12383,
5 REVISED RATINGS NAMEPLATE W. Holt D. Muetzel 01/18/07 SUBSTATION:
4 CHANGED TO 24 POINT GROUND BAR W. Holt D. Muetzel 01/16/07 J12384, J12385, J12386, J12387,
SERIAL No.: 12079A-GL09, 12079B-GL09, 12079C-GL09, 12381A-GL09. 12381B-GL09
4 3
2
CORRECTED CONNECTION OF MA1-13,14
CHANGED ALL WIRE FROM SIS VW1 TO TEFZEL
D. Muetzel
W. Holt
D. Muetzel
D. Muetzel
01/07/06
12/08/06
12382A-GL09, 12382B-GL09, 12383A-GL09, 12383B-GL09, 12384-GL09
12385-GL09, 12386-GL09, 12387-GL09, 12388-GL09, 12389-GL09
J12388, 12389
AREVA ORDER #
4
REV. DESCRIPTION ENG. REVIEW DATE BREAKER TYPE: 72.5kV, 1200A, LT CIRCUIT SWITCHER CX03714, CX03841
72.5kV, 1200A, 31.5kA, 48VDC STOCK CODE: 0451030 M. Marino D. Muetzel 10/20/06 AREVA T&D Inc.
One Power Lane
CONTROL WIRING SCHEMATIC ENG. REVIEW DATE Charleroi, PA 15022 DRAWING No.: GL09C0003 SHT 4 OF 11
A B C D
A B C D
TERMINAL BLOCK WIRING
1 1
1 3
5 1
9
2 2
26S TB4:57 26P MA2:3 TB4:53 23 TB2:B4,EA:13 CN:36S 67
27S TB4:58 27P MA2:4
3
2 7
6
13 14 15 16 17 18 19 20 21 22 23 24
30S TB5:73 30P MA4:9 B2 ER1:33 CN:33S 70
31S TB5:74 31P MA4:10 2 CN:64S
2
B 0
7
WIRING NOTES:
34S TB6:77 34P MA4:11 35 FE:1 CN:30S 73
35S TB6:78 35P MA4:12
5
3 3
7
40S TB4:61 40P MA3:3 SHOW OPPOSITE END SAME END DESIGNATION.
41S TB4:62 41P MA3:4 5) ALL WIRE LUGS TO BE UNINSULATED RING-TYPE (EXCEPT
42S TB6:83 42P MA4:3 FOR DEVICES THAT DO NOT ACCEPT RING-TYPE TERMINALS).
43S TB6:84 43P MA4:4 TB3 TB6
44S TB4:63 44P MA3:11 51 CN:8S CN:34S 77
45S TB4:64 45P MA3:12
1
5 7
3 50S
51S
TB7:91
TB7:92
50P
51P
MA4:7
MA4:8
B8
B9
8
B
9
B
CN:59S
CN:14S
CN:52S
CN:53S
81
1
8
82
2
8
3
52S TB6:81 52P MA4:13 B10 CN:15S CN:42S 83
53S TB6:82 53P MA4:14
B1
0 3
8
7 ADDED CUSTOMER INFORMATION W. Holt D. Muetzel 01/29/07 CUSTOMER: SALT RIVER PROJECT AREVA JOB #
6 CORRECTED PRESSURE SWITCH NUMBER W. Holt D. Muetzel 01/22/07 CUSTOMER ORDER No.: SRP-0000208655, SRP-0000217237 J12079, J12381, J12382, J12383,
5 REVISED RATINGS NAMEPLATE W. Holt D. Muetzel 01/18/07 SUBSTATION:
4 CHANGED TO 24 POINT GROUND BAR W. Holt D. Muetzel 01/16/07 J12384, J12385, J12386, J12387,
SERIAL No.: 12079A-GL09, 12079B-GL09, 12079C-GL09, 12381A-GL09. 12381B-GL09
4 3
2
CORRECTED CONNECTION OF MA1-13,14
CHANGED ALL WIRE FROM SIS VW1 TO TEFZEL
D. Muetzel
W. Holt
D. Muetzel
D. Muetzel
01/07/06
12/08/06
12382A-GL09, 12382B-GL09, 12383A-GL09, 12383B-GL09, 12384-GL09
12385-GL09, 12386-GL09, 12387-GL09, 12388-GL09, 12389-GL09
J12388, 12389
AREVA ORDER #
4
REV. DESCRIPTION ENG. REVIEW DATE BREAKER TYPE: 72.5kV, 1200A, LT CIRCUIT SWITCHER CX03714, CX03841
72.5kV, 1200A, 31.5kA, 48VDC STOCK CODE: 0451030 M. Marino D. Muetzel 10/20/06 AREVA T&D Inc.
One Power Lane
WIRING DIAGRAM ENG. REVIEW DATE Charleroi, PA 15022 DRAWING No.: GL09C0003 SHT 5 OF 11
A B C D
A B C D
LINKAGE COVER
EGA 63G WIRING DIAGRAM MECHANISM ENCLOSURE AND LINKAGE COVER
1NO 1NC 2NO 2NC 3NO 3NC 4NO 4NC 2C AT2:2D
2NC AT2:1D
3C AT2:4D MB 88LS
3NC AT2:3D 1 CN:10P 13 CN:54P MECHANISM
1 1C 2C 3C 4C
4C
4NC
AT2:6D
AT2:5D
1 3 5 7 9 11 13 15 2
3
DM:T1
DM:T2
14 CN:55P
1
78 psig 74 psig G AT2:7D 4 CN:11P ME 52TC2 MD 52TC1
a a a a b b b b 5 CN:56P 1 CN:14P 1 CN:12P
2 4 6 8 10 12 14 16 6 CN:57P 1 2 MA2:5 1 2 MA1:5
9 MA1:10
10 CN:4P
DM 88
T1 MB:2 2 2
T1
T2 MB:3 COIL VOLTAGE - 48 VDC COIL VOLTAGE - 48 VDC
COIL RESISTANCE - 5.6 OHM COIL RESISTANCE - 5.6 OHM
T2
2 2
3 CN:18P 13 CN:8P 5 ME:2
4 CN:19P 14 CN:9P 6 MA2:8
a a a a b b b b 5 MD:2 a a a a b b b b 7 CN:15P
2 4 6 8 10 12 14 16 6 MA1:8 2 4 6 8 10 12 14 16 8 MA2:6
7 CN:13P 9 CN:24P
8 MA1:6 10 CN:25P
MA3 52-3 MA4 52-4
1 CN:22P 9 CN:20P 1 CN:46P 9 CN:30P
1 3 5 7 9 11 13 15 2 CN:23P 10 CN:21P 1 3 5 7 9 11 13 15 2 CN:47P 10 CN:31P
3 CN:40P 11 CN:44P 3 CN:42P 11 CN:34P
4 CN:41P 12 CN:45P 4 CN:43P 12 CN:35P
a a a a b b b b 5 CN:36P 13 CN:28P a a a a b b b b 5 CN:38P 13 CN:52P
2 4 6 8 10 12 14 16 6 CN:37P 14 CN:29P 2 4 6 8 10 12 14 16 6 CN:39P 14 CN:53P
7 CN:48P 15 CN:32P 7 CN:50P 15 CN:16P
8 CN:49P 16 CN:33P 8 CN:51P 16 CN:17P
AT2
EGA:2NC 1D 1W CN:60P MC 52CC
EGA:2C 2D 2W CN:61P 1 CN:3P
1 2 MA1:9 CUSTOMER USE ONLY
EGA:3NC 3D 3W CN:6P
EGA:3C 4D 4W CN:7P
EGA:4NC 5D 5W CN:58P
3 EGA:4C 6D
EGA:G 7D
6W CN:59P
7W CN:64P
2
7 ADDED CUSTOMER INFORMATION W. Holt D. Muetzel 01/29/07 CUSTOMER: SALT RIVER PROJECT AREVA JOB #
6 CORRECTED PRESSURE SWITCH NUMBER W. Holt D. Muetzel 01/22/07 CUSTOMER ORDER No.: SRP-0000208655, SRP-0000217237 J12079, J12381, J12382, J12383,
5 REVISED RATINGS NAMEPLATE W. Holt D. Muetzel 01/18/07 SUBSTATION:
4 CHANGED TO 24 POINT GROUND BAR W. Holt D. Muetzel 01/16/07 J12384, J12385, J12386, J12387,
SERIAL No.: 12079A-GL09, 12079B-GL09, 12079C-GL09, 12381A-GL09. 12381B-GL09
4 3
2
CORRECTED CONNECTION OF MA1-13,14
CHANGED ALL WIRE FROM SIS VW1 TO TEFZEL
D. Muetzel
W. Holt
D. Muetzel
D. Muetzel
01/07/06
12/08/06
12382A-GL09, 12382B-GL09, 12383A-GL09, 12383B-GL09, 12384-GL09
12385-GL09, 12386-GL09, 12387-GL09, 12388-GL09, 12389-GL09
J12388, 12389
AREVA ORDER #
4
REV. DESCRIPTION ENG. REVIEW DATE BREAKER TYPE: 72.5kV, 1200A, LT CIRCUIT SWITCHER CX03714, CX03841
72.5kV, 1200A, 31.5kA, 48VDC STOCK CODE: 0451030 M. Marino D. Muetzel 10/20/06 AREVA T&D Inc.
One Power Lane
WIRING DIAGRAM ENG. REVIEW DATE Charleroi, PA 15022 DRAWING No.: GL09C0003 SHT 6 OF 11
A B C D
A B C D
WIRING DIAGRAM RELAY PANEL
RELAY PANEL
1 TH1 SA FA FE 1
1 1 FE:2 1 3 1 TB1:1 1 3 1 SA:2 1 3 1 TB2:35
2 HT1:1W 2 TB3:B11,FA:1 2 TB2:B3,DT:1 2 CN:62S,TH1:1
3 TB1:2 3 SA:4 3 TB2:36
4 FA:3,EA:A2 4 CN:4S,TB1:6 4 CN:63S,HT1:2W
2 2 4 2 4 2 4
TEMP SETTING - 110 DEG F AMP RATING - 16A AMP RATING - 16A
ER1 43M
SWITCH POSITION 11 TB1:7R
CONTACTS
DECK FRONT END 12 TB1:7
NORMAL MAINT. 13 PB1:2
12
11 X 15 TB1:9R
16 TB1:9
1
13 X 17 PB2:2
16
15 X 21 TB2:21
17 X 22 TB2:B4
31 TB4:55
22
21 X 32 TB2:B1
DT EA ES
23 X 33 TB2:B2
49
1 FA:2
63TX1 52Y 2 25 X 35 CN:9S
1 3 5 13 21 A1 CN:7S A1 ES:14 26
2 2
2 DT:3 13 43 21 31 A1 A2 13 43 21 31 A1 A2 36 TB3:B6,ES:A2
3 DT:2
TB1:14,SA:4 TB1:6,ER1:36 27 X
13 TB2:23 13 CN:1S,ES:31
4 CN:10S 14 TB2:24 14 CN:2S,ES:A1 32
31 X
5 CN:11S 21 ES:32 31 ES:13,TB1:8 33 X
6 TB3:B6 22 CN:3S 32 EA:21 3 35 X
2 4 6 14 22 14 44 22 32 A2 14 44 22 32 A2 36
31 TB1:14
AMP RATING - 16-20A 32 TB1:13 COIL VOLTAGE - 48VDC
37 X
53 83 61 71
COIL RESISTANCE - 852 ohm
54 84 62 72
PB1 52C
1 1 TB1:5
2 ER1:13 CUSTOMER USE ONLY
H1
1 1 HT1:1D
2 HT1:2D
3 2
COLOR - RED
3
2
WATTAGE - 95 W
PB2 52T1 RESISTANCE - 600 OHM
1 1 TB3:B11,TB2:41 HT1
WIRING NOTES: 2 ER1:17
H1:1 1D 1W TH1:2
1) AC WIRES ARE TO BE GRAY 12GA TEFZEL H1:2 2D 2W FE:4
2) AC GROUND WIRES TO BE GREEN 12GA TEFZEL 3D 3W
3) DC WIRES TO BE GRAY 14GA TEFZEL
2 4D 4W
4) WIRE MARKERS TO BE SHRINK-TYPE AND
COLOR - BLK 5D 5W
SHOW OPPOSITE END SAME END DESIGNATION.
6D 6W
5) ALL WIRE LUGS TO BE UNINSULATED RING-TYPE (EXCEPT
FOR DEVICES THAT DO NOT ACCEPT RING-TYPE TERMINALS).
7 ADDED CUSTOMER INFORMATION W. Holt D. Muetzel 01/29/07 CUSTOMER: SALT RIVER PROJECT AREVA JOB #
6 CORRECTED PRESSURE SWITCH NUMBER W. Holt D. Muetzel 01/22/07 CUSTOMER ORDER No.: SRP-0000208655, SRP-0000217237 J12079, J12381, J12382, J12383,
5 REVISED RATINGS NAMEPLATE W. Holt D. Muetzel 01/18/07 SUBSTATION:
4 CHANGED TO 24 POINT GROUND BAR W. Holt D. Muetzel 01/16/07 J12384, J12385, J12386, J12387,
SERIAL No.: 12079A-GL09, 12079B-GL09, 12079C-GL09, 12381A-GL09. 12381B-GL09
4 3
2
CORRECTED CONNECTION OF MA1-13,14
CHANGED ALL WIRE FROM SIS VW1 TO TEFZEL
D. Muetzel
W. Holt
D. Muetzel
D. Muetzel
01/07/06
12/08/06
12382A-GL09, 12382B-GL09, 12383A-GL09, 12383B-GL09, 12384-GL09
12385-GL09, 12386-GL09, 12387-GL09, 12388-GL09, 12389-GL09
J12388, 12389
AREVA ORDER #
4
REV. DESCRIPTION ENG. REVIEW DATE BREAKER TYPE: 72.5kV, 1200A, LT CIRCUIT SWITCHER CX03714, CX03841
72.5kV, 1200A, 31.5kA, 48VDC STOCK CODE: 0451030 M. Marino D. Muetzel 10/20/06 AREVA T&D Inc.
One Power Lane
WIRING DIAGRAM ENG. REVIEW DATE Charleroi, PA 15022 DRAWING No.: GL09C0003 SHT 7 OF 11
A B C D
A B C D
MECHANISM - FRONT SIDE
MOUNTED UNDER
LINKAGE COVER
MB ME MD
88LS 52TC2 52TC1
1 0 0 0 0 0 0 0
MA1 MA2
PG
1
63G
52-1 52-2
EGA
DM
88
CN
AT2 MC 52-3 52-4
52CC
MA3 MA4
NOTE:
- TAGS TO BE ATTACHED USING S.S. SCREWS
- ALL CONTROL TERMINAL BLOCKS USE SLOTTED TYPE SCREWS
(DO NOT USE COMBINATION OR PHILIPS SCREWS)
AT3
- ALL AUXILIARY TERMINAL BLOCKS USE STAINLESS STEEL 1/4" #6-32
SLOTTED SCREWS (REMOVE AND DISCARD COMBINATION SCREWS)
- INSTALL DUST FILTERS ON CABINET WEEP HOLES
- FLOOR ACCESS PANEL TO BE MOUNTED TO INSIDE OF CABINET
- DISABLE MANUAL TRIPPING ON MECHANISM
H2
CONNECTION HARNESS
RELAY PANEL - FRONT SIDE
TERMINAL BLOCK PANEL - BACK SIDE
2 2
MFG. WIREWAY 1x3
TH1 SA TB1 TB4 TB7
FA FE
H1
PB1
52C
3 PB2
52T1
3
HT1
GND
7 ADDED CUSTOMER INFORMATION W. Holt D. Muetzel 01/29/07 CUSTOMER: SALT RIVER PROJECT AREVA JOB #
6 CORRECTED PRESSURE SWITCH NUMBER W. Holt D. Muetzel 01/22/07 CUSTOMER ORDER No.: SRP-0000208655, SRP-0000217237 J12079, J12381, J12382, J12383,
5 REVISED RATINGS NAMEPLATE W. Holt D. Muetzel 01/18/07 SUBSTATION:
4 CHANGED TO 24 POINT GROUND BAR W. Holt D. Muetzel 01/16/07 J12384, J12385, J12386, J12387,
SERIAL No.: 12079A-GL09, 12079B-GL09, 12079C-GL09, 12381A-GL09. 12381B-GL09
4 3
2
CORRECTED CONNECTION OF MA1-13,14
CHANGED ALL WIRE FROM SIS VW1 TO TEFZEL
D. Muetzel
W. Holt
D. Muetzel
D. Muetzel
01/07/06
12/08/06
12382A-GL09, 12382B-GL09, 12383A-GL09, 12383B-GL09, 12384-GL09
12385-GL09, 12386-GL09, 12387-GL09, 12388-GL09, 12389-GL09
J12388, 12389
AREVA ORDER #
4
REV. DESCRIPTION ENG. REVIEW DATE BREAKER TYPE: 72.5kV, 1200A, LT CIRCUIT SWITCHER CX03714, CX03841
72.5kV, 1200A, 31.5kA, 48VDC STOCK CODE: 0451030 M. Marino D. Muetzel 10/20/06 AREVA T&D Inc.
One Power Lane
COMPONENT LAYOUT ENG. REVIEW DATE Charleroi, PA 15022 DRAWING No.: GL09C0003 SHT 8 OF 11
A B C D
A B C D
ITEM QTY AREVA # MFR # MFR DESCRIPTION DEVICE ID
001 001 1_004_529 1-004-529 AREVA AUX CONTACT DT
002 003 1_410_504_P5 MAR1512STD73796 MARATHON TERMINAL BLOCK 12PT TB3, TB6, TB7
003 004 1_410_504_P5 MAR1512STD73796 MARATHON TERMINAL BLOCK 12PT TB1, TB2, TB4, TB5
004 001 1_410_629_P61 24203B ELECTROSWITCH CONTROL SWITCH, NORM/MAINT 3 STAGE ER1
005 001 1_410_634_P7 STO-110 STANCOR THERMOSTAT 110F TH1
1 006
007
001
002
1_410_635_P9
1_410_641_P73
202-AW
CLIPFIX35-5
STATES
PHOENIX
KNIFE SWITCH 2 POLE
END CLAMP
SA
END2, END3
1
008 001 1_410_749_P100 CS4C-22Z-48D SPRECHER + SCHUH CONTROL RELAY 2NO 2NC (48 VDC) ES
009 001 1_410_749_P100 CS4C-22Z-48D SPRECHER + SCHUH CONTROL RELAY 4NO 4NC (48 VDC) EA
010 001 1_410_749_P108 CS4-P22 SPRECHER + SCHUH AUXILIARY CONTACT EA
011 001 1_413_166_G5 1-413-166-g5 C3CONTROLS PUSHBUTTON, BLK, 1NO PB2
012 001 1_413_166_G6 1-413-166-g6 C3CONTROLS PUSHBUTTON, RED, 1NO PB1
013 002 1_413_167_P2 ME82SD16 AEG MINATURE CIRCUIT BREAKER, 2 POLE 16A FA, FE
014 001 1_413_167_P8 MBS 25 AEG THERMAL OVERLOAD 16-20A DT
015 001 1_413_461_P1 1-413-461-P1 AREVA CONTROL SWITCH BRACKET - 6.5" 7
016 002 1_413_999_G1 17000_0, PCN 265480 CHROMALOX ANTICONDENSATION HEATER ASSY 240VAC H1, H2
017 001 1_415_866 1-415-866 AREVA PUSH BUTTON / IND LITE BRACKET 6
018 001 1_415_884 1-415-884 AREVA S1-145 DROP BOX PANEL 4
019 001 1_417_294_G10 1-417-294-G10 AREVA SPRING CHARGE MOTOR FOR FK3-1/131 DM
020 001 1_417_375_P6 2TC/800 SOLON PRESSURE SWITCH (93,78,74) SOLON EGA
021 001 2_990_226_G2 2-990-226-G2 AREVA CONNECTOR PANEL ASSY - RIGID CONDUIT CN
022 001 1_410_748_P1 TB206 BUSSMAN AUX. TERMINAL BLOCK, 6 PT HT1
023 002 1_410_748_P3 TB207 BUSSMAN AUX. TERMINAL BLOCK, 7 PT AT2, AT3
2 024
025
003
004
49.102.110-16
49.105.100-01
49.102.110-16
49.105.100-01
AREVA
AREVA
COIL (48 VDC)
AUXILIARY SWITCH
MC, MD, ME
MA1, MA2, MA3, MA4 2
026 001 49.105.100-01 49.105.100-01 AREVA AUXILIARY SWITCH MB
027 001 FK3-1 AREVA FK3-1 MECHANISM PAN2
028 001 1_415_885 1-415-885 AREVA GL PANEL ASSY - W-DROP BOX 4
029 001 GROUND_BAR AREVA GROUND BAR, 24PT GND
030 001 351009SW 02BXLLOSSG ASHCROFT PRESSURE GAUGE, 0-150 PSI, 3.5 INCH, STAINLESS PG
031 001 1_417_418_G7 1-417-418-G7 WALTHER CONNECTOR, 64 PIN (64 COND) CN
3 3
7 ADDED CUSTOMER INFORMATION W. Holt D. Muetzel 01/29/07 CUSTOMER: SALT RIVER PROJECT AREVA JOB #
6 CORRECTED PRESSURE SWITCH NUMBER W. Holt D. Muetzel 01/22/07 CUSTOMER ORDER No.: SRP-0000208655, SRP-0000217237 J12079, J12381, J12382, J12383,
5 REVISED RATINGS NAMEPLATE W. Holt D. Muetzel 01/18/07 SUBSTATION:
4 CHANGED TO 24 POINT GROUND BAR W. Holt D. Muetzel 01/16/07 J12384, J12385, J12386, J12387,
SERIAL No.: 12079A-GL09, 12079B-GL09, 12079C-GL09, 12381A-GL09. 12381B-GL09
4 3
2
CORRECTED CONNECTION OF MA1-13,14
CHANGED ALL WIRE FROM SIS VW1 TO TEFZEL
D. Muetzel
W. Holt
D. Muetzel
D. Muetzel
01/07/06
12/08/06
12382A-GL09, 12382B-GL09, 12383A-GL09, 12383B-GL09, 12384-GL09
12385-GL09, 12386-GL09, 12387-GL09, 12388-GL09, 12389-GL09
J12388, 12389
AREVA ORDER #
4
REV. DESCRIPTION ENG. REVIEW DATE BREAKER TYPE: 72.5kV, 1200A, LT CIRCUIT SWITCHER CX03714, CX03841
72.5kV, 1200A, 31.5kA, 48VDC STOCK CODE: 0451030 M. Marino D. Muetzel 10/20/06 AREVA T&D Inc.
One Power Lane
BILL OF MATERIALS ENG. REVIEW DATE Charleroi, PA 15022 DRAWING No.: GL09C0003 SHT 9 OF 11
A B C D
A B C D
TB1 TB2 TB3 TB4 TB5 TB6 TB7 AT2 AT3 CN DM DT
1 21 51 53 65 77 91
TYPE GL309 CUSTOMER P.O. XXXXXXXXX
SERIAL NUMBER XXXX-GL09 ORDER NUMBER CX0XXXX 88 49
1 INSTRUCTION BOOK No. GL09-IM
EA ES HT1
1
PARTS LIST No. GL09A0003 2 22 52 54 66 78 92 H1 H2
MANUFACTURE DATE
* WIRING DIAGRAM GL09C0003
RATED MAXIMUM VOLTAGE RATED INTERRUPTING TIME SF6 PRESSURE (@ 20°C / 68°F) 63TX1 52Y 95 W 95 W
72.5 kV RELATIVE PRESSURE 5 23 B6 55 67 79 104
3.0 CYCLES MA1 MA2 MA3 MC MD
RATED VOLTAGE RANGE FACTOR (K) RATED SHORT CIRCUIT CURRENT -NORMAL OPERATING PRESSURE
93 psig
1.0 -TERMINAL FAULT 31.5 kA 52-1 52-2 52-3 52CC 52TC1
-LOW PRESSURE ALARM
RATED FREQUENCY
78 psig 6 24 B7 56 68 80 105
-90% SLF WITH 0 nF L_g CAPACITANCE
60 Hz (WITHIN 100m) 31.5 kA -MINIMUM PRESSURE
ME PB1 PB2 SA ER1
DUTY CYCLE 74 psig
-ISOLATED BANK 630 A % DC COMPONENT SPRING 8 41 B10 59 71 83 108 2) TAG DIMENSIONS AS SHOWN ON AREVA FABRICATION DRAWING 1_417_376_P1
14 B5 B15 64 76 88 B19
P4 P4 P4 P4 P4 P4 P4
NOTES:
1) TERMINAL MARKER STRIPS ARE WHITE TEXT ON A BLACK BACKGROUND
2) TAG DIMENSIONS AS SHOWN ON AREVA FABRICATION DRAWING 1_417_376_P...(SEE P#s FOR EACH TAG)
7 ADDED CUSTOMER INFORMATION W. Holt D. Muetzel 01/29/07 CUSTOMER: SALT RIVER PROJECT AREVA JOB #
6 CORRECTED PRESSURE SWITCH NUMBER W. Holt D. Muetzel 01/22/07 CUSTOMER ORDER No.: SRP-0000208655, SRP-0000217237 J12079, J12381, J12382, J12383,
5 REVISED RATINGS NAMEPLATE W. Holt D. Muetzel 01/18/07 SUBSTATION:
4 CHANGED TO 24 POINT GROUND BAR W. Holt D. Muetzel 01/16/07 J12384, J12385, J12386, J12387,
SERIAL No.: 12079A-GL09, 12079B-GL09, 12079C-GL09, 12381A-GL09. 12381B-GL09
4 3
2
CORRECTED CONNECTION OF MA1-13,14
CHANGED ALL WIRE FROM SIS VW1 TO TEFZEL
D. Muetzel
W. Holt
D. Muetzel
D. Muetzel
01/07/06
12/08/06
12382A-GL09, 12382B-GL09, 12383A-GL09, 12383B-GL09, 12384-GL09
12385-GL09, 12386-GL09, 12387-GL09, 12388-GL09, 12389-GL09
J12388, 12389
AREVA ORDER #
4
REV. DESCRIPTION ENG. REVIEW DATE BREAKER TYPE: 72.5kV, 1200A, LT CIRCUIT SWITCHER CX03714, CX03841
72.5kV, 1200A, 31.5kA, 48VDC STOCK CODE: 0451030 M. Marino D. Muetzel 10/20/06 AREVA T&D Inc.
One Power Lane
NAMEPLATE - DEVICE TAGS ENG. REVIEW DATE Charleroi, PA 15022 DRAWING No.: GL09C0003 SHT 10 OF 11
A B C D
A B C D
POLE A POLE B POLE C
93 psig - NORMAL
78 psig - ALARM
Density in kg/m 3
NORMAL
116 3) POLE ISOLATION VALVES USED TO
ISOLATE TANK FROM GAS PIPING.
101.5 4) 3-WAY VALVE TO BE USED TO
ISOLATE PRESSURE SWITCH FOR TESTING.
ALARM 5) PRESSURE SWITCH EXTERNAL WIRING
87 LOCK OUT TO BE WRAPPED IN FOIL TAPE
72.5 30
1/4" NPT
58
2 43.5 20 2
29 37 DEG FLARE
FEMALE 3 WAY BALL TEST VALVE
14.5 10
FILL VALVE
FILL HOSE
Temperature in Celsius
Temperature in Fahrenheit 4.0 7.75 3.5
CUSTOMER USE ONLY
6.0
RATINGS NAMEPLATE NOTES:
HINGE SIDE
INSTRUCTION
BOOK HOLDER
NAMEPLATE LOCATION
7 ADDED CUSTOMER INFORMATION W. Holt D. Muetzel 01/29/07 CUSTOMER: SALT RIVER PROJECT AREVA JOB #
6 CORRECTED PRESSURE SWITCH NUMBER W. Holt D. Muetzel 01/22/07 CUSTOMER ORDER No.: SRP-0000208655, SRP-0000217237 J12079, J12381, J12382, J12383,
5 REVISED RATINGS NAMEPLATE W. Holt D. Muetzel 01/18/07 SUBSTATION:
4 CHANGED TO 24 POINT GROUND BAR W. Holt D. Muetzel 01/16/07 J12384, J12385, J12386, J12387,
SERIAL No.: 12079A-GL09, 12079B-GL09, 12079C-GL09, 12381A-GL09. 12381B-GL09
4 3
2
CORRECTED CONNECTION OF MA1-13,14
CHANGED ALL WIRE FROM SIS VW1 TO TEFZEL
D. Muetzel
W. Holt
D. Muetzel
D. Muetzel
01/07/06
12/08/06
12382A-GL09, 12382B-GL09, 12383A-GL09, 12383B-GL09, 12384-GL09
12385-GL09, 12386-GL09, 12387-GL09, 12388-GL09, 12389-GL09
J12388, 12389
AREVA ORDER #
4
REV. DESCRIPTION ENG. REVIEW DATE BREAKER TYPE: 72.5kV, 1200A, LT CIRCUIT SWITCHER CX03714, CX03841
72.5kV, 1200A, 31.5kA, 48VDC STOCK CODE: 0451030 M. Marino D. Muetzel 10/20/06 AREVA T&D Inc.
One Power Lane
DEVICE TAGS - SF6 GAS SCHEMATIC ENG. REVIEW DATE Charleroi, PA 15022 DRAWING No.: GL09C0003 SHT 11 OF 11
A B C D
UNCONTROLLED COPY
UNCONTROLLED COPY
AREVA T&D Circuit Switchers Chapter 8 Rev. 1
Type GL309 Additional Operating Mechanism Instructions
Chapter 8
Additional Operating Mechanism
Instructions
Contents
8.1 Spring Operating Mechanism............................................................................3
8.1.1 Charging the Closing Energy Storage Mechanism....................................3
8.1.2 Closing Operation ...................................................................................3
8.1.3 Recharging the Closing Energy Storage Mechanism ................................4
8.1.4 Opening Operation .................................................................................4
8.1.5 Slow Closing Operation ..........................................................................5
8.1.6 Slow Opening Operation .........................................................................8
8.1.7 Troubleshooting......................................................................................9
List of Figures
Figure 8-1: FK 3-1 Spring Operating Mechanism (schematic diagram) ........................5
Figure 8-2: Removing the Side Panel from the Mechanism .........................................6
Figure 8-3: Manual Lever ...........................................................................................6
Figure 8-4: Blocking Device .......................................................................................7
Figure 8-5: Slow Operation Device .............................................................................7
Figure 8-6: Charging the Closing Spring Manually ....................................................10
Revision History
Revision Record Description Revised by Date
6. At the same time, the spring position indicator (70.31) has been set to "closing spring
discharged."
1.8.07
1.8
70.19
70.26 1.8.06
2.3
70.27
70.18
70.28
70.29
70.17
70.30
70.16
70.31 70.15
70.52
70.14
70.53
70.13
a. Closing spring discharged or charged: the closing spring is charged when the roller
(Figure 8-1, Item 70.28) is engaged with the closing latch (Figure 8-1, Item 70.05).
b. The switcher is in the switcher open position.
2. Remove the right side panel (Figure 8-2):
IMPORTANT
Take the following safety precautions:
• Disconnect the control voltage.
• Block the manual opening levers (Figure 8-3, Item 70.13):
• Loosen the M6 screws.
• Push the plate (Figure 8-3, Item 70.58) up to the right.
• Retighten the M6 screws.
IMPORTANT
If you connect the control voltage again when the closing spring (Figure 8-1, Item 70.25) is
discharged, the motor (Figure 8-1, Item 70.01) will immediately begin to charge it.
IMPORTANT
Take the following safety precautions:
• Disconnect the control voltage.
• Block the manual opening levers (Figure 8-3, Item 70.13):
• Loosen the M6 screws.
• Push the plate (Figure 8-3, Item 70.58) up to the right.
• Retighten the M6 screws.
3. If the closing spring is charged, insert the blocking device (Figure 8-4, Item 70.71) for the
closing latch (Figure 8-4, Item 70.05), and attach to the axis of the manual opening lever (Figure
8-4, Item 70.13).
4. Mount the slow operation device (Figure 8-5, Item 70.72):
a. Place the support plate (Figure 8-5, Item 70.73) of the device on the upper right spacer
sleeve (Figure 8-5, Item 70.76) and prop the device against the mechanism housing.
b. Attach the hook (Figure 8-5, Item 70.74) of the device to the bolt (Figure 8-5, Item 70.77)
of the support latch (Figure 8-5, Item 70.78).
5. Turn the M16 nut (Figure 8-5, Item 70.75) clockwise until the pressure is removed from the
opening latch (Figure 8-5, Item 70.16).
6. Release the block on the manual opening lever (Figure 8-4, Item 70.13).
7. Push the plate (Figure 8-3, Item 70.58) down.
8. Execute a slow opening operation:
a. Unlock the opening latch (Figure 8-5, Item 70.16) using the manual opening lever
(Figure 8-4, Item 70.13).
b. At the same time, turn the nut (Figure 8-5, Item 70.75) counterclockwise until the support
latch (Figure 8-5, Item 70.78) of the roller follower (Figure 8-5, Item 70.11) has passed
the opening latch (Figure 8-5, Item 0.16).
c. Continue turning the nut (Figure 8-5, Item 70.75) counterclockwise until the pressure is
removed from the hook (Figure 8-5, Item 70.74).
d. At the end of this operation, the opening spring (Figure 8-1, Item 70.20) is discharged
and the switcher position indicator (Figure 8-1, Item 70.52) indicates "Switcher open."
9. Block the manual opening levers (Figure 8-4, Item 70.13):
a. Push the plate (Figure 8-3, Item 70.58) up.
b. Tighten the M6 screws.
10. Remove the slow operation device (Figure 8-5, Item 70.72).
11. Remove the blocking device (Figure 8-4, Item 70.71) for the closing latch (Figure 8-4, Item
70.05).
12. Replace the right side panel.
13. Connect the control voltage.
IMPORTANT
If you connect the control voltage again when the closing spring (Figure 8-1, Item 70.25) is
discharged, the motor (Figure 8-1, Item 70.01) will immediately begin to charge it.
8.1.7 Troubleshooting