SIMPLIFIED ANNUAL ENERGY
ESTIMATION METHODS
  Hourly analysis for peak
  design heating and cooling   Sizing HVAC equipment
  load calculations
  Annual energy calculations   Energy Consumption
                               Energy Audits
Repeating         Quicker
hourly            methods
analysis
                                                               1
The yearly energy consumption Qyr is needed to evaluate the
operating cost.
Consumption Qyr is the time integral of the instantaneous
consumption over the heating (or cooling season); the
instantaneous consumption is the instantaneous heating load
Qh divided by the instantaneous efficiency ηh of the heating (or
cooling) equipment.
    • degree-day methods
    •   bin methods
 Degree-day methods are the simplest and these are appropriate if the
 building is operated in the same manner (for example, the indoor
 thermostat is set at a constant value throughout the year) and if the
 efficiency of the HVAC equipment can be considered constant for all the
 hours of operation over the year or the season.
 For situations where efficiency or conditions of utilization vary with
 outdoor temperature, one can calculate the consumption for different
 values or bins of the outdoor temperature and multiply it by the
 corresponding number of hours over the year or season. This is the bin
 methods.
                                                                              2
One needs the value of outdoor dry-bulb air temperature To
below which heating becomes necessary (or above which
cooling is needed); that is called the “balance-point
temperature”
The severity of a climate can be characterized concisely in
terms of degree-days.
Degree-Day Method
Balance-Point Temperature
Consider a small building in a cold location maintained at an
indoor air temperature Ti with “free” heat gains Qgain
(from the sun, occupants, lights, etc.).
The balance-point temperature Tbal of this building is defined
as that value of the outdoor dry-bulb temperature To where,
for the specified value of Ti, the total heat loss is equal to the
free heat gain.
                                                                         3
 If the peak winter design load of the building is known, it can be
 conveniently determined from design temperatures:
 The balance-point temperature is
 Tbal is the outdoor dry-bulb temperature above which cooling is
 required and below which heating is required
Heating Degree-Day Method
Heating is needed only when To drops below Tbal.
The rate of energy consumption of the heating system is
                                                                     Plus sign
where ηh is the efficiency of the heating system                     indicates that
                                                                     only positive
                                                                     numbers are
The annual heating consumption is                                    considered.
 Note that ηh, Tbal, and Ktot are constant for the simplification.
The integral of the temperature difference is approximated by a sum of
averages over short-time intervals (daily or hourly), and the result is called
“degree-days” or “degree-hours.”
                                                                                      4
  If daily average values of outdoor temperature To are used for evaluating
  the integral, one obtains the degree-days for heating HDD(Tbal) as
  with dimensions of K · days
  For shorter time intervals
   In terms of degree-days, the annual
   heating consumption is
Degree-days or degree-hours for a balance-point temperature of 18°C
                                                                        10
                                                                              5
                                           11
Isıtma derece-gün bölgelerinin
tespitinde 18 C denge noktası
sıcaklığındaki derece-gün
değerleri esas alınmıştır.
Başlangıçta derece-gün değerleri
artan şekilde sıralanmıştır. Daha
sonra aşağıdaki 1000 C.gün
aralıklarına göre bölgeler
oluşturulmuştur.
I. Bölge ≤ 1250
1251≤ II. Bölge ≤2250
2251≤ III. Bölge ≤3250
3251≤ IV. Bölge ≤4250
V. Bölge ≥4251
ULIBTK’07 16. Ulusal Isı Bilimi ve Tekniği Kongresi, 30
Mayıs-2 Haziran 2007, KAYSERİ TÜRKİYE İÇİN ISITMA
VE SOĞUTMA DERECE-GÜN BÖLGELERİ Hüsamettin
BULUT , Orhan BÜYÜKALACA, Tuncay YILMAZ
                                           12
                                                          6
                                                               13
Example: Annual Heating Energy
Find the annual heating bill for a house in Ankara under the
following conditions.
Given: Heat transmission coefficient Ktot = 205 W/K
Heat gain          = 569 W
Indoor temperature Ti = 21.1°C
Efficiency of heating system ηh = 0.75
Fuel price $8/GJ
Assumptions: Ktot ,          , Ti , and ηh are constant.
                                                               14
                                                                    7
The balance-point temperature:
                      = 205 W/ K x 2677 K × days X 24 h/day x 3600 s/h / 0.75
                      = 47.415 GJ / 0.75 = 63.22 GJ
 The annual cost is 63.22 GJ × $8/GJ = $ 505.8 / year.
                                                                          15
 Cooling Degree-Day Method
 The numerical values of degree-days for cooling (CDD) are generally
 different from HDD because Ti, Qgain, and Ktot can be different.
 Annual heating and cooling degree-days, if based on the same Tbal, are
 related by
                                                                          16
                                                                                8
17
18
     9
                                           Outdoor average daily
                                           temperatures To for the months
                                           of March (a mild month) and
                                           July (a very hot month) are
                                           plotted along with the 65°F
                                           line as shown. The hatched
                                           areas are indicative of the
                                           CDD (65°F) values for the 2
                                           months.
                                           For the month of March, there
                                           are days when To < 65°F, and
                                           such days do not contribute to
                                           the CDD value, i.e., no cool-
                                           ing is necessary and the air
                                           conditioner does not operate.
                                           During the month of July, we
                                           note that To > 65°F for all the
                                           days, and so the air
                                           conditioner has to run
                                           continuously.
                                                                  19
If an air conditioner operates continously the CDD equation can
be simplified to
where Nm is the number of days in the month.
The annual cooling energy use is
                              Not precise due to
                              • Opening windows (occupant behaviour)
                              • İncreasing ventilation rate in industrial
                                buildings
                                                                  20
                                                                             10
 Therefore, the air conditioner is needed only when the outdoor
 temperature exceeds the threshold Tmax.
                                             Ktot (closed window) is
                                             replaced by Kmax
                                                    The solid line is the load
                                                    with open windows or
                                                    increased ventilation; the
                                                    dashed line is the load if
                                                    Ktot is kept constant.
                                                                        21
The annual cooling load for this mode is the sum of the cooling load
during the days when To > Tmax with windows closed plus that needed to
cool down the building from Tmax to Tbal during these same days:
 where CDD(Tmax) is the cooling degree-days for base Tmax and Nmax is the
 number of days during the season when To rises above Tmax.
                                                                        22
                                                                                 11
   Example: Annual Cooling Energy
   Estimate the annual cooling degree-days in New York for a base of
   Tbal = 23.1°C (73.6°F) and for a base of Tbal = 18.1°C (64.7°F).
   Find: CDD(Tbal)
   Lookup values: To,yr = 12.5°C, from the weather data
                                                                           23
                                                          HDD(23.1°C) = 4080 K × days
                                                          HDD(18.1°C) » 2778 K × days
CDD(23.1°C) = HDD(23.1°C) - 365 days x [(23.1 - 12.5) K] = 208 K × days
Likewise for 18.1°C,
CDD(18.1°C) = HDD(18.1°C) - 365 days x [(18.1 - 12.5) K] = 734 K × days
                                                                           24
                                                                                        12
Example: Effect of Window Opening on Cooling Energy
Estimate the annual cooling load, with and without a window opening, for
a house in New York under the following conditions:
Given: Heat transmission coefficient Ktot= 205 W/K with closed windows at
0.5 air change/h
Kcond = 145 W/K due to conduction alone
Heat gains Qgain = 1200 W
Ti = 24.0°C
Average air change rate with open windows = 10 air changes/h
Find: Qc,yr
Assumptions: Ktot, Kmax, Qgain, and Ti are constant.
                                                                     25
 The balance-point temperature for cooling is
 From previous example, CDD(Tbal ) = 734 K × days
 If windows were always closed, the annual cooling load would be
                                                                     26
                                                                            13
If windows are opened for ventilative cooling, we first have to find Kmax.
Noting that at 0.5 air change/h, the contribution of the air change is
Hence, at 10 air changes/h this term must be multiplied by 10/0.5,
giving a value
                                                                             27
The required number of cooling degree-days was calculated in the
previous Example as
If Nmax = 56.5 days
It is found from the graph given in the previous example. Outside air
temperature greater than 24.2 C gives 1004 hours. That is approximately
equal to the 56.5 days.
                                                                             28
                                                                                  14
By opening windows the energy consumption for cooling decreases
from 13 GJ to 8.7 GJ.
That is the reason why actual residental cooling loads are highly
sensetive to occupant behaviour.
                                                                     29
Bin Method
 There are problems in the application of degree day method.
 • Effect of solar loads
 • The efficiency of a heat pump and directly related to the To
 • The efficiency of the HVAC equipment indirectly related to the To
   especially for the chillers and boilers
 • Occupancy
 • Indoor temperature
 • Ventilation rate
 If different temperature intervals and time periods are evaluated
 separately a steady state calculation (bin method) can yield good
 results.
                                                                     30
                                                                          15
The consumption is calculated for several values of the outdoor
temperature To and multiplied by the number of hours Nbin in the
temperature interval (or bin) centered on that temperature:
The plus subscript on the parentheses indicates that only positive
values are to be counted; no heating is needed when To is above Tbal.
This equation is evaluated for each bin, and the total consumption is
the sum of the Qbin values over all bins.
                                                                         31
In the United States, the necessary data, called “bin data,” have been
generated in temperature intervals of 5°F (2.8°C) A bin data for
Gaziantep with 3°C temperature difference was given below.
                                                                         32
                                                                              16
                                                                             33
MIDTERM
1. Bin Method to Determine Annual Heating Needs of an Office Building
Find the heating energy consumption of a simple commercial building in Gaziantep
in December, January, and February for the following conditions:
Given: Occupied 7 days per week, 8:00 to 18:00; unoccupied otherwise
Ktot = 2.0 kW/K occupied
     = 1.0 kW/K unoccupied (reduced because ventilation system shut off)
Efficiency of heating system η = 0.94
2. Find the heating energy consumption for the same building with the
Degree-day method
3. Compare the results.
Last submission date and time:
                                                                             34
                                                                                   17