This document provides calibration instructions for the Salwico ST200 and ST600EX gas detectors, detailing the necessary tools, prerequisites, and step-by-step procedures for zero and span calibration. It emphasizes the importance of periodic gas response checks and outlines the proper handling of the detectors during calibration. Additionally, it includes contact information for Consilium Building Safety AB and notes that the document's contents may be revised without notice.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
76 views8 pages

Salwico st200

This document provides calibration instructions for the Salwico ST200 and ST600EX gas detectors, detailing the necessary tools, prerequisites, and step-by-step procedures for zero and span calibration. It emphasizes the importance of periodic gas response checks and outlines the proper handling of the detectors during calibration. Additionally, it includes contact information for Consilium Building Safety AB and notes that the document's contents may be revised without notice.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

Salwico ST200 & Salwico

ST600EX

CGD50/500
Calibration Instruction
Consilium Building Safety AB
Phone: +46 31 28 59 40
Fax: +46 31 28 85 95
E-mail: sales.cbs@consilium.se
service.cbs@consilium.se

The contents of this document are subject to revision without notice


due to continued progress in methodology, design and
manufacturing. Consilium Building Safety AB assumes no legal
responsibility for any error or damage resulting from the usage of
this document.

April 2019
Document no. 5103026_Salwico ST200 & Salwico ST600EX_Calibration Instruction_I0_EN_2019_C
Part no. 5103026

© Copyright 2019, Consilium Building Safety AB


1 Calibration Instruction for Salwico ST200 and
Calibration Instruction Salwico ST600EX

1 Calibration Instruction for Salwico ST200


and Salwico ST600EX

1.1 Preliminaries
This instructions applies to the following products:

Figure 1. Salwico ST200. Part No. 4470

Figure 2. Salwico ST600EX. Part No. 4460.

NOTE!
It is recommended to periodically carry out a gas response check on the gas detector
to ensure correct operation.

The ST200 and ST600EX detectors for 0-100% LEL Hydrocarbon can be
calibrated and the out-signal adjusted.

Hint!
Reading at 0% is 4.0 mA, and full range 100% LEL is 20 mA.

Tools
Tools required for this operation are:

5103026_Salwico ST200 & Salwico ST600EX_Calibration Instruction_I0_EN_2019_C 1


1 Calibration Instruction for Salwico ST200 and
Salwico ST600EX Calibration Instruction

• A small terminal screw driver, with thin straight tip.


• A multimeter with mA (milliampere) capacity.

1.2 Prerequisites
1 Use the arrow keys on the control panel to
manoeuvre through the different menus.
Press the right arrow key to access the
menu tree.

2 Scroll to 4 Gas Detectors and press


Continue.

3 Scroll to the detector that should be


calibrated and press Options.

4 Scroll to 3 Disable and choose Continue.

5 You have to confirm the disablement before


you can proceed.
Press Disable to continue.

6 You will get a confirmation message that


the detector has been disabled.
Press Close to continue.

7 If the ambient air is NOT considered


reliable to use to set the ZERO, apply a
clean source of zero gas or compressed air.
8 NOTE!
For the following steps in the
zero calibration instruction
proceed to the Salwico ST200 or
ST600EX detector.

2 5103026_Salwico ST200 & Salwico ST600EX_Calibration Instruction_I0_EN_2019_C


1 Calibration Instruction for Salwico ST200 and
Calibration Instruction Salwico ST600EX

9 Connect the Flowcap to the sensor head as


shown in the picture.
Connect the measuring tips of the
multimeter to the test points in the detector.
Plus is red, minus is black.
Hint!
Picture shows a ST200. The
ST600EX has identical
connections and calibration, only
fitted in an EX proof housing.

1.3 Calibrating the sensor (Zero calibration)


Before gas Calibration is made, a Zero-adjustment should be made.

1 Connect the multimeter to the two test


points as shown in the picture.

2 The multimeter readout should be 4.0 mA


with normal air / zero gas exposed to the
sensor.
Adjust to this reading with the ‘Zero’
potentiometer, marked in red. (See where
the screwdriver is placed in the picture.)

1.4 Calibrating the sensor (Span calibration with


test gas)
NOTE!
For the ST600EX the procedure is identical as below, but note that the EX-Seal is
void if the unit is open, so necessary precautions in the working area may be
required.
Check on site what is applicable before the unit is opened up.

5103026_Salwico ST200 & Salwico ST600EX_Calibration Instruction_I0_EN_2019_C 3


1 Calibration Instruction for Salwico ST200 and
Salwico ST600EX Calibration Instruction

1 Connect the suitable test-gas for the Recommendations:


detector, normally a 50% LEL mixture. The ST200 and ST600EX can
only respond to gas in normal
Air. This means that
Calibration gas in N2 /
Nitrogen are not suited for
these detectors.
On LNG vessels a 50% LEL
gas of CH4 Methane in air is
to be used.
For LPGs and Tankers we
normally recommend a 50%
LEL C3H8 Propane gas in air.
2 Adjust the reading to 12.0 mA using the
‘SPAN’ pot. See picture.

Figure 3. Detector ST200

Figure 4. Detector ST600EX


3 If the readout of 12.0 mA cannot be Catalytic detectors have a
reached even with the “SPAN” pot in the limited lifespan of up to 5
bottom position, the sensor cell must be years, but can be ‘poisoned’
replaced to a new one. Consilium by silicones, salt air, very
Replacement article number for ST200 and humid air, etc. and their
ST600EX detectors is 004460-S. output will be reduced.
NOTE!
When a new sensor is fitted, a
new Zero adjustment as well as
span calibration should be made.

1.5 Reconnecting disabled detectors


All disablements in the CGD50/500 gas detection system are presented in the
disablements list. Any enablement is made from this list.

4 5103026_Salwico ST200 & Salwico ST600EX_Calibration Instruction_I0_EN_2019_C


1 Calibration Instruction for Salwico ST200 and
Calibration Instruction Salwico ST600EX

1 Scroll to Menu » Disablements.


2 Choose the detector you just disabled and press Options.
3 Select Reconnect and press Continue.

5103026_Salwico ST200 & Salwico ST600EX_Calibration Instruction_I0_EN_2019_C 5


FOR ALL THOSE MOMENTS
WHEN SAFETY MATTERS
Consilium is a producer of safety and safety-related technologies for the marine, oil and gas,
transport and building sectors. Our commitment goes beyond the products: We protect the
lives of mothers and fathers, sisters and brothers, colleagues and friends. With representation in
more than 25 countries in all time zones, we are always close to you.

www.consilium.se

You might also like