IS 2189 2008 (Reaffirmed 2018)
IS 2189 2008 (Reaffirmed 2018)
(Reaffirmed 2018)
                             'J.f N cf) '4   JOtI 'i Cjj
                         Indian Standard
              SELECTION, INSTALLATION AND
                                                                                       SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
             MAINTENANCE OF AUTOMATIC FIRE·
             DETECTION AND ALARM SYSTEM-
ICS 13.220.10
© BIS 2008
FOREWORD
This Indian Standard (Fourth Revision) was adopted by the Bureau of Indian Standards, after the draft
finalized by the Fire Fighting Sectional Committee had been approved by the Civil Engineering Division
Council.
The purpose of a fire detection and alarm system is to detect fire at the earliest practicable moment and to give an
alarm so that appropriate action can be taken (for example, evacuation of occupants, summoning the fire
fighting organization, triggering of extinguishing processes, etc). An alarm system may be activated by automatic
detection devices or by manual operation of manual call points.
                                                                                                                    SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
This standard covering the requirements of heat sensitive fire 'detectors was first published in 1962 and revised in
1976, 1988 and 1999. The present revision includes modifications with regard to terminology, inclusion of
probe type high temperature bi-metal heat detector, optical smoke detector, spark/ember detector, UV flame
detector, lR flame detector etc, and figures for arrangement for smoke detectors and addressable fire detection
For the purpose of deciding whether a particular requirement of this standard is complied with, the final value,
observed or calculated, expressing the result of a test or analysis, shall be rounded off in accordance with
IS 2 : 1960 'Rules for rounding off numerical values (revised)'. The number of significant places retained in the
rounded off value should be the same as that of the specified value in this standard.
                                                                                                     IS 2189 : 2008
                          Indian Standard
                   SELECTION, INSTALLATION AND
                  MAINTENANCE OF AUTOMATIC FIRE
                  DETECTION AND ALARM SYSTEM -
                        CODE OF PRACTICE
                                            ( Fourth Revision)
] SCOPE                                                      3 TERMINOLOGY
                                                                                                                         SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
].1 This standard covers the planning, design,               3.0 For the purpose of this standard, the following
selection, installation and maintenance of fire detection    definitions and definitions given in IS 8757 shall
and alarm systems. It is applicable to simple systems        apply.
with a few manual call points as well as to complex
indicator lamps, alphanumeric displays, graphical                    transmission of calls for assistance to emergency
displays or other equivalent means in which each                     services.
indication provides status information about a circuit,
                                                                     3.22 Control Unit - A system component that
condition or location.
                                                                     monitors inputs and controls outputs through various
3.10 Approved -      Acceptable to the authority having              types of circuits.
jurisdiction.
                                                                     3.23 Detection Zone - Sub-division of the protected
3.11 Audibility - Property of a sound which allows                   premises such that the occurrence of fire within it will
it to be heard among other sounds in the, background.                be indicated by a fire alarm system separately from an
                                                                     indication of fire in any other sub-division.
3.12 Authority having Jurisdiction - The
organization, office, or individual responsible for                  3.24 Detector - A device suitable for connection to a
approving equipment, materials, an installation or a                 circuit that has a sensor that responds to a physical
procedure.                                                           stimulus such as heat or smoke or flame.
                                                                                                                                 SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
3.13 Automatic Fire Detection and Alarm                              3.25 Display -    The visual representation of output
System - Fire alarm system comprising components                     data, other than printed copy.
and sub-system required for automatically detecting a
fire, initiating an automatic alarm for fire and initiating          3.26 Electrical Conductivity Heat Detector - A
                                                                     line-type or spot-type sensing element in which
                                                                 2
                                                                                                               IS 2189 : 2008
   c) is used to monitor automatically the correct               processed and used to convey an alarm condition when
      functioning of the system; and                             it meets preset criteria.
   d) is used to indicate or display the location of fire/           NOTE - It is suggested that the use of such detectors be
      alarm activation device.                                       discouraged/avoided, as they have a radioactive source. Multi-
                                                                     function detectors may be used instead.
3.35 Fire Alarm Signal - A signal initiated by a
                                                                 3.46 Line Detector - Detector which responds to the
fire alarm-initiating device, such as a manual fire alarm        phenomenon sensed in the vicinity of a continuous
box, automatic fire detector, water flow switch, or              line.
other device in which activation is indicative of the
presence of a fire or fire signature.                            3.47 Maintenance - Repair service, including
                                                                 periodic inspections and tests, required to keep the fire
3.36 Fire Alarm System - A combination of                        alarm system and its component parts in an operative
components for giving an audible and visible andlor              condition at all times, and the replacement of the system
other perceptible alarm of fire. The system may also             or its components when they become undependable or
                                                                                                                                      SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
initiate other ancillary action.                                 inoperable for any reason.
3.37 Fire Rating - The classification indicating in              3.48 Manual Call Point -              A manually operated
time (hours) the ability ofa structure or component to           device used to initiate an alann signal. It can be man~l
withstand a standardized fire test. This classification          alarm system or part of automatic alarm system.                .
3.56 Protected Premises - The physical location                 connected to the fire alarm system when the normal
protected by a fire alarm system.                               power supply fails.
3.57 Radio Alarm System (RAS) - A system in                     3.71 Trouble Signal- A signal initiated by the fire
which signals are transmitted from a radio alarm                alarm system or device indicative of a fault in a
transmitter (RAT) located at the protected premises             monitored circuit or component.
through a radio channel to two or more radio alarm
repeater station receivers (RARSR) and that are                 3.72 Zone - Area or space that has a group of
annunciated by a radio alarm supervising station                automatic and/or non-automatic fire detection devices
receiver (RASSR) located at the central station.                for which there is a separate common display in the
                                                                control and indicating equipment.
3.58 Rate-or-Rise Detector - A device that responds
when the temperature rises at a rate exceeding a                4 GENERAL REQUIREMENTS
predetermined value.                                            4.1 Automatic fire detection and alarm system consists
                                                                                                                                       SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
3.59 Search Distance - Distance which has to be                 of fire detectors and manual call points connected by
travelled by a searcher within a zone in order to               appropriate cables to sectorlzonal panels which in tum
determine visually the position of fire.                        are connected to control and indicating equipment
                                                                (C and I). The equipment and cables of automatic fire
3.60 Sector - A sub-division of the protected                   detection and alarm system should be independent of
                                                            4
                                                                                                              IS 2189: 2008
                                                                                                                                        SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
       300 m2, a zone can cover more than one floor.
                                                                    guidelines regarding the requirements for the
    c) If the total area of a building is more than                 division of sectors, etc, as stated above due to
       300 m\ each z;one shall be restricted to a single            the fact that the configurations are not same for
       floor.                                                       all risks. The division into zones andlor sectors
                                                             5
IS 2189: 2008
4.2.3 Size and Number oj Zones (Protected with                  sounders should be such that the alarm is heard at all
Manual Call Points)                                             sites which can be occupied within the protected area.
   a) In systems containing only manual call points,            A minimum sound level of either 65 dB (A) or 5 dB
      location of a fire is usually known to the person         (A) above any other noise likely to persist for a period
      operating the call point. As it is often difficult        longer than 30 s, whichever is greater should be
      to get information in time to the safety personnel,       produced by the sounders at any point which can be
      the restriction on the size and number of zones           occupied in a bUilding. Sounders should be suitably
      shall also apply to the systems protected with            distributed throughout the building in regard to
      manual call points only.                                  attenuation of sound caused by walls, floors ceilings
   b) To prevent misleading indication ofthe position           and partitions. If the fire routine for the premises
      ofthe fire, it is advisable that manual call points       requires the audible alarm to arouse sleeping persons,
      be indicated in the control equipment separately          the minimum sound level should be 75 dB (A) at the
      from the detectors in zones, which are protected,         bed head with all doors shut. A large number of quieter
                                                                                                                            SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
      by both detectors and manual call points. It is           sounders rather than a few very loud sounders may be
      strongly recommended that the circuits for the            preferable to prevent noise levels in some areas from
      detectors and the call points shall be different          becoming too loud. In siting sounders in corridors to
      in case of conventional detection systems.                serve the surrounding rooms, account should be taken
                                                                of the attenuation of the sounder frequency by any
4.2.4.3 Each loop should not be divided into more               5.1 The types of detectors covered in the standard are
than 8 fire zones. Minimum two isolators are required           given in 5.1.1 and 5.1.2.
per zone. It is recommended that a pair offault isolator
                                                                5.1.1 Heat Detectors
modules be employed for every 20-30 detectors/manual
call points.                                                    See IS 2175.
4.2.4.4 In partially addressable system zone                    5.1.1.1 Fixed temperature
addressable module are used in the loop to connect
non-addressable fire detection ' devices. Wherever              The fixed temperature heat detectors are designed to
non-addressable detectors are connected provisions              operate when the temperature of the detector exceeds
of 4.1.1 to 4.2.3 are to be followed.                           a predetermined value.
4.3 The sounders for fire alarm should be electronic            5.1.1.2 Rate-oj-rise         temperature-cum-fixed
hooters/horns/electric bell having a frequency range            temperature detector
of 500 to I 000 Hz. The sound of the fire alarm should          The detectors are designed to operate within a given
be continuous although the frequency and amplitude              time:
may vary. If a two tone alarm is used, at least one of
the major frequencies should be within the frequency                a) when the rate of temperature rise at the detector
range of 500 to I 000 Hz. The distribution of fire alarm               exceeds a predetermined value regardless of the
                                                                       actual temperature; and
                                                            6
                                                                                           IS 2189: 2008
                                                                                                           SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                         ON 19/11/2022 17:30:47 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
                          CONVENTIONAL (NON - ADDRESSABLE)
                          DETECTION SYSTEM - CLASS B WIRING
                                                                              RELAY I CONTROL
                                                                              MODULE
                                                               24VDC
                                                            ADDRESSABLE
                                                            PULL STATION
                                                    7
IS 2189: 2008
                                                                               END OF LINE
                                                                               RESISTOR
                                                                                                                          SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                  ADDRESSABLE
    1D Addressable Fire Detection and Alarm System -                  Class A Wiring with Class B Tapping
                          FIG.   1   WIRING DETAILS FOR FIRE DETECTION AND ALARM SYSTEM
    b) when temperature at the detector exceeds a              These cables are used for detecting fire and overheating
       predetermined value.                                    in certain specific occupancies such as:
5.1. 1.3 Probe type high temperature bi-metal heat                a) cables tunnels, trays and vaults;
detector                                                          b) material conveyors;
Bi-metal heat detectors are resettable and highly                 c) bulk storage multi-racked areas;
suitable to use above 80°C where electronic                       d) rim seals of floating roof tanks storing hazardous
components cannot be used. The following are type of                 chemicals; and
application for which probe type high temperature heat            e) a few other special occupancies.
detectors are suitable.
                                                               5.1.1.5 Heat detectors application
Generator enclosure, turbine enclosure, oven and
furnace area, kitchen wood and other places as per the         These are suitable for use in situation where sufficient
requirement where automatic fire extinguishing/                heat is likely to be generated and damage caused by
suppression systems are used.                                  heat generated by the fire constitutes main hazard. This
                                                               is to be minimized through early detection. In many
5.1.1.4 Linear heat sensing cables                             buildings, especially non-air-conditioned buildings,
Linear heat sensing cables can be broadly divided into         these conditions prevail where heat detectors can be
two categories. Digital or analogue, depending upon            advantageously used. Heat detectors are however, not
the principle by which the sensing cable registers a           suitable for protection of places where larger losses
change in temperature.                                         can be caused by small fires and where safety of life is
                                                               involved.
 Digital sensor consists of two core cable in which the
 conductors are separated by a heat sensitive insulator.       5.1.2 Smoke Detectors
 When a specified temperature is reached, the cable            See IS 11360.
 insulation breaks down and an alarm is indicated. In
 the case of analogue sensor, cores are separated by a         5.1.2.1 Ionization smoke detectors
 negative temperature co-efficient polymer whose
                                                               Detectors employing ionization chamber(s) as sensing
 resistance will reduce in proportion to the temperature
                                                               means for detecting aerosols given-off by fires.
 increase.
                                                           8
                                                                                                       IS 2189 : 2008
A detector whose operation is based on light                   UV Flame detector makes use of ultraviolet sensitive
attenuation by smoke and/or light scattering by smoke          photocathode for detecting flame. It has a narrow
particles.                                                     spectral sensitivity of 185 to 260 J.l.m which is
                                                               insensitive to visible light.
5.1.3 Air Sampling Type Detector
                                                               5.1.5.1 IR Flame detector
Laser type smoke detectors are used in this type of
detection system. A detector that consists of a piping         Single or multiple wavelength infra-red flame detector
or tubing distribution network that runs from the              sense wavelength in the infra-red spectrum. Almost
detector to the areas to be protected. An aspiration fan       all the materials that participate in the flaming
in the detector housing draws air from the protected           combustion emit ultraviolet radiation to some degree
                                                               during flaming combustion, whereas only carbon-
                                                                                                                            SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
area back to the detector through air sampling ports,
piping or tubing. At the detector, the air is analyzed         containing fuels emit significant radiation at the 4.35
for fire products. Typical application of the systems is       micron (carbon dioxide) band used by many detector
where a trace of smoke needs to be detected, where             types to detect a flame.
high airflow can make traditional smoke detector               The following are types of application for which flame
   b) Electromagnetic interference (EMI, RFI);                 Fire detectors are designed to detect one or more of
      and                                                      three characteristics of a fire that is smoke, heat or
                                                               radiation (flame). No one type of detector is the most
   c) Electrostatic discharge in the fuel stream.              suitable for all applications and final choice is
                                                           9
IS 2189: 2008
                                                                                                                                           SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
detectors in the same area but these would IOcrease                                 away from fire due to strong convection currents
the cost of the system.                                                             threaten the life of the occupants even at far away
                                                                                    places; and
It is possible to increase the frequency of testing but
this might lead to increased disturbances on the                                 c) Detectable quantity ofsmoke from a hostile fire
                                                                         10
                                                                                                        IS 2189: 2008
should be efficient in detecting flaming fire to keep                 adequate concentra~ion. In a building, the
losses to a minimum. It is important to minimize                      hottest gas and the greatest concentration of
incidence of false alarms particularly when detectors                 smoke will generally form at the highest parts
are hooked up to actuate means of automatic extinction.               of the enclosed areas, and it is here, therefore,
Automatic extinction should generally be initiated only               that heat and smoke detectors need to be
on confirmation of two detecting signals to avoid                     sited.
possibility of false actuation.                                    b) There are other constraining factors in siting
                                                                      the detectors like the height of the ceiling
5.2.2.1 Computer/EDP centre/other electronic
                                                                      (more the height means more cooling of hot
equipment which have a very high value should be
                                                                      gases, thus diluting the performance of the
protected by smoke detectors.
                                                                      detectors), effects of stratification (where
5.2.2.2 Archives, high value libraries, and museums                   smoke does not rise to the ceiling at all), type
                                                                                                                             SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
with high value combustibles should be protected by                   of roof (with beams extending deep below,
combination of heat, flame, smoke detectors. The heat                 etc), air movement (within the protected area
detectors should be used on the racks and cupboards                    below the detectors), supply air inlets (in the
and smoke detectors in open space on the ceiling.                      vicinity of detectors), HVAC systems (with
Flame detectors may be used where height of the ceiling                high air change rates), obstructions (in the path
                                                           11
IS 2189: 2008
       separate enclosure for provision/spacing of                         the detectors may be greater than the determined
       detectors.                                                          spacing provided the maximum spacing from
   g) Detectors shall not be mounted within I m of                         the detector to the farthest point of a side wall
       any air inlet (supply air inlets of HVAC system)                    or comer within its zone of protection is not
       or a forced ventilation system.                                     greater than 0.7 times the determined spacing.
   h) Detector siting shall be such that a clear                     Table 1 gives spacing parameter(s) at different
       space of 500 mm is maintained below each                      ceiling heights for open areas under smooth and
       detector.                                                     flat ceiling with no-forced ventilation/air-flows.
    j) Where detectors are constrained to be fixed to                    NOTE - Refer Fig. 2 for the arrangement details of the
       the wall, they shall be sited in such a way that                  detectors.
       the top of the detection element is between                   6.3.3 Compensation to the Spacing of Detectors
        150 mm and 300 mm below the ceiling and
       the bottom of the detection element is above                     a) Height consideration
                                                                                                                                  SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
       the level of door opening. Additional detector                      Spacing of 7.5 m for smoke detectors is
        shall be placed on the ceiling at a position                       valid up to a height of 7 m only and that of
        1.5 m from any opening which might act like a                      5.3 m for heat detectors is valid only up to a
       flue .                                                              height of 5 m. Beyond these heights, spacing
                                                                           between the detectors shall be adjusted as
                                                                12
                                                                                                                          IS 2189 : 2008
                                 r -----------------~-----------------........
                                   Up to 3.5     4.0         5.0       6.0        7.0       8.0       9.0     10.0
(I) (2) (3) (4) (5) (6) (7) (8) (9) (10)
                                                                                                                                                  SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
optical type)
                   Grade I
                   (time instant       7       No chance       6         5         5         4         3        Nil
                   205)
   NOTES
   I The spacings have been adopted from charts of Fire Detection Institute of America, adopting the parameters mentioned in 6.3
   (nearest/rounded offvalues).
    2 It is presumed that 'No chance' means 'No change'.
                                                                     r ------------~
                                                                       Spacing
                                                                                   .....          -----------    "'"
                                                                                                     (Area Coverage)
                                                                        13
IS 2189 : 2008
                                    •ANY'MiERE IN
                                     THIS AREA
                                                                                                   I
                                                                                                   I
                                                                                                   I
                                                                                                   I
                                                                                                   I
                                                                                           I
                                                                             I I  I  I  I  I
  1/2 S            S            S                112 S               112 S I S I SiS I SiS I               3 ft (O.9m)
      ~--+-----~------~~--
                                                                                                           (max.)
                                                                                                                         SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
 S = SPACE BETVVEEN DETECTORS                                         =
                                                                   S SPACE BETVVEEN DETECTORS
 • = SMOKE DETECTOR OR HEAT DETECTOR                               • • SMOKE DETECTOR OR HEAT DETECTOR
 2A Smoke or Heat Detector Spacing Layout,                         29 Smoke or Heat Detector Spacing Layout,
       Sloped Ceiling (Peaked Type)                                       Sloped Ceiling (Shed Type)
                                    SMOKE
                                    DETECTOR
                       RAISED FLOOR
                       PANEL
                                                                          SMOKE
                                                         '-,.-""'I'"!!/   DETECTOR   j-C:!::!:::Iuc:.=-t
                                                              14
                                                                                                       IS 2189 : 2008
     is farther than 7.5 m from the nearest point of                  type smoke detector. Accordingly, all
     optical beam.                                                    requirements specified under items (a) to (j)
                                                                      above are applicable.
  b) In case of a sloping roof or pitched ceiling
     (where the distance between the top of apex                      However, as the detector actually draws
     and bottom of the roof exceeds 600 mm),                          samples of air through sampling points (holes
     distance stated in (a) above may be increased to                 in pipe work), it shall be possible to mount the
     8.5 m.                                                           sampling points flush with a ceiling,
                                                                      provided otherwise the system's effectiveness
  c) Where optical beam type smoke detectors are                      is confirmed by the manufacturer.
     llsed at more than 600 nun from ceiling level
     in order to provide supplementary detection of                 b) If the system is intended to co-exist with
     rising smoke within a high space (like Atrium                     other types of detection system for specific
     etc), the width of the area protected on each                     application within the protected area,
                                                                                                                           SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
     side of optical beam shall be regarded as                         installation shall comply with the
      12.5 percent of the height of the above beam                     manufacturer's specifications.
      from ground level.                                            c) Maximum air sample transport time from
   d) Where there is a probability of people walking                   the farthest sampling point shall not exceed
                                                            15
IS 2189: 2008
                                                                                                                                SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
       to fuel. It is, therefore, necessary to fix the            illuminated and conspicuous positions, which are free
       distances as per the recommendations of the                of obstructions.
       manufacturers;
                                                                  Where the call points are not visible from the front as
    d) The location of the detectors shall also be such           in the case of a long corridor, they shall be surface
                                                             16
                                                                                                             IS 2189 : 2008
the wider dimension of the duct and the length of                      sensitivity test instrument, or
the probe shall be at least two-thirds of that                      c) approved control equipment arranged for the
dimension.                                                             purpose, or
7 INSPECTION, TESTING AND                                           d) other approved calibrated sensitivity test
MAINTENANCE                                                            method.
7.1 General                                                      7.2.7.1 Detectors found to have sensitivity outside the
                                                                 approved range should be replaced.
Even a well designed and properly installed
                                                                     NOTE - Detector sensitivity cannot be tested or measured
automatic fire alarm system will not be able to render               using any spray/smoke producing device that administers an
reliable and trouble-free service unless high standard               unmeasured concentration of aerosol/smoke into the detector.
of maintenance and supervision are ensured during
the entire service period of the system. Regular                 7.3 ServicinglPeriodical Maintenance
                                                                                                                                    SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
inspections and scheduled preventive maintenance are
                                                                 7.3.1 To ensure that regular and reliable servicing/
critical and should include all the components of the
                                                                 maintenance of the systems and its components is
system.
                                                                 carried out; any of the following methods should be
7.2 Initial Installation Inspection Tests                        adopted:
                                                            17
IS 2189 : 2008
7.4.3 Daily Attention by User                                          examined and tested to ensure that they are in
                                                                       good serviceable condition.
A check should be made every day to ascertain
                                                                    c) Where applicable, secondary batteries should be
that:                                                                  examined to ensure that the specific gravity of
    a) the panel indicates normal operation; if not, that              electrolyte in each cell is correct. Necessary
       any fault indicated is recorded in the log book                 remedial action should be taken and an
       and is receiving urgent attention; and                          appropriate entry made in the log book. Care
    b) any fault warning recorded the previous day has                 should be taken to ensure that hydrometers,
       received attention.                                             vessels, etc, used in the servicing of alkaline
                                                                       secondary cells are not contaminated by acid
7.4.4 Weekly Attention by the User                                     and vice versa. Contamination of electrolyte
The following tests should be made every week to                       can ruin a cell.
ensure that the system is capable of operating under                d) Primary batteries, including reserves, should be
alarm conditions:                                                      tested to verify that they are satisfactory for a
                                                                                                                               SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
    a) Once a week, at least one trigger device or                     further period.
       end of line switch on one zone circuit should                 e) The alarm function of control and indicating
       be operated to test the ability of the control                   equipment should be checked by the operation
       and indicating equipment to receive a signal                     of a trigger device in each zone as described.
 Any defect noticed should be recorded in the log book               a) The instruction and test routines detailed in
 and reported to the responsible person, and action                     7.4.5(a) to (t).
 should be taken to correct it.                                      b) Operation of at least 20 percent of the detectors
                                                                        in an installation should be checked each year
 7.4.5 Quarterly Inspection and Test by the User                        and the selection should be done in such a way
 The following check-list and test sequence should be                   that all the detectors in an installation shall have
 carried out:                                                           been checked once in every 5 years - replacement
                                                                        by a new one.
     a) Entries in the log book since the previous
        inspection should be checked and any necessary                c) Each detector should be checked for correct
        action taken.                                                    operation using specified test equipment and
                                                                         method, except non-resettable detectors. The
     b) Batteries and their connections should be                        checks to be carried out are specified in 7.2.2 to
                                                             18
                                                                                                          IS 2189 : 2008
       7.2.5 in respect of heat detectors and, 7.2.6              a period of 3 months. For each detector, the cleaning,
       and 7.2.7 in respect of smoke detectors.                   checking, operating and sensitivity adjustment should
    d) Visual inspection should be made to conftrm                be attempted only after consulting manufacturer's
       that all cable ftttings and equipment are secure,          instructions. These instructions should detail methods
       undamaged and adequately protected.                        such as creating vacuum to remove loose dust and
                                                                  insects, and cleaning heavy greasy deposits, following
    e) At least once in every three years at the annual           partial disassembly or the cleaning or the washing of
       inspection, the electrical installation should be          detectors to remove contamination, the sensitivity test
       tested. Any defect should be recorded in log               requirements in accordance with the relevant clauses
       book and suitable remedial action should be                should be performed.
       taken.
    f) On completion of the annual inspection, the                7.7 Tests Following an Alarm or Fire
       entry should be made in register in respect of
                                                                  All detectors suspected of exposure to a ftre condition
                                                                                                                              SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
       defects found. After the defects are rectifted,
                                                                  should be tested in accordance with the provisions
       the entries should then again be made.
                                                                  contained in this Code pertaining to annual inspection
7.S General Points About Detectors                                tests. In addition, a visual check of the battery charger
                                                                  should be carried out to ensure perfect serviceability.
 It is essential (particularly for installations involving        However, a check should be made to the extent of
Detectors require periodic cleaning to remove dust or             It may not be necessary to keep spares in premises other
dirt that has accumulated. The frequency of cleaning              than covers for manual call point and fuses and other
depends upon the type of detector and local ambient               essential spares which should be worked out based on
conditions. In any case, the interval should not exceed           installation.
                                                             19
IS 2189 : 2008
                                                  ANNEXA
                                                  (Clause 5.2)
               MERITS AND RELATIVE DEMERITS OF VARIOUS TYPES OF DETECTORS
    Smoke detectors     Slow burning fires, smoldering fires,        Not sensitive for clean burning fires
    (general)           for most of the areas where principal        which does not produce smoke
                        fire hazard is not from the presence of      particles; areas in which the principal
                                                                                                                 SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                        flammable liquids. Fires involving           fire hazard is the presence oftlammable
                        wood, paper, textile, etc, in earlier        liquids or gases that produce little
                        stages                                       smoke during a fire
    Ionization smoke     General purpose smoke detector -            Less sensitive to the larger particles
    Aspirating (air-     They are suitable for use where usage       Air-sampling detectors are not
    sampling) type       of other types of smoke detectors           suitable if the air movement due to
    smoke detector       present difficulties, such as aesthetics,   HVAC requirements is outside the
                         height and temperature of the               range specified by the manufacturers
                                                       20
                                                                                          IS 2189 : 2008
                                                                                                           SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                    equipment
Heat detectors      Clean burning fires, such as those          Unlikely to respond to smoldering and
(general)           involving certain flammable liquids.        slow burning fires, unsuitable for high
                    Areas subject to smoke, steam, dust or      value areas where a small fITe can cause
Rate-of-rise heat   Areas subject to smoke, steam, dust or      Areas subject to rapid changes of
detector            dirt during normal use                      temperature or temperatures over 43°C
Fixed temperature   Areas subject to smoke, steam, dust or
heat detector       dirt and rapid changes of temperature
                    during normal use
Multi-sensor fire   Combines the characters of two
detector            types of detectors, each of which
                    responds to different physical and/or
                    chemical characteristics of fire. The
                    purpose of combining sensors in this
                    way is to enhance the performance of
                    the system in detection of fire or its
                    resistance to at least certain categories
                    of false alarms or both. There is
                    significant potential for reduction of
                     many types of false alarm. It is also
                     possible to disable an individual sensor
                    depending on the circumstances
                    at the place of installation
FI ame detectors    High ceiling, open spaced buildings         Not sensitive to smoldering/slow
(general)           like warehouses/aircraft hangers,           burning fires and hence cannot be
                    outdoor/semi-outdoor areas, areas           called general purpose detectors. Not
                    where rapidly developing flames occur       suitable for the type of fires where.
                    like petrochemical/refinery/gas             flaming can occur only after substantial
                    installations/paint shops, etc              release of smoke
Infra red flame     Same as above, these detectors              Affected by temperature range in the
detector            penetrate through smoke well. High          vicinity, subject to false alarms caused
                    speed, moderate sensitivity. Suitable       by blackbody radiation like heaters,
                    for indoor/outdoor applications             incandescent lamps, halogen lamps,
                                                                flickering sunlight, etc and hence usage
                                                  21
IS 2189: 2008
                                                                                                                 SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                     usage in such areas to be avoided.
                                                                     Blinded by thick smoke and oil vapours
                                                                     on optics
 IR/IR          flame    High speed, moderate sensitivity, low       Somewhat affected by temperature
  Spark detector         Spark detectors are suitable for            Extraneous sources of radiant
                         detection of sparks some types of duct      emissions that have been identified as
                         or conveyor, monitoring the fuel, etc,      interfering with the stability of spark
                         as it passes by. Usually, it is necessary   detectors include: (a) ambient light (b)
                         to enclose the portion of the conveyor      electromagnetic interference (EMl,
                         where the detectors are located, as these   RFI), and (c) electrostatic discharge
                         devices generally requ ire a dark           in the fuel stream
                         environment
  Ember detector         Same as above except that ember              Detector window clarity shall always
                         detectors can also detect fires in lit       be ensured
                         environment like coal conveyors, etc
  Linear heat sensing    Cables tunnels, trays and vaults,            Not suitable at all applications other
  cables                 material conveyors, bulk storage             than what is specified
                         multi-racked areas, rim seals of
                         floating roof tanks storing hazardous
                         chemicals, and a few other special
                         occupancies
                                                       22
Bureau of Indian Standards
BIS is a statutory institution established under the Bureau of Indian Standards Act, 1986 to promote
harmonious development of the activities of standardization, marking and quality certification of goods and
attending to connected matters in the country.
Copyright
BIS has the copyright of all its publications. No part of these publications may be reproduced in any form
without the prior permission in writing of BIS. This does not preclude the free use, in the course of implementing
the standard, of necessary details, such as symbols and sizes, type or grade designations. Enquiries relating to
copyright be addressed to the Director (Publications), BIS.
                                                                                                                             SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
needed; if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standards
should ascertain that they are in possession of the latest amendments or edition by referring to the latest issue of
'BIS Catalogue' and 'Standards: Monthly Additions'.
This Indian Standard has been developed from Doc: No. CED 22 (7466).
Eastern     : 1114 C.LT. Scheme VII M, V.I.P. Road, Kankurgachi                              2337 8499,23378561
              KOLKA TA 700054                                                              { 2337 8626,2337 9120
Southern    : C.LT. Campus, IV Cross Road, CHENNAI 600113                                    2254 1216,2254 1442
                                                                                           { 22542519,22542315
Western     : Manakalaya, E9 MIDC, Marol, Andheri (Fllst)                                    2832 9295, 2832 7858
              MUMBAI 400093                                                                { 2832 7891, 2832 7892