Is 732 2019
Is 732 2019
Indian Standard
                                                                         SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                       ( pkSFkk iqujh{k.k )
ICS 91.140.50
© BIS 2019
Foreword ................................................................................................................................................................ v
  1 Scope ............................................................................................................................................................... 1
  2 References ....................................................................................................................................................... 2
  3 Terminology .................................................................................................................................................... 6
  4 Fundamental Principles, Assessment of General Characteristics .................................................................. 15
    4.1 Protection for Safety .............................................................................................................................. 15
                                                                                                                                                                              SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
    4.2 Protection for Safety—Protection against Electric Shock ..................................................................... 35
    4.3 Protection for Safety — Protection Against Thermal Effects ............................................................... 45
    4.4 Protection for Safety — Protection Against Overcurrent ....................................................................... 50
    4.5 Protection for Safety — Protection Against Voltage Disturbance and Electromagnetic Disturbance .... 55
  5 Selection and Erection of Electrical Equipment ............................................................................................ 83
ANNEXURES
  Annex A Provisions for Basic Protection ....................................................................................................... 138
  Annex B Obstacles and Placing Out of Reach ............................................................................................... 139
  Annex C Protective Measures for Application Only When the Installation is Controlled or Under the
          Supervision of Skilled or Instructed Persons ................................................................................... 140
  Annex D Protection of Conductors in Parallel Against Overcurrent ........................................................ 141
  Annex E Conditions 1 and 2 of 4.4.4.1 .......................................................................................................... 144
  Annex F Position or Omission of Devices for Overload Protection .............................................................. 145
  Annex G Position or Omission of Devices for Short-circuit Protection ......................................................... 147
  Annex H Explanatory Notes Concerning 4.4.5.1 and 4.4.5.2 ......................................................................... 149
   Annex J Guidance for Overvoltage Control by SPDs Applied to Overhead Lines ....................................... 150
  Annex K Determination of the Conventional Length, D ............................................................................ 151
  Annex L Concise List of External Influences ................................................................................................. 153
 Annex M Interdependence of Air Temperature, Relative Air Humidity and Absolute Air Humidity .............. 154
  Annex N Classification of Mechanical Conditions ......................................................................................... 163
  Annex P Classification of Macro-Environments ............................................................................................ 164
  Annex Q Permissible Protective Conductor Currents for Equipment............................................................. 164
  Annex R Methods of Installations .................................................................................................................. 166
  Annex S Current-Carrying Capacities ............................................................................................................ 173
  Annex T Example of a Method of Simplification of the Tables of 5.2.6 ....................................................... 199
                                                                                 ( iii )
IS 732 : 2019
                                                                                                                                                  Page
  Annex U Formulae to Express Current-Carrying Capacities .......................................................................... 201
  Annex V Effect of Harmonic Currents on Balanced Three-Phase Systems .................................................... 204
 Annex W Selection of Conduit Systems .......................................................................................................... 205
  Annex Y Voltage Drop in Consumers’ Installations ....................................................................................... 206
  Annex Z Examples of Configurations of Parallel Cables ............................................................................... 207
Annex AA Installation of Surge Protective Devices in TN Systems ................................................................. 209
Annex BB Installation of Surge Protective Devices in TT Systems ................................................................. 210
Annex CC Installation of Surge Protective Devices in IT Systems .................................................................. 212
                                                                                                                                                             SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
Annex DD Installation of Class I, II and III Tested SPDs, for Example in TN-C-S Systems ........................... 213
Annex EE Method for Deriving the Factor K in 5.4.3.1.2 (see also IEC 60724 and IEC 60949) .................... 214
Annex FF Example of Earthing Arrangements and Protective Conductors ..................................................... 217
                                                                         ( iv )
FOREWORD
This Indian Standard (Fourth Revision) was adopted by the Bureau of Indian Standards, after the draft finalized
by the Electrical Installation Sectional Committee had been approved by Electrotechnical Division Council.
This standard was first published in 1958 to guide and govern installation of electrical wiring in buildings with
particular reference to safety and good engineering practice.
                                                                                                                         SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
The second revision of this standard was brought out in 1982 in 3 parts. Soon after the publication of the second
revision, work on the preparation of National Electric Code (NEC) began. NEC was published in 1985. NEC,
besides drawing assistance from IS 732, further elaborates the stipulations on wiring practice with reference to
specific occupancies.
                                                        (v)
    IEC 60364-5-54 : 2011            Electric installations of buildings — Part 5-54: Selection and erection of
                                     electrical equipment — Earthing arrangements and protective conductors
    IEC 60364-5-55 : 2016            Electric installations of buildings — Part 5-55: Selection and erection of
                                     electrical equipment — Other equipment
    IEC 60364-5-56 : 2009            Electric installations of buildings — Part 5-56: Selection and erection of
                                     electrical equipment — Safety services
    IEC 60364-6 : 2016               Low voltage electrical installations — Part 6: Verification
Necessary changes have been made to ensure that the above mentioned points are taken care of. Whenever necessary,
provision of this code shall be read in conjunction with other codes such as those on earthing, lightning protection
and the National Electrical Code.
                                                                                                                       SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
The major deviations from the IEC standards are listed below. These differences are mainly because the revision
takes into account the National Electric Code and CEA notification dated 20th September 2010 for ‘Measures
relating to Safety and Electric supply’:
    a)   All country specific comments and notes for special applications mentioned in IEC 60364 have not been
                                                       ( vi )
                                                                                                                   IS 732 : 2019
                                                 Indian Standard
     CODE OF PRACTICE FOR ELECTRICAL WIRING
                 INSTALLATIONS
                                              ( Fourth Revision )
1 SCOPE                                                                 1.2.1 This standard applies to items of electrical
                                                                        equipment only, so far as, its selection and application
This Code gives the rules for the design, erection, and
                                                                        in the building electrical installation are concerned. The
                                                                                                                                      SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
verification of electrical installations. The rules are
                                                                        rules in this standard do not deal with the requirements
intended to provide for the safety of persons, livestock
                                                                        for the factory-built construction of electrical equipment,
and property against dangers and damage which may
                                                                        namely, type tested (TT) and partially type tested (PTT),
arise in the reasonable use of electrical installations
                                                                        Switchgear and Controlgear Assemblies, Distribution
and to provide for the proper functioning of those
                                                                    1
IS 732 : 2019
       concerning mobile units are applicable;                    regulations made by the appropriate Electricity
    p) electrical equipment on board ships;                       Regulatory Commission shall prevail. The Electricity
    q) electrical equipment of mobile and fixed off-              Regulatory Commissions in the Supply Code and
       shore installations;                                       Distribution Code made by them generally include a
    r) electrical equipment in aircraft;                          deeming provision that the statutory requirements in
    s) those aspects of mines and quarries which are              Supply Code and Distribution Code are duly observed
       specially covered by statutory Regulation                  by users and consumers of electricity, if the electrical
       under Mines Act, 1952 (35 of 1952);                        installation owned by them are constructed, installed,
    t) radio interference suppression equipment,                  protected, inspected, tested, operated, worked and
       except so far as, it affects safety of the                 maintained according to this Indian Standard besides,
       electrical installation;                                   complying with the provisions of sub regulation (1),
                                                                  (3) and (4) of the Central Electricity Authority
                                                                                                                                SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
    u) external lighting protection systems (LPS)
                                                                  (Measures Relating to Safety and Electric Supply)
       for buildings and structures covered under
                                                                  Regulations, 2010 and all other applicable statutory
       IS/IEC 62305;
                                                                  regulations made under the Electricity Act, 2003.
    v) safety machinery and electric equipment of
       machinery covered under Factory Act, 1948                  2 REFERENCES
11731 (All Parts)      Methods of test for determi-              (Part 6/Sec 1) :     Generic standards, Section 1:
                       nation of the flammability of             2008                 Immunity for residential,
                       solid electrical insulating                                    commercial and light-industrial
                       materials when exposed to an                                   environments
                       igniting source                           (Part 6/Sec 2) :     Generic standards, Section 2
12032 (All Parts)      Graphical symbols for use on              2008                 Immunity for industrial
                       equipment                                                      environments
12360 : 1988           Voltage bands for electrical              (Part 6/Sec 3) :     Generic standards, Section 3
                                                                                                                             SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                       installations including preferred         2002                 Emission        standard         for
                       voltages and frequency                                         residential, commercial and
13234 (Part 0) : 2016 Short-circuit currents in three-                                light-industrial environments
                       phase a.c. systems: Part 0               14772 : 2000          Enclosures for accessories for
                       Calculation of currents (first                                 household and similar fixed
                                                            3
IS 732 : 2019
                                                                                                                          SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                      installations of buildings
                      Supplementary requirements for            IS/IEC 60479-1 :      Effects of current on human
                      fuses for use by unskilled persons         2005                 beings and livestock — Part 1:
                      (fuses mainly for household and                                 General aspects
                      similar applications) —                   IEC 60502 (All Parts) Power cables with extruded
                      Examples of standardized
                                                            4
                                                                                                         IS 732 : 2019
IS/IEC 60947-3        Low-voltage switchgear and              IEC 61439-1           Low-voltage switchgear and
                      controlgear — Part 3: Switches,                               controlgear assemblies — Part 1:
                      disconnectors,           switch-                              General rules
                      disconnectors and fuse-                 IEC 61439-2           Low-voltage switchgear and
                      combination units                                             controlgear assemblies — Part 2:
IEC 60947-6-2         Low-voltage switchgear and                                    Power        switchgear       and
                      controlgear — Part 6-2: Multiple                              controlgear assemblies
                      function equipment — Control            IEC 61534 (All Parts) Power track systems
                                                                                                                         SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                      and protective switching devices        IEC 61535             Installation couplers intended for
                      (or equipment) (CPS)                                          permanent connection in fixed
IEC 60947-7           Low-voltage switchgear and                                    installations
  (All Parts)         controlgear — Part 7: Ancillary         IEC 61537             Cable management — Cable
                      equipment                                                     tray systems and cable ladder
                                                                                                                                     SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                      connected to low-voltage power
                      distribution systems — Part 1:
                      Performance requirements and
                      testing methods
IEC 61936-1           Power installations exceeding 1
                                                               6
                                                                                                              IS 732 : 2019
(reached by persons) without the use of ladders or                  or in the ground, open or ventilated or closed, and
similar means. For basins of fountains which may be                 having dimensions which do not permit the access of
occupied by persons, the requirement of swimming                    persons but allow access to the conductor and/or cables
pools applies.                                                      throughout their length during and after installation.
3.11 Bonding Conductor — A protective conductor                        NOTE — A cable channel may or may not form part of the
                                                                       building construction.
providing equipotential bonding.
3.12 Bonding Network (BN) — A set of                                3.22 Cable Cleat — A component of a support system
interconnected conductive parts that provide a path for             which consists of elements spread at intervals along
current at frequencies from direct current (d.c.) to radio          the length of the cable or conduits and which
frequency (RF) intended to divert, block or impede the              mechanically retains the cable or conduit.
passage of electromagnetic energy.                                  3.23 Cable Bracket — A cable support consisting of
                                                                                                                                SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
3.13 Bonding Ring Conductor (BRC) —A bus                            single devices fixed to elements of building or plant
earthing conductor in the form of a closed ring.                    construction.
   NOTE — Normally the bonding ring conductor, as part of the       3.24 Cable Coupler — A means enabling the
   bonding network, has multiple connections to the common          connection, at will, of two flexible cables. It consists
                                                                7
IS 732 : 2019
          which is supplied from a safety source.                        3.40 Competent Person —A person who possesses
    c)    Category 3 Circuit — A fire alarm circuit or                   sufficient technical knowledge, relevant practical skill
          an emergency lighting circuit.                                 and experience for the nature of the electrical work
                                                                         undertaken and is able at all the time to prevent danger
3.31 Cartridge Fuse Link — A device comprising a                         and, where appropriate, injury to him/herself and others.
fuse element or several fuse elements connected in
parallel enclosed in a cartridge usually filled with an                  3.41 Conduit —A part of a closed wiring system a
arc-extinguishing medium and connected to                                circular or non-circular cross-section for conductors
terminations. The fuse link is the part of a fuse which                  and/or cables in electrical installations, allowing them
requires replacing after the fuse has operated.                          to be drawn in and/or replaced. Conduits should be
                                                                         sufficiently closed-jointed so that the conductors can
3.32 Circuit Breaker — A mechanical switching                            only be drawn in and not inserted laterally.
device capable of making, carrying and breaking
                                                                                                                                                  SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
currents under normal circuit conditions and also of                     3.42 Confined Conductive Location — Allocation
making, carrying for as specified, and breaking currents                 having surfaces which are mainly composed of
under specified abnormal circuit conditions such as                      extraneous conductive parts and which are of such
those of short circuit.                                                  dimensions that movement is restricted to such an extent
                                                                         that contact with surfaces is difficult to avoid (for
3.34 Class I Equipment — Equipment in which                              3.44 Consumer Unit (may also be known as a
protection against electric shock does not rely on basic                 consumer control unit or electricity control unit) — A
insulation only, but which includes an additional safety                 particular type of distribution board comprising a type-
precaution in such a way that means are provided for                     tested co-ordinated assembly for the control and
the connection of exposed conductive parts to a                          distribution of electrical energy, principally in domestic
protective conductor in the fixed wiring of installation                 premises, incorporating manual means of double-pole
in such a way that accessible conductive parts may not                   isolation on the incoming circuit(s) and an assembly of
become live in the event of a failure of basic installation.             one or more fuses, circuit-breakers, residual current
                                                                         operated devices or signalling and other devices proven
   NOTE — For information on classification of equipment with            during the type-test of the assembly as suitable for such
   regard to means provided for protection against electric shock,
   see IEC 61140.
                                                                         use.
3.35 Class II Equipment — Equipment in which                             3.45 Continuous Operating Voltage (Uc) —
protection against electric shock does not rely on basic                 Maximum r.m.s voltage which may be continuously
insulation only, but in which additional safety                          applied to an SPD’s mode of protection. This is equal
precautions, such as double or reinforced insulation are                 to rated voltage.
provided, there being no provision for the connection                    3.46 Conventional Impulse Withstand Voltage —
of exposed metal work of the equipment to a protective                   The peak value of an impulse test voltage at which
conductor, and no reliance upon precautions to be taken                  insulation does not show any disruptive discharge, when
in the fixed wiring of the installation.                                 subjected to a specified number of applications of
                                                                         impulses of this value, under specified condition.
3.36 Class III Equipment — Equipment in which
protection against electric shock relies on supply at                    3.47 Conventional Touch Voltage Limit —
SELV and in which voltages higher than those of SELV                     Maximum value of the touch voltage which is permitted
are not generated.                                                       to be maintained indefinitely in specified conditions
                                                                         of external influences.
3.37 Cold Tail — The interface between the fixed
installation and a heating unit.                                         3.48 Conventional Operating Current (of a
                                                                         Protective Device) — A specified value of the current
3.38 Combustible — Capable of burning.                                   which causes the protective device to operate within a
3.39 Common Equipotential Bonding System,                                specified time, designated conventional time.
Common Bonding Network — Equipotential bonding                              NOTES
system providing both protective equipotential bonding                      1 For fuses this current is called the conventional fusing current.
and functional equipotential bonding.                                       For circuit breakers this current is called the conventional
                                                                            operating current.
                                                                     8
                                                                                                                         IS 732 : 2019
   2 The conventional operating current is greater than the rated        3.62 Earth Fault Current — A current resulting from
   current or current setting of the device and the conventional
                                                                         a fault of negligible impedance between a line
   time varies according to the type and rated current of the
   protective device.                                                    conductor and an exposed conductive part or a
                                                                         protective conductor.
3.49 Current Carrying Capacity of a Conductor —
The maximum current which can be carried by a                            3.63 Earth Electrode Resistance — The resistance
conductor under specified conditions without its steady                  of an earth electrode to earth.
state temperature exceeding a specified value.                           3.64 Earth Fault Loop Impedance — The impedance
3.50 Current Using Equipment — Equipment which                           of the earth fault current loop (phase to earth loop)
converts electrical energy into another form of energy,                  starting and ending at the point of earth fault. This
such as light, heat, or motive power.                                    impedance is denoted by the symbol Z. The earth fault
                                                                         loop comprises the following, starting at the point of
                                                                                                                                              SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
3.51 Danger — Danger to health or danger to life or                      fault:
limb from shock, burn or injury from mechanical
movement to persons (and livestock where present), or                        a) the circuit protective conductor;
from fire attendant upon the use of electrical energy.                       b) the consumer’s earthing terminal and earthing
                                                                                conductor, and for TN systems, the metallic
3.52 Design Current (of a Circuit) — The magnitude
                                                                     9
IS 732 : 2019
                                                                                                                                                 SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
3.74 Electrical Source for Safety Services —
                                                                        or extraneous conductive parts at the fault position is
Electrical source intended to be used as part of an
                                                                        considered negligible.
electrical supply system for safety services.
                                                                        3.85 Fault Current — A current resulting from a fault.
3.75 Electrical Supply System for Safety Services —
A supply system intended to maintain the operation of                   3.86 Fault Protection — Protection against electric
   NOTE — The supply system includes the source and the                 3.87 Final Circuit — A circuit connected directly to
   circuit(s) up to the terminals of the electrical equipment.          current using equipment, or to socket outlets or other
                                                                        outlet points for the connection of such equipment.
3.76 Electrode Boiler (or Electrode Water Heater)
— Equipment for the electrical heating of water or                      3.88 Fire
electrolyte by the passage of an electric current between
electrodes immersed in the water or electrolyte.                            a) A process of combustion characterized by the
                                                                               emission of heat and effluent accompanied by
3.77 Emergency Switching — Rapid cutting off of                                smoke, and/or flame and/or glowing.
electrical energy to remove any hazard to persons,
                                                                            b) Rapid combustion spreading uncontrolled in
livestock, or property which may occur unexpectedly.
                                                                               time and space.
3.78 Enclosure — A part providing protection of
                                                                        3.89 Fixed Equipment — Equipment fastened to a
equipment against certain external influences and, in
                                                                        support or otherwise secured.
any direction, protection against direct contact.
                                                                        3.90 Flammability — Ability of a material or product
3.79 Equipotential Bonding — Electrical connection
                                                                        to burn with a flame under specified test condition.
putting various exposed conductive parts and
extraneous conductive parts at a substantially equal                    3.91 Functional Bonding Conductor — Conductor
potential.                                                              provided for functional equipotential bonding.
   NOTE — In a building installation equipotential bonding              3.92 Functional Earthing — Connection to earth
   conductors shall interconnect the following conductive parts:        necessary for proper functioning of electrical
   a) Protective conductor,                                             equipment.
   b) Earth continuity conductor, and
   c) Risers of air-conditioning system and heating systems (if         3.93 Functional Extra-low Voltage (FELV) — An
   any).                                                                extra-low voltage system in which not all of the
3.80 Exposed Conductive Part — A conductive part                        protective measures required for SELV or PELV have
of electrical equipment, which can be touched and                       been applied.
which is not normally live, but which may become live                   3.94 Fuse — A device which, by melting of one or
under fault conditions.                                                 more of its specially designed and proportioned
3.81 External Influence — Any influence external to                     components, opens the circuit in which it is inserted by
an electrical installation which affects the design and                 breaking the current when this exceeds a given value
safe operation of that installation.                                    for a sufficient time. The fuse comprises all the parts
                                                                        that form the complete device.
                                                                   10
                                                                                                                  IS 732 : 2019
3.95 Fuse Carrier — The movable part of a fuse                      enclosing surrounding or supporting a conductor.
designed to carry a fuse link.                                         NOTE — See also the definitions for basic insulation, double
                                                                       insu lation , rein forced insulation and sup p lemen tary
3.96 Fuse Element — A part of a fuse designed to
                                                                       insulation.
melt when the fuse operates.
                                                                    3.110 Insulation Co-ordination — The selection of
3.97 Fuse Link — A part of fuse, including the fuse                 the electric strength of equipment in relation to the
element(s), which requires replacement by a new or                  voltages which can appear on the system for which the
renewable fuse link after the fuse has operated and                 equipment is intended, taking into account the service
before the fuse is put back into service.                           environment and the characteristics of the available
3.98 Gas Installation Pipe — Any pipe, not being a                  protective devices.
service pipe or pipe comprised in a gas appliance, for              3.111 Isolation — Cutting off an electrical installation,
                                                                                                                                      SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
conveying gas for a particular consumer and including               a circuit, or an item of equipment from every source of
any associated valve or other gas fitting.                          electrical energy.
3.99 Hand-Held Equipment — Portable equipment                       3.112 Isolator — A mechanical switching device which,
intended to be held in the hand during normal use, in               in the open position, complies with the requirements
which the motor, if any, forms an integral part of the
                                                               11
IS 732 : 2019
etc, completely assembled under the responsibility of                NOTE — An electrical installation may have more than one
                                                                     origin.
the manufacturer with all the internal electrical and
mechanical inter-connections and structural parts. The            3.132 Overcurrent — A current exceeding the rated
components of the assembly may be electromechanical               value. For conductors the rated value is the current
or electronic.                                                    carrying capacity.
3.121 Main Earthing Terminal — The terminal or                    3.133 Overcurrent Detection — A method of
bar which is the equipotential bonding conductor of               establishing that the value of current in a circuit exceeds
protective conductors, and conductors for functional              a predetermined value for a specified length of time.
earthing, if any, to the means of earthing.
                                                                  3.134 Overload Current (of a Circuit) — An
3.122 Mechanical Maintenance — The replacement,                   overcurrent occurring in a circuit in the absence of an
refurbishment or cleaning of lamps and non-electrical             electrical fault.
                                                                                                                                SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
parts of equipment, plant and machinery.
                                                                  3.135 PEL Conductor —A conductor combining the
3.123 Meshed Bonding Network (MESH-BN) —                          function of both a protective earthing and a line
Bonding network in which all associated equipment                 conductor.
frames, racks and cabinets and usually the d.c. power
                                                                  3.136 PELV (Protective Extra-low Voltage) — An
                                                             12
                                                                                                                 IS 732 : 2019
3.145 Prospective Fault Current (Ipf) — The value                 insulation under the conditions specified in the relevant
of overcurrent at a given point in a circuit resulting            standard.
from a fault of negligible impedance between live                    NOTE — The term ‘single insulation’ does not imply that
conductor having a difference of potential under normal              the insulation must be one-homogeneous piece. It may comprise
operating conditions, or between a live conductor and                several layers which cannot be tested singly as supplementary
an exposed conductive part.                                          or basic insulation.
3.146 Prospective Touch Voltage — The highest touch               3.156 Residual Current — The algebraic sum of the
voltage liable to appear in the event of a fault of               instantaneous values of current flowing through all live
negligible impedance in the electrical installation.              conductors of a circuit at a point of the electrical
                                                                  installation.
3.147 Protective Conductor — A conductor used for
some measures of protection against electric shock and            3.157 Residual Current Device (RCD) — A
                                                                                                                                     SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
intended for connecting together any of the following             mechanical switching device or association of devices
parts:                                                            intended to cause the opening of the contacts when the
                                                                  residual current attains a given value under specified
    a)   Exposed conductive parts,                                conditions.
    b)   Extraneous conductive parts,
                                                                  3.158 Residual Current Operated Circuit-Breaker
3.151 Protective Multiple Earthing (PME) —An                      3.161 Resistance Area (for an Earth Electrode only)
earthing arrangement, found in TN-C-S systems, in                 — The surface area of ground (around an earth
which the supply neutral conductor is used to connect             electrode) on which a significant voltage gradient may
the earthing conductor of an installation with Earth.             exist.
3.152 Protective Separation — Separation of one                   3.162 Response Time —The time that elapses between
electric circuit from another by means of:                        the failure of the normal power supply and the of the
                                                                  auxiliary power supply to energize the equipment
    a) Double insulation,
                                                                  3.163 Ring Final Circuit —A final circuit arranged
    b) Basic insulation and electrically protective
                                                                  in the form of a ring and connected to a single point of
       screening (shielding), or
                                                                  supply.
    c) Reinforced insulation.
                                                                  3.164 Safety Service —An electrical system for
3.153 Rated Current —Value of current used for                    electrical equipment provided to protect or warn
specification purposes, established for a specified set           persons in the event of a hazard, or essential to their
of operating conditions of a component, device,                   evacuation from a location.
equipment or system.
                                                                  3.165 SELV (Separated Extra Low-Voltage) — An
3.154 Rated Impulse Withstand Voltage Level (Uw)                  extra low-voltage system which is electrically separated
—The level of impulse withstand voltage assigned by               from earth and from other system in such a way that a
the manufacturer to the equipment, or to part of it,              single fault cannot give rise to the risk of electric shock.
characterizing the specified withstand capability of its
insulation against overvoltages.                                  3.166 Shock Current —A current passing through the
                                                                  body of a person or an animal and having
3.155 Reinforced Insulation — Single insulation                   characteristics likely to cause dangerous patho-
applied to live parts, which provides a degree of                 physiological effects.
protection against electric shock equivalent to double
                                                             13
IS 732 : 2019
3.167 Short-Circuit Current — An overcurrent                             handle and having such a mass that it cannot easily be
resulting from a fault of negligible impedance between                   moved.
live conductors having a difference in potential under
                                                                         3.176 Supplementary Insulation — Independent
normal operating conditions.
                                                                         insulation applied in addition to basic insulation in
3.168 Simple Separation —Separation between                              order to provide protection against electric shock in
circuits or between a circuit and earth by means of basic                the event of a failure of basic insulation.
insulation.
                                                                         3.177 Surge Current — A transient wave appearing
3.169 Simultaneously Accessible Parts — Conductors                       as an overcurrent caused by a lightning electromagnetic
or conductive parts which can be touched                                 impulse.
simultaneously by a person or, where applicable by                       3.178 Surge Protective Devices (SPD) — A device
livestock.                                                               that is intended to limit transient overvoltages and divert
                                                                                                                                       SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
   NOTE — In the context of protection against direct contacts a         surge currents. It contains at least one non-linear
   live part may be accessible with:                                     component.
   a) another live part, or
   b) an exposed conductive part, or                                     3.179 Switch — A mechanical switching device
   c) an extraneous conductive part, or                                  capable of making, carrying and breaking current under
                                                                    14
                                                                                                                              IS 732 : 2019
       and protective conductors are combined in a                        in the reasonable use of electrical installations. The
       single conductor throughout the system.                            requirements to provide for the safety of livestock are
    c) TN-S system — A system having separate                             applicable in locations intended for them.
       neutral and protective conductor throughout                           NOTE — In electrical installations, the following hazards may
       the system.                                                           arise:
    d) TN-C-S system — A system in which neutral                             a) shock currents;
       and protective conductors are combined in a                           b) excessive temperatures likely to cause burns, fires and other
                                                                             injurious effects;
       single conductor in part of the system.
                                                                             c) ignition of a potentially explosive atmosphere;
    e) TT system — A system having one point of                              d) undervoltages, overvoltages and electromagnetic influences
       the source of energy directly earthed, the                            likely to cause or result in injury or damage;
       exposed-conductive-parts of the installation                          e) power supply interruptions and/or interruption of safety
                                                                                                                                                    SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
       being connected to the earth electrodes                               services;
       electrically independent of the earth electrodes                      f) arcing, likely to cause blinding effects, excessive pressure,
                                                                             and/or toxic gases; and
       of the source.
                                                                             g) mechanical movement of electrically activated equipment.
    f) IT system — A system having no direct
       connection between live parts and Earth, the                       4.1.2 Protection Against Electric Shock
                                                                     15
IS 732 : 2019
and property shall be protected against damage due to                 following factors shall be taken into account to provide:
excessive temperatures or electromechanical stresses
                                                                          a) the protection of persons, livestock and
caused by any overcurrents likely to arise in conductors.
                                                                             property in accordance with 4.1.
Protection can be achieved by limiting the overcurrent                    b) the proper functioning of the electrical
to a safe value or duration.                                                 installation for the intended use.
4.1.2.5 Protection against fault currents                             The information required as a basis for design is listed
Conductors, other than live conductors, and any other                 in 4.1.3.2 to 4.1.3.5. The requirements with which the
parts intended to carry a fault current shall be capable              design shall comply are stated in 4.1.3.6 and 4.1.3.7.
of carrying that current without attaining an excessive               4.1.3.2 Characteristics of available supply or supplies
temperature. Electrical equipment, including
                                                                      When designing electrical installations in accordance
                                                                                                                                  SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
conductors shall be provided with mechanical
protection against electromechanical stresses of fault                with this standard it is necessary to know the
currents as necessary to prevent injury or damage to                  characteristics of the supply. Relevant information from
persons, livestock or property.                                       the network operator is necessary to design a safe
                                                                      installation according to this standard. The
Live conductors shall be protected against over currents              characteristics of the power supply should be included
                                                                 16
                                                                                                                     IS 732 : 2019
heating, power, control, signalling, information and                          g) other stresses to which the wiring can be
communication technology, etc shall be determined by:                            subjected during the erection of the electrical
    a)    location of points of power demand;                                    installation or in service.
    b)    loads to be expected on the various circuits;                   4.1.3.8 Protective equipment
    c)    daily and yearly variation of demand;
                                                                          The characteristics of protective equipment shall be
    d)    any special conditions such as harmonics;                       determined with respect to their function which may
    e)    requirements for control, signalling,                           be, for example, protection against the effects of:
          information and communication technology,
          etc; and                                                            a)   overcurrent (overload, short-circuit),
    f)    anticipated future demand if specified.                             b)   earth fault current,
4.1.3.4 Electric supply systems for safety services or                        c)   overvoltage, and
                                                                                                                                        SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
standby electric supply systems                                               d)   undervoltage and no voltage.
    a) Source of supply (nature, characteristics).                        The protective devices shall operate at values of current,
    b) Circuits to be supplied by the electric source                     voltage and time which are suitably related to the
       for safety services or the standby electrical                      characteristics of the circuits and to the possibilities of
                                                                     17
IS 732 : 2019
                                                                                                                                  SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                     installed in accordance with the instructions provided
    a)   Voltage — Electrical equipment shall be                     by the manufacturer of the equipment.
         suitable with respect to the maximum steady-
         state voltage (r.m.s. value for a.c.) likely to be          4.1.5.1.2 The characteristics of the electrical equipment,
         applied, as well as overvoltages likely to occur.           as determined in accordance with 4.1.4.2, shall not be
                                                                     impaired during erection.
4.1.4.3 Conditions of installation                                   4.1.5.1.7 Where necessary for safety purposes, suitable
                                                                     warning signs and/or notices shall be provided.
All electrical equipment shall be selected so as to
withstand safely the stresses and the environmental                  4.1.5.1.8 Where an installation is erected by using new
conditions (see 4.1.3.5) characteristic of its location              materials, inventions or methods leading to deviations
and to which it may be subjected. If, however, an item               from the rules of this standard, the resulting degree of
of equipment does not have by design the properties                  safety of the installation shall not be less than that
corresponding to its location, it may be used on                     obtained by compliance with this standard.
condition that adequate additional protection is
                                                                     4.1.5.1.9 In the case of an addition or alteration to an
provided as part of the completed electrical installation.
                                                                     existing installation, it shall be determined that the
4.1.4.4 Prevention of harmful effects                                rating and condition of existing equipment, which will
                                                                     have to carry any additional load, is adequate for the
All electrical equipment shall be selected so that it will
not cause harmful effects on other equipment or impair               altered circumstances. Furthermore, the earthing and
the supply during normal service including switching                 bonding arrangements, if necessary for the protective
operations. In this context, the factors which can have              measure applied for the safety of the addition or
an influence include, for example:                                   alteration, shall be adequate.
                                                                18
                                                                                                              IS 732 : 2019
placed in service and after any important modification                 under normal operating conditions; and
to confirm proper execution of the work in accordance               b) types of system earthing.
with this standard.
                                                                4.1.5.8.1 Current-carrying conductors depending on
4.1.5.3 Periodic verification                                   kind of current
It is recommended that every electrical installation is         The following arrangements of current-carrying
subjected to periodic verification.                             conductors under normal operating conditions are taken
4.1.5.4 Void                                                    into account in this standard:
                                                                   NOTE — The conductor arrangements described in this clause
4.1.5.5 Assessment of general characteristics                      are not exhaustive. They are included as examples of typical
                                                                   arrangements.
An assessment shall be made of the following
                                                                                                                                  SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
characteristics of the installation in accordance with              a)    Current carrying conductors in a.c. circuits
the clauses indicated:                                                    (see Fig. 2 to Fig. 6).
    a) the purposes for which the installation is
       intended to be used, its general structure and
       its supplies (4.1.5.9, 4.1.5.14 and 4.1.5.15);
                                                           19
IS 732 : 2019
                                                                                                                                               SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                                                             ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
                                            FIG. 6 T HREE-P HASE 4-WIRE (see Note 3)
   NOTE — PEL and PEM conductors are not live conductors                    of this standard. For this case, the figures may be completely
   although they carry operating current. Therefore, the designation        shown in solid lines.
   2-wire arrangement or 3-wire arrangement applies.                        4 The codes used have the following meanings:
4.1.5.8.2 Types of system earthing                                          First letter — Relationship of the power system to earth:
                                                                                T = direct connection of one point to earth; and
The following types of system earthing are taken into                           I = all live parts isolated from earth, or one point
account in this standard.                                                               connected to earth through a high impedance.
                                                                            Second letter — Relationship of the exposed-conductive-parts
   NOTES
                                                                            of the installation to earth:
   1 Figure 9 to Fig. 21 show examples of commonly used three-                  T = direct electrical connection of exposed-conductive-
   phase systems. Figure 22 to Fig. 26 show examples of commonly                        parts to earth, independently of the earthing of any
   used d.c. systems.                                                                   point of the power system; and
   2 The dotted lines indicate the parts of the system that are not             N = direct electrical connection of the exposed-
   covered by the scope of the standard, whereas the solid lines                        conductive-parts to the earthed point of the power
   indicate the part that is covered by the standard.                                   system (in a.c. systems, the earthed point of the
   3 For private systems, the source and/or the distribution system                     power system is normally the neutral point or, if a
   may be considered as part of the installation within the meaning                     neutral point is not available, a line conductor).
                                                                       20
                                                                                                                   IS 732 : 2019
                                                                                                                                   SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                      Fig. 11).
                           Protective conductor (PE)                     NOTE — For symbols, see explanation given in 4.1.5.8.2.
                                                                 21
IS 732 : 2019
                                                                                                       SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                     ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
  NOTE — Additional earthing of the PE in the distribution and in the installation must be provided.
         FIG. 11 TN-S SYSTEM WITH EARTHED PROTECTIVE CONDUCTOR AND NO DISTRIBUTED NEUTRAL
                                 CONDUCTOR T HROUGHOUT THE SYSTEM
                                                                22
                                                                                                                  IS 732 : 2019
2) TN-C-S system in which neutral and protective conductor functions are combined in a single conductor in a
part of the system (see Fig. 12 to Fig. 14).
  NOTE — For symbols, see explanation given in 4.1.3.2.
                                                                                                                                  SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                                                ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
  NOTE — Additional earthing of the PEN or PE in the installation must be provided.
              FIG. 12 TN-C-S SYSTEM 3-P HASE, 4-W IRE, WHERE PEN IS SEPARATED INTO PE AND N
                                     ELSEWHERE IN THE INSTALLATION
NOTE — Additional earthing of the PEN in the distribution and of the PE in the installation must be provided.
                    FIG. 13 TN-C-S SYSTEM 3-P HASE, 4-W IRE, WHERE PEN IS SEPARATED INTO
                                PE AND N AT THE ORIGIN OF THE INSTALLATION
                                                               23
IS 732 : 2019
                                                                                                                   SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                                 ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
  NOTE — Additional earthing of the PEN in the distribution and of the PE in the installation must be provided.
                FIG. 14 TN-C-S SYSTEM SINGLE-P HASE, 2-W IRE , WHERE THE PEN IS SEPARATED INTO
                                 PE AND N AT THE ORIGIN OF THE INSTALLATION
3) TN-C system in which neutral and protective conductor functions are combined in a single conductor throughout
the system (see Fig. 15).
  NOTE — For symbols, see explanation given in 4.1.5.8.2.
   FIG. 15 TN-C WITH NEUTRAL AND PROTECTIVE CONDUCTOR FUNCTIONS COMBINED IN A SINGLE CONDUCTOR
                                     T HROUGHOUT THE SYSTEM
                                                               24
                                                                                                                           IS 732 : 2019
b) Multiple source systems                                                 unintended paths. The essential design rules shown in
     NOTE — The multiple source system is shown for the TN
                                                                           Fig. 16 from a) to d) are given in the legend below
     system with the unique aim of providing EMC. The multiple             Fig. 16.
     source system is not shown for IT and TT systems because these
     systems are generally compatible with regard to EMC.                  The marking of the PE conductor shall be in accordance
                                                                           with IEC 60446.
In the case of an inappropriate design of an installation
forming part of a TN system with multiple sources some                     Any extension of the system shall be taken into account
of the operating current may flow through unintended                       with regard to the proper functioning of the protective
paths. These currents may cause                                            measures.
                                                                                                                                              SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                           provide a neutral conductor (see Fig. 17). In this case,
      c) electromagnetic interference.
                                                                           the protective conductor should have multiple
The system shown in Fig. 16 is a system where minor                        connections to earth.
partial operating currents flow as currents through
Key
a)   — No direct connection from either the transformer neutral point or the generator star point to earth is permitted.
b)   — The interconnection conductor between either the neutral points of the transformers or the generator star points shall be insulated.
       The function of this conductor is like a PEN; however, it shall not be connected to current-using equipment.
c)   — Only one connection between the interconnected neutral points of the sources and the PE shall be provided. This connection shall
       be located inside the main switchgear assembly.
d)   — Additional earthing of the PE in the installation must be provided.
               FIG. 16 TN-C-S MULTIPLE SOURCE SYSTEM WITH SEPARATE P ROTECTIVE CONDUCTOR AND
                              NEUTRAL CONDUCTOR TO CURRENT USING E QUIPMENT
                                                                      25
IS 732 : 2019
                                                                                                                                              SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                                                            ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
Key
a)   — No direct connection from either the transformer neutral point or the generator star point to earth is permitted.
b)   — The interconnection conductor between either the neutral points of the transformers or the generator star points shall be insulated.
       The function of this conductor is like a PEN; however, it shall not be connectedto current-using equipment.
c)   — Only one connection between the interconnected neutral points of the sources and the PE shall be provided. This connection shall
       be located inside the main switchgear assembly.
d)   — Additional earthing of the PE in the installation must be provided.
     FIG. 17 TN-C-S MULTIPLE SOURCE SYSTEM WITH P ROTECTIVE CONDUCTOR AND NO NEUTRAL CONDUCTOR
                           T HROUGHOUT THE SYSTEM FOR 2- OR 3-P HASE LOAD
                                                                    26
                                                                                       IS 732 : 2019
                                                                                                       SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                     ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
NOTE — Additional earthing of the PE in the installation must be provided.
FIG. 18 TT SYSTEM WITH SEPARATE NEUTRAL CONDUCTOR AND P ROTECTIVE CONDUCTOR T HROUGHOUT THE
                                        INSTALLATION
                                                            27
IS 732 : 2019
                                                                                                                                  SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                                                ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
  NOTE — Additional earthing of the PE in the installation must be provided.
    a) The system may be connected to earth via a sufficiently high impedance. This connection may be made, for example, at the
    neutral point, artificial neutral point, or a line conductor.
    b) The neutral conductor may or may not be distributed.
                                                              28
                                                                                                           IS 732 : 2019
Type a)
                                                                                                                            SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                                          ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
  NOTE — Additional earthing of the PE in the installation must be provided.
Type b)
                                                              29
IS 732 : 2019
Type a)
                                                                                                                             SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                                           ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
   NOTE — Additional earthing of the PEL in the installation must be provided.
Type b)
                                                               30
                                                                                                            IS 732 : 2019
Type a)
                                                                                                                              SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                                            ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
   NOTE — Additional earthing of the PE in the installation must be provided.
Type b)
                                                               31
IS 732 : 2019
4.1.5.8.2.4.4 TT-system
Type a)
                                                                               SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                             ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
  NOTE — Additional earthing of the PE in the installation must be provided.
Type b)
4.1.5.8.2.4.5 IT-system
Type a)
                                                                                                SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                              ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
1) — The system may be connected to earth via a sufficiently high impedance.
   NOTE — Additional earthing of the PE in the installation must be provided.
Type b)
                                                                33
IS 732 : 2019
                                                                                                                               SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
       origin of the installation;                                4.1.5.12 Compatibility
    d) the earth fault loop impedance of that part of
       the system external to the installation;                   4.1.5.12.1 Compatibility of characteristics
    e) the suitability for the requirements of the                An assessment shall be made of any characteristics of
       installation, including the maximum demand;                equipment likely to have harmful effects upon other
                                                             34
                                                                                                                         IS 732 : 2019
the requirements of 4 to 6 so that, having regard to the                           e)   long break: an automatic supply available in
frequency and quality of maintenance expected:                                          more than 15 s.
    a) any periodic inspection and testing,                                    4.1.5.15 Continuity of service
       maintenance and repairs likely to be necessary
                                                                               An assessment shall be made for each circuit of any
       during the intended life can be readily and
                                                                               need for continuity of service considered necessary
       safely carried out;
                                                                               during the intended life of the installation. The
    b) the effectiveness of the protective measures                            following characteristics should be considered:
       for safety during the intended life shall remain,
       and                                                                         a) selection of the system earthing,
    c) the reliability of equipment for proper                                     b) selection of the protective device in order to
       functioning of the installation is appropriate                                 achieve discrimination,
                                                                                                                                           SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
       to the intended life.                                                       c) number of circuits,
4.1.5.14 Safety services                                                           d) multiple power supplies, and;
                                                                                   e) use of monitoring devices.
4.1.5.14.1 General
                                                                               4.2 Protection for Safety—Protection against
                                                                          35
IS 732 : 2019
Additional protection is specified as part of a protective             installation or part of an installation or within equipment
measure under certain conditions of external influences                shall have no influence on each other such that failure
and in certain special locations (see IEC 60364-7).                    of one protective measure could impair the other
                                                                       protective measures.
   NOTES
   1 For special applications, protective measures which do not        4.2.10 The provision for fault protection (protection
   follow this concept are permitted (see 4.2.6 and 4.2.7).            against indirect contact) may be omitted for the
   2 An example of an enhanced protective measure is reinforced        following equipment:
   insulation.
4.2.3 In each part of an installation one or more                          a) metal supports of overhead line insulators
protective measures shall be applied, taking into                             which are attached to the building and are
                                                                              placed out of arm’s reach;
account of the conditions of external influence.
                                                                           b) steel reinforced concrete poles of overhead
                                                                                                                                           SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
The following protective measures generally are                               lines in which the steel reinforcement is not
permitted:                                                                    accessible;
    a) automatic disconnection of supply (4.2.11),                         c) exposed conductive parts which, owing to
    b) double or reinforced insulation (4.2.12),                              their reduced dimensions (approximately 50
    c) electrical separation for the supply of one item                       mm × 50 mm) or their disposition cannot be
                                                                  36
                                                                                                                             IS 732 : 2019
provisions for basic protection (protection against direct              Conductors for protective equipotential bonding shall
contact) described in Annex A or, where appropriate,                    comply with 5.4 and IS 3043.
Annex B.
                                                                        Any metallic sheath of telecommunication cables shall
4.2.11.3 Requirements for fault protection                              be connected to the protective equipotential bonding,
                                                                        taking account of the requirements of the owners or
4.2.11.3.1 Protective earthing and protective
                                                                        operators of these cables.
equipotential bonding
                                                                        4.2.11.3.2 Automatic disconnection in case of a fault
4.2.11.3.1.1 Protective earthing
                                                                        4.2.11.3.2.1 Except as provided by 4.2.11.3.2.5
Exposed conductive parts shall be connected to a
                                                                        and 4.2.11.3.2.6, a protective device shall automatically
protective conductor under the specific conditions for
                                                                        interrupt the supply to the line conductor of a circuit or
each type of system earthing as specified in 4.2.11.4
                                                                                                                                                  SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                        equipment in the event of a fault of negligible
to 4.2.11.6.
                                                                        impedance between the line conductor and an exposed-
Simultaneously accessible exposed conductive parts                      conductive-part or a protective conductor in the circuit
shall be connected to the same earthing system                          or equipment within the disconnection time required
individually, in groups or collectively.                                in 4.2.11.3.2.2, 4.2.11.3.2.3 or 4.2.11.3.2.4.
    System               50 V <Uo < 120 V                120 V <Uo < 230 V                230 V <Uo < 400 V                 Uo > 400 V
                                s                                s                                s                              s
                       a.c.          d.c.                a.c.          d.c.               a.c.          d.c.              a.c.       d.c.
       (1)             (2)              (3)              (4)            (5)                (6)              (7)           (8)          (9)
       TN              0.8            Note 1             0.4             5                 0.2              0.4            0.1         0.1
       TT              0.3            Note 1             0.2            0.4               0.07              0.2           0.04         0.1
 Where in TT systems the disconnection is achieved by an overcurrent protective device and the protective equipotential bonding is
 connected with all extraneous-conductive-parts within the installation, the maximum disconnection times applicable to TN systems may
 be used.
 Uo is the nominal a.c. or d.c. line to earth voltage.
 NOTES
 1 Disconnection may be required for reasons other than protection against electric shock.
 2 Where disconnection is provided by an RCD see Note to 4.2.11.4.4, Note 4 to 4.2.11.5.3 and Note to 4.2.11.6.4.
                                                                   37
IS 732 : 2019
by 4.2.11.3.2.2, 4.2.11.3.2.3, or 4.2.11.3.2.4 as                              that the protective conductors also be connected to such points
                                                                               wherever possible. Earthing at additional points, distributed as
appropriate, supplementary protective equipotential
                                                                               evenly as possible, may be necessary to ensure that the potentials
bonding shall be provided in accordance with 4.2.15.2.                         of protective conductors remain, in case of a fault, as near as
                                                                               possible to that of earth. In large buildings such as h i g h - ri s e
4.2.11.3.3 Additional protection                                               buildings, additional earthing of protective conductors is not
                                                                               possible for practical reasons. In such buildings protective-
In a.c. systems, additional protection by means of a
                                                                               equipotential-bonding between protective conductors and
residual current protective device (RCD) in accordance                         extraneous-conductive-parts has, however, a similar function.
with 4.2.15.1 shall be provided for:                                           2 It is recommended that protective conductors (PE and PEN)
                                                                               should be earthed where they enter any buildings or premises
    a) at the incomer of every sub-distribution board                          taking account of any diverted neutral currents.
       having one or more outgoing circuits with
       fixed installation and socket-outlets to ensure                      4.2.11.4.3 In fixed installations, a single conductor may
                                                                            serve both as a protective conductor and as a neutral
                                                                                                                                                        SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
       safety of user from earth leakage, and
    b) mobile equipment.                                                    conductor (PEN conductor) provided that the
                                                                            requirements of 5.4.3.4 are satisfied. No switching or
System voltages independent RCD not exceeding                               isolating device shall be inserted in the PEN conductor.
30 mA shall be used for domestic and similar
application of a particular item of equipment.                              4.2.11.4.4 The characteristics of the protective devices
                                                                       38
                                                                                                                               IS 732 : 2019
be used in TN-C systems.                                                    high impedance. This connection may be made either
                                                                            at the neutral point or mid-point of the system or at an
Where an RCD is used in a TN-C-S system, a PEN
                                                                            artificial neutral point. The latter may be connected
conductor shall not be used on the load side. The
                                                                            directly to earth if the resulting impedance to earth is
connection of the protective conductor to the PEN
                                                                            sufficiently high at the system frequency. Where no
conductor shall be made on the source side of the RCD.
                                                                            neutral point or mid-point exists, a line conductor may
   NOTE — Where discrimination between RCDs is necessary,                   be connected to earth through a high impedance.
   see 5.3.6.3.
                                                                            The fault current is then low in the event of a single
4.2.11.5 TT system                                                          fault to an exposed conductive part or to earth and
4.2.11.5.1 All exposed conductive parts collectively                        automatic disconnection in accordance with 4.2.11.3.2
protected by the same protective device shall be                            is not imperative provided the condition in 4.2.11.6.2
                                                                                                                                                    SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
connected by the protective conductors to an earth                          is fulfilled. Provisions shall be taken, however, to avoid
electrode common to all those parts. Where several                          risk of harmful patho-physiological effects on a person
protective devices are utilized in series, this requirement                 in contact with simultaneously accessible exposed
applies separately to all the exposed-conductive-parts                      conductive parts in the event of two faults existing
protected by each device.                                                   simultaneously.
                                                                       39
IS 732 : 2019
visual signal which shall continue as long as the fault                        protective device within the time required
persists.                                                                      in 4.2.11.3.2.2 for TN systems
                                                                               or 4.2.11.3.2.3.
If there are both audible and visible signals, it is
                                                                              NOTES
permissible for the audible signal to be cancelled.
                                                                              1 The time stated in Table 1 of 4.2.11.3.2.2 for the TN
   NOTE — It is recommended that a first fault be eliminated                  system is applicable to IT systems with a distributed or
   with the shortest practicable delay.                                       non-distributed neutral conductor or mid-point
                                                                              conductor.
4.2.11.6.3.2 Except where a protective device is                              2 The factor 2 in both formulas takes into account that
installed to interrupt the supply in the event of the first                   in the event of the simultaneous occurrence of two faults,
earth fault, an RCM or an insulation fault location                           the faults may exist in different circuits.
system may be provided to indicate the occurrence of                          3 For fault loop impedance, the most severe case should
a first fault from a live part to exposed conductive parts                    be taken into account, for example, a fault on the line
                                                                                                                                           SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                              conductor at the source and simultaneously another fault
or to earth. This device shall initiate an audible and/or                     on the neutral conductor of a current-using equipment
visual signal, which shall continue as long as the fault                      of the circuit considered.
persists.                                                               b) Where the exposed-conductive-parts are
If there are both audible and visual signals it is                         earthed in groups or individually, the
                                                                           following condition applies:
          or where the neutral conductor or mid-point               Where, for functional reasons, a nominal voltage not
          conductor respectively is distributed:                    exceeding 50 V a.c. or 120 V d.c. is used but all the
                                                                    requirements of 4.2.14 relating to SELV or to PELV
                       2IaZ's < Uo                                  are not fulfilled, and where SELV or PELV is not
   where                                                            necessary, the supplementary provisions described
                                                                    in 4.2.11.7.2 and 4.2.11.7.3 shall be taken to ensure
   Uo = the nominal a.c. or d.c. voltage, in V, between
                                                                    basic protection and fault protection. This combination
        line conductor and neutral conductor or mid-
                                                                    of provisions is known as FELV.
        point conductor, as appropriate;
   U     = the nominal a.c. or d.c. voltage in V between               NOTE — Such conditions may, for example, be encountered
                                                                       when the circuit contains equipment (such as transformers,
           line conductors;                                            relays, remote-control switches, contactors) insufficiently
   Zs = the impedance in Ω of the fault loop                           insulated with respect to circuits at higher voltage.
        comprising the line conductor and the                       4.2.11.7.2 Requirements for basic protection
        protective conductor of the circuit;
                                                                    Basic protection shall be provided by either,
   Z's = the impedance in Ω of the fault loop
         comprising the neutral conductor and the                       a)    basic insulation according to A-1
         protective conductor of the circuit; and                             corresponding to the nominal voltage of the
   Ia    = the current in A causing operation of the                          primary circuit of the source, or
                                                               40
                                                                                                                            IS 732 : 2019
                                                                                                                                                 SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
The source of the FELV system shall be either a
                                                                            Where the protective measure, using double or
transformer with at least simple separation between
                                                                            reinforced insulation, is used for the complete
windings or shall comply with 4.2.14.3.
                                                                            installation or part of the installation, electrical
   NOTE — If the system is supplied from a higher voltage system            equipment shall comply with one of the following sub-
   by equipment which does not provide at least simple separation
    a) plugs shall not be able to enter socket-outlets                          a) electrical equipment having double or
       of other voltage systems,                                                   reinforced insulation (Class II equipment);
    b) socket-outlets shall not admit plugs of other                            b) electrical equipment declared in the relevant
       voltage systems, and                                                        product standard as equivalent to Class II, such
                                                                                   as assemblies of electrical equipment having
    c) socket-outlets shall have a protective
                                                                                   total insulation [see IS 8623 (Part 1)].
       conductor contact.
                                                                                      NOTE — This equipment is identified by the symbol
4.2.12 Protective Measure: Double or Reinforced
                                                                                         see IS 12032.
Insulation
4.2.12.1 General                                                            4.2.12.2.1.2 Electrical equipment having basic
                                                                            insulation only shall have supplementary insulation
4.2.12.1.1 Double or reinforced insulation is a                             applied in the process of erecting the electrical
protective measure in which,                                                installation, providing a degree of safety equivalent to
    a) basic protection is provided by basic                                electrical equipment according to 4.2.12.2.1.1 and
       insulation, and fault protection is provided by                      complying with 4.2.12.2.2.1 to 4.2.12.2.2.3.
       supplementary insulation, or                                            NOTE — The symbol         should be fixed in a visible position
    b) basic and fault protection is provided by                               on the exterior and interior of the enclosure [see IEC 60417-
       reinforced insulation between live parts and                            5019 (DB: 2002-10) : Protective earth (ground)].
       accessible parts.                                                    4.2.12.2.1.3 Electrical equipment having uninsulated
          NOTE — This protective measure is intended to prevent             live parts shall have reinforced insulation applied in
          the appearance of dangerous voltage on the accessible             the process of erecting the electrical installation,
          parts of electrical equipment through a fault in the basic
          insulation.                                                       providing a degree of safety equivalent to electrical
                                                                            equipment according to 4.2.12.2.1.1 and complying
4.2.12.1.2 The protective measure by double or                              with 4.2.12.2.2.2 and 4.2.12.2.2.3; such insulation
reinforced insulation is applicable in all situations,                      being recognized only where constructional features
unless some limitations are as given in IEC 60364-7.                        prevent the application of double insulation.
4.2.12.1.3 Where this protective measure is to be used                         NOTE — The symbol         should be fixed in a visible position
as the sole protective measure (that is, where a whole                         on the exterior and interior of the enclosure [see IEC 60417-
installation or circuit is intended to consist entirely of                     019 (DB: 2002-10): Protective earth (ground)].
                                                                       41
IS 732 : 2019
                                                                                                                                         SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
       potential; and
    b) the insulating enclosure shall not contain any             4.2.12.2.4.1 Wiring systems installed in accordance
       screws or other fixing means of insulating                 with 5.2 are considered to meet the requirements
       material which might need to be removed, or                of 4.2.12.2 if:
       are likely to be removed, during installation                  a) the rated voltage of the wiring system shall be
                                                             42
                                                                                                                                  IS 732 : 2019
4.2.13.1.3 Where more than one item of current-using                             This protective measure requires:
equipment is supplied from an unearthed source with
                                                                                     a) limitation of voltage in the SELV or PELV
simple separation, the requirements of C-3 shall be met.
                                                                                        system to the upper limit of Voltage Band I,
4.2.13.2 Requirements for basic protection                                              50 V a.c. or 120 V d.c. [see IS 12360 (Part
                                                                                        2)],
All electrical equipment shall be subject to one of the
basic protective provisions given in Annex A or to the                               b) protective separation of the SELV or PELV
protective measure in 4.2.12.                                                           system from all circuits other than SELV and
                                                                                        PELV circuits, and basic insulation between
4.2.13.3 Requirements for fault protection                                              the SELV or PELV system and other SELV or
4.2.13.3.1 Protection by electrical separation shall be                                 PELV systems; and
ensured by compliance with 4.2.13.3.2 to 4.2.13.3.6.                                 c) for SELV systems only, basic insulation
                                                                                                                                                       SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                        between the SELV system and earth.
4.2.13.3.2 The separated circuit shall be supplied
through a source with at least simple separation, and                            4.2.14.1.2 The use of SELV or PELV according
the voltage of the separated circuit shall not exceed                            to 4.2.14 is considered as a protective measure in all
500 V.                                                                           situations.
4.2.13.3.6 The exposed conductive parts of the                                   4.2.14.3 Sources for SELV and PELV
separated circuit shall not be connected either to the
protective conductor or exposed conductive parts of                              The following sources may be used for SELV and PELV
other circuits, or to earth.                                                     systems.
   NOTE — If the exposed-conductive-parts of the separated circuit               4.2.14.3.1 A safety isolating transformer in accordance
   are liable to come into contact, either intentionally or fortuitously,        with IEC 61558-2-6.
   with the exposed-conductive-parts of other circuits, protection
   against electric shock no longer depends solely on protection by              4.2.14.3.2 A source of current providing a degree of
   electrical separation but on the protective provisions to which               safety equivalent to that of the safety isolating
   the latter exposed-conductive-parts are subject.                              transformer specified in 4.2.14.3.1 (for example, motor
4.2.14 Protective Measure: Extra-Low-Voltage                                     generator with windings providing equivalent
Provided by SELV and PELV                                                        isolation).
4.2.14.1 General                                                                 4.2.14.3.3 An electrochemical source (for example, a
                                                                                 battery) or another source independent of a higher
4.2.14.1.1 Protection by extra-low-voltage is a                                  voltage circuit (for example, a diesel-driven generator).
protective measure which consists of either of two
different extra-low-voltage systems:                                             4.2.14.3.4 Certain electronic devices complying with
                                                                                 appropriate standards where provisions have been taken
     –     SELV; or                                                              in order to ensure that, even in the case of an internal
     –     PELV.                                                                 fault, the voltage at the outgoing terminals cannot
                                                                            43
IS 732 : 2019
exceed the values specified in 4.2.14.1.1. Higher                                 c) circuit conductors at voltages higher than
voltages at the outgoing terminals are, however,                                     Band I may be contained in a multi-conductor
permitted if it is ensured that, in case of contact with a                           cable or other grouping of conductors if the
live part or in the event of a fault between a live part                             SELV and PELV conductors are insulated for
and an exposed-conductive-part, the voltage at the                                   the highest voltage present;
output terminals is immediately reduced to those values                           d) the wiring systems of other circuits are in
or less.                                                                             compliance with 4.2.12.2.4.1; and
   NOTES                                                                          e) physical separation.
   1 Examples of such devices include insulation testing equipment
                                                                              4.2.14.4.3 Plugs and socket-outlets in SELV and PELV
   and monitoring devices.
                                                                              systems shall comply with the following requirements:
   2 Where higher voltages exist at the outgoing terminals,
   compliance with this clause may be assumed if the voltage at                   a) plugs shall not be able to enter socket-outlets
                                                                                                                                                      SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
   the outgoing terminals is within the limits specified in 4.2.14.1.1
   when measured with a voltmeter having an internal resistance
                                                                                     of other voltage systems;
   of at least 3 000 Ω.                                                           b) socket-outlets shall not admit plugs of other
                                                                                     voltage systems; and
4.2.14.3.5 Mobile sources supplied at low voltage, for
example, safety isolating transformers or motor                                   c) plugs and socket-outlets in SELV systems shall
                                                                         44
                                                                                                                               IS 732 : 2019
                                                                                                                                                    SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
protective equipotential bonding                                            not present a fire hazard to adjacent materials.
   NOTES                                                                       NOTE — Damage, injury or ignition may be caused by effects
   1 Supplementary protective equipotential bonding is considered              such as
   as an addition to fault protection.
                                                                                  i) heat accumulation, heat radiation, hot elements,
   2 The use of supplementary protective bonding does not exclude
           the emissions at a sufficient distance from                          erected that its temperature in normal use and
           material upon which the emissions could have                         foreseeable temperature rise during a fault cannot cause
           harmful effects.                                                     a fire.
Arc-resistant material used for this protective measure                         These arrangements may be effected by the construction
shall be non-ignitable, of low thermal conductivity, and                        of equipment or its conditions of installation.
of adequate thickness to provide mechanical stability.
                                                                                Special measures are not necessary where the
   NOTE — For example, a sheet made of fibreglass silicone of                   temperature of surfaces is unlikely to cause ignition of
   20 mm thickness may be considered as arc-resistant.
                                                                                nearby substances.
4.3.1.4 Fixed equipment causing a concentration of heat                         4.3.2.1.3 Thermal cut-out devices shall have manual
shall be at a sufficient distance from any fixed object                         resetting only.
or building element so that the object or element, in
                                                                                                                                                       SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
normal conditions, is not subjected to a dangerous                              4.3.2.2 Conditions of evacuation in an emergency
temperature.                                                                    Condition BD2: Low density occupation, difficult
For example, a temperature in excess of its ignition                                      conditions of evacuation
temperature.                                                                              BD3: High density occupation, easy
                                                                           46
                                                                                                                         IS 732 : 2019
Wiring within escape routes shall have a limited rate                     normally flammable surfaces are marked with symbols:
of smoke production.
4.3.2.2.2 In conditions BD2, BD3 and BD4, switchgear                                                 and/or
and controlgear devices, except certain devices to
                                                                          (see N.4 of IEC 60598-1 : 2008 for further
facilitate evacuation, shall be accessible only to
                                                                          explanations).
authorized persons. If they are placed in passages, they
shall be enclosed in cabinets or boxes constructed of                     4.3.2.3.2 Measures shall be taken to prevent an
non-combustible or not readily combustible material.                      electrical enclosure of equipment such as a heater or
   NOTE —This clause does not prohibit plastic enclosures that            resistor from exceeding the following temperatures:
   are not readily combustible.
                                                                              a) 90 °C under normal conditions, and
4.3.2.2.3 In conditions BD3 and BD4 and in escape                             b) 115 °C under fault conditions.
                                                                                                                                              SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
routes, electrical equipment containing flammable
liquids shall not be installed.                                           Where materials such as dust or fibres sufficient to
                                                                          cause a fire hazard could accumulate on an enclosure
   NOTE — Individual capacitors incorporated in equipment are             of electrical equipment, adequate measures shall be
   not subject to this requirement. This exception principally
   concerns discharge luminaires and capacitors of motor starters.
                                                                          taken to prevent that enclosure from exceeding the
                                                                     47
IS 732 : 2019
4.3.2.3.5 Wiring systems which traverse these locations,                    specified in (a) may be used. In the event of a
but are not necessary for the use of the locations, shall                   second fault, see 4.2.11 for disconnection
satisfy the following conditions:                                           times.
    a) the wiring systems shall meet the requirements              Mineral insulated cables and busbar trunking systems
       of 4.3.2.3.5;                                               are not considered likely to cause a fire from insulation
                                                                   faults and therefore need not be protected.
    b) they have no connection along the route inside
       the locations, unless these connections are                    NOTE — Cables with metallic coverings are recommended.
                                                                      The metallic covering should be connected to the protective
       placed in fire-resistant enclosures;                           conductor.
    c) they are protected against overcurrent in
       accordance with 4.3.2.3.10; and                             4.3.2.3.10 Circuits supplying or traversing locations
                                                                   where condition BE2 applies, shall be protected against
    d) bare conductors shall not be used.
                                                                                                                                    SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                   overload and short-circuit by protective devices located
4.3.2.3.6 In forced-air heating installations, the air             outside and on the supply side of these locations.
intake shall be outside locations where a presence of              Circuits originating inside the locations shall be
combustible dust may be expected.                                  protected against overcurrent by protective devices
                                                                   located at their origin.
The temperature of the outgoing air shall not be such
                                                              48
                                                                                                                                 IS 732 : 2019
4.3.2.4.2 Luminaires shall be kept at an adequate                               significant value. Examples include: national monuments,
                                                                                museums and other public buildings. Buildings such as railway
distance from combustible materials. If no other
                                                                                stations and airports, buildings or facilities such as laboratories,
information is given by manufacturers, spotlights and                           computer centres and certain industrial and storage facilities.
projectors shall be installed at the following minimum                          2 The following measures may be considered:
distances from combustible materials:                                           a) installation of mineral insulated cables according to
                                                                                    IEC 60702-1;
    100 W                         0.5 m
                                                                                b) installation of cables with improved fire-resisting
    100 W to 300 W                0.8 m                                             characteristics in case of a fire hazard, and complying with
    300 W to 500 W                1.0 m                                             IEC 60331-1 or IEC 60331-21 or similar;
                                                                                c) installation of cables in non-combustible solid walls,
    above 500 W                   greater distances can be                          ceilings and floors;
                                  necessary.                                    d) installation of cables in areas with constructional partitions
   NOTE — In the absence of manufacturers’ instructions, the                        having a fire-resisting capability for a time of 30 min or 90
                                                                                                                                                       SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
   above distances imply all directions.                                            min, the latter in locations housing staircases and needed
                                                                                    for an emergency escape.
Lamps and other components of luminaires shall be
                                                                             Where these measures are not practicable, enhanced
protected against foreseeable mechanical stresses. Such
                                                                             fire protection may be possible by use of reactive fire
protective means shall not be fixed on lampholders,
                                                                             protection systems.
unless they form an integral part of the luminaire.
4.3.2.6 Selection and erection of installations in                           Forced air heating systems shall be such that their
locations with endangering of irreplaceable goods                            heating elements, other than those of central storage
                                                                             heaters, cannot be activated until the prescribed air flow
The requirements of 4.3.2.1.2 shall be met.                                  has been established and are deactivated when the air
   NOTES                                                                     flow is less than the prescribed value. In addition, they
   1 The locations include buildings or rooms with assets of                 shall have two temperature limiting devices
                                                                        49
IS 732 : 2019
independent of each other which prevent permissible                     appropriate precautions shall be taken.
temperatures from being exceeded in air ducts.
                                                                        4.4.2.1.2 In a TT or TN system, for a circuit supplied
Supporting parts, frames and enclosures of heating                      between line conductors and in which the neutral
elements shall be of non-combustible material.                          conductor is not distributed, overcurrent detection need
                                                                        not be provided for one of the line conductors, provided
4.3.4.2 Appliances producing hot water or steam
                                                                        that the following conditions are simultaneously
All appliances producing hot water or steam shall be                    fulfilled:
protected by design or erection against overheating in
                                                                            a) there exists, in the same circuit or on the supply
all service conditions. Unless the appliances comply
                                                                               side, protection intended to detect unbalanced
as a whole with the appropriate Indian standards, the
                                                                               loads and intended to cause disconnection of
protection shall be by means of an appropriate non-
                                                                               all the line conductors; and
                                                                                                                                               SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
self-resetting device, functioning independently of the
thermostat.                                                                 b) the neutral conductor is not distributed from
                                                                               an artificial neutral point of the circuits
If an appliance has no free outlet, it shall also be                           situated on the load side of the protective
provided with a device which limits the internal water                         device mentioned in (a).
pressure.
                                                                                                                                               SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                         NOTES
       sufficient breaking capacity for all poles.
                                                                         1 These devices are generally inverse time lag protective devices.
         NOTE — In IT systems, it is strongly recommended                2 Fuses type aM do not protect against overload.
         that the neutral conductor should not be distributed.
                                                                      4.4.3.3 Devices ensuring protection against short-
4.4.2.2.3 Harmonic currents                                           circuit current only
   NOTE — Further requirements regarding protection of neutral            a) circuit-breakers with short-circuit release only,
   conductors are given in 5.2.                                              and
4.4.2.3 Disconnection and reconnection of the                             b) fuses with gM, aM type fuse links.
neutral conductor in multi-phase systems                              4.4.3.4 Characteristics of protective devices
Where disconnection of the neutral conductor is                       The operating characteristics of overcurrent protective
required, disconnection and reconnection shall be such                devices shall comply with those specified in, for
that the neutral conductor shall not be disconnected                  example,      IS/IEC 60898,         IS/IEC 60947-2,
before the line conductors and shall be reconnected at                IS/IEC 60947-6-2, IS 12640 (Part 2), IS 13703 (Part 2),
the same time as or before the line conductors.                       IEC 60269-3, IS 13730 (Part 4) or IS/IEC 60947-3.
4.4.3 Nature of Protective Devices                                       NOTE — The use of other devices is not excluded provided
                                                                         that their time/current characteristics provide an equivalent level
The protective devices shall be of the appropriate types                 of protection to that specified in this clause.
indicated by 4.4.2.1 to 4.4.2.3.
                                                                      4.4.4 Protection Against Overload Current
4.4.3.1 Devices providing protection against both
overload current and short-circuit current                            4.4.4.1 Coordination between conductors and overload
                                                                      protective devices
Except as stated in 4.4.5.5.1, a device providing
protection against both overload and short-circuit                    The operating characteristics of a device protecting a
current shall be capable of breaking and, for a circuit-              cable against overload shall satisfy the two following
breaker, making any overcurrent up to and including                   conditions:
the prospective short-circuit current at the point where                           IB < In < IZ                                    ... (1)
the device is installed. Such devices may be:                                      I2 < 1.45 × IZ                                  ... (2)
    a) circuit-breakers incorporating overload and                    where
       short-circuit release;
                                                                         IB    = the design current for that circuit;
    b) circuit-breakers in conjunction with fuses; and
                                                                         IZ    = the continuous current-carrying capacity of
    c) fuses having fuse links with gG characteristics.
                                                                                 the cable (see 5.2.6);
                                                                 51
IS 732 : 2019
   In    = the rated current of the protective device;                      4.4.4.3 Omission of devices for protection against
            NOTE — For adjustable protective devices, the rated             overload
            current In is the current setting selected.
                                                                            The various cases stated in this sub-clause shall not be
   I2    = the current ensuring effective operation in                      applied to installations situated in locations presenting
           the conventional time of the protective                          a fire risk or risk of explosion or where the requirements
           device.                                                          for special installations and locations specify different
The current I2 ensuring effective operation of the                          conditions.
protective device shall be provided by the manufacturer
                                                                            4.4.4.3.1 General
or as given in the product standard.
                                                                            Devices for protection against overload need not be
Protection in accordance with this clause may not
                                                                            provided:
ensure protection in certain cases, for example where
                                                                                                                                          SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
sustained overcurrents less than I2 occur. In such cases,                       a) for a conductor situated on the load side of a
consideration should be given to selecting a cable with                              change in cross-sectional area, nature, method
a larger cross-sectional area.                                                       of installation or in constitution, that is
   NOTES
                                                                                     effectively protected against overload by a
                                                                                     protective device placed on the supply side;
                                                                       52
                                                                                                                       IS 732 : 2019
   NOTE — It is recommended to install an insulation fault                unequal if the difference between any currents is more than 10
   location system. With the application of such a system it is           percent of the design current for each conductor. Guidance is
   possible to                                                            given in G-2.
detect and locate the insulation fault without                         4.4.5 Protection Against Short-Circuit Currents
interruption of the supply.
                                                                       This standard only considers the case of short-circuit
4.4.4.3.2.2 In IT systems without a neutral conductor,                 between conductors belonging to the same circuit.
the overload protective device may be omitted in one
                                                                       4.4.5.1 Determination of prospective short-circuit
of the phase conductors if a residual current protective
                                                                       currents
device is installed in each circuit.
                                                                       The prospective short-circuit current at every relevant
4.4.4.3.3 Cases where omission of devices for overload
                                                                       point of the installation shall be determined. This may
protection shall be considered for safety reasons
                                                                       be carried out either by calculation or by measurement.
                                                                                                                                           SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
The omission of devices for protection against overload                   NOTE — The prospective short-circuit current at the supply
is permitted for circuits supplying current-using                         point may be obtained from the supply utility.
equipment where unexpected disconnection of the
circuit could cause danger or damage. Examples of such                 4.4.5.2 Position of devices for short-circuit protection
                                                                  53
IS 732 : 2019
                                                                                                                                      SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
              the protective devices being placed in                protective device having the necessary breaking
              these panels;                                         capacity is installed on the supply side. In that case,
         b) circuits where disconnection could cause                the characteristics of the devices shall be coordinated
              danger for the operation of the                       so that the energy let through by these two devices does
              installations concerned, such as those                not exceed that which can be withstood without damage
    a) The wiring shall be carried out in such a way                                    t = (k × S/I)2                     ... (3)
                                                                    where
       as to reduce to a minimum the risk of a short-
       circuit in any parallel conductor, for example,                 t    = the duration, in s;
       by protection against mechanical damage, and                    S    = the cross-sectional area, in mm2;
       conductors shall be installed in such a manner                  I    = the effective short-circuit current, in A,
       as to reduce to a minimum the risk of fire or                          expressed as an r.m.s. value; and
       danger to persons.
                                                                       k    = a factor taking account of the resistivity,
    b) For two conductors in parallel, a short-circuit                        temperature coefficient and heat capacity of
       protective device shall be provided at the                             the conductor material, and the appropriate
       supply end of each parallel conductor.                                 initial and final temperatures. For common
    c) For more than two conductors in parallel,                              conductor insulation, the values of k for line
       short-circuit protective devices shall be                              conductors are shown in Table 3.
       provided at the supply and load ends of each
       parallel conductor.
                                                               54
                                                                                                                             IS 732 : 2019
                                                                                                                                             SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
 Conductor material:
 Copper                            115         103     100           86              143              141            115        135-1151)
 Aluminium                          76          68      66           57              94               93              –              –
 Tin-soldered joints in copper     115          –       –            –                –                –              –              –
 conductors
4.4.5.5.3 For busbar trunking systems complying with                           4.4.6.2 Protection Afforded by Separate Devices
IEC 61439-2 and powertrack complying with the
                                                                               The requirements of 4.4.4 and 4.4.5 apply, respectively,
IEC 61534 series, one of the following requirements
                                                                               to the overload protective device and the short-circuit
shall apply:
                                                                               protective device.
      a) The rated short-time withstand current (ICW)
                                                                               The characteristics of the devices shall be coordinated so
         and the rated peak withstand current of a
                                                                               that the energy let through by the short-circuit protective
         busbar trunking or powertrack system shall not
                                                                               device does not exceed that which can be withstood
         be lower than the prospective short-circuit
                                                                               without damage by the overload protective device.
         current r.m.s. value and the prospective short-
         circuit peak current value, respectively. The                            NOTE — This requirement does not exclude the type of
                                                                                  coordination specified in IS/ IEC 60947-4-1.
         maximum time for which the ICW is defined
         for the busbar trunking or powertrack system                          4.4.7 Limitation of overcurrent by characteristics of
         shall not be less than the maximum operating                          supply
         time of the protective device.
                                                                               Conductors are considered to be protected against
      b) The rated conditional short-circuit current of
                                                                               overload and short-circuit currents where they are
         the busbar trunking or powertrack system
                                                                               supplied from a source incapable of supplying a current
         associated with a specific protective device,
                                                                               exceeding the current-carrying capacity of the
         shall not be lower than the prospective short-
                                                                               conductors (for example, certain bell transformers,
         circuit current.
                                                                               certain welding transformers and certain types of
4.4.6 Coordination of Overload and Short-Circuit                               thermoelectric generating sets).
Protection
                                                                               4.5 Protection for Safety — Protection Against Voltage
4.4.6.1 Protection afforded by one device                                      Disturbance and Electromagnetic Disturbance
A protective device providing protection against                               4.5.1 Void
overload and short-circuit currents shall fulfil the
applicable requirements of 4.4.4 and 4.4.5.                                    4.5.2 Protection of Low-voltage Installations against
                                                                               Temporary Overvoltages Due to Earth Faults in the
                                                                          55
IS 732 : 2019
High-voltage System and Due to Faults in the Low-                         low-voltage system neutral, for low-voltage
voltage System                                                            systems in which the earthing arrangements
                                                                          of the transformer substation and of the low-
4.5.2.1 Field of application
                                                                          voltage system neutral are electrically
The rules of this clause provide requirements for the                     independent.
safety of low-voltage installation in the event of:                  Uo   in TN- and TT-systems: nominal a.c. r.m.s. line
    a) a fault between the high-voltage system and                        voltage to earth
       earth in the transformer substation that                           in IT-systems: nominal a.c. voltage between
       supplies the low-voltage installation,                             line conductor and neutral conductor or
    b) a loss of the supply neutral in the low-voltage                    midpoint conductor, as appropriate.
       system,                                                       Uf   power-frequency fault voltage that appears in
                                                                                                                                         SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
    c) a short-circuit between a line conductor and                       the low-voltage system between exposed-
       neutral, and                                                       conductive-parts and earth for the duration of
                                                                          the fault.
    d) an accidental earthing of a line conductor of a
       low-voltage IT-system.                                        U1   power-frequency stress voltage between the
                                                                          line conductor and the exposed-conductive-
                                                            56
                                                                                                                          IS 732 : 2019
                                                                                                                                              SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                                                            ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
     FIG. 27 REPRESENTATIVE SCHEMATIC SKETCH FOR POSSIBLE CONNECTIONS TO EARTHING SUBSTATION AND
                    LV-INSTALLATION AND OCCURRING OVERVOLTAGES IN CASE OF FAULTS
In case of a fault to earth on the HV-side of the                         installation between exposed conductive parts and
substation, the following types of overvoltage may                        earth, shall not exceed the values given for Uf by the
affect the LV-installation:                                               curve of Fig. 28 for the duration of the fault.
    a) power frequency fault-voltage (Uf);                                Normally, the PEN conductor of the low-voltage system
    b) power frequency stress-voltages (U1 and U2).                       is connected to earth at more than one point. In this
                                                                          case, the total resistance is reduced. For these multiple
Table 4 provides the relevant methods of calculation                      grounded PEN conductors, Uf can be calculated as:
for the different types of overvoltages.
                                                                                                 Uf = 0.5 RE×IE
   NOTE — Table 4 deals with IT systems with a neutral point
   only. For IT systems with no neutral point, the formulae should           NOTE — The curve shown in Fig. 28 is taken from IEC 61936-
   be adjusted accordingly.                                                  1. On the basis of probabilistic and statistical evidence this
                                                                             curve represents a low level of risk for the simple worst case
Where high- and low-voltage earthing systems exist in                        where the low voltage system neutral conductor is earthed only
proximity to each other, two practices are presently                         at the transformer substation earthing arrangements.
used:
                                                                          4.5.2.2.2 Magnitude and duration of power-frequency
     — interconnection of all high-voltage (RE) and                       stress voltages
         low-voltage (RB) earthing systems; and
                                                                          The magnitude and the duration of the power-frequency
     — separation of high-voltage (RE) from low-                          stress voltage (U1 and U2) as calculated in Table 4 of
         voltage (RB) earthing systems.                                   the low-voltage equipment in the low-voltage
The general method used is interconnection. The high-                     installation due to an earth fault in the high-voltage
and low-voltage earthing systems shall be                                 system shall not exceed the requirements given in
interconnected if the low-voltage system is totally                       Table 5.
confined within the area covered by the high-voltage
earthing system (see IEC 61936-1).                                        4.5.2.2.3 Requirements for calculation of limits
   NOTE — Details of the different types of system earthing (TN,          Where required by Table 4, the permissible power-
   TT, IT) are shown in National Electrical Code 2011 and IS 3043.        frequency stress voltage shall not exceed the value given
                                                                          in Table 5.
4.5.2.2.1 Magnitude and duration of power-frequency
fault voltage                                                             Where required by Table 4, the permissible power-
                                                                          frequency fault voltage shall not exceed the value given
The magnitude and the duration of the fault voltage Uf
                                                                          in Table 5.
(as calculated in Table 4) which appears in the LV
                                                                     57
IS 732 : 2019
  Table 4 Power-Frequency Stress Voltages and Power-Frequency Fault Voltage in Low-Voltage System
                                    (Clauses 4.5.2.2 and 4.5.2.2.2).
  Types of System Earthing              Types of Earth Connections                    U1                    U2                 Uf
                                                                                                                                             SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                    Uo×√3            RE× IE + Uo×√3          RA× Ih
                                   RE and Z connected
                                                                                     Uo1)                   Uo1)             RE×IE
                                   RE and RA interconnected
                IT
                                                                                    Uo ×√3                 Uo×√3             RE×IE
 1)
  No consideration needs to be given.
 2)
  See 4.3.2.2.1 second paragraph.
 With existing earth fault in the installation.
      NOTES
      1 The requirements for U1 and U2 are derived from design criteria for insulation of low-voltage equipment with regard to temporary
      power-frequency overvoltage (see also Table 4).
      2 In a system whose neutral is connected to the earthing arrangement of the transformer substation, such temporary power-frequency
      overvoltage is also to be expected across insulation which is not in an earthed enclosure when the equipment is outside a building.
      3 In TT- and TN-systems the statement “connected” and “separated” refers to the electrical connection between RE and RB. For IT-
      systems it refers to the electrical connection between RE and Z and the connection between RE and RA.
      Duration of the Earth Fault in the High-            Permissible Power-Frequency Stress Voltage on Equipment in Low-Voltage
                  Voltage System                                                       Installations
                         t                                                                   U
                        >5 s                                                                 Uo + 250 V
                        5s                                                                  Uo + 1 200 V
 In systems without a neutral conductor, Uo shall be the line-to-line voltage.
 NOTES
 1 The first line of the table relates to high-voltage systems having long disconnection times, for example, isolated neutral and resonant
 earthed high-voltage systems. The second line relates to high-voltage systems having short disconnection times, for example low-
 impedance earthed high-voltage systems. Both lines together are relevant design criteria for insulation of low-voltage equipment with
 regard to temporary power frequency overvoltage, IS 15382 (Part 1).
 2 In a system whose neutral is connected to the earthing arrangement of the transformer substation, such temporary power-frequency
 overvoltage is also to be expected across insulation which is not in an earthed enclosure when the equipment is outside a building.
The requirements of 4.3.2.2.2 and 4.3.2.2.3 are deemed                     necessary. Compliance with the above requirements
to be fulfilled for installations receiving a supply at low-               mainly falls into the responsibility of the substation
voltage from a public electricity distribution system.                     installer/owner/operator who needs also to fulfil
                                                                           requirements provided by IEC 61936-1. Therefore the
To fulfil the above requirements, coordination between
                                                                           calculation for U1, U2 and Uf is normally not necessary
the HV-system operator and the LV-system installer is
                                                                           for the LV system installer.
                                                                      58
                                                                                                                 IS 732 : 2019
                                                                                                                                     SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                                                   ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
                FIG. 28   T OLERABLE FAULT VOLTAGE DUE TO AN EARTH-FAULT IN THE HV SYSTEM
Possible measures to fulfil the above requirements are,          of a short-circuit between a line conductor and the
for example                                                      neutral conductor
    a) separation of earthing arrangement between                Consideration shall be given to the fact that if a short-
       HV and LV;                                                circuit occurs in the low-voltage installation between a
    b) change of LV system earthing; and                         phase conductor and the neutral conductor, the voltage
                                                                 between the other line conductors and the neutral
    c) reduction of earth resistance RE.
                                                                 conductor can reach the value of 1.45 ×Uo for a time
4.5.2.3 Power-frequency stress voltage in case of loss           up to 5 s.
of the neutral conductor in a TN and TT system
                                                                 4.5.3  Protection Against Overvoltages of
Consideration shall be given to the fact that, if the            Atmospheric Origin or Due to Switching
neutral conductor in a multi-phase system is interrupted,
                                                                 4.5.3.1 General
basic, double and reinforced insulation as well as
components rated for the voltage between line and                This clause deals with protection of electrical
neutral conductors can be temporarily stressed with the          installations against transient overvoltages of
line-to-line voltage. The stress voltage can reach up to         atmospheric origin transmitted by the supply
U = √3 Uo.                                                       distribution system and against switching overvoltages.
4.5.2.4 Power-frequency stress voltage in the event              In general, switching overvoltages are lower than
of an earth fault in an IT system with distributed               overvoltages of atmospheric origin and, therefore, the
neutral                                                          requirements regarding protection against overvoltages
                                                                 of atmospheric origin normally cover protection against
Consideration shall be given to the fact that, if a line         switching overvoltages.
conductor of an IT system is earthed accidentally,
                                                                    NOTE — Statistical evaluations of measurements have shown
insulation or components rated for the voltage between              that there is a low risk of switching overvoltages higher than
line and neutral conductors can be temporarily stressed             the level of overvoltage category II (see 4.5.3.2).
with the line-to-line voltage. The stress voltage can
                                                                 Consideration shall be given to the overvoltages which
reach up to U = √3 Uo.
                                                                 can appear at the origin of an installation, to the expected
4.5.2.5 Power-frequency stress voltage in the event              keraunic level and to the location and characteristics of
                                                            59
IS 732 : 2019
surge protective devices, so that the probability of                       4.5.3.2.2 Relationship between impulse withstand
incidents due to overvoltage stresses is reduced to an                     voltages of equipment and overvoltage categories
acceptable level for the safety of persons and property,
                                                                           Equipment with an impulse withstand voltage
as well as for the continuity of service desired.
                                                                           corresponding to overvoltage category IV is suitable
The values of transient overvoltages depend on the                         for use at, or in the proximity of, the origin of the
nature of the supply distribution system (underground                      installation, for example, upstream of the main
or overhead) and the possible existence of a surge                         distribution board. Equipment of category IV has a very
protective device upstream of the origin of the                            high impulse withstand capability providing the
installation and the voltage level of the supply system.                   required high degree of reliability.
This clause provides guidance where protection against                        NOTE — Examples of such equipment are electricity meters,
                                                                              primary overcurrent protection devices and ripple control units.
overvoltages is covered by inherent control or assured
                                                                                                                                                  SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
by protective control. If the protection according to this                 Equipment with an impulse withstand voltage
clause is not provided, insulation co-ordination is not                    corresponding to overvoltage category III is for use in
assured and the risk due to overvoltages shall be                          the fixed installation downstream of, and including the
evaluated.                                                                 main distribution board, providing a high degree of
                                                                           availability.
   NOTE — A suspended cable having insulated conductors with                           example, loss of public services, IT centres,
   earthed metallic screen is considered as equivalent to an
                                                                                       museums;
   underground cable.
                                                                                    c) consequences to commercial or industrial
Where an installation is supplied by or includes a low-                                activity, for example, hotels, banks, industries,
voltage overhead line and the keraunic level is lower                                  commercial markets, farms;
than or equal to 25 days per year (AQ 1), no specific
                                                                                    d) consequences to groups of individuals, for
protection against overvoltages of atmospheric origin
                                                                                       example, large residential buildings, churches,
is required.
                                                                                       offices, schools; and
   NOTE — Irrespective of the AQ value, protection against                          e) consequences to individuals, for example,
   overvoltages may be necessary in applications where a higher
   reliability or higher risks (for example, fire) are expected.
                                                                                       residential buildings, small offices.
In both cases, consideration regarding protection For levels of consequences (a) to (c), protection against
                                                                                                                                                      SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
against transient overvoltages shall be given to                             overvoltage shall be provided.
equipment with an impulse withstand voltage according                           NOTE — There is no need to perform a risk assessment
to overvoltage category I (see 4.5.3.2.2).                                      calculation according to Annex K for levels of consequences
                                                                                (a) to (c) because this calculation always leads to the result that
4.5.3.3.2 Protective overvoltage control                                        the protection is required.
    a) consequences related to human life, for                               4.5.4 Measures Against Electromagnetic Influences
       example, safety services, medical equipment                           4.5.4.1 General
       in hospitals;
                                                                             The 4.5.4 provides basic recommendations for the
    b) consequences related to public services, for
                                                                             mitigation of electromagnetic disturbances.
                                                                        61
IS 732 : 2019
                                                                                                                                          SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
        400/690                 –                       8                           6                    4                 2.5
          1 000                 –                      12                           8                    6                  4
  1)
      According to IEC 60038.
  2), 3)
         This impulse withstand voltage is applied between live conductors and PE.
                                                                     62
                                                                                                       IS 732 : 2019
c) Inductive loops should be avoided by selection             NOTE — The provision of a by-pass conductor in
                                                              proximity to a signal, or data, cable sheath also reduces
   of a common route for power, signal and data
                                                              the area of the loop associated with equipment, which
   circuits wiring.                                           is only connected by a protective conductor to earth.
d) Power and signal cables should be kept                     This practice considerably reduces the EMC effects of
   separate and should, wherever practical, cross             lightning electromagnetic pulse (LEMP).
   each other at right-angles (see 4.5.4.6.3).            k) Where screened signal cables or data cables
e) Use of cables with concentric conductors to               are common to several buildings supplied
   reduce currents induced into the protective               from a TT-system, a by-pass equipotential
   conductor.                                                bonding conductor should be used (see
f) Use of symmetrical multicore cables (for                  Fig. 30), The by-pass conductor shall have a
   example, screened cables containing separate              minimum cross-sectional area of 16 mm2 Cu
                                                             or equivalent. The equivalent cross-sectional
                                                                                                                             SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
   protective conductors) for the electrical
   connections between convertors and motors,                area shall be dimensioned in accordance
   which have frequency controlled motor-                    with 5.4.4.1.
   drives.                                                    NOTES
                                                              1 Where the earthed shield is used as a signal return
g) Use of signal and data cables according to the
                                                              path, a double-coaxial cable may be used.
                                                     63
IS 732 : 2019
                                                                                                                                              SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
      FIG. 30 EXAMPLE OF A SUBSTITUTE OR B Y-PASS E QUIPOTENTIAL BONDING CONDUCTOR IN A TT-SYSTEM
                                                                       64
                                                                                          IS 732 : 2019
                                                                                                          SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                        ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
FIG. 31 AVOIDANCE OF NEUTRAL CONDUCTOR CURRENTS IN A BONDED STRUCTURE BY U SING THE TN-S SYSTEM
     FROM THE O RIGIN OF THE P UBLIC S UPPLY UP TO AND I NCLUDING THE FINAL CIRCUIT WITHIN A B UILDING
                                                           65
IS 732 : 2019
                                                                                                  SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
  FIG. 32 AVOIDANCE OF NEUTRAL CONDUCTOR CURRENTS IN A B ONDED STRUCTURE BY USING A TN-S SYSTEM
                      DOWNSTREAM OF A CONSUMER’S PRIVATE SUPPLY T RANSFORMER
                                                                  66
                                                                                                                  IS 732 : 2019
                                                                                                                                      SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                                                    ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
                                                                67
IS 732 : 2019
                                                                                       SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                     ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
                                                                   68
                                                                                   IS 732 : 2019
                                                                                                   SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                 ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
                                                               69
IS 732 : 2019
                                                                                                                                         SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                                                       ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
                   FIG. 36 TN MULTIPLE-S OURCE P OWER S UPPLY WITH A NON-SUITABLE M ULTIPLE
                                    CONNECTION BETWEEN PEN AND EARTH
around the core conductor that may interfere with                       NOTE — Interconnection is only permitted with the consent
                                                                        of the operator of the external service.
electronic equipment. Harmonic currents produce
similar electromagnetic fields but they attenuate more               For EMC reasons, closed building voids housing parts
rapidly than those produced by fundamental currents.                 of the electrical installation should be exclusively
4.5.4.4.6.1 TN multiple source power supplies                        reserved for electrical and electronic equipment (such
                                                                     as monitoring, control or protection devices, connecting
In the case of TN multiple-source power supplies to an               devices, etc) and access shall be providedfor their
installation, the star points of the different sources shall,        maintenance.
for EMC reasons, be interconnected by an insulated
conductor that is connected to earth centrally at one                4.5.4.4.9 Separate buildings
and the same point (see Fig. 37).                                    Where different buildings have separate equipotential
4.5.4.4.6.2 TT multiple-source power supplies                        bonding systems, metal-free fibre optic cables or other
                                                                     non-conducting systems may be used for signal and
In the case of TT multiple-source power supplies to an               data transmission, for example, microwave signal
installation, it is recommended that the star points of              transformer for isolation in accordance with
the different sources are, for EMC reasons,                          IEC 61558-2-1, IEC 61558-2-4, IEC 61588-2-6,
interconnected and connected to earth centrally at only              IEC 61888-2-15 and IS 13252 (Part 1).
one point (see Fig. 38).
                                                                        NOTES
4.5.4.4.7 Transfer of supply                                            1 The problem of earth differential voltages on large public
                                                                        telecommunication networks is the responsibility of the
In TN systems the transfer from one supply to an                        network operator, who may employ other methods.
alternative supply shall be by means of a switching                     2 In case of non-conducting data-transmission systems, the use
device, which switches the line conductors and the                      of a by-pass conductor is not necessary.
neutral, if any (see Fig. 39, Fig. 40 and Fig. 41).                  4.5.4.4.10 Inside buildings
4.5.4.4.8 Services entering a building                               Where there are problems in existing building
                                                                     installations due to electromagnetic influences, the
Metal pipes (for example, for water, gas or district                 following measures may improve the situation (see
heating) and incoming power and signal cables should                 Fig. 43):
preferably enter the building at the same place. Metal
pipes and the metal armouring of cables shall be bonded                  1) use of metal free fibre optic links for signal
to the main earthing terminal by means of conductors                        and data circuits (see 4.5.4.4.9);
having low impedance (see Fig. 42).                                      2) use of Class II equipment; and
                                                                70
                                                                                                                          IS 732 : 2019
                                                                                                                                               SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                                                             ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
    a) — No direct connection from either transformer neutral points or generator star points to earth is permitted.
    b) — The conductor interconnecting either the neutral points of transformers, or the star-points of generators, shall be insulated. This
         conductor functions as a PEN conductor and it may be marked as such; however, it shall not be connected to current-using-
         equipment and a warning notice to that effect shall be attached to it, or placed adjacent to it.
    c) — Only one connection between the interconnected neutral points of the sources and the PE shall be provided. This connection
         shall be located inside the main switchgear assembly.
    d) — Additional earthing of the PE in the installation must be provided.
  FIG. 37 TN MULTIPLE SOURCE POWER SUPPLIES TO AN I NSTALLATION WITH CONNECTION                              TO   EARTH OF THE STAR
                                P OINTS AT ONE AND THE SAME P OINTS
                                                                   71
IS 732 : 2019
                                                                                                                                           SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                                                         ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
    a) — No direct connection from either the transformer star points or the generator star points to earth is permitted.
    b) — The conductor interconnecting either the star points of transformers, or generator star points, shall be insulated. However, it
         shall not be connected to current-using-equipment and a warning notice to that effect shall be attached to it, or placed
         adjacent to it.
    c) — Only one connection between the interconnected star points of the sources and the PE shall be provided. This connection shall
         be located inside the main switchgear assembly.
 FIG. 38 TT MULTIPLE-SOURCE P OWER SUPPLIES TO AN INSTALLATION WITH CONNECTION                            TO   E ARTH OF THE STAR
                                 P OINTS AT ONE AND THE SAME P OINT
Therefore, all protective and functional earthing                     disconnected the connections of all the other conductors
conductors should be connected to one single main                     remain secured.
earthing terminal.                                                    4.5.4.5.2 Interconnection of incoming networks and
Moreover, all earth electrodes associated with a                      earthing arrangements
building, for example, protective, functional and                     Exposed conductive parts of information technology
lightning protection, shall be interconnected (see                    and electronic equipment within a building are
Fig. 44).                                                             interconnected via protective conductors.
In the case of several buildings, where interconnection               For dwellings where normally a limited amount of
of the earth electrodes is not possible or practical, it is           electronic equipment is in use, a protective conductor
recommended that galvanic separation of                               network in the form of a star network may be acceptable
communication networks is applied, for instance by the                (see Fig. 45).
use of fibre optic links (see also 4.5.4.4.10).                       For commercial and industrial buildings and similar
                                                                      buildings containing multiple electronic applications,
Protective and functional bonding conductors shall be                 a common equipotential bonding system is useful in
connected individually to the main earthing terminal                  order to comply with the EMC requirements of different
in such a way that if one conductor becomes                           types of equipment (see Fig. 47).
                                                                 72
                                                                                                                       IS 732 : 2019
                                                                                                                                            SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                                                          ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
NOTE — This method prevents electromagnetic fields due to stray currents in the main supply system of an installation. The sum of
the currents within one cable must be zero. It ensures that the neutral current flows only in the neutral conductor of the circuit, which
is switched on. The 3rd harmonic (150 Hz) current of the line conductors will be added with the same phase angle to the neutral
conductor current.
                    FIG. 39 T HREE-P HASE ALTERNATIVE P OWER SUPPLY WITH A 4-P OLE SWITCH
NOTE — A three-phase alternative power supply with an unsuitable 3-pole switch will cause unwanted circulating currents, that will
generate electromagnetic fields.
                                                                73
IS 732 : 2019
                                                                                                                                        SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                                                      ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
  NOTE — The earth connection to the secondary circuit of a UPS is not mandatory. If the connection is omitted, the supply inthe UPS-
  mode will be in the form of an IT system and, in by-pass mode, it will be the same as the low-voltage supply system.
FIG. 41 SINGLE-P HASE ALTERNATIVE P OWER SUPPLY WITH 2-P OLE SWITCH
FIG. 42 ARMOURED CABLES AND METAL P IPES ENTERING THE BUILDINGS (E XAMPLES)
                                                                74
                                                                                            IS 732 : 2019
                                                                                                            SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                          ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
Reference                     Description of the Illustrated Measures                     Sub-Clause/
                                                                                           Standard
   1)       Cables and metal pipes enter the building at the same place                 4.5.4.4.8
   2)       Common route with adequate separations and avoidance of loops               4.5.4.4.2
   3)       Bonding leads as short as possible, and use of earthed conductor parallel   IEC 61000-2-5
            to a cable                                                                  4.5.4.4.2
   4)       Signal cables screened and/or conductors twisted pairs                      4.5.4.4.12
   5)       Avoidance of TN-C beyond the incoming supply point                          4.5.4.4.3
   6)       Use of transformers with separate windings                                  4.5.4.4.10
   7)       Local horizontal bonding system                                             4.5.4.5.4
   8)       Use of class II equipment                                                   4.5.4.4.10
                                                    75
IS 732 : 2019
                                                                                                                              SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
4.5.4.5.3 Different structures for the network of                etc, and from a general point of view to equipment,
equipotential conductors and earthing conductors                 that is not interconnected by signal cables (see Fig. 45).
The four basic structures described in the following             4.5.4.5.3.3 Multiple meshed bonding star network
                                                            76
                                                                                                                 IS 732 : 2019
                                                                                                                                    SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                                                  ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
                           FIG. 46 EXAMPLE OF MULTIPLE MESHED BONDING STAR NETWORK
The area covered by a mesh shall have overall dimensions; the mesh-size refers to the dimensions of square spaces enclosed by the
conductors forming the mesh.
Mesh-size shall be adapted to the dimensions of the                 In some cases, parts of this network may be meshed
installation to be protected, but shall not exceed 2 m ×            more closely in order to meet specific requirements.
2 m in areas where equipment sensitive to
                                                                    4.5.4.5.4 Equipotential bonding networks in buildings
electromagnetic interferences is installed.
                                                                    with several floors
It is suitable for protection of private automatic branch
                                                                    For buildings with several floors, it is recommended
exchange equipment (PABX) and centralized data
                                                                    that, on each floor, an equipotential bonding system be
processing systems.
                                                                    installed (see Fig. 48) for examples of bonding
                                                                    networks in common use; each floor is a type of
                                                               77
IS 732 : 2019
                                                                                                                              SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                                            ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
                      FIG. 48 EXAMPLE OF EQUIPOTENTIAL BONDING NETWORKS IN STRUCTURES
                                   W ITHOUT LIGHTNING P ROTECTION S YSTEMS
network. The bonding systems of the different floors               4.5.4.5.6 Commercial or industrial buildings
should be interconnected, at least twice, by conductors.           containing significant amounts of information
                                                                   technology equipment
4.5.4.5.5 Functional earthing conductor
                                                                   The following additional specifications are intended
Some electronic equipment requires a reference voltage
                                                                   to reduce the influences of electromagnetic disturbances
at about earth potential in order to function correctly;
                                                                   on the information technology equipment operation.
this reference voltage is provided by the functional
earthing conductor.                                                In severe electromagnetic environments, it is
                                                                   recommended that the common meshed bonding star
Conductors for functional earthing may be metallic
                                                                   network described in 4.5.4.5.3.3 be adopted.
strips, flat braids and cables with circular cross-section.
                                                                   4.5.4.5.6.1 Equipotential bonding designed as a
For equipment operating at high frequencies, metallic
                                                                   bonding ring network shall have the following minimum
strips or flat braids are preferred and the connections
                                                                   dimensions:
shall be kept as short as possible.
                                                                       a) flat copper cross-section: 30 mm × 2 mm.
No colour is specified for functional earthing
conductors. However, the colours green-and-yellow                      b) round copper diameter: 8 mm.
specified for earthing conductors shall not be used. It                c) as per IS 3043
is recommended that the same colour is used throughout             Bare conductors shall be protected against corrosion
the whole installation to mark functional earthing                 at their supports and on their passage through walls.
conductors at each end.
                                                                   4.5.4.5.6.2 Parts to be connected to the equipotential
For equipment operating at low frequencies, cross                  bonding network
sectional areas as indicated in 5.4.4.1 are considered
satisfactory, independent of the conductor shape                   The following parts shall also be connected to the
[see 4.5.4.4.2 (b) and (k)].                                       equipotential bonding network:
                                                              78
                                                                                                                             IS 732 : 2019
    a) conductive screens, conductive sheaths or                          (see 4.2.13 and/or 4.5.4.7.2). Electrical safety and
       armouring of data transmission cables or of                        electromagnetic compatibility require different
       information technology equipment;                                  clearances in some cases. Electrical safety always has
    b) earthing conductors of antenna systems;                            the higher priority.
    c) earthing conductors of the earthed pole of d.c.                    Exposed conductive parts of wiring systems, for
       supply for information technology equipment;                       example, sheaths, fittings and barriers, shall be
       and                                                                protected by requirements for fault protection
    d) functional earthing conductors.                                    (see 4.2.13).
4.5.4.5.7 Earthing arrangements and equipotential                         4.5.4.6.2 Design guidelines
bonding of information technology installations for
                                                                          The minimum separation between power cables and
functional purposes
                                                                                                                                                   SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                          information technology cables to avoid disturbance is
4.5.4.5.7.1 Earthing busbar                                               related to many factors such as:
Where an earthing busbar is required for functional                           a)    the immunity level of equipment connected
purposes, the main earthing terminal (MET) of the                                   to the information technology cabling system
building may be extended by using an earthing busbar.                               to different electromagnetic disturbances
                                                                     79
IS 732 : 2019
                                                                                                                             SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                      FIG. 49    SEPARATION BETWEEN P OWER AND INFORMATION T ECHNOLOGY
                                   CABLES FOR CABLE ROUTE LENGTHS < 35 m
    b) the authorised level of conducted and radiated            agreed quantity of additional cables to be installed. The
       emissions;                                                cable-bundle height shall be lower than the side-walls
    c) the type of cabling (screened, twisted, optical           of the cable-tray, as shown in Fig. 52. The use of
       fibre);                                                   overlapping lids improves the cable-tray’s
    d) the immunity of the equipment connected to                electromagnetic compatibility performance.
       the information technology cabling system;                For a U-shape cable-tray, the magnetic field decreases
    e) the other environment constraints (chemical,              near the two corners. For this reason, deep side-walls
       mechanical, climatic, fire, etc);                         are preferred (see Fig. 52).
    f) any future information technology cabling                    NOTE — The depth of the section should be at least twice the
       system extension.                                            diameter of the largest cable being considered.
                                                                                                                                   SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
following cases:
                                                                 4.5.4.7.3.1 Metallic or composite cable management
    –    electromagnetic        environment      with            systems specially designed for electromagnetic
         permanently low levels of disturbance;                  compatibility purposes
    –    the cabling system has a low emission level;            Metallic or composite cable management systems
                                                            81
IS 732 : 2019
to ensure continuity by effective bonding between                 recommendations for example, not replacing a metallic
adjacent elements. Preferably, the elements should be             conduit by a plastic one.
welded together over their full perimeter. Riveted,
                                                                  Metallic construction elements of buildings can serve
bolted or screwed joints are allowed, provided that the
                                                                  electromagnetic compatibility objectives very well.
surfaces in contact are good conductors, that is, they
                                                                  Steel beams of L-, H-, U-, or T-shape often form a
have no paint or insulating cover, that they are
                                                                  continuous earthed structure, that contains large cross-
safeguarded against corrosion and that a good electrical
                                                                  sections and large surfaces with many intermediate
contact between adjacent elements is ensured.
                                                                  connections to earth. Cables are preferably laid against
The shape of the metallic section should be maintained            such beams. Inside corners are preferred to outside
over its full length. All interconnections shall have low         surfaces (see Fig. 54).
impedance. A short single-lead connection between two
                                                                  Covers for metallic cable trays shall meet the same
                                                                                                                               SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
parts of a cable management system will result in a
                                                                  requirements as the cable trays. A cover with many
high local impedance and, therefore, degradation of its
                                                                  contacts over the full length is preferred. If that is not
electromagnetic compatibility performance (see
                                                                  possible, the covers should be connected to the cable
Fig. 53).
                                                                  tray at least at both ends by short connections less than
From frequencies of a few MHz upwards, a 10 cm long               10 cm, for example, braided or mesh straps.
                                                             82
                                                                                                                   IS 732 : 2019
                                                                                                                                        SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                               OF
The by-pass equipotential bonding conductor shall be               5.1.1.1 Every item of equipment shall comply with
designed to withstand large common mode and diverted               Indian Standards as are appropriate.
fault currents.
                                                                   5.1.1.2 Where there are no applicable or Indian
4.5.5 Protection Against Undervoltage                              Standards, the item of equipment concerned shall be
4.5.5.1 General requirements                                       selected by special agreement between the person
                                                                   specifying the installation and the installer.
4.5.5.1.1 Where a drop in voltage, or a loss and
subsequent restoration of voltage could imply                      5.1.2 Operational Conditions and External Influences
dangerous situations for persons or property, suitable
precautions shall be taken. Also, precautions shall be             5.1.2.1 Operational conditions
taken where a part of the installation or current-using            5.1.2.1.1 Voltage
equipment may be damaged by a drop in voltage.
                                                                   Equipment shall be suitable for the nominal voltage
An undervoltage protective device is not required if
                                                                   (r.m.s. value for a.c.) of the installation.
damage to the installation or to current-using equipment
is considered to be an acceptable risk, provided that              If, in IT installations, the neutral conductor is
no danger is caused to persons.                                    distributed, equipment connected between phase and
4.5.5.1.2 The operation of undervoltage protective                 neutral shall be insulated for the voltage between
devices may be delayed if the operation of the appliance           phases.
protected allows without danger a brief interruption or               NOTE — For certain equipment, it may be necessary to take
loss of voltage.                                                      account of the highest and/or lowest voltage likely to occur in
                                                                      normal service.
4.5.5.1.3 If use is made of contactors, delay in their
opening and reclosing shall not impede instantaneous               5.1.2.1.2 Current
disconnection by control or protective devices.
                                                                   Equipment shall be selected for the design current
4.5.5.1.4 The characteristics of the undervoltage                  (r.m.s. value for a.c.) which it has to carry in normal
protective device shall be compatible with the                     service.
requirements of the IS standards for starting and use
of equipment.                                                      Equipment shall also be capable of carrying the currents
4.5.5.1.5 Where the reclosure of a protective device is            likely to flow in abnormal conditions for such periods
likely to create a dangerous situation, the reclosure shall        of time as are determined by the characteristics of the
not be automatic.                                                  protective devices.
                                                              83
IS 732 : 2019
                                                                                                                                            SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                        be significantly impaired by mounting equipment in
Unless other suitable precautions are taken during                      enclosures or compartments.
erection, all equipment shall be selected so that it will
not cause harmful effects on other equipment nor impair                 5.1.4 Identification
the supply during normal service, including switching                   5.1.4.1 General
                                                                   84
IS 732 : 2019
                                                                                                                           SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
         where the equipment is to be installed
         It is assumed that the ambient temperature includes the
         effects of other equipment installed in the same
         location
         The ambient temperature to be considered for the
         equipment is the temperature at the place where the
                                                                   85
IS 732 : 2018
Table 7 — (Continued)
                                                                                                                                       SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
           Low      High           Low         High    Low      High
 AB3        -25          +5         10          100     0.5       7      Indoor and outdoor locations     IS 13736 (All Parts)
                                                                         with       low      ambient
                                                                         temperatures
                                                                         Appropriate arrangements
                                                                       86
                                                                                                                  IS 732 : 2019
Table 7 — (Continued)
                                                                                                                                  SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                            IPX1 or IPX2
AD3    Sprays               Possibility of water falling as a spray at an angle up to 60° from the    IS 13736 (All Parts)
                            vertical
                            Locations in which sprayed water forms a continuous film on floors
                            and/or walls                                                              IS/IEC 60529
AE2    Small objects        Presence of foreign solid bodies where the smallest dimension             IS 13736 (All Parts)
       (2.5 mm)             is not less than 2.5 mm                                                   IS/IEC 60529
                            IP3X
                            Tools and small objects are examples of foreign solid bodies
                            of which the smallest dimension is at least 2.5 mm
                                                            87
IS 732 : 2018
Table 7 — (Continued)
 AE4       Light dust          Presence of light deposits of dust:                                   IS 13736 (All Parts)
                               10<deposit of dust ≤ 35 mg/m² a day                                   IS/IEC 60529
                                                                                                                            SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                               IP5X or equipment IP6X if dust should not penetrate
                               equipment
 AE5       Moderate dust       Presence of medium deposits of dust:                                  IS 13736 (All Parts)
                               35 < deposit of dust ≤ 350 mg/m² a day                                IEC 60529
                               IP5X or equipment IP6X if dust should not penetrate
                                                              88
                                                                                                                      IS 732 : 2019
Table 7 — (Continued)
                                                                                                                                        SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                              The hazard depends on local conditions and the nature of flora.
                              Distinction should be made between harmful growth of vegetation or
                              conditions for promotion of mould growth
                              Special protection, such as:
                              –        increased degree of protection (see AE)
                              –        special materials or protective coating of enclosures
                                                                89
IS 732 : 2018
Table 7 — (Continued)
                                                                                                                                    SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
 AM-9-3    High level           See IEC 61000-2-5
 AM-9-4    Very high level      see IEC 61000-2-5
           High-frequency electromagnetic phenomena conducted, induced or radiated (continuous or transient)
           Induced oscillatory voltages or currents
                                         2
                                                                 90
                                                                                                            IS 732 : 2019
Table 7 — (Continued)
                                                                                                                            SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                               Vibration which may cause the destruction of the building is outside
                               the classification
                               Frequency is not taken into account in the classification; however, if
                               the seismic wave resonates with the building, seismic effects must be
                               specially considered. In general, the frequency of seismic acceleration
                               is between 0 Hz and 10 Hz
                                                                91
IS 732 : 2018
Table 7 — (Continued)
                                                                                                                                   SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                them to avoid danger which electricity may create (engineers and
                                technicians)
                                Closed electrical operating areas
 BB        Electrical resistance of the human body (under consideration)
 BC        Contact of persons with earth potential
0-0I I II III
                                                                   92
                                                                                                                         IS 732 : 2019
Table 7 — (Concluded)
                                                                                                                                            SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                   Requirements for electrical apparatus for explosive atmospheres (see
                                   IS/IEC 60079)
BE4          Contamination         Presence of unprotected foodstuffs, pharmaceutics, and similar            Under consideration
             risks                 products without protection
                                   Foodstuff industries, kitchens:
                                   Certain precautions may be necessary, in the event of fault, to prevent
CB2          Propagation of fire   Buildings of which the shape and dimensions facilitates the spread of     4.2 & 4.3
                                   fire (for example, chimney effects)
                                   High-rise buildings. Forced ventilation systems
                                   Equipment made of material retarding the propagation of fire
                                   including fires not originating from the electrical installation. Fire
                                   barriers 6
CB3          Movement              Risk due to structural movement (for example, displacement between        Contraction or expansion
                                   different parts of a building or between a building and the ground or     joints (under consideration)
                                   building foundations                                                      5.2
                                   Buildings of considerable length or erected on unstable ground
                                   Contraction or expansion joints in electrical wiring
CB4          Flexible or           Structures which are weak or subject to movement (for example,            Flexible wiring (under
             unstable              oscillation)                                                              consideration)
                                   Tents, air-support structures, false ceilings, removable partitions.      5.2
                                   Installations to be structurally self-supporting Under consideration
1 May necessitate certain supplementary precautions (for example, special lubrication).
2 This means that ordinary equipment will operate safely under the described external influences.
3 This means that special arrangements need to be made, for example, between the designer of the installation and the equipment
  manufacturer, for example, for specially designed equipment.
4 This means that ordinary equipment will operate safely under the described external influences.
5 This class does not necessarily apply to family dwellings.
6 Fire detectors may be provided.
                                                                   93
IS 732 : 2019
in accordance with IEC 61346-1 and the IEC 61082               (see Table 7) that can occur when connected and erected
series shall be provided, indicating in particular:            as for normal use, and taking into account the intended
                                                               level of continuity of service necessary for the
    a) the type and composition of circuits (points
                                                               application.
       of utilization served, number and size of
       conductors, type of wiring); and                        5.1.5.3.1.2 Equipment shall be chosen with sufficiently
    b) the characteristics necessary for the                   low emission levels so that it cannot cause
       identification of the devices performing the            electromagnetic interference by electrical conduction
       functions of protection, isolation and                  or propagation in the air with other electrical equipment
       switching and their locations.                          inside or outside the building. If necessary, means of
                                                               mitigation shall be installed to minimize the emission
For simple installations the foregoing information may         (see 4.5).
be given in a schedule.
                                                                                                                                     SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                               5.1.6 Measures Related To Protective Conductor
5.1.4.5.2 The symbols used shall be chosen from the            Currents
IS 12032 series.
                                                               The protective conductor current generated by electrical
5.1.5 Prevention of Mutual Detrimental Influence               equipment under normal conditions of operation and
                                                          94
                                                                                                                          IS 732 : 2019
    a)    cables and conductors,                                            5.2.4.6 Conduit systems, cable ducting systems, cable
    b)    their termination and/or jointing,                                trunking systems, cable tray systems and cable ladder
    c)    their associated supports or suspensions, and                     systems
    d)    their enclosure or methods of protection                          Several circuits are allowed in the same conduit system,
          against external influences.                                      separated compartment of cable ducting system or cable
                                                                            trunking system provided all conductors are insulated
5.2.4 Types of Wiring System
                                                                            for the highest nominal voltage present.
5.2.4.1 The method of installation of a wiring system
                                                                            Conduit systems shall comply with the IS 14930 series,
(excluding systems covered by 5.2.4.4) in relation to
                                                                            cable trunking or ducting systems shall comply with
the type of conductor or cable used shall be in
                                                                            the IS 14297 series and cable tray and cable ladder
accordance with Table 17, provided the external
                                                                            systems shall comply with IEC 61537.
                                                                                                                                              SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
influences are taken into account according to 5.2.5.
                                                                               NOTE — Guidance on the selection of conduit systems is given
5.2.4.2 The method of installation of a wiring system                          in Annex W.
(excluding systems covered by 5.2.4.4) in relation to
the situation concerned shall be in accordance with                         5.2.4.7 Several circuits in one cable
Table 18. Other methods of installation of cables,                          Several circuits are allowed in the same cable provided
5.2.4.5.2 Single-core cables armoured with steel wire                       5.2.4.9.1 A flexible cable may be used for fixed wiring
or steel tape shall not be used for a.c. circuits.                          where the provisions of this standard are met.
   NOTE — The steel wire or steel tape armour of a single-core              5.2.4.9.2 Equipment that is intended to be moved in
   cable is regarded as a ferromagnetic enclosure. For single-core          use shall be connected by flexible cables or cords,
   wire armoured cables, the use of aluminium armour is                     except equipment supplied by contact rails.
   recommended.
                                                                       95
IS 732 : 2019
5.2.4.9.3 Stationary equipment which is moved                                   b)   from plant, appliances and luminaires,
temporarily for the purpose of connecting, cleaning etc,                        c)   from manufacturing processes,
for example, cookers or flush-mounting units for                                d)   through heat conducting materials, and
installations in false floors, shall be connected with                          e)   from solar gain of the wiring system or its surrounding
                                                                                     medium.
flexible cables or cords.
5.2.4.9.4 Flexible conduit systems may be used to                            5.2.5.3 Presence of water (AD) or high humidity (AB)
protect flexible insulated conductors.                                       5.2.5.3.1 Wiring systems shall be selected and erected
5.2.4.10 Installation of cables                                              so that no damage is caused by condensation or ingress
                                                                             of water. The completed wiring system shall comply
Insulated conductors (non-sheathed) for fixed wiring                         with the IP degree of protection relevant to the
shall be enclosed in conduit, cable ducting system or                        particular location.
                                                                                                                                                     SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
cable trunking system. This requirement does not apply
                                                                                NOTE — In general, the sheaths and insulation of cables for
to a protective conductor complying with 5.4.                                   fixed installations may be regarded, when intact, as proof against
                                                                                penetration by moisture. Special considerations apply to cables
5.2.5 Selection and Erection of Wiring Systems in
                                                                                liable to frequent splashing, immersion or submersion.
Relation to External Influences
                                                                             5.2.5.3.2 Where water may collect or condensation may
5.2.5.1 Ambient temperature (AA) 5.2.5.4 Presence of solid foreign bodies (AE)
5.2.5.1.1 Wiring systems shall be selected and erected                       5.2.5.4.1 Wiring systems shall be selected and erected
so as to be suitable for any temperature between the                         so as to minimize the danger arising from the ingress
highest and the lowest local ambient temperature and                         of solid foreign bodies. The completed wiring system
to ensure that the limiting temperature in normal                            shall comply with the IP degree of protection relevant
operation (see Table 8) and the limiting temperature in                      to the particular location.
case of a fault will not be exceeded.                                        5.2.5.4.2 In a location where dust in significant quantity
   NOTE — “Limiting temperature” means maximum continuous                    is present (AE4), additional precautions shall be taken
   operating temperature.                                                    to prevent the accumulation of dust or other substances
5.2.5.1.2 Wiring system components including cables                          in quantities which could adversely affect the heat
and wiring accessories shall only be installed or handled                    dissipation from the wiring system.
at temperatures within the limits stated in the relevant                        NOTE — A wiring system which facilitates the removal of dust
product standard or as given by the manufacturer.                               may be necessary (see 5.2.12).
                                                                        96
                                                                                                                           IS 732 : 2019
deterioration or hazardous degradation shall not be                       5.2.5.8.2 Where buried in the structure, conduit systems
placed in contact with each other.                                        or cable ducting systems, other than pre-wired conduit
                                                                          assemblies specifically designed for the installation,
5.2.5.6 Impact (AG)
                                                                          shall be completely erected between access points
5.2.5.6.1 Wiring systems shall be selected and erected                    before any insulated conductor or cable is drawn in.
so as to minimize the damage arising from mechanical
stress, for example, by impact, penetration or                            5.2.5.8.3 The radius of every bend in a wiring system
compression during installation, use or maintenance.                      shall be such that conductors or cables do not suffer
                                                                          damage and terminations are not stressed.
5.2.5.6.2 In fixed installations where impacts of
medium severity (AG2) or high severity (AG3) can                          5.2.5.8.4 Where the conductors or cables are not
occur, protection shall be afforded by:                                   supported continuously due to the method of
                                                                          installation, they shall be supported by suitable means
                                                                                                                                                SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
     a) the mechanical characteristics of the wiring                      at appropriate intervals in such a manner that the
        system, or                                                        conductors or cables do not suffer damage by their own
     b) the location selected, or                                         weight, or due to electro-dynamic forces resulting from
     c) the provision of additional local or general                      short-circuit current.
        mechanical protection, or
5.2.5.8.11 Cable supports and enclosures shall not have                   5.2.5.12 Seismic effects (AP)
sharp edges liable to damage the cables or insulated                      5.2.5.12.1 The wiring system shall be selected and
conductors.                                                               erected with due regard to the seismic hazards of the
5.2.5.8.12 Cables and conductors shall not be damaged                     location of the installation.
by the fixing means.                                                      5.2.5.12.2 Where the seismic hazards experienced are
5.2.5.8.13 Cables, busbars and other electrical                           low severity (AP2) or higher, particular attention shall
conductors which pass across expansion joints shall                       be paid to the following:
be so selected and erected that anticipated movement                           a) the fixing of wiring systems to the building
does not cause damage to the electrical equipment, for                            structure; and
example, by use of flexible wiring system.                                     b) the connections between the fixed wiring and
                                                                                  all items of essential equipment, for example,
                                                                                                                                              SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
5.2.5.8.14 Where wiring passes through fixed partitions,
it shall be protected against mechanical damage, for                              safety services, shall be selected for their
example, metallic sheathed or armoured cables, or by                              flexible quality.
use of conduit or grommets.                                               5.2.5.13 Wind (AR)
   NOTE — No wiring system should penetrate an element of                 5.2.5.13.1 See 5.2.5.7, Vibration (AH), and 5.2.5.8,
                                                                     98
                                                                                                                           IS 732 : 2019
                                                                                                                                               SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
 3)
      For mineral insulated cables, higher operating temperatures may be permissible dependent upon the temperature rating of the cable, its
      terminations, the environmental conditions and other external influences.
 4)
      Where certified, conductors or cable may have maximum operating temperature limits in accordance with the manufacturer’s
      specification.
NOTES
recognized method, provided that the method is stated.                    current-carrying capacity as a three-core cable having
Where appropriate, account shall be taken of the                          the same conductor cross-sectional area for each line
characteristics of the load and, for buried cables, the                   conductor. Four- and five-core cables may have higher
effective thermal resistance of the soil.                                 current-carrying capacities when only three conductors
                                                                          are loaded. This assumption is not valid in the case of
5.2.6.4 The ambient temperature is the temperature of
                                                                          the presence of third harmonic or multiples of 3
the surrounding medium when the cable(s) or insulated
                                                                          presenting a THD (total harmonic distortion) greater
conductor(s) under consideration are not loaded.
                                                                          than 15 percent.
5.2.6.5 Groups containing more than one circuit
                                                                          5.2.6.6.2 Where the neutral conductor in a multicore
The group reduction factors (Tables 36 to Table 40),                      cable carries current as a result of an imbalance in the
are applicable to groups of insulated conductors or                       line currents, the temperature rise due to the neutral
cables having the same maximum operating                                  current is offset by the reduction in the heat generated
temperature.                                                              by one or more of the line conductors. In this case, the
                                                                          neutral conductor size shall be chosen on the basis of
For groups containing cables or insulated conductors
                                                                          the highest line current.
having different maximum operating temperatures, the
current-carrying capacity of all the cables or insulated                  In all cases, the neutral conductor shall have a cross-
conductors in the group shall be based on the lowest                      sectional area adequate to afford compliance
maximum operating temperature of any cable in the                         with 5.2.6.1.
group, together with the appropriate group reduction
                                                                          5.2.6.6.3 Where the neutral conductor carries current
factor.
                                                                          without a corresponding reduction in load of the line
If, due to known operating conditions, a cable or                         conductors, the neutral conductor shall be taken into
insulated conductor is expected to carry a current not                    account in ascertaining the current-carrying capacity
greater than 30 percent of its grouped current-carrying                   of the circuit. Such currents may be caused by a
capacity, it may be ignored for the purpose of obtaining                  significant triple harmonic current in three-phase
the reduction factor for the rest of the group.                           circuits. If the harmonic content is greater than 15
                                                                          percent of the fundamental line current, the neutral
5.2.6.6 Number of loaded conductors
                                                                          conductor size shall not be smaller than that of the line
5.2.6.6.1 The number of conductors to be considered                       conductors. Thermal effects due to the presence of third
in a circuit are those carrying load current. Where it                    harmonic or multiples of 3 and the corresponding
can be assumed that conductors in polyphase circuits                      reduction factors for higher harmonic currents are given
carry balanced currents, the associated neutral                           in Annex V.
conductor need not be taken into consideration. Under
                                                                          5.2.6.6.4 Conductors which serve the purpose of
these conditions, a four-core cable is given the same
                                                                          protective conductors only (PE conductors) shall not
                                                                     99
IS 732 : 2019
be taken into consideration. PEN conductors shall be                    5.2.6.9 Single-core cables with a metallic covering
taken into consideration in the same way as neutral
                                                                        The metallic sheaths and/or non-magnetic armour of
conductors.
                                                                        single-core cables in the same circuit shall be connected
5.2.6.7 Conductors in parallel                                          together at both ends of their run. Alternatively, to
                                                                        improve current-carrying capacity, the sheaths or
Where two or more live conductors or PEN conductors
                                                                        armour of such cables having conductors of cross-
are connected in parallel in a system, either:
                                                                        sectional area exceeding 50 mm2 and a non-conducting
    a)    measures shall be taken to achieve equal load                 outer sheath may be connected together at one point in
          current sharing between them;                                 their run with suitable insulation at the unconnected
          This requirement is considered to be fulfilled                ends, in which case the length of the cables from the
          if the conductors are of the same material, have              connection point shall be limited so that voltages from
                                                                                                                                           SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
          the same cross-sectional area, are                            sheaths and/or armour to earth:
          approximately the same length and have no                         a) do not cause corrosion when the cables are
          branch circuits along the length, and either                         carrying their full load current, for example,
          – the conductors in parallel are multi-core                          by limiting the voltage to 25 V, and
                cables or twisted single-core cables or                     b) do not cause danger or damage to property
                                                                  100
                                                                                                                              IS 732 : 2019
                                                                                                                                                   SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
   ii)      Bare Conductors              Power circuits                              Cu          10
                                                                                     Al          16
                                         Signalling and control circuits             Cu          4
  iii)      Flexible connections with    For a specific appliance                    Cu          As specified in the relevant Indian Standard
            insulated conductors and     For any other application                               0.5 (see Note 2)
            cables
                                         Extra low voltage circuits for                          0.5
 NOTES
 1 Connectors used to terminate aluminium conductors shall be tested and approved for this specific use.
 2 In multi-core flexible cables containing 7 or more cores and in signalling control circuits intended for electronic equipment a minimum
 nominal cross sectional area of 0.1 mm is permitted.
   a) For multi-core cables, the cross-sectional area of the line            drop between the origin of the consumer’s installation
   conductors is equal to the cross-sectional area of the neutral
                                                                             and the equipment should not be greater than that given
   conductor, this cross-sectional area being chosen for the neutral
                                                                             in Table 47.
   to carry 1.45 × IB of the line conductor.
   b) For single-core cables, the cross-sectional area of the line              NOTE — Other considerations include start-up time for motors
   conductors may be lower than the neutral cross-sectional                     and equipment with high inrush current. Temporary conditions
   area, the calculation being made :                                           such as voltage transients and voltage variation due to abnormal
                                                                                operation may be disregarded.
   – for the line: at IB
   – for the neutral: at a current equal to 1.45 IB of the line.             5.2.9 Electrical Connections
   2 See 4.4.4 for an explanation of IB.
                                                                             5.2.9.1 Connections between conductors and between
5.2.7.2.3 For polyphase circuits where the cross-                            conductors and other equipment shall provide durable
sectional areaof line conductorsisgreater than 16 mm2                        electrical continuity and adequate mechanical strength
copper or 25 mm2 aluminium, the cross-sectional area                         and protection.
of the neutral conductor may be lower than the cross-
                                                                                NOTE — See IEC 61200-52.
sectional area of the line conductors if the following
conditions are fulfilled simultaneously:                                     5.2.9.2 The selection of the means of connection shall
                                                                             take account of, as appropriate:
    a)      the load carried by the circuit in normal service
            is balanced between the phases and the third                         a) the material of the conductor and its insulation;
            harmonic and odd multiples of third harmonics                        b) the number and shape of the wires forming
            currents do not exceed 15 percent of the line                           the conductor;
            conductor current;                                                   c) the cross-sectional area of the conductor; and
         NOTE — Usually, the reduced neutral cross-sectional area
         is not lower than 50 percent of the line conductor cross-               d) the number of conductors to be connected
         sectional area.                                                            together.
    b) the neutral conductor is protected against                                      NOTES
       overcurrents according to 4.4.2.2; and                                          1 The use of soldered connections should be avoided,
    c) the cross-sectional area of the neutral                                         except in communication circuits. If used, the
                                                                                       connections should be designed to take account of creep
       conductor is not less than 16 mm2 copper or                                     and mechanical stresses and temperature rise under fault
       25 mm2 aluminium.                                                               conditions (see 5.2.5.6, 5.2.5.7 and 5.2.5.8).
                                                                                       2 Applicable standards include the IEC 60998 series,
5.2.8 Voltage Drop in Consumers’ Installations                                         IEC 60947 (all Parts ) and IEC 61535.
In the absence of any other consideration, the voltage                                 3 Terminals without the marking “r” (only rigid
                                                                                       conductors), “f” (only flexible conductors), “s” or “sol”
                                                                       101
IS 732 : 2019
         (only solid conductors) are suitable for the connection         connection and junction points which are subject in
         of all types of conductors.
                                                                         service to a relative movement between the soldered
5.2.9.3 All connections shall be accessible for                          and the non-soldered part of the conductor.
inspection, testing and maintenance, except for the                         NOTE — Fine and very fine wire is in accordance with
following:                                                                  IEC 60228, Class 5 and Class 6.
    a) joints designed to be buried in the ground;                       5.2.9.9 Cores of sheathed cables from which the sheath
    b) compound-filled or encapsulated joints;                           has been removed and non-sheathed cables at the
                                                                         termination of conduit, ducting or trunking shall be
    c) connections between a cold tail and the heating
                                                                         enclosed as required by 5.2.9.5.
       element as in ceiling heating, floor
       heating and trace heating systems;                                5.2.10 Selection and Erection of Wiring Systems to
    d) a joint made by welding, soldering, brazing                       Minimize the Spread of Fire
                                                                                                                                              SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
       or appropriate compression tool; and                              5.2.10.1 Precautions within a fire-segregated
    e)   joint forming part of the equipment                             compartment
       complying with the appropriate product
                                                                         5.2.10.1.1 The risk of spread of fire shall be minimized
       standard.
                                                                         by the selection of appropriate materials and erection
elements of building construction such as floors, walls,                               product standard, if such a standard is prepared.
roofs, ceilings, partitions or cavity barriers, the openings                           a) They should be compatible with the materials of the
                                                                                       wiring system with which they are in contact.
remaining after passage of the wiring system shall be
                                                                                       b) They should permit thermal movement of the wiring
sealed according to the degree of fire resistance (if any)                             system without reduction of the sealing quality.
prescribed for the respective element of building                                      c) They should be of adequate mechanical stability to
construction before penetration.                                                       withstand the stresses which may arise through damage
                                                                                       to the support of the wiring system due to fire.
   NOTES
                                                                                       2 The requirements of 5.2.10.2.5 may be satisfied if:
   1 During erection of a wiring system temporary sealing
   arrangements may be required.                                                       a) either cable cleats, cable ties or cable supports are
                                                                                       installed within 750 mm of the seal and are able to
   2 During alteration work, sealing should be reinstated as quickly
                                                                                       withstand the mechanical loads expected following the
   as possible.
                                                                                       collapse of the supports on the fire side of the seal to
5.2.10.2.2 Wiring systems which penetrate elements of                                  the extent that no strain is transferred to the seal; or
                                                                                                                                                    SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
building construction having specified fire resistance                                 b) the design of the sealing system itself provides
                                                                                       adequate support.
shall be internally sealed to the degree of fire resistance
of the respective element before penetration as well as                      5.2.11 Proximity of Wiring Systems to other Services
being externally sealed as required by 5.2.10.2.1.
                                                                             5.2.11.1 Proximity to electrical services
     a) the system satisfies the test of IS/ IEC 60529                           a) every cable or conductor is insulated for the
        for IP33; and                                                               highest voltage present; or
     b) any termination of the system in one of the                              b) each conductor of a multicore cable is
        compartments, separated by the building                                     insulated for the highest voltage present in the
        construction being penetrated, satisfies the test                           cable; or
        of IS/IEC 60529 for IP33.                                                c) the cables are insulated for their system
                                                                                    voltage and installed in a separate
5.2.10.2.4 No wiring system shall penetrate an element                              compartment of a cable ducting or cable
of building construction which is intended to be load                               trunking system; or
bearing unless the integrity of the load bearing element
                                                                                 d) the cables are installed on a cable tray system
can be assured after such penetration.
                                                                                    where physical separation is provided by a
5.2.10.2.5 Sealing arrangements intended to                                         partition; or
satisfy 5.2.10.2.1 or 5.2.10.2.2 shall resist external                           e) a separate conduit, trunking or ducting system
influences to the same degree as the wiring system with                             is employed.
which they are used, and in addition, they shall meet
all of the following requirements:                                           For SELV and PELV systems the requirements of 4.2.14
                                                                             shall apply.
     a) they shall be resistant to the products of
                                                                                NOTES
        combustion to the same extent as the elements
                                                                                1 Special considerations concerning electrical interference, both
        of building construction which have been                                electromagnetic and electrostatic, may apply to telecommuni-
        penetrated;                                                             cation circuits, data transfer circuits and the like.
     b) they shall provide the same degree of                                   2 In the case of proximity of wiring systems and lightning
                                                                                protection systems, the IS/IEC 62305 series should be
        protection from water penetration as that
                                                                                considered.
        required for the building construction element
        in which they have been installed;                                   5.2.11.2 Proximity of communications cables
     c) the seal and the wiring system shall be                              In the event of crossing or proximity of underground
        protected from dripping water which may                              telecommunication cables and underground power
        travel along the wiring system or which                              cables, a minimum clearance of 100 mm shall be
        may otherwise collect around the seal unless                         maintained, or the requirements according to (a) or (b)
        the materials used in the seal are all resistant                     shall be fulfilled:
        to moisture when finally assembled for use.
                                                                                 a)    a fire-retardant partition shall be provided
          NOTES
                                                                                       between the cables, for example, bricks, cable
          1 These requirements may be transferred to an IEC
                                                                                       protecting caps (clay, concrete), shaped blocks
                                                                       103
IS 732 : 2019
        (concrete), or additional protection provided                 shall be made so that the protective measure can be
        by cable conduit or troughs made of fire-                     reinstated without reduction of the degree of protection
        retardant materials, or                                       originally intended.
     b) for crossings, mechanical protection between                  5.2.12.3 Provision shall be made for safe and adequate
        the cables shall be provided, for example,                    access to all parts of the wiring system which may
        cable conduit, concrete cable protecting caps                 require maintenance.
        or shaped blocks.
                                                                         NOTE — In some situations, it may be necessary to provide
5.2.11.3 Proximity to non-electrical services                            permanent means of access by ladders, walkways, etc.
5.2.11.3.1 Wiring systems shall not be installed in the               5.3   Selection and Erection of Electrical
vicinity of services which produce heat, smoke or fumes               Equipment— Isolation, Switching and Control
likely to be detrimental to the wiring, unless it is suitably
                                                                                                                                     SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
protected from harmful effects by shielding arranged                  5.3.1 General and Common Requirements
so as not to affect the dissipation of heat from the wiring.          This standard shall provide compliance with the
In areas not specifically designed for the installation               measures of protection for safety, the requirements for
of cables, for example, service shafts and cavities, the              proper functioning for intended use of the installation,
                                                                      and the requirements appropriate to the external
                                                                104
                                                                                                                           IS 732 : 2019
                                                                                                                                               SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
conditions and fault conditions.                                             this case, exposed conductive parts need not be
5.3.2.2.1.1 A residual current protective device shall                       connected to the TN earthing system protective
ensure the disconnection of all live conductors in the                       conductor, provided that they are connected to an earth
circuit protected. In TN-S systems, the neutral need                         electrode affording a resistance appropriate to the
not be disconnected if the supply conditions are such                        operating current of the residual current protective
5.3.2.2.2 Selection of devices according to their                               NOTE — Insulation monitoring devices may operate with an
                                                                                appropriate response time.
method of application
                                                                             An insulation monitoring device provided is, a device
5.3.2.2.2.1 Residual current protective devices may or
                                                                             continuously monitoring the insulation of an electrical
may not have an auxiliary source, taking into account
                                                                             installation. It is intended to indicate a significant
the requirements of 5.3.2.2.2.2.
                                                                             reduction in the insulation level of the installation to
   NOTE — The auxiliary source may be the supply system.                     allow the cause of this reduction to be found before the
5.3.2.2.2.2 The use of residual current protective                           occurrence of a second fault, and thus avoid
devices with an auxiliary source not operating                               disconnection of the supply.
automatically in the case of failure of the auxiliary                        Accordingly, it is set at a value below that specified
source is permitted only if one of the two following                         in 6.2.3.3 appropriate to the installation concerned.
conditions is fulfilled:
                                                                       105
IS 732 : 2019
Insulation monitoring devices shall be so designed or                        5.3.4.3 Selection of devices for protection of wiring
installed that it shall be possible to modify the setting                    systems against short circuits
only by the use of a key or a tool.
                                                                             The application of the rules of 4.4 for short-circuit
5.3.3 Devices for Protection against Thermal Effects                         duration up to 5 s shall take into account minimum and
                                                                             maximum short-circuit conditions.
Under consideration.
   NOTE — Pending this consideration, reference should be made
                                                                             Where the standard covering a protective device
   to 705.422 of IEC 60364-7-705.                                            specifies both a rated service short-circuit breaking
                                                                             capacity, and a rated ultimate short-circuit breaking
5.3.4 Devices for Protection against Overcurrent                             capacity, it is permissible to select the protective device
5.3.4.1 General requirements                                                 on the basis of the ultimate short-circuit breaking
                                                                             capacity for the maximum short-circuit conditions.
                                                                                                                                           SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
5.3.4.1.1 Fuse bases using screw-in fuses shall be                           Operational circumstances may, however, make it
connected so that the centre contact is on the supply                        desirable to select the protective device on the service
side of the fuse base.                                                       short-circuit breaking capacity, for example, where a
5.3.4.1.2 Fuse bases for plug-in fuse carriers shall be                      protective device is placed at the origin of the
arranged so as to exclude the possibility of the fuse                        installation.
                                                                       106
                                                                                                                       IS 732 : 2019
protection is normally provided by the installation of                              conductor and either the main earthing
test class II SPDs and if necessary test class III SPDs.                            terminal or the protective conductor,
                                                                                    whichever route is shorter – connection
When required in accordance with 4.5 or otherwise
                                                                                    type 2.
specified, SPDs shall be installed near the origin of the
                                                                               NOTE — If a line conductor is earthed, it is considered
installation or in the main distribution assembly, closest                     to be equivalent to a neutral conductor for the application
to the origin of the installation inside the building.                         of this subclause.
The protection against the effects of direct lightning                SPDs at or near the origin of the installation are, in
strokes or strokes near to the supply system are included             general, installed as shown in Annexes AA, BB and
in IEC 61312-1 which, also describes the correct                      CC and according to Table 10.
selection and application of SPDs according to the
Lightning Protection Zones (LPZ) concept. The LPZ                     5.3.5.2.3 Selection of surge protective devices (SPDs)
                                                                                                                                             SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
concept describes the installation of test class I, test              The SPDs shall comply with IEC 61643-1. Additional
class II and test class III SPDs.                                     information regarding selection and application is given
When required in accordance with IEC 61312-1 or                       in IEC 61643-12.
otherwise specified, SPDs shall be installed at the origin            5.3.5.2.3.1 Selection with regard to protection level
                                                                107
IS 732 : 2019
                                                                                                                                                       SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
PE conductor
Each line conductor              NA             NA             .       NA             NA              NA                 NA               NA
and PEN conductor
Line conductors                   +               +            +        +              +               +                 +                 +
.— mandatory
NA — not applicable
In addition, SPDs installed in location 4a according to                       for three-phase systems and 10 kA 8/20 for single-phase
Fig. 89 shall withstand such TOVs as defined in test                          systems.
of 7.7.4 of IS/IEC 61643-1.
                                                                              If IEC 61312-1 requires SPDs, the lightning impulse
     NOTES                                                                    current I imp according to IEC 61643-1 shall be
     1 Appropriate pass criteria are under consideration to define            calculated according to IEC 61312-1. Further
     the meaning of withstand.
                                                                              information is given in IEC 61643-12. If the current
     2 The loss of neutral is not covered by these requirements.
     Though there is currently no specific test in IS/IEC 61643-1,
                                                                              value cannot be established, the value of Iimp shall not
     SPDs are expected to fail safely.                                        be less than 12.5 kA for each mode of protection.
5.3.5.2.3.4 Selection with regard to discharge current                        In case of an installation according to 5.3.5.2.2
(In) and impulse current (Iimp)                                               connection type 2, the lightning impulse current Iimp
                                                                              for the surge protective device connected between the
If 4.5.3 requires SPDs, the nominal discharge current                         neutral conductor and the PE shall be calculated
In shall not be less than 5 kA 8/20 for each mode of                          similarly to the above mentioned standards. If the
protection.                                                                   current value cannot be established the value of Iimp
In case of installation according to 5.3.5.2.2 connection                     shall not be less than 50 kA for three-phase systems
type 2, the nominal discharge current In for the surge                        and 25 kA for single-phase systems.
protective device connected between the neutral                               When a single SPD is used for protection according to
conductor and the PE shall not be less than 20 kA 8/20                        both 7.7.4 and IEC 61312-1, the rating of In and of Iimp
                                                                        108
                                                                                                            IS 732 : 2019
shall be in agreement with the above values.                      may be given either to the continuity of supply or to
                                                                  the continuity of protection.
5.3.5.2.3.5 Selection with regard to the expected short-
circuit current                                                   In all cases, the discrimination between protective
                                                                  devices shall be ensured.
The short-circuit withstand of the SPDs (in case of SPD
failure) together with the specified associated (internal             –    If protective devices are installed in the surge
or external) overcurrent protective device shall be equal                  protective device circuit, the continuity of the
to or higher than the maximum short-circuit current                        supply is ensured, but neither the installation
expected at the point of installation taking into account                  nor the equipment is protected against possible
the maximum overcurrent protective devices specified                       further overvoltages (see Fig. 56). These
by the SPD manufacturer.                                                   protective devices may be internal
                                                                           disconnectors.
                                                                                                                              SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
In addition, when a follow current interrupting rating
is declared by the manufacturer, it shall be equal to or              –    If protective devices are inserted in the
higher than the expected short-circuit current at the                      installation upstream of the circuit where
point of installation.                                                     SPDs are installed, the failure of the surge
                                                                           protective device may cause interruption of
SPDs connected between the neutral conductor and the                       supply: the circuit interruption will last until
                                                            109
IS 732 : 2019
In order to increase the reliability and the probability          RCD with or without time delay, but having an
of having at the same time continuity of supply and               immunity to surge currents of at least 3 kA 8/20 shall
continuity of protection, it is permitted to use the              be used.
scheme described in Fig. 58.                                         NOTES
                                                                     1 S-type RCDs in accordance with IS 12640 (Part 1) and
                                                                     IS 12640 (Part 2) satisfy this requirement.
                                                                     2 In the case of surge current higher than 3 kA 8/20, the RCD
                                                                     may trip causing interruption of the power supply.
                                                                                                                                     SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                  the origin of the installation or in a distribution board
                                                                  and not rated for the test voltage of the insulation
                                                                  measurement may be disconnected.
                                                                  In the case where SPDs connected to the PE conductor
FIG. 58 COMBINATION OF CONTINUITY OF SUPPLY AND                   are part of a socket outlet, they shall withstand the test
In case of automatic disconnection of supply:                     Because increasing the length of the connecting
                                                                  conductors of SPDs reduces the effectiveness of
    a) in TN systems this may, in general, be fulfilled           overvoltage protection, optimum overvoltage
       by the overcurrent device on the supply side               protection is achieved when all connecting conductors
       of the surge protective device;                            of SPDs are as short as possible (preferably not
    b) in TT systems this may be fulfilled by either,             exceeding 0.5 m for the total lead length) and without
       1) the installation of SPDs on the load side               any loops (see Fig. 59). If distance a + b (see Fig. 59)
            of an RCD (seeFig. 90), or                            cannot be reduced below 0.5 m, the scheme in Fig. 60
                                                                  may be adopted.
       2) the installation of SPDs on the supply side
            of an RCD. Because of the possibility of              5.3.5.2.10 Cross-section of earthing conductors
            the failure of an SPD between N and PE
                                                                  The earthing conductors of SPDs at or near the origin
            conductors,                                           of the installation shall have a minimum cross-sectional
             the conditions of 4.2.11.5.1 shall be               area of 4 mm2 copper or equivalent.
               met, and
                                                                  When there is a lightning protection system, a minimum
             the SPD shall be installed in
                                                                  cross-sectional area of 16 mm2 copper or equivalent
               accordance with 5.3.5.2.2 connection
                                                                  is necessary for SPDs tested in accordance with test
               type 2.                                            class I of IS/IEC 61643-1.
    c) in IT systems, no additional measure is
       needed.                                                    5.3.6 Co-ordination of various Protective Devices
5.3.5 2.6 SPD installation in conjunction with RCDs               5.3.6.1 Discrimination between overcurrent protective
                                                                  devices
If SPDs are installed in accordance with 5.3.5.2.1 and
are on the load side of a residual current device, an             Under consideration.
                                                            110
                                                                                                                    IS 732 : 2019
                                                                                                                                         SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
            FIG. 59 E XAMPLE OF I NSTALLATION OF SPDS AT OR N EAR THE ORIGIN OF THE INSTALLATION
5.3.6.2 Association of residual current protective                           conditions even when, due to unbalanced
devices with overcurrent protective devices                                  current or to current flowing to earth, the
                                                                             residual current protective device itself tends
5.3.6.2.1 Where a residual current protective device is
                                                                             to open.
incorporated or combined with a device for overcurrent
protection, the characteristics of the assembly of                           NOTE — The stresses mentioned depend on the
                                                                             prospective short-circuit current at the point where the
protective devices (breaking capacity, operating
                                                                             residual current prospective device is installed, and the
characteristics in relation to rated current) shall satisfy                  operating characteristics of the device providing short-
the rules of 4.4.4, 4.4.5, 5.3.4.2 and 5.3.4.3.                              circuit protection.
5.3.6.2.2 Where a residual current protective device is             5.3.6.3 Discrimination between residual current
neither incorporated in, nor combined with, a device                protective devices
for overcurrent protection:
                                                                    Discrimination between residual current protective
    a) overcurrent protection shall be ensured by                   devices installed in series may be required for service
       appropriate protective devices according to                  reasons, particularly when safety is involved, to provide
       the rules of 4.4;                                            continuity of supply to the parts of the installation not
    b) the residual current protective device shall be              involved in the fault, if any.
       able to withstand without damage the thermal
                                                                    This discrimination can be achieved by selecting and
       and mechanical stresses to which it is likely
                                                                    erecting residual current protective devices which,
       to be subjected in the event of a short-circuit
                                                                    while ensuring the required protection to the different
       occurring on the load side of the location
                                                                    parts of the installation, disconnect from the supply only
       where it is installed; and
                                                                    that part of the installation that is located on the load
    c) the residual current protective device shall not             side of the residual current protective device installed
       be damaged under these short-circuit
                                                              111
IS 732 : 2019
on the supply side of the fault, and closest to it.                     any equipment from being unintentionally energized.
To ensure discrimination between two residual current                      NOTE — Such precautions may include one or more of the
                                                                           following measures:
protective devices in series, these devices shall satisfy
                                                                             a) padlocking;
both the following conditions:
                                                                             b) warning notices; and
    a) the non-actuating time-current characteristic                         c) location within a lockable space or enclosure.
       of the residual current protective device
       located on the supply side (upstream) shall lie                  Short-circuiting and earthing may be used as a
       above the total operating time-current                           supplementary measure.
       characteristic of the residual current protective                5.3.7.3.1.3 Where an item of equipment or enclosure
       device located on the load side (downstream),                    contains live parts connected to more than one supply,
       and                                                              a warning notice shall be placed in such a position that
                                                                                                                                           SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
    b) the rated residual operating current on the                      any person gaining access to live parts will be warned
       device located on the supply side shall be                       of the need to isolate those parts from the various
       higher than that of the residual current                         supplies unless an interlocking arrangement is provided
       protective device located on the load side.                      to ensure that all the circuits concerned are isolated.
                                                                  112
                                                                                                                                 IS 732 : 2019
                                                                                                                                                       SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
 1)
      According to IS 12360.
 NOTES
 1 As regards transient atmospheric overvoltages no distinction is made between earthed and unearthed systems.
 2 The impulse withstand voltages are referred to an altitude of 2 000 m.
5.3.7.3.2.8 All devices used for isolation shall be clearly                    5.3.7.4.2 Devices for switching-off for mechanical
identified, for example by marking, to indicate the                            maintenance
circuit which they isolate.                                                    5.3.7.4.2.1 Devices for switching-off for mechanical
                                                                         113
IS 732 : 2019
maintenance shall be inserted preferably in the main                         a)   pumping facilities for flammable liquids;
supply circuit.                                                              b)   ventilation systems;
                                                                             c)   large computers;
Where for this purpose switches are provided, they shall                     d)   discharge lighting with high-voltage supply, for example,
be capable of cutting off the full-load current of the                            neon signs;
relevant part of the installation. They need not                             e)   certain large buildings, for example department stores;
necessarily interrupt all live conductors.                                   f)   electrical testing and research facilities;
                                                                             g)   teaching laboratories;
Interruption of a control circuit of a drive or the like is
                                                                             h)   boiler-rooms;
permitted only where,                                                        j)   large kitchens.
    –     supplementary safeguards, such as mechanical
                                                                          5.3.7.5.1.2 Where a risk of electric shock is involved,
          restrainers, or
                                                                          the emergency switching device shall cut off all live
                                                                                                                                              SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
    –     requirements of an IS specification for the                     conductors except as provided in 5.3.7.2.2.
          control devices used
                                                                          5.3.7.5.1.3 Means for emergency switching, including
          provide a condition equivalent to the direct                    emergency stopping, shall act as directly as possible
          interruption of the main supply.                                on the appropriate supply conductors.
                                                                    114
                                                                                                                               IS 732 : 2019
                                                                                                                                                    SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
   by means of:
   a) switches in the main circuit, and                                     change-over of supply from alternative sources shall
   b) push-buttons and the like in the control (auxiliary) circuit.         affect all live conductors and shall not be capable of
                                                                            putting the sources in parallel, unless the installation is
5.3.7.5.4.2.3 Hand-operated switching devices for                           specifically designed for this condition.
direct interruption of the main circuit shall be selected
                                                                      115
IS 732 : 2019
                                                                                                                                               SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                         soil or in concrete, shall be as specified in IS 3043.
5.4.1 Void                                                               2 The minimum thickness of protective coating is greater for
                                                                         vertical earth electrodes than for horizontal earth electrodes
5.4.2 Earthing Arrangements                                              because of their greater exposure to mechanical stresses while
                                                                         being embedded.
5.4.2.1 General requirements                                             If a lightning protection system is required, 5.4 of
                                                                116
                                                                                                                              IS 732 : 2019
     Table 13 Minimum Size of Commonly Used Earth Electrodes, Embedded in Soil or Concrete Used to
                          Prevent Corrosion and Provide Mechanical Strength
                                          (Clause 5.4.2.3.1)
                                                                                                                                                  SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                          90            3            500             63
                                   Solid plate – Lattice plate
                                   Round rod installed vertically         16                                         350             45
                                   Round wire installed
                                                                          10                                         350             45
                                   horizontally
Steel hot-dip galvanized3)
                                   Pipe                                   25                            2            350             45
connectors shall be installed in accordance with the                      solder shall not be used independently, as they do not
manufacturer’s instructions. Where a clamp is used, it                    reliably provide adequate mechanical strength.
shall not damage the electrode or the earthing                                  NOTE — Where vertical electrodes are installed, means may
conductor.                                                                      be provided to allow the inspection of the connection and there
                                                                                placement of the vertical rod.
Connection devices or fittings that depend solely on
                                                                    117
IS 732 : 2019
                                                                                                                                                SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
      1 It is not intended to connect every individual protective              The cross-sectional area of a protective conductor shall
      conductor directly to the main earthing terminal where they              either be calculated in accordance with 5.4.3.1.2, or
      are connected to this terminal by other protective conductors.           selected in accordance with Table 14. In either case,
      2 The main earthing terminal of the building can generally be            the requirements of 5.4.3.1.3 shall be taken into
      used for functional earthing purposes. For information
      technology purposes, it is then regarded as the connection point
                                                                               account.
5.4.2.4.2 Each conductor connected to the main                                 In TT systems, where the earth electrodes of the supply
earthing terminal shall be able to be disconnected                             system and of the exposed conductive parts are
individually. This connection shall be reliable and such                       electrically independent, the cross-sectional area of
that it can only be disconnected by means of a tool.                           protective conductors need not exceed:
      NOTE — Disconnection means may conveniently be combined                      –    25 mm2 copper,
      with the main earthing terminal, to permit measurement of the                –    35 mm2 aluminium.
      resistance of the earth electrode.
                                                                                                                  k1
                S < 16                                        S                                                      ×S
                                                                                                                  k2
                                                                                                                  k1
              16 < S < 35                                    161)                                                    × 16
                                                                                                                  k2
                                                             S 1)                                                 k1 S
                S > 35                                                                                              ×
                                                              2                                                   k2 2
 where
 k1 = is the value of k for the line conductor derived from the formula given in Annex A or selected from tables given in
       IEC 60364-4-43, according to the materials of the conductor and insulation;
 k2 = is the value of k for the protective conductor, selected from Tables 58 to Table 62 as applicable.
 1)
   For a PEN conductor, the reduction of the cross-sectional area is permitted only in accordance with the rules for sizing of the neutral
 conductor (see 5.2).
                                                                         118
                                                                                                                              IS 732 : 2019
5.4.3.1.2 The cross-sectional areas of protective                                  a) calculated in accordance with 5.4.3.1.2 for the
conductors shall be not less than the value determined                                most onerous prospective fault current and
either:                                                                               operating time encountered in these circuits; or
       a) in accordance with IEC 60949; or                                         b) selected in accordance with Table 14 so as to
                                                                                      correspond to the cross-sectional area of the
       b) by the following formula applicable only for
                                                                                      largest line conductor of the circuits.
          disconnection times not exceeding 5 s:
                                                                               5.4.3.2 Types of protective conductors
                                        l 2t
                                S=                                             5.4.3.2.1 Protective conductors may consist of one or
                                        k
                                                                               more of the following:
   where
   S        = the cross-sectional area in mm2;                                     a) conductors in multicore cables;
                                                                                                                                                  SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                   b) insulated or bare conductors in a common
   I        = the r.m.s value expressed in amperes of
                                                                                      enclosure with live conductors;
              prospective fault current, for a fault of
              negligible impedance, which can flow                                 c) fixed installed bare or insulated conductors;
              through     the    protective     device                             d) metallic cable sheath, cable screen, cable
              (IS/IEC 60909-0);                                                       armour, wirebraid, concentric conductor,
                                                                         119
IS 732 : 2019
5.4.3.3 Electrical continuity of protective conductors                         2 IS/IEC 60079-14 does not permit the use of a PEN, PEL or
                                                                               PEM conductor in explosive atmospheres.
5.4.3.3.1 Protective conductors shall be suitably
protected against mechanical damage, chemical or                            5.4.3.4.2 The PEN, PEL or PEM conductor shall be
electrochemical deterioration, electrodynamics forces                       insulated for the rated voltage of the line conductor.
and thermodynamic forces.                                                   Metallic enclosures of wiring systems shall not be used
Every connection (for example, screwed connections,                         as PEN, PEL or PEM conductors, except for busbar
clamp connectors) between protective conductors or                          trunking systems complying with IS 8623 (Part 2) and
between a protective conductor and other equipment                          for powertrack systems complying with IEC 61534-1.
shall provide durable electrical continuity and adequate                       NOTE — Product committees should consider the potential
mechanical strength and protection. Screws for                                 effect of EMI introduced into the equipment from a PEN, PEL
                                                                               or PEM conductor.
connecting protective conductors shall not serve any
                                                                                                                                                SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
other purpose.                                                              5.4.3.4.3 If, from any point of the installation, the
                                                                            neutral/mid-point/line and protective functions are
Joints shall not be made by soldering.
                                                                            provided by separate conductors, it is not permitted to
   NOTE — All electrical connections should have satisfactory               connect the neutral/mid-point/line conductor to any
   thermal capacity and mechanical strength to withstand any
                                                                            other earthed part of the installation. However, it is
                                                                      120
                                                                                     KEY
                                                       MDB—main distribution board
121
                                                                                                                                                                                      61A Example 1
                                                                                           Fig.61C Example 3
                                                                                                                                          Fig. 61B Example 2
                                                                                                               SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                             ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
IS 732 : 2019
5.4.3.7 Reinforced protective earthing conductors for                    5.4.4.2 Protective bonding conductors for
protective earthing conductor currents exceeding                         supplementary bonding
10 mA
                                                                         5.4.4.2.1 A protective bonding conductor connecting
For current-using equipment intended for permanent                       two exposed conductive parts shall have a conductance
connection and with a protective earthing conductor                      not less than that of the smaller protective conductor
current exceeding 10 mA the following applies:                           connected to the exposed conductive parts.
    a)   where the current-using equipment has only                      5.4.4.2.2 A protective bonding conductor connecting
         one protective earthing terminal, the protective                exposed conductive parts to extraneous conductive
         earthing conductor shall have a cross-sectional                 parts shall have a conductance not less than half that of
         area of at least 10 mm2 Cu or 16 mm2 Al,                        the cross-sectional area of the corresponding protective
         through its total run;                                          conductor.
                                                                                                                                                  SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
         NOTE — A PEN, PEL or PEM conductor in accordance
         with 5.4.3.4 complies with this requirement.                    5.4.4.2.3 The minimum cross-sectional area of
                                                                         protective bonding conductors for supplementary
    b) where the current-using equipment has a
                                                                         bonding, and of bonding conductors between two
       separate terminal for a second protective
                                                                         extraneous conductive parts, shall be in accordance
       earthing conductor a second protective
                                                                   122
                                                                                                                           IS 732 : 2019
                                                                                                                                                SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
    b) mains-excited and self-excited asynchronous                         moving parts, parts at high temperature or by the presence of
       generators;                                                         inflammable fluids and noxious gases, etc.
    c) mains-commutated and self-commutated static                      5.5.2.2.4 Provision for isolation shall meet the
       converters with or without by-pass facilities;                   requirements of 5.3.7 for each source or combination
       and                                                              of sources of supply.
                                                                                                                                                       SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
residual current devices in accordance with 4.2 remains                     filters.
effective for every intended combination of sources of                      5.5.2.4.3.3.3 A means of isolation shall be installed on
supply.                                                                     both sides of a static converter.
   NOTE — Connection of live parts of the generator with earth
                                                                            This requirement does not apply on the power source
5.5.2.4.3.3 Additional requirements for installations                            a)    the selection of generating sets with
incorporating static converters                                                        compensated windings;
                                                                                 b)    the provision of a suitable impedance in the
5.5.2.4.3.3.1 Where fault protection for parts of the                                  connection to generator star points;
installation supplied by the static converter relies upon
                                                                                 c)    the provision of switches which interrupt the
the automatic closure of the by-pass switch and the
operation of protective devices on the supply side of                                  circuit but which are interlocked so that at all
the by-pass switch is not within the time required                                     times fault protection is not impaired;
by 4.2.11, supplementary equipotential bonding shall                             d)    the provision of filtering equipment; and
be provided between simultaneously accessible                                    e)   other suitable means.
exposed-conductive-parts and extraneous-conductive-                                    NOTES
parts on the load side of the static converter in                                      1 Consideration should be given to the maximum voltage
accordance with 4.2.15.2.                                                              which may be produced across an impedance connected
                                                                                       tolimit harmonics.
The resistance of supplementary equipotential bonding
                                                                                       2 Monitoring equipment complying with IEC 61557-
conductors required between simultaneously accessible                                  12 provides information on level of disturbances
conductive parts shall fulfil the following condition:                                 resulting from the presence of harmonics.
                                                                      124
                                                                                                                                IS 732 : 2019
switched alternative to the normal supply to the                                        for a final circuit of the installation, but in this
installation                                                                            case all the following additional requirement
                                                                                        shall be fulfilled:
5.5.2.6.1 Precautions complying with the relevant
requirements of 5.3 for isolation shall be taken, so that                               1) the conductors of the final circuit shall
the generator cannot operate in parallel with the public                                     meet the following requirement:
supply system for distribution of electricity to the                                                        IZ > In + Ig
public. Suitable precautions may include:                                                  where
    a) an electrical, mechanical or electro-                                                IZ = the current-carrying capacity of the
       mechanical interlock between the operating                                                 final circuit conductors;
       mechanisms or control circuits of the change-                                        In = the rated current of the protective
       over switching devices;                                                                    device of the final circuit; and
                                                                                                                                                     SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
    b) a system of locks with a single transferable                                         Ig = the rated output current of the
       key;                                                                                       generating set.
    c) a three-position, break-before-make, change-                                     2) a generating set shall not be connected to
       over switch;                                                                        a final circuit by means of a plug and
The type of protection and the sensitivity and operating                         c) IEC 60364-7-713 for electrical installations
times depend upon the protection of the system for                                  in furniture;
distribution of electricity to the public and the number                         d) IEC 60364-7-714 for outdoor lighting
of generating sets connected and shall be agreed by the                             installations; and
distributor.                                                                     e) IEC 60364-7-715 for extra-low-voltage
In case of presence of static converters, the means of                              lighting installations.
switching shall be provided on the load side of this                         The requirements of this clause do not apply to:
static converter.
                                                                                 a)    high-voltage signs supplied at low voltage
5.5.2.7.5 Where a generating set is intended to run in                                 (called neon-tube);
parallel with the system for distribution of electricity                               NOTE — Requirements for high-voltage signs supplied
to the public, means shall be provided to prevent the                                  at low voltage (called neon-tube) are included in
                                                                                                                                                 SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
connection of a generating set to the system for                                       IEC 60598-214.
distribution of electricity to the public in the event of                        b) signs and luminous-discharge-tube
loss of that supply or deviation of the voltage or                                  installations operating from a no-load rated
frequency at the supply terminals from values declared                              output voltage exceeding 1 kV but not
for normal supply.                                                                  exceeding 10 kV; and
5.5.2.8 Requirements for installations incorporating                         Apparatus which distributes, filters or transforms the
stationary batteries                                                         light transmitted from one or more lamps and which
                                                                             includes, except the lamps themselves, all the parts
5.5.2.8.1 Stationary batteries shall be installed so that                    necessary for fixing and protecting the lamps and, where
they are accessible only to skilled or instructed persons.                   necessary, circuit auxiliaries together with the means
   NOTE — This generally requires the battery to be installed in             for connecting them to the electric supply.
   a secure location, or, for smaller batteries, a secure enclosure.
                                                                             5.5.3.2.2 Display stands for luminaires
The location or enclosure shall be adequately ventilated.
                                                                             Permanent stands in sales rooms or part of sales rooms
5.5.2.8.2 Battery connections shall have basic                               which are used to display luminaires.
protection by insulation or enclosures or shall be
                                                                                NOTE — The following items are not regarded as display
arranged so that two bare conductive parts having                               stands:
between them a potential difference exceeding 120 V                             a) trade fair stands, in which luminaires remain connected for
cannot be inadvertently touched simultaneously.                                 the duration of the fair;
                                                                                b) temporary exhibition panels with permanently connected
5.5.3 Luminaires and Lighting Installations                                     luminaires; and
5.5.3.1 Scope                                                                   c) exhibition panels with a range of luminaires which can be
                                                                                connected with a plug-in device.
The particular requirements of this clause apply to the
                                                                             5.5.3.3 General requirements for installations
selection and erection of luminaires and lighting
installations intended to be part of the fixed installation.                 Luminaires shall be selected and erected in accordance
                                                                             with the manufacturer’s instructions and shall comply
Additional requirements for specific types of lighting
                                                                             with IS 10322 series. An electrical supply track system
installations are covered in:
                                                                             for luminaires shall comply with the requirements of
    a) IEC 60364-7-702 for installations in                                  IEC 60570.
       swimming pools and fountains;                                            NOTES
    b) IEC 60364-7-711 for installations in                                     1 Refer to 5.1.2.1.5 regarding compatibility such as between
       exhibitions, shows and stands;                                           lamp and control devices. During the installation process of
                                                                       126
                                                                                                                            IS 732 : 2019
   luminaires the following items shall at least be considered:                  b) a device for connecting a luminaire (DCL)
   a) starting current;                                                             outlet according to IEC 61995 mounted in a
   b) harmonics current;                                                            box; or
   c) compensation;
                                                                                 c) electrical equipment designed to be connected
   d) leakage current;
                                                                                    directly to the wiring system.
   e) primer ignition current; and
   f) voltage dip withstand.
                                                                             5.5.3.5.2 Fixing of the luminaire
   2 Concerning the right selection of the protection and control
   devices, information about the currents relevant to all frequency         It shall be ensured that adequate means to fix the
   generated by lamps and for all transient currents should be
   provided.
                                                                             luminaire to a stable element of the construction are
   3 See Annex GG for an explanation of symbols used in                      provided.
   luminaires, in controlgear for luminaires and in the installation
                                                                             The fixing means may be mechanical accessories (for
                                                                                                                                                SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
   of the luminaires.
                                                                             example, hooks or screws), boxes or enclosures which
For the purposes of this clause, luminaires without                          are able to support luminaires (see IS 14772) or
transformer/converter and used with extra-low-voltage                        supporting devices for connecting a luminaire.
(ELV) lamps connected in series shall be considered
as low-voltage equipment and not as ELV equipment.                           The fixing means shall be capable of supporting a mass
    b) for luminaires complying with IS 10322 but                             transformer(s), marked with the symbol   ;
       with no temperature marking, heat-resistant                            or
       cables are not required unless specified in the
                                                                           b) a temperature declared thermally protected
       manufacturer’s instructions; and
                                                                              ballast(s)/transformer(s), marked with the
    c) in the absence of information, heat-resistant
       cables and/or insulated conductors in                                    symbol        .
       accordance with IEC 60245-3 or those of an                      5.5.3.7 Compensation capacitors
       equivalent type shall be used.
   NOTE — The temperature marking on the luminaire indicates           Compensation capacitors having a total capacitance
   the maximum temperature according to Table 12.2 of IS 10322         exceeding 0.5 µF shall only be used in conjunction with
   and is marked with the symbol         (see Annex GG).               discharge resistors in accordance with the requirements
                                                                       of IS 1569.
                                                                                                                                  SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
5.5.3.5.4 Devices for connection to the supply
                                                                       5.5.3.8 Protection against electric shock for display
If the luminaire does not provide connecting devices                   stands for luminaires
for connection to the supply, the connecting devices
                                                                       Protection against electric shock for circuits supplying
shall be:
                                                                       display stands for luminaires shall be provided by
5.5.3.5.5 Groups of luminaires                                         In the case of lighting for premises where machines
                                                                       with moving parts are in operation, consideration shall
Groups of luminaires divided between the three line                    be given to stroboscopic effects which can give a
conductors of a three-phase circuit with only one                      misleading impression of moving parts being stationary.
common neutral conductor shall be provided with at                     Such effects may be avoided by selecting luminaires
least one device disconnecting simultaneously all line                 with suitable lamp controlgear (for example, high
conductors (see also 5.3.6).                                           frequency electronic controlgear).
5.5.3.5.6 Protection against heat and UV radiation                     5.5.3.10 Ground recessed luminaires
effects within the luminaire
                                                                       The requirements as given in IS 10322 series shall be
External cables and cores of cables connected within a                 fulfilled by the selection and erection of ground
luminaire or passing through shall be so selected and                  recessed luminaires.
erected that they will not suffer damage or deterioration
due to heat and UV radiation generated by the luminaire                5.6 Selection and Erection of Electrical
or its lamps (for example, shielding).                                 Equipment — Safety Services
5.5.3.6 Independent lamp controlgear, for example,                     5.6.1 Void
ballasts
                                                                       5.6.2 Classification
Only independent lamp controlgear marked as suitable
                                                                       5.6.2.1 An electrical supply system for safety services
for independent use, according to the relevant standard,
                                                                       is either:
shall be used external to a luminaire.
                                                                           a) a non-automatic supply, the starting of which
   NOTE — The generally recognised symbol is:     independent                 is initiated by an operator, or
   ballast standard IEC 60417-5138 (2011-01).                              b) an automatic supply, the starting of which is
Only the following are permitted to be mounted on                             independent of an operator.
flammable surfaces:                                                    An automatic supply is classified as follows, according
    a)   a “class P” thermally protected ballast(s)/                   to the maximum changeover time:
                                                                 128
                                                                                                                          IS 732 : 2019
                                                                                                                                               SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
    e) Medium break: an automatic supply available
       within 15 s; and                                                  location and be accessible only to skilled or instructed
                                                                         persons (BA5 or BA4).
    f) Long break: an automatic supply available in
       more than 15 s.                                                   5.6.4.4 The location of the safety source shall be
                                                                         properly and adequately ventilated so that exhaust
5.6.2.2 The essential equipment for safety services shall
                                                                   129
IS 732 : 2019
maintenance-free type and shall be of heavy duty                          impairing the correct operation of circuits of safety
industrial design, for example cells complying with                       services.
IEC 60623 or the IEC 60896 series.
                                                                          5.6.5.5 Switchgear and controlgear shall be clearly
   NOTE — The minimum design life of the batteries at 20 °C               identified and grouped in locations accessible only to
   should be 10 years.                                                    skilled or instructed persons (BA5 or BA4).
5.6.4.11 Low-power supply system                                          5.6.5.6 In equipment supplied by two different circuits
The power output of a low-power supply system is                          with independent sources, a fault occurring in one
limited to 500 W for a 3 h duration and 1500 W for a 1                    circuit shall not impair the protection against electric
h duration. Batteries can be of gas-tight or valve-                       shock, nor the correct operation of the other circuit.
regulated maintenance-free type and shall be of heavy                     Such equipment shall be connected to the protective
duty industrial design, for example cells complying with                  conductors of both circuits, if necessary.
                                                                                                                                          SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
IEC 60623 or the IEC 60896 series.                                        5.6.5.7 Safety circuit cables, other than metallic
   NOTE — The minimum design life of the batteries at 20 °C               screened, fire-resistant cables, shall be adequately and
   should be 5 years.                                                     reliably separated by distance or by barriers from other
5.6.4.12 Uninterruptible power supply sources                             circuit cables, including other safety circuit cables.
    a) be able to operate distribution circuit                            5.6.5.8 Circuits for safety services, with the exception
       protective devices,                                                of wiring for fire rescue service lift supply cables, and
                                                                          wiring for lifts with special requirements, shall not be
    b) be able to start the safety devices when it is                     installed in lift shafts or other flue-like openings.
       operating in the emergency condition from the
       inverter supplied by the battery,                                  5.6.5.9 In addition to a general schematic diagram, full
    c) comply with the requirements of 5.6.4.10, and                      details of all electrical safety sources shall be given.
    d) comply with IEC 62040-1-1, IEC 62040-1-2                           The information shall be maintained adjacent to the
       or IEC 62040-3, as applicable.                                     distribution board. A single-line diagram is sufficient.
5.6.4.13 Safety generating sets                                           5.6.5.10 Drawings of the electrical safety installations
                                                                          shall be available showing the exact location of:
Where a safety generating set is used as a safety source,
it shall comply with ISO 8528-12.                                             a) all electrical equipment and distribution
                                                                                 boards, with equipment designations;
5.6.4.14 The condition of the source for safety services                      b) safety equipment with final circuit designation
(ready for operation, under fault conditions, feeding                            and particulars and purpose of the equipment;
from the source for safety services) shall be monitored.                         and
5.6.5 Circuits of Safety Services                                             c) special switching and monitoring equipment
                                                                                 for the safety power supply (for example, area
5.6.5.1 Circuits of safety services shall be independent                         switches, visual or acoustic warning
of other circuits.                                                               equipment).
   NOTE — This means that an electrical fault or any intervention
   or modification in one system must not affect the correct              5.6.5.11 A list of all the current-using equipment
   functioning of the other. This may necessitate separation by           permanently connected to the safety power supply,
   fire-resistant materials or different routes or enclosures.            indicating the nominal electrical power, nominal
5.6.5.2 Circuits of safety services shall not pass through                currents and starting currents and time for current-using
locations exposed to fire risk (BE2) unless they are                      equipment, shall be provided.
fire-resistant. The circuits shall not, in any case, pass                    NOTE — This information may be included in the circuit
through zones exposed to explosion risk (BE3).                               diagrams.
   NOTE — Where practicable, the passage of any circuit through           5.6.5.12 Operating instructions for safety equipment
   locations presenting a fire risk should be avoided.                    and electrical safety services shall be available. They
5.6.5.3 According to 4.4.3, protection against overload                   shall take into account all the particulars of the
may be omitted where the loss of supply may cause a                       installation.
greater hazard. Where protection against overload is                      5.6.6 Wiring Systems
omitted, the occurrence of an overload shall be
monitored.                                                                5.6.6.1 One or more of the following wiring systems
                                                                          shall be utilized for safety services required to operate
5.6.5.4 Overcurrent protective devices shall be selected                  in fire conditions:
and erected so as to avoid an overcurrent in one circuit
                                                                    130
                                                                                                                      IS 732 : 2019
    a) mineral insulated cable complying with                           be used so that a short-circuit in one circuit does not
       IEC 60702-1 and IEC 60702-2;                                     interrupt the supply to the adjacent luminaires within
    b) fire-resistant cables complying with the                         the fire compartment or the luminaires in other fire
       appropriate part of IEC 60331 and with                           compartments.
       IEC 60332-1-2; and                                               No more than 20 luminaires with a total load not
    c) a wiring system maintaining the necessary fire                   exceeding 60 percent of the nominal current of the
       and mechanical protection.                                       overcurrent protective device shall be supplied from
Wiring systems shall be mounted and installed in such                   any final circuit.
a way that the circuit integrity will not be impaired                   Any circuit distribution, control or protective devices
during the fire.                                                        shall not impair the circuit integrity.
   NOTE — Examples of a system maintaining the necessary fire
                                                                                                                                          SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                        5.6.7.3 A safe value of minimum illuminance, response
   and mechanical protection could be:
                                                                        time and rated operation time is required to enable
   a) constructional enclosures to maintain fire and mechanical
   protection, or                                                       evacuation of a building. Where there are no national
   b) wiring systems in separate fire compartments.                     or local rules, illumination systems should comply with
                                                                        ISO 30061.
5.6.6.2 Wiring for control and bus systems of safety
                                                                  131
IS 732 : 2019
                                                                                                                                                    SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
intentionally ‘blacked-out’ before the supply was lost;                       requirements this standard have been met.
in these cases, emergency lighting shall not switch off
automatically.                                                                6.2.1.4 Precautions shall be taken to ensure that the
                                                                              verification shall not cause danger to persons or
5.6.7.11 In addition to central switching, it is                              livestock and shall not cause damage to property and
                                                                        132
                                                                                                                    IS 732 : 2019
                                                                                                                                        SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
    j) presence of diagrams, warning notices or other               IEC 60079-17 and IEC 61241-17 are necessary.
       similar information (see 5.1.4.5);
                                                                 6.2.3.2 Continuity of conductors
    k) identification of circuits, overcurrent
       protective devices, switches, terminals, etc              An electrical continuity test shall be made on:
       (see 5.1.4);
                                                           133
IS 732 : 2019
before carrying out the insulation resistance test.                          connected to it, at least one of the faulty circuits shall
                                                                             be disconnected. The disconnection time shall be in
Where it is not reasonably practicable to disconnect
                                                                             accordance with that for the protective measure
such equipment (for example, in case of fixed socket-
                                                                             automatic disconnection of supply in a TN-system.
outlets incorporating an SPD), the test voltage for the
particular circuit may be reduced to 250 V d.c., but the                     6.2.3.5 Insulation resistance/impedance of floors and
insulation resistance must have a value of at least 1 MΩ.                    walls
   NOTES                                                                     When it is necessary to comply with the requirements
   1 For measurement purposes, the neutral conductor is                      of MM-1, at least three measurements shall be made
   disconnected from the protective conductor.
                                                                             in the same location, one of these measurements being
   2 In TN-C systems, measurement is made between the live
   conductors and the PEN conductor.
                                                                             approximately 1 m from any accessible extraneous-
                                                                             conductive-part in the location. The other two
                                                                                                                                                  SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
   3 In locations exposed to fire hazard, a measurement of the
   insulation resistance between the live conductors should be               measurements shall be made at greater distances.
   applied. In practice, it may be necessary to carry out this
   measurement during erection of the installation before the                The measurement of resistance/impedance of insulating
   connection of the equipment.                                              floors and walls is carried out with the system voltage
   4 Insulation resistance values are usually much higher than those         to earth at nominal frequency.
The separation of the live parts from other circuits,                        1) measurement of the fault loop impedance
according to 4.2.13, shall be confirmed by a                                 (see 6.2.3.6.3).
measurement of the insulation resistance. The resistance                        NOTE — When RCDs with I n < 500 mA are used as
values obtained shall be in accordance with Table 15.                           disconnecting devices, measurement of the fault loop impedance
                                                                                is normally not necessary.
6.2.3.4.3 Protection by electrical separation
                                                                             Alternatively, where the calculation of the fault loop
The separation of the live parts from those of other                         impedance or of the resistance of the protective
circuits and from earth, according to 4.2.13, shall be                       conductors are available, and where the arrangement
confirmed by a measurement of the insulation                                 of the installation permits the verification of the length
resistance. The resistance values obtained shall be in                       and cross-sectional area of the conductors, the
accordance with Table 15.                                                    verification of the electrical continuity of the protective
In case of electrical separation with more than one item                     conductors (see 6.2.3.2) is sufficient.
of current-using equipment, either by measurement or                            NOTE — Compliance may be verified by measurement of the
by calculation, it shall be verified that in case of two                        resistance of protective conductors.
coincidental faults with negligible impedance between                        2) verification of the characteristics and/or the
different line conductors and either the protective                          effectiveness of the associated protective device. This
bonding conductor or exposed-conductive-parts                                verification shall be made:
                                                                       134
                                                                                                                            IS 732 : 2019
                                                                                                                                                 SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
disconnecting times shall be verified in case of:                         by calculation or measurement of the current Id in case
    — re-used RCDs;                                                       of a first fault at the line conductor or at the neutral.
    — additions or alterations to an existing                                NOTE — The measurement is made only if the calculation is
      installation where existing RCDs are also to                           not possible, because all the parameters are not known.
                                                                             Precautions are to be taken while making the measurement in
satisfied or in case of doubt and where supplementary                      of the inspection and the results of testing.
equipotential bonding according to 4.2.15.2 is applied,
                                                                           Any defects or omissions revealed during verification
the effectiveness of that bonding shall be checked
                                                                           of the work shall be made good before the contractor
according to 4.2.15.2.2.
                                                                           declares that the installation complies with this
6.2.3.7 Additional protection                                              standard.
The verification of the effectiveness of the measures                      6.2.4.2 In the case of initial verification of alterations
applied for additional protection is fulfilled by visual                   or additions of existing installations, the report may
inspection and test.                                                       contain recommendations for repairs and
                                                                           improvements, as may be appropriate.
Where RCDs are required for additional protection,
the effectiveness of automatic disconnection of supply                     6.2.4.3 The initial report shall include:
                                                                                                                                                  SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
by RCDs shall be verified using suitable test equipment
                                                                               a) records of inspections; and
according to IEC 61557-6 (see 6.2.3. 1) confirming that
the relevant requirements of 4.2 are met.                                      b) records of circuits tested and test results.
   NOTE — Where an RCD is provided for fault protection and                The records of circuit details and test results shall
   for additional protection, it should be tested according to the         identify every circuit, including its related protective
Assemblies, such as switchgear and controlgear                             6.2.4.5 Reports shall be compiled and signed or
assemblies, drives, controls and interlocks, shall be                      otherwise authenticated by a person or persons
subjected to a test of their function to verify that they                  competent in verification.
are properly mounted, adjusted and installed in                               NOTE — Annexes QQ, RR and SS give model forms of
accordance with the relevant requirements of this                             schedules that might be used for the description and for initial,
                                                                              and also periodic, verification of installations, particularly
standard.
                                                                              suitable for domestic installations.
Protective devices shall be submitted to a test of their
function, as necessary, to check that they are properly                    6.3 Periodic Verification
installed and adjusted.                                                    6.3.1 General
   NOTE — This functional test does not replace the functional             6.3.1.1 Where required, periodic verification of every
   test indicated by the relevant standards.
                                                                           electrical installation shall be carried out in accordance
6.2.3.10 Verification of voltage drop                                      with 6.3.1.2 to 6.3.1.6.
Where required to verify compliance with 5.2.8, the                        Wherever possible, the records and recommendations
following options may be used:                                             of previous periodic verifications shall be taken into
                                                                           account.
    a) the voltage drop may be evaluated by
       measuring the circuit impedance;                                    6.3.1.2 Periodic inspection comprising a detailed
    b) the voltage drop may be evaluated by using                          examination of the installation shall be carried out
       diagrams similar to the one shown as an                             without dismantling, or with partial dismantling, as
       example in Annex NN.                                                required, supplemented by appropriate tests from 6.2,
                                                                           including verification, to show that the requirements
6.2.4 Reporting for Initial Verification                                   for disconnecting times as set out in 4.2 for RCDs are
6.2.4.1 Upon completion of the verification of a new                       complied with, and by measurements, to provide for:
installation or additions or alterations to an existing                        a) safety of persons and livestock against the
installation, an initial report shall be provided. Such                           effects of electric shock and burn,
documentation shall include details of the extent of the
                                                                               b) protection against damage to property by fire
installation covered by the report, together with a record
                                                                     136
                                                                                                                            IS 732 : 2019
                                                                                                                                             SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
Measuring instruments and monitoring equipment and                          inspection and testing of the electrical installation in
methods shall be chosen in accordance with relevant                         the building premises should be attached with the rent
parts of IEC 61557. If other measuring equipment is                         agreement document. When occupancy of a dwelling
used, it shall provide no less degree of performance                        has changed (for example, from residential to office
and safety.                                                                 etc), a verification of the electrical installation is
                                                                      137
IS 732 : 2019
                                                          ANNEX A
                                                      (Clause 4.2.13.2)
                                                        (Normative)
                                      PROVISIONS FOR BASIC PROTECTION
   NOTE — Provisions for basic protection provide protection             A-2.2 Horizontal top surfaces of barriers or enclosures
   under normal conditions and are applied where specified as a
                                                                         which are readily accessible shall provide a degree of
   part of the chosen protective measure.
                                                                         protection of at least IPXXD or IP4X.
A-1 BASIC INSULATION OF LIVE PARTS                                       A-2.3 Barriers and enclosures shall be firmly secured
   NOTE — The insulation is intended to prevent contact with             in place and have sufficient stability and durability to
                                                                                                                                              SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
   live parts.                                                           maintain the required degrees of protection and
Live parts shall be completely covered with insulation                   appropriate separation from live parts in the known
which can only be removed by destruction.                                conditions of normal service, taking account of relevant
                                                                         external influences.
For equipment, the insulation shall comply with the
                                                                   138
                                                                                                                          IS 732 : 2019
                                                              ANNEX B
                                                       (Clause 4.5.3.2.2.1)
                                                           (Normative)
                                     OBSTACLES AND PLACING OUT OF REACH
B-1 APPLICATION                                                              B-3 PLACING OUT OF REACH
The protective measures of obstacles and placing out                            NOTE — Protection by placing out of reach is intended only
                                                                                to prevent unintentional contact with live parts.
of reach provide basic protection only.
They are for application in installations with or without                    B-3.1 Simultaneously accessible parts at different
fault protection that are controlled or supervised by                        potentials shall not be within arm’s reach.
                                                                                                                                              SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
skilled or instructed persons.                                                  NOTE — Two parts are deemed to be simultaneously accessible
                                                                                if they are not more than 2.50 m apart (see Fig. 62).
The conditions of supervision under which, the basic
protective provisions of this Annex may be applied, as                       B-3.2 If a normally occupied position is restricted in
part of the protective measure are given in 4.2.6.                           the horizontal direction by an obstacle (for example,
                                                                             handrail, mesh screen etc) affording a degree of
                                                                       139
IS 732 : 2019
                                                             ANNEX C
                                                       (Clause 4.2.13.1.3)
                                                          (Normative)
      PROTECTIVE MEASURES FOR APPLICATION ONLY WHEN THE INSTALLATION
  IS CONTROLLED OR UNDER THE SUPERVISION OF SKILLED OR INSTRUCTED PERSONS
   NOTE — The conditions of supervision under which the fault               2 000 V. Leakage current shall not exceed 1 mA in
   protective provisions (protection against indirect contact) of
                                                                            normal conditions of use.
   Annex C may be applied as part of the protective measure are
   given in 4.2.7.                                                          C-1.5 The resistance of insulating floors and walls at
                                                                            every point of measurement under the conditions
                                                                                                                                                       SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
C-1 NON-CONDUCTING LOCATION
                                                                            specified in 6 shall be not less than:
   NOTE — This protective measure is intended to prevent
   simultaneous contact with parts which may be at different                     a) 50 kΩ, where the nominal voltage of the
   potential through failure of the basic insulation of live parts.                 installation does not exceed 500 V, or
C-1.1 All electrical equipment shall comply with one                             b) 100 kΩ, where the nominal voltage of the
                                                                      140
                                                                                                                   IS 732 : 2019
C-2.4 Precautions shall be taken to ensure that persons                 earthed equipotential bonding conductors. Such
entering the equipotential location cannot be exposed                   conductors shall not be connected to the protective
to a dangerous potential difference, in particular, where               conductors or exposed-conductive-parts of other
a conductive floor insulated from earth is connected to                 circuits or to any extraneous-conductive-parts (see Note
the earth-free equipotential bonding system.                            under 4.2.13.3.6).
C-3 ELECTRICAL SEPARATION FOR THE                                       C-3.5 All socket-outlets shall be provided with
SUPPLY OF MORE THAN ONE ITEM OF                                         protective contacts which shall be connected to the
CURRENT-USING EQUIPMENT                                                 equipotential bonding system provided in accordance
                                                                        with C-3.4.
   NOTE — Electrical separation of an individual circuit is
   intended to prevent shock currents through contact with              C-3.6 Except where supplying equipment with double
   exposed-conductive-parts that may be energized by a fault in         or reinforced insulation, all flexible cables shall embody
                                                                                                                                     SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
   the basic insulation of the circuit.
                                                                        a protective conductor for use as an equipotential
C-3.1 All electrical equipment shall comply with one                    bonding conductor in accordance with C-3.4.
of the provisions for basic protection described in
                                                                        C-3.7 It shall be ensured that if two faults affecting
Annex A.
                                                                        two exposed-conductive-parts occur and these are fed
                                                         ANNEX D
                                                        (Clause 4.4)
                                                        (Normative)
          PROTECTION OF CONDUCTORS IN PARALLEL AGAINST OVERCURRENT
                                                                  141
IS 732 : 2019
significant effect on the current sharing. The reactive             The value used for Iz in 4.4.4.1, Equations (1) and (2),
component is influenced by the relative physical                    is either the continuous current-carrying capacity of
position of each cable. If, for example, a circuit consists         each conductor, Izk, if an overload protective device is
of two large cables per phase, having the same length,              provided for each conductor (see Fig. 63) hence:
construction and cross-sectional area and arranged in
                                                                              IBk < Ink < Izk                              ....(6)
parallel but with adverse relative positioning (that is,
cables of the same phase bunched together) the current              or
sharing may be 70 percent/30 percent rather than                    the sum of the current-carrying capacities of all the
50 percent/50 percent).                                             conductors, ∑Izk, if a single overload protective device
Where the difference in impedance between parallel                  is provided for the conductors in parallel (see Fig. 64)
conductors causes unequal current sharing, for example              hence:
                                                                                                                                     SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
greater than 10 percent difference, the design current                        IB < In < Izk                                ....(7)
and requirements for overload protection for each
conductor should be considered individually.                        where
                                                                         Ink = the nominal current of the protective device
The design current for each conductor can be calculated
                                                                                for conductor k;
from the total load and the impedance of each
where
   IB     = the current for which the circuit is designed;
   IBk = the design current for conductor k;
   Zk = the impedance of conductor k; and
   Z1 and Zm = the impedances of conductors 1 and m,
          respectively.
                                                              142
                                                                                                              IS 732 : 2019
                                                                                                                                SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                                              ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
                                                                     FIG. 65 CURRENT FLOW AT THE B EGINNING OF THE
                                                                                        FAULT
   FIG. 64 CIRCUIT IN WHICH A SINGLE OVERLOAD
     P ROTECTIVE DEVICE IS P ROVIDED FOR THE m
             CONDUCTORS IN P ARALLEL
                                                             143
IS 732 : 2019
                                                                                                                          SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                     ANNEX E
                                                             144
                                                                                                             IS 732 : 2019
                                                    ANNEX F
                                                   (Clause 4.4)
                                                   (Normative)
              POSITION OR OMISSION OF DEVICES FOR OVERLOAD PROTECTION
                                                                                                                                SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
of the devices for overload protection or for short-
circuit protection may not follow this general
requirement, provided the other protection remains
operative.
                                                            145
IS 732 : 2019
                                                                                                                                      SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
  NOTE — P2, P3 and P4 are the short-circuit protective devices for branch circuits S2, S3 and S4 respectively.
NOTE — P2, P3 and P4 are the short-circuit protective devices for branch circuits S2, S3 and S4, respectively.
                                                                 146
                                                                                                                IS 732 : 2019
                                                    ANNEX G
                                         (Clauses 4.4.4.4.2 and 4.4.5.2.2)
                                                   (Normative)
            POSITION OR OMISSION OF DEVICES FOR SHORT-CIRCUIT PROTECTION
                                                                                                                                    SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
For some applications, one of the devices for overload                      specification proposed by the “triangular
protection or for short-circuit protection may not follow                   rule”.
this general requirement, provided the other protection
                                                                  The maximum length of the conductor branched off at
remains operative.
                                                                  O, with the cross-sectional area S2, that is protected
    FIG. 73 LIMITED CHANGE OF POSITION OF SHORT-CIRCUIT P ROTECTIVE D EVICE (P2) ON A BRANCH CIRCUIT
                                            (see 4.4.5.2.1)
                                                            147
IS 732 : 2019
                                                         A                        O                 B
                                           P1
                                                                  S1
                                                                                      S2            P
                                                                              N                     P 22
                                                     S2
                                                                                  P2
                                                M
                                                                                                         S2
                                                    P2
                                                                         L1
                                                A                                 0                  B
                                                                                                                                            SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                             S1
                                                                                      S2
                                      L2
                                                                                  N
                                                M
   2 If, for section S2, the lengths of wiring differ according to the         protective device may be omitted for some applications
   nature of insulation, the method is applicable by taking the
                                                                               such as transformers or measuring circuits provided
   length:
                                                                               that, in accordance with the requirements of 4.4.5.3,
                               AB = L2S1/S2
   If, for section S2, the lengths of wiring are the same whatever to
                                                                               the risk of short-circuit, fire and danger to persons is
   the nature of insulation, the method is applicable by taking the            reduced to a minimum.
   length:
                                                                               Note that a measuring circuit employing a current
                                  AB= L1
                                                                               transformer must not be open-circuited otherwise an
G-3 CASE WHERE SHORT-CIRCUIT                                                   overvoltage will result.
PROTECTION MAY BE OMITTED                                                      For some applications, such as a magnetic crane, short-
With reference to 4.4.5.3 and Fig. 75, the short-circuit                       circuit protection may be omitted (see 4.4.5.3).
                                                                         148
                                                                                                             IS 732 : 2019
                                                     ANNEX H
                                                    (Clause 4.5)
                                                    (Normative)
                        EXPLANATORY NOTES CONCERNING 4.4.5.1 AND 4.4.5.2
                                                                                                                               SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
those that may occur on the high-voltage side of the               impedance and where earth faults are cleared in a
substation supplying a low-voltage system through a                reasonably short time given by the protective
distribution system operating at a higher voltage. Such            equipment.
faults cause a current to flow in the earth electrode to
which the exposed-conductive-parts of the substation               No connection of the neutral to earth in the relevant
                                                                   transformer substation is considered.
The fault-current flowing in the earth electrode of the            Only single-fault conditions due to a first earth fault
exposed-conductive-parts of the substation causes a rise           between a high-voltage live-part and exposed-
of the potential with respect to earth of the exposed-             conductive-parts of the transformer substation are taken
conductive-parts of the substation whose magnitude is              into account. This (capacitive) current may or may not
governed by:                                                       be interrupted, depending on its magnitude and the
                                                                   protective system.
    a) the fault-current magnitude, and
    b) the resistance of the earth electrode of the                High-voltage systems with arc-suppression coils
       exposed-conductive-parts of the substation.                 No arc-suppression coils in the relevant transformer
The fault-voltage may be as high as several thousand               substation are considered.
volts and, depending on the earthing systems of the
                                                                   Where an earth fault in the high-voltage system occurs
installation, may cause
                                                                   between a high-voltage conductor and the exposed-
    a) a general rise of the potential of the exposed-             conductive-parts of the transformer substation, only
       conductive-parts of the low-voltage system                  small fault currents occur (residual currents mostly in
       with respect to earth, which may give rise to               the order of some tens of amperes). These currents may
       fault and touch-voltages;                                   persist for longer times.
    b) a general rise of the potential of the low-
       voltage system with respect to earth, which                 H-2 OVERVOLTAGES IN LV-SYSTEMS DURING
       may cause a breakdown in the low-voltage                    A HIGH-VOLTAGE EARTH FAULT
       equipment.                                                  Figure 28 has been derived from curve c2 of Fig. 20 of
It usually takes longer to clear a fault in a high-voltage         IS/IEC 60479-1 and was also taken as a practical
system than in a low-voltage system, because the relays            proofed decision in IEC 61936-1.
have time delays for discrimination against unwanted               When considering the values for the fault-voltage, the
tripping on transients. The operating times of the high-           following should be taken into account:
voltage switchgear are also longer than for low-voltage
switchgear. This means that the resulting duration of                  a) the low risk of an earth-fault in the HV system;
the fault-voltage and the corresponding touch-voltage                     and
on the exposed-conductive-parts of the low-voltage                     b) the fact that the touch voltage is always lower
system may be longer than required by the LV                              than the fault-voltage due to the main
installation rules.                                                       equipotential bonding required in 4.2.11.3.1.2
There may also be a risk of breakdown in the low-                         and the presence of additional earth electrodes
voltage system of the substation or consumer’s                            at the consumer’s installation or elsewhere.
installation. The operation of protective devices under            Values given by ITU-T 650 V for 0.2 s and 430 V for
abnormal conditions of transient recovery voltages may             automatic disconnection in longer than 0.2 s are slightly
give rise to difficulties in opening the circuit or even           in excess of the values given in Fig. 28.
failure to do so.
                                                             149
IS 732 : 2019
                                                                ANNEX J
                                                              (Clause 4.5)
                                                              (Normative)
       GUIDANCE FOR OVERVOLTAGE CONTROL BY SPDs APPLIED TO OVERHEAD LINES
J-1 In the conditions of 4.5.3.3.2.1 and according to                              accordance with (a) at each transition point
Note 1, the protective control of the overvoltage level                            from and overhead line to an underground
may be obtained either by installing surge protective                              cable;
devices directly in the installation, or with the consent                       c) in a TN distribution network supplying
of the network operator, in the overhead lines of the                              electrical installations, where protection
supply distribution network.
                                                                                                                                                  SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                   against indirect contact is provided by
As an example, the following measures may be applied:                              automatic disconnection of supply, the
                                                                                   earthing conductors of the overvoltage
      a) in the case of overhead supply distribution                               protective devices connected to the line
         networks, overvoltage protection is erected at                            conductors are connected to the PEN
         network junction points and especially at the
       b                                                               0                                                              01)
                                                                                           U0      3       R × Im + U0       3
      C2)                 0                      0                     0                                                              01)
                                                                                     R × Im + U0       3         U0      3
       d                  0                                                                                                           01)
                                                                                     R × Im + U0       3         U0      3
       e2)                                       0                                                                                   R × Im
                                                                                     R × Im + U0       3   R × Im + U0       3
1)
      In fact, Uf is equal to the product of first fault current by the resistance of the earth electrode of the exposed-conductive-parts
      (RA × Id) which shall be less or equal to UL.
      Further, in systems a, b and d, the capacitive currents which flow through the first fault may increase in certain cases the value of Uf,
      but this is disregarded.
2)
      In systems c1 and e1, an impedance is installed between the neutral and earth (impedance neutral).
      In systems c2 and e2, no impedance is installed between the neutral and earth (isolated neutral).
                                                                      150
                                                                                                     IS 732 : 2019
                                                     ANNEX K
                                                (Clause 4.5.3.3.2.2)
                                                    (Normative)
                       DETERMINATION OF THE CONVENTIONAL LENGTH, d
K-1 The configuration of the low-voltage distribution                  unscreened line of the structure, limited to
line, its earthing, insulation level and the phenomena                 1 km;
considered: (induced coupling, resistive coupling) lead
                                                                d3 = the length of the high-voltage overhead
to different choices for d. The determination proposed
                                                                     supply line of the structure, limited to 1 km;
below represents, by convention, the worst case.
                                                                       The length of a high-voltage underground
                                                                                                                       SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
   NOTE — This simplified method is based on IEC 61662.
                                                                       supply line is neglected.
                             d 2 d3                                    The length of a screened low-voltage
                   d =d1 +      +                                      underground line is neglected.
                             Kg K t
                                                                Kg = 4 is the reduction factor based on the ratio
                                                          151
IS 732 : 2019
                                                                                                        SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
HV line overhead
                                                           152
                                                                                                          IS 732 : 2019
                                                 ANNEX L
                                                  (Clause 5.1)
                                                  (Normative)
                              CONCISE LIST OF EXTERNAL INFLUENCES
                                                                                                                               SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
    AA6   +5      +60                       AM       Electromagnetic, electrostatic, or AM23       Conducted
    AA7   –25 +55                                    ionizing influences                           unidirectional transients
    AA8   –50 +40                                    Low-frequency electromagnetic                 of the microsecond to
                                                     phenomena (conducted or                       the millisecond time
    AB    Temperature and humidity                   radiated)                                     scale
    AB1   –60°C +5°C         3%      100%            Harmonics, interharmonics                     Controlled level
    AB2   –40°C +5°C         10%     100%            Controlled level                              Medium level
                                                       153
IS 732 : 2019
                                                                                                                                            SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                          CB1      Negligible risks
               CA    Construction materials               CB2      Propagation of fire
 Building
                                                                     154
                                                                                                   IS 732 : 2019
M-1.6 In practice, the climatograms may be used as        climatogram for class AB6 up to the point where it
follows:                                                  meets the curve for 35 g/m3 absolute air humidity
                                                          which is the limit value for high absolute air humidity
        The relevant value of relative air humidity at
                                                          for this class. From this point one draws a horizontal
        a certain value of air temperature within the
                                                          line to the scale of relative air humidity, and one will
        temperature range of a class may be found at
                                                          find a value of 67 percent relative air humidity.
        the point where the curve for constant
        absolute air humidity cuts the straight lines     Using this method, any other possible combination of
        for air temperature and relative air humidity     air temperature and relative air humidity within the
        respectively.                                     range of the class may be found, for example, in class
                                                          AB6 a value of 27 percent relative air humidity will
Example:
                                                          be found at the limit value of high air temperature
A product may be selected for installation conditions     which is 60 °C.
                                                                                                                     SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
covered by class AB6. To find out which relative air
                                                          Climatogram
humidity the product will have to withstand in the
utmost at, for example, 40 °C, one follows the            Interdependence of air temperature, relative air
vertical line for air temperature 40 °C in the            humidity and absolute air humidity.
                                                         155
                                                                                              Class AB 2
                                                                                                                                                                                                  Climatogram
                                                                                                                                                                                                                IS 732 : 2019
156
                                                                                                           Interdependence of air temperature, relative air humidity and absolute air humidity.
      SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                    ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
                                                                                              Class AB 3
                                                                                                                                                                                                  Climatogram
157
                                                                                                           Interdependence of air temperature, relative air humidity and absolute air humidity.
                                                                                                                                                                                                                IS 732 : 2019
      SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                    ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
                                                                                              Class AB 4
                                                                                                                                                                                                  Climatogram
                                                                                                                                                                                                                IS 732 : 2019
158
                                                                                                           Interdependence of air temperature, relative air humidity and absolute air humidity.
      SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                    ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
                                                                                              Class AB 5
                                                                                                                                                                                                  Climatogram
159
                                                                                                           Interdependence of air temperature, relative air humidity and absolute air humidity.
                                                                                                                                                                                                                IS 732 : 2019
      SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                    ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
                                                                                              Class AB 6
                                                                                                                                                                                                  Climatogram
                                                                                                                                                                                                                IS 732 : 2019
160
                                                                                                           Interdependence of air temperature, relative air humidity and absolute air humidity.
      SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                    ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
                                                                                              Class AB 7
                                                                                                                                                                                                  Climatogram
161
                                                                                                           Interdependence of air temperature, relative air humidity and absolute air humidity.
                                                                                                                                                                                                                IS 732 : 2019
      SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                    ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
                                                                                              Class AB 8
                                                                                                                                                                                                  Climatogram
                                                                                                                                                                                                                IS 732 : 2019
162
                                                                                                           Interdependence of air temperature, relative air humidity and absolute air humidity.
      SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                    ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
                                                                                                                        IS 732 : 2019
                                                          ANNEX N
                                                         (Clause 5.1)
                                                          (Normative)
                           CLASSIFICATION OF MECHANICAL CONDITIONS
  Environmental     Unit                                                          Class
    Parameter
                                        AG1/AH1                                  AG2/AH2                     AG3/AH3
                                                                                                                                        SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
Stationary
vibration,
sinusoidal
Displacement      mm       0.3         1.5             1.5            3.0            3.0         7.0         10            15
amplitude
                                                                   163
IS 732 : 2019
                                                                ANNEX P
                                                               (Clause 5.1)
                                                                (Normative)
                                    CLASSIFICATION OF MACRO-ENVIRONMENTS
                                                                                                                                                SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                     3K 3                                       3C 2/3S 1
                        II                                         AB 4                                         AF 1/AE 4
                                                   3K 5, but the high air temperature                           3C 1/3S 2
                                                         is restricted to +40 °C
                       III                                           AB 7                                       AF 2/AE 5
NOTE  The macro-environment is the environment of the room or other location in which the equipment is installed or used.
                                                               ANNEX Q
                                                              (Clause 5.1.6)
                                                                (Normative)
                 PERMISSIBLE PROTECTIVE CONDUCTOR CURRENTS FOR EQUIPMENT
As additional information to 5.1.6, IEC 61140                              The requirements of 7.5.2 of IEC 61140 take into
specifies protective conductor currents and their                          account equipment intended to be supplied by plug
limits as follows.                                                         and socket-outlet systems, or by a permanent
      NOTE  Subclauses are reproduced directly from IEC 61140.
                                                                           connection, or the case of stationary equipment.
                                                                        164
                                                                                                       IS 732 : 2019
                                                                                                                         SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
       should state the maximum values for the
       protective conductor current, which in no             These values are for consideration by product
       case shall exceed 5 percent of the rated              committees in order to prevent excessive protective
       input current per phase.                              conductor currents and to provide co-ordination of
                                                             electrical equipment and of protective measures
However, product committees shall consider that, for         within an electrical installation.
                                                            165
IS 732 : 2019
                                                                         ANNEX R
                                                                       (Clause 5.2.4.1)
                                                                           (Normative)
                                                       METHODS OF INSTALLATIONS
                                                                                                                                                                   SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
          and Cables                                                             Skirting Trunking, Ducting             Cable Tray,
                                       Fixings       Direct        Systems                                                               Insulators       Wire
                                                                                    Flush Floor      Systems              Cable
                                                                                     Trunking)                           Brackets
1.      Bare conductors                    –          –                –                  –                      –            –              +              –
2.      Insulated conductors2)             –          –                +                  +1)                    +            –              +              –
        Sheathed        Multi-             +          +                +                  +                      +            +              0              +
                                                                                    166
                                                                                                   IS 732 : 2019
                                                                                         Reference Method of
                                                                                       Installation to be Used to
Item No.   Methods of Installation                     Description                     Obtain Current-Carrying
                                                                                                Capacity
                                                                                             (see Annex S)
                                                                                                                    SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                       conduit in a thermally insulated wall11.3)
                                                167
IS 732 : 2019
Table 19 — (Continued)
                                                                                                  Reference Method of
                                                                                                Installation to be Used to
 Item
                Methods of Installation                       Description                       Obtain Current-Carrying
  No.
                                                                                                         Capacity
                                                                                                      (see Annex S)
                                                                                                                             SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                            Insulated conductors in conduit or single-core or
  15                                                                                                       A1
                                            multi-core cable in architrave3,6)
  30                    > <
                               0,3 De                                                                C with item 2
                                                                                                       of Table 36
                 > <
                        0,3 De
                                                       168
                                                                                                        IS 732 : 2019
Table 19 — (Continued)
                                                                                               Reference Method of
                                                                                             Installation to be Used to
Item
         Methods of Installation                              Description                    Obtain Current-Carrying
 No.
                                                                                                      Capacity
                                                                                                   (see Annex S)
31                  > <
                            0,3 De
                                                                                                                          SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                       E or F
                                             NOTE  Refer to S-6.2 of Annex S for
                                             description
       > <
               0,3 De
34
36
                                             Bare or insulated conductors on insulators                  G
                                                       169
IS 732 : 2019
Table 19 — (Continued)
                                                                                                             Reference Method of
                                                                                                           Installation to be Used to
  Item
                      Methods ofInstallation                               Description                     Obtain Current-Carrying
   No.
                                                                                                                    Capacity
                                                                                                                 (see Annex S)
                                                                                                              Under consideration
   42                                                                                                      The following may be used:
                                                         Single-core or multi-core cable in conduit in a       1.5 De < V < 20 De
                                                         building void3)                                               B2
                                                                                                                    V > 20 De
                                                                                                                       B1
                                                                                                                                        SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                              1.5 De < V < 20 De
   43                                                                                                                 B2
         D                                V              Insulated conductors in cable ducting
         Dee                                                                                                       V > 20 De
                                                         in a building void3,9,10)
                                                                                                                      B1
                                                                                                              Under consideration
                                                                                                           The following may be used
                                                         Single-core or multi-core cable in cable             1.5 De < V < 20 De
   46           De                                V      ducting in masonry having a thermal resistivity              B2
                                                         not greater than 2 K·m/W3)                                V > 20 De
                                                                                                                      B1
                       ICT
                       ISDN        ICT
                                   ISDN
                                                                    170
                                                                                                          IS 732 : 2019
Table 19 — (Continued)
                                                                                                 Reference Method of
                                                                                               Installation to be Used to
Item No.         Methods of Installation                       Description                     Obtain Current-Carrying
                                                                                                        Capacity
                                                                                                     (see Annex S)
                                                                                                                            SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                              Insulated conductors in conduit in
  55                                          an open or ventilated cable channel                         B1
                                              in the floor12,13)
                                                        171
IS 732 : 2019
Table 19 — (Concluded)
                                                                                                                    Reference Method of
                                                                                                                  Installation to be Used to
 Item No.                Methods of Installation                                Description                       Obtain Current-Carrying
                                                                                                                           Capacity
                                                                                                                        (see Annex S)
                                                                                                                                                  SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
 1)
       The inner skin of the wall has a thermal conductance of not less than 10 W/m2·K.
 2)
       Values given for installation methods B1 and B2 in Annex S are for a single circuit. Where there is more than one circuit in the
       trunking the group reduction factor given in Table 36 is applicable, irrespective of the presence of an internal barrier or partition.
 3)
       Care shall be taken where the cable runs vertically and ventilation is restricted. The ambient temperature at the top of the vertical
       section can be increased considerably. The matter is under consideration.
                                                                         172
                                                                                                                        IS 732 : 2019
                                                          ANNEX S
                                                        (Clause 5.2.6.2)
                                                            (Normative)
                                          CURRENT-CARRYING CAPACITIES
                                                                                                                                             SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                               irrespective of the method of installation:
cross-sectional area of conductors, such as the
                                                                               30 °C; and
requirements for protection against electric shock
(see 4.2), protection against thermal effects (see 4.3),                    b) for buried cables, either directly in the soil
overcurrent protection (see 4.4), voltage drop                                 or in ducts in the ground: 20 °C.
(see 5.2.8), and limiting temperatures for terminals                  S-2.2 Where the ambient temperature in the intended
                                                                     173
IS 732 : 2019
   resistivity appropriate for the load to be carried, the values of    containing different sizes of equally loaded insulated
   current-carrying capacity may be derived by the methods of
   calculation given in IEC 60287 series or obtained from the
                                                                        conductors or cables is dependent on the total number
   cable manufacturer.                                                  in the group and the mix of sizes. Such factors cannot
                                                                        be tabulated but shall be calculated for each group.
S-4 GROUPS CONTAINING MORE THAN ONE                                     The method of calculation of such factors is outside
CIRCUIT                                                                 the scope of this standard. Some specific examples of
                                                                        where such calculations may be advisable are given
S-4.1 Installation Types A to D in Table 20
                                                                        below.
The current-carrying capacities given in Tables 21 to
Table 26 relate to single circuits consisting of the                         NOTE  A group containing sizes of conductor spanning a
following numbers of conductors:                                             range of more than three adjacent standard sizes may be
                                                                             considered as a group containing different sizes. A group of
    a) two insulated conductors or two single-core                           similar cables is taken to be a group where the current-carrying
                                                                                                                                                SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                             capacity of all the cables is based on the same maximum
       cables, or one twin-core cable; and                                   permissible conductor temperature and where the range of
    b) three insulated conductors or three single-                           conductor sizes in the group spans not more than three adjacent
       core cables, or one three-core cable.                                 standard sizes.
Where more insulated conductors or cables, other                        S-5.1 Groups in Conduit Systems, Cable
than bare mineral insulated cables not exposed to                       Trunking Systems or Cable Ducting Systems
                                                                       174
                                                                                                                     IS 732 : 2019
installation for which the current-carrying capacity                             increase and the cable becomes overloaded. One way of
                                                                                 avoiding this heating is to use the tables for 70 °C
has been determined by test or calculation.                                      conductor temperature even for cables designed for
    a) Reference methods A1, item 1 of Table 19                                  90 °C.
       (insulated conductors in conduit in a                                e)   Reference methods E, F and G, items 32
       thermally insulated wall) and A2, item 2 of                               and 33 of Table 19 (single-core or multi-
       Table 19 (multi-core cable in conduit in a                                core cable in free air):
       thermally insulated wall):                                                A cable so supported that the total heat
       The wall consists of an outer weatherproof                                dissipation is not impeded. Heating due to
       skin, thermal insulation and an inner skin of                             solar radiation and other sources shall be
       wood or wood-like material having a                                       taken into account. Care shall be taken that
       thermal conductance of at least 10 W/m2·K.                                natural air convection is not impeded. In
       The conduit is fixed so as to be close to, but                            practice, a clearance between a cable and
                                                                                                                                         SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
       not necessarily touching the inner skin. Heat                             any adjacent surface of at least 0.3 times the
       from the cables is assumed to escape                                      cable external diameter for multi-core cables
       through the inner skin only. The conduit can                              or 1 time the cable diameter for single-core
       be metal or plastic.                                                      cables is sufficient to permit the use of
    b) Reference methods B1, item 4 of Table 19                                  current-carrying capacities appropriate to
                                                                      175
IS 732 : 2019
          installation which are commonly used for fixed                                     reference method A. It may be necessary to
          electrical installations. The tabulated capacities relate to
          continuous steady-state operation (100 % load factor)
                                                                                             apply the correction factors due to higher
          for d.c. or a.c. of nominal frequency 50 Hz or 60 Hz.                              ambient temperatures that may arise in the
          2 Table 20 itemizes the reference methods of                                       junction boxes and similar mounted in the
          installation to which the tabulated current-carrying                               ceiling.
          capacities refer. It is not implied that all these items are                       NOTE  Where a junction box in the ceiling is used
          necessarily recognized in national rules of all countries.                         for supply to a luminaire, the heat dissipation from the
          3 For convenience where computer-aided installation                                luminaire may provide higher ambient temperatures
          design methods are employed, the current-carrying                                  than prescribed in Tables 21 to Table 24 (see
          capacities in Tables 21 to Table 32 can be related to                              also 5.2.5.1). The temperature may be between 40 °C
          conductor size by simple formulae. These formulae                                  and 50 °C, and a correction factor according to “Table
          with appropriate coefficients are given in Annex U.                                33” has to be applied.
    f)    Cables in a ceiling: this is similar to
                                                                                                                                                        SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
  Table 20 Installation Reference Methods Forming Basis of Tabulated Current-Carrying Capacities
                                   (Clauses S-1, S-2.2 and S-4.1)
                                 Insulated
                                conductors
                               (single- core
                 Room                                       21            23          22         24                        33
                                 cables) in      A1                                                           –                            36
                                                           col 2         col 2       col 2      col 2
                               conduit in a
                                 thermally
                              insulated wall
                             Multi-core cable                                                                                             36
                 Room        in conduit in a                21            23          22         24                        33          except D
                                                 A2                                                           –
                                thermally                  col 3         col 3       col 3      col 3                                  (Table 38
                              insulated wall                                                                                            applies)
                                Insulated
                               conductors
                              (single- core                 21            23          22         24                        33
                                                 B1                                                           –                            36
                                cables) in                 col 4         col 4       col 4      col 4
                              conduit on a
                              wooden wall
                               Multi-core
                             cable in conduit    B2         21            23          22         24           –            33              36
                              on a wooden                  col 5         col 5       col 5      col 5
                                   wall
                                                  C         21            23          22         24        70 °C           33              36
                              Single-core or               col 6         col 6       col 6      col 6      Sheath
                             multi-core cable                                                                25
                               on a wooden                                                                 105 °C
                                   wall                                                                    Sheath
                                                                                                             26
                                Multi-core       D1         21            23          22         24           –            34              38
                              cable in ducts               col 7         col 7       col 7      col 7
                              in the ground
                                                                           176
                                                                                                                                  IS 732 : 2019
Table 20 — (Concluded)
Number of cores
                                                                                                                                                   SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                           2            3           2            3     2 and 3
                                                                                                       70 °C
                                                            Copper                Copper               Sheath
                                                              29                    31                   27
                              Multi-core cable                                                                            33
                                                  E        Aluminium             Aluminium                                                39
                                in free air                                                            105 °C
                                                              30                    32
Clearance to wall not less                                                                             Sheath
     than 0,3 times                                                                                      28
     cable diameter
                                                               Copper                   Copper         70 °C
                                                                 29                       31           Sheath
                                Single-core                                                              27               33
                              cables, touching                                                                                            40
                                 in free air      F        Aluminium             Aluminium             105 °C
                                                              30                    32                 Sheath
Clearance to wall not less                                                                               28
 than one cable diameter
                                                                                                       70 °C
                                                               Copper                   Copper
                                                                                                       Sheath
                               Single-core                       29                       31
                                                                                                         27               33
                             cables, spaced in   G                                                                                        —
 At least one                     free air                                                             105 °C
                                                           Aluminium             Aluminium
 cable diameter                                                                                        Sheath
                                                              30                    32
                                                                                                         28
                                                                        177
IS 732 : 2019
                                                                                                                                       SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
      (1)             (2)              (3)              (4)              (5)              (6)             (7)              (8)
    Copper
      1.5             14.5             14              17.5             16.5             19,5              22              22
                                                                 178
                                                                                                                    IS 732 : 2019
                                                                                                                                       SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
      (1)             (2)              (3)              (4)              (5)              (6)              (7)             (8)
    Copper
      1.5              19             18.5              23               22               24               25               27
                                                                  179
IS 732 : 2019
    Nominal
 Cross-sectional
Area of Conductor
       mm2
                                                                                                                                     SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
       (1)               (2)            (3)            (4)              (5)            (6)            (7)               (8)
     Copper
       1.5              13.5            13             15.5             15            17.5            18                19
                                                                  180
                                                                                                                        IS 732 : 2019
   Nominal             A1               A2                B1               B2                C                D1                D2
Cross-sectional
   Area of
  Conductor
     mm2
                                                                                                                                           SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
      (1)              (2)              (3)               (4)              (5)               (6)              (7)               (8)
    Copper
      1.5              17               16.5              20               19.5              22               21                23
      2.5              23                22               28               26                30               28                30
                                                                    181
IS 732 : 2019
                                                                                                                                           SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
           mm2
            500 V
             1.5                                 23                                   19                                21
             2.5                                 31                                   26                                29
              4                                  40                                   35                                38
            750V
             1.5                                 25                                   21                                23
             2.5                                 34                                   28                                31
              4                                  45                                   37                                41
              6                                  57                                   48                                52
              10                                 77                                   65                                70
              16                                 102                                  86                                92
              25                                 133                                 112                               120
              35                                 163                                 137                               147
  NOTES
  1 For single-core cables the sheaths of the cables of the circuit are connected together at both ends.
  2 For bare cables exposed to touch, values should be multiplied by 0.9.
  3 The values of 500 V and 750 V are the rated voltage of the cable.
                                                                     182
                                                                                                                   IS 732 : 2019
                                                                                                                                    SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
    of Conductor
         mm2
NOTES
1 For single-core cables, the sheaths of the cables of the circuit are connected together at both ends.
2 No correction for grouping need be applied.
3 For this table reference method C refers to a masonry wall because the high sheath temperature is not normally acceptable for a
wooden wall.
4 The values of 500 V and 750 V are the rated voltage of the cable.
                                                              183
IS 732 : 2019
                                                                                                                                        SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                  Formation
Area of Conductor        Method E or F                                   Method F                                      Method G
                                               Method E or F                                         Method G
         mm2
                                 or                       or                      or
                                                                                  or
     500 V
         1.5                    25                       21                       23                       26                29
         2.5                    33                       28                       31                       34                39
          4                     44                       37                       41                       45                51
      750 V
         1.5                    26                       22                       26                       28                32
         2.5                    36                       30                       34                       37                43
          4                     47                       40                       45                       49                56
          6                     60                       51                       57                       62                71
         10                     82                       69                       77                       84                95
         16                     109                      92                       102                      110               125
         25                     142                      120                      132                      142               162
         35                     174                      147                      161                      173               197
  NOTES
  1 For single-core cables the sheaths of the cables of the circuit are connected together at both ends.
  2 For bare cables exposed to touch, values should be multiplied by 0,9.
  3 De is the external diameter of the cable.
  4 The values of 500 V and 750 V are the rated voltage of the cable.
                                                                      184
                                                                                                                      IS 732 : 2019
                                                                                                                                        SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
Area of Conductor        Method E or F           Method E or F               Method F                Method G
      mm2
                              or
                              or                        or
                                                       or                      or
                                                                               or
                                                                                                             Dee
                                                                                                             D
                                                                                                                           Dee
                                                                                                                           D
     500 V
       1.5                     31                      26                       29                         33              37
       2.5                     41                      35                       39                         43              49
        4                      54                      46                       51                         56              64
     750 V
       1.5                     33                      28                       32                         35              40
       2.5                     45                      38                       43                         47              54
        4                      60                      50                       56                         61              70
        6                      76                      64                       71                         78              89
  NOTES
  1 For single-core cables the sheaths of the cables of the circuit are connected together at both ends.
  2 No correction for grouping need be applied.
  3 De is the external diameter of the cable.
  4 The values of 500 V and 750 V are the rated voltage of the cable.
                                                                      185
IS 732 : 2019
                                                                                                                                          SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
 of Conductor
     mm2
                                                      or
                                                      or                                or
                                                                                        or                                           De
                                                                                                                                      e
                                                                                                             Dee
                                                                                                             D
  NOTES
  1 Circular conductors are assumed for sizes up to and including 16 mm2. Values for larger sizes relate to shaped conductors and may
  safely be applied to circular conductors.
  2 De is the external diameter of the cable.
                                                                    186
                                                                                                                       IS 732 : 2019
                                                                                                                                           SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
Sectional Area
 of Conductor
    mm2
                                                      or
                                                      or                                or
                                                                                        or
                                                                                                                                     Dee
                                                                                                             Dee
     10               54              46               –                   –             –                   –                   –
     16               73              61               –                   –             –                   –                   –
     25               89              78               98                 84             87                 112                 99
     35              111              96              122                 105           109                 139                 124
     50              135              117             149                 128           133                 169                 152
     70              173              150             192                 166           173                 217                 196
     95              210              183             235                 203           212                 265                 241
     120             244              212             273                 237           247                 308                 282
     150             282              245             316                 274           287                 356                 327
     185             322              280             363                 315           330                 407                 376
     240             380              330             430                 375           392                 482                 447
     300             439              381             497                 434           455                 557                 519
     400               –               –              600                 526           552                 671                 629
     500               –               –              694                 610           640                 775                 730
     630               –               –              808                 711           746                 900                 852
  NOTES
  1 Circular conductors are assumed for sizes up to and including 16 mm2. Values for larger sizes relate to shaped conductors and may
  safely be applied to circular conductors.
  2 De is the external diameter of the cable.
                                                                    187
IS 732 : 2019
                                                                                                                                            SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
Sectional Area
of Conductor
     mm2
                                                        or
                                                        or                               or
                                                                                         or                                           Dee
                                                                                                                                      D
                                                                                                            D
                                                                                                            Dee
      10              86               75                –                  –             –                  –                    –
      16              115              100               –                  –             –                  –                    –
      25              149              127              161               135            141                182                  161
      35              185              158              200               169            176                226                  201
   NOTES
   1 Circular conductors are assumed for sizes up to and including 16 mm2. Values for larger sizes relate to shaped conductors and may
   safely be applied to circular conductors.
   2 De is the external diameter of the cable.
                                                                    188
                                                                                                                        IS 732 : 2019
                                                                                                                                            SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
Sectional Area
of Conductor
     mm2
                                                        or
                                                        or                                or
                                                                                          or                                          Dee
                                                                                                               Dee
   NOTES
   1 Circular conductors are assumed for sizes up to and including 16 mm2. Values for larger sizes relate to shaped conductors and may
   safely be applied to circular conductors.
   2 De is the external diameter of the cable.
                                                                    189
IS 732 : 2019
                                                                              Insulation
          Ambient
        Temperature                                                                                     Mineral1)
            °C                          PVC                    XLPE and EPR
                                                                                    PVC Covered or Bare and Bare not Exposed to Touch
                                                                                     Exposed to Touch 70 °C           105 °C
                                                                                                                                        SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
              10                         1.22                      1.15                      1.26                     1.14
65 – 0.65 – 0.70
70 – 0.58 – 0.65
75 – 0.50 – 0.60
80 – 0.41 – 0.54
85 – – – 0.47
90 – – – 0.40
95 – – – 0.32
 1)
      For higher ambient temperatures, consult the manufacturer.
                                                                    190
                                                                                                                                   IS 732 : 2019
                                                                                                                                                   SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                    25                                              0.95                                                0.96
                    30                                              0.89                                                0.93
                    35                                              0.84                                                0.89
                    40                                              0.77                                                0.85
Correction Factor for Cables in Buried Ducts 1.28 1.20 1.18 1.1 1.05 1 0.96
Correction Factor for Direct Buried Cables 1.88 1.62 1.5 1.28 1.12 1 0.90
   NOTES
   1 The correction factors given have been averaged over the range of conductor sizes and types of installation included in Tables 21 to
   Table 24. The overall accuracy of correction factors is within 5 percent.
   2 The correction factors are applicable to cables drawn into buried ducts; for cables laid direct in the ground the correction factors for
   thermal resistivities less than 2.5 K.m/W will be higher. Where more precise values are required they may be calculated by methods
   given in IEC 60287 series.
   3 The correction factors are applicable to ducts buried at depths of up to 0.8 m.
   4 It is assumed that the soil properties are uniform. No allowance had been made for the possibility of moisture migration which can
   lead to a region of high thermal resistivity around the cable. If partial drying out of the soil is foreseen, the permissible current rating
   should be derived by the methods specified in IEC 60287 series.
                                                                            191
IS 732 : 2019
                                                                                                                           To be Used with
            Arrangement                               Number of Circuits or Multi-core Cables                                 Current-
 Item                                                                                                                         Carrying
          (Cables Touching)
                                                                                                                             Capacities,
                                   1      2      3       4      5       6      7       8      9     12     16      20         Reference
  1     Bunched in air, on a     1.00   0.80   0.70   0.65   0.60    0.57    0.54   0.52    0.50   0.45 0.41    0.38         Tables 21
        surface, embedded or                                                                                                   to 32
                                                                                                                                             SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
        enclosed                                                                                                           Methods A to F
  2     Single layer on wall,    1.00   0.85   0.79   0.75   0.73    0.72    0.72   0.71    0.70
        floor or unperforated
        cable tray systems                                                                                                    Tables 21
                                                                                                                                to 26
  3     Single layer fixed       0.95   0.81   0.72   0.68   0.66    0.64    0.63   0.62    0.61                              Method C
  NOTES
  1 These factors are applicable to uniform groups of cables, equally loaded.
  2 Where horizontal clearances between adjacent cables exceeds twice their overall diameter, no reduction factor need be applied.
  3 The same factors are applied to:
     – groups of two or three single-core cables;
     – multi-core cables.
  4 If a system consists of both two- and three-core cables, the total number of cables is taken as the number of circuits, and the
  corresponding factor is applied to the tables for two loaded conductors for the two-core cables, and to the tables for three loaded
  conductors for the three-core cables.
  5 If a group consists of n single-core cables it may either be considered as n/2 circuits of two loaded conductors or n/3 circuits of
  three loaded conductors.
  6 The values given have been averaged over the range of conductor sizes and types of installation included in Tables 21 to Table 32
  the overall accuracy of tabulated values is within 5 percent.
  7 For some installations and for other methods not provided for in the above table, it may be appropriate to use factors calculated for
  specific cases, see for example, Table 39 and Table 40.
                                                                    192
                                                                                                                               IS 732 : 2019
        Table 37 Reduction Factors for More Than One Circuit, Cables Laid Directly in the Ground –
              Installation Method D2 in Table 21 to Table 24 Single-Core or Multi-Core Cables
                                         (Clauses 5.2.6.5, and S-4.1)
                                                                                                                                                  SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
          5                        0.55                     0.55                  0.65                    0.70                     0.80
a Multi-core cables
a Single-core cables
a a
    NOTES
    1 Values given apply to an installation depth of 0.7 m and a soil thermal resistivity of 2.5 K·m/W. They are average values for the
    range of cable sizes and types quoted for Tables 21 to Table 24. The process of averaging, together with rounding off, can result in
    some cases in errors up to 10 %. (Where more precise values are required they may be calculated by methods given in
    IEC 60287-2-1).
    2 In case of a thermal resistivity lower than 2.5 K·m/W the corrections factors can, in general, be increased and can be calculated by
    the methods given in IEC 60287-2-1.
    3 If a circuit consists of m parallel conductors per phase, then for determining the reduction factor, this circuit should be considered as
    m circuits.
                                                                        193
IS 732 : 2019
     Table 38 Reduction Factors for More Than One Circuit, Cables Laid in Ducts in the Ground —
                            Installation Method D1 in Table 20 to Table 24
                                       (Clauses 5.2.6.5 and S-4.1)
                               Nil
                                                       0.25 m                     0.5 m   1.0 m
                        (Ducts Touching)
                                                                                                  SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
          3                   0.75                      0.85                      0.90    0.95
                                                          194
                                                                                                                                  IS 732 : 2019
Table 38 — (Concluded)
                                                                                                                                                    SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                 5                           0.60                         0.70                        0.80                         0.90
a Multi-core cables
b Single-core cables
        NOTES
        1 Values given apply to an installation depth of 0.7 m and a soil thermal resistivity of 2.5 K·m/W. They are average values for the
        range of cable sizes and types quoted for Table 20 to Table 24. The process of averaging, together with rounding off, can result in
        some cases in errors up to 10 percent. Where more precise values are required they may be calculated by methods given in the
        IEC 60287series.
        2 In case of a thermal resistivity lower than 2.5 K·m/W the corrections factors can, in general, be increased and can be calculated
        by the methods given in IEC 60287-2-1.
        3 If a circuit consists of n parallel conductors per phase, then for determining the reduction factor this circuit shall be considered as
        n circuits.
                                                                           195
IS 732 : 2019
                Table 39 Reduction Factors for Group of More Than One Multi-core Cable
        to be Applied to Reference Current-Carrying Capacities for Multi-core Cables in Free Air —
                              Method of Installation E in Table 27 to Table 32
                                              (Clause 5.2.6.5)
                                       Touching
                     31
                                                                    1      1.00     0.88     0.82    0.79     0.76      0.73
                                                                                                                               SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                    2      1.00     0.87     0.80    0.77     0.73      0.68
                                                                    3      1.00     0.86     0.79    0.76     0.71      0.66
Touching
Touching
                               20
                                20 mm
                                   mm              300
                                                    300 mm
Touching
                                                                 196
                                                                                                                             IS 732 : 2019
Table 39 — (Concluded)
                                        Spaced
                                        Dee
                                        D                            1          1.00         1.00          1.00    1.00      1.00       –
                                                                     2          1.00         0.99          0.98    0.97      0.96       –
                                                                     3          1.00         0.98          0.97    0.96      0.93       –
                                  20
                                   20mm
                                      mm
                                                                                                                                                SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
    NOTES
    1 Values given are averages for the cable types and range of conductor sizes considered in Tables 27 to Table 32. The spread of
    values is generally less than 5 percent.
    2 Factors apply to single layer groups of cables as shown above and do not apply when cables are installed in more than one layer
    touching each other. Values for such installations may be significantly lower and has to be determined by an appropriate method.
         Table 40 Reduction Factors for Groups of One or More Circuits of Single-core Cables to
       be Applied to Reference Current-Carrying Capacity for One Circuit of Single-Core Cables in
                       Free Air — Method of Installation F in Table 27 to Table 32
                                           (Clause 5.2.6.5)
Touching
                                    20 mm
                                   20 mm
Touching
     Vertical
perforated cable                                                        1         0.96             0.86           –        Three cables in
                   31                  225 mm
  tray systems                          225                              2         0.95             0.84           –       vertical formation
    (Note 4)                            mm
Touching
 Cable ladder
                   32                                                    1         1.00             0.97          0.96      Three cables in
   systems,
                   33                    300
                                           300 mm
                                               mm                        2         0.98             0.93          0.89        horizontal
  cleats, etc
                   34                                                    3         0.97             0.90          0.86        formation
   (Note 3)
                                       20mm
                                     20  mm
                                                                   197
IS 732 : 2019
Table 40 — (Concluded)
                                         2Dee
                                        2D
                                                     D
                                                     Dee
Perforated cable                                                          1           1.00         0.98        0.96
  tray systems      31                                                    2           0.97         0.93        0.89
                                          300
                                            300 mm
                                                mm
                                                                                                                                              SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
    (Note 3)                                                              3           0.96         0.92        0.86
                                         20mm
                                        20 mm
Spaced
                                          2D
                                           2De
                                             e           D
                                                         Dee
  Cable ladder
                    32                                                    1           1.00         1.00        1.00
 systems, cleats,
                    33                                                    2           0.97         0.95        0.93
       etc                                   300
                                               300 mm
                                                   mm
                    34                                                    3           0.96         0.94        0.90
     (Note 3)
                                         20mm
                                       20  mm
    NOTES
    1 Values given are averages for the cable types and range of conductor sizes considered in Table 27 to Table 32. The spread of
    values is generally less than 5 percent.
    2 Factors are given for single layers of cables (or trefoil groups) as shown in the table and do not apply when cables are installed in
    more than one layer touching each other. Values for such installations may be significantly lower and should be determined by an
    appropriate method.
    3 Values are given for vertical spacing between cable trays of 300 mm and at least 20 mm between cable trays and wall. For closer
    spacing the factors should be reduced.
    4 Values are given for horizontal spacing between cable trays of 225 mm with cable trays mounted back to back. For closer spacing
    the factors should be reduced.
    5 For circuits having more than one cable in parallel per phase, each three phase set of conductors should be considered as a circuit
    for the purpose of this table.
    6 If a circuit consists of m parallel conductors per phase, then for determining the reduction factor this circuit should be considered
    as m circuits.
                                                                      198
                                                                                                                    IS 732 : 2019
                                                         ANNEX T
                                                        (Normative)
             EXAMPLE OF A METHOD OF SIMPLIFICATION OF THE TABLES OF 5.2.6
This Annex is intended to illustrate one possible method by which the Table 21 to Table 24, Table 29 to
Table 32 and Table 36 to Table 40 can be simplified for adoption.
The use of other suitable methods is not excluded (see Note of 5.2.6.2).
                                                                                                                                       SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
 Reference
 Methods in                                     Number of Loaded Conductors and type of Insulation
  Table 20
     A1                 3 PVC 2 PVC                     3 XLPE 2 XLPE
     A2        3 PVC 2 PVC                   3 XLPE 2 XLPE
     B1                                      3 PVC 2 PVC                      3 XLPE               2 XLPE
                                                                 199
IS 732 : 2019
                                                                                                             SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                         10             63                  52                  73                    61
                         16             81                  67                  95                    79
                         25             104                 86                  121                  101
      D1/D2              35             125                 103                 146                  122
                                                   200
                                                                                                                        IS 732 : 2019
            Table 43 Reduction Factors for Groups of Several Circuits or of Several Multi-core Cables
                          (to be Used with Current-Carrying Capacities of Table 41)
                                                                                                                                          SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
             Single layer fixed directly
      3                                         0.95      0.80         0.70       0.70      0.65     0.60      –        –        –
             under a ceiling
                                                                ANNEX U
                                                               (Clause 5.2)
                                                                 (Normative)
                          FORMULAE TO EXPRESS CURRENT-CARRYING CAPACITIES
The values given in Table 21 to Table 32 lie on                               Values of the coefficients and exponents are given in
smooth curves relating current-carrying capacity to                           the accompanying table. Current-carrying capacities
cross-sectional area of conductor.                                            should be rounded off to the nearest 0.5 A for values
                                                                              not exceeding 20 A and to the nearest ampere for
These curves can be derived using the following
                                                                              values greater than 20 A.
formulae:
                                                                              The number of significant figures obtained is not to
                            I = a × sm – b × s n
                                                                              be taken as an indication of the accuracy of the
where                                                                         current-carrying capacity.
  I = the current-carrying capacity, in amperes;                              For practically all cases, only the first term is needed.
  S = the nominal cross-sectional area of                                     The second term is needed in only eight cases where
         conductor, in square millimetres [(mm)2]1)                           large single-core cables are used.
  a and b are coefficients and m and n are exponents                          It is not advisable to use these coefficients and
         according to cable and method of                                     exponents for conductor sizes outside the appropriate
         installation.                                                        range used in Table 21 to Table 32.
1)
     Where the nominal size is 50 mm2, for cables with extruded
     insulation, the value of 47.5 mm2 should be used. For all other
     sizes and for all sizes of mineral insulated cables the nominal
     value is sufficiently precise.
                                                                        201
IS 732 : 2019
                                                                                                                                 SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                             3(s) < 120 mm2               14.46             0.598               11.26              0.602
                             3(s)  120 mm2               13.56             0.611               10.56              0.615
           22                        4                    17.76             0.625 0             13.95              0.627
                                     5                    17.25             0.600               13.5               0.603
                               6 < 16 mm2                 18.77             0.628               14.8               0.625
                               6  16 mm2                 17.0              0.650               12.6               0.648
                                                                  202
                                                                                           IS 732 : 2019
Table 44 — (Concluded)
                                                                                                           SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                   5       26.1              0.549           –                 –
                                   6       29.0              0.57            –                 –
         28               750 V 2          26.04             0.599 7         –                 –
                                   3       21.8              0.60            –                 –
                                   4       25.0              0.585           –                 –
                         5 < 120 mm2       27.55             0.579 2         –                 –
                                                   203
IS 732 : 2019
                                                   ANNEX V
                                               (Clause 5.2.6.6.3)
                                                  (Normative)
         EFFECT OF HARMONIC CURRENTS ON BALANCED THREE-PHASE SYSTEMS
V-1 REDUCTION FACTORS FOR HARMONIC                          current-carrying capacity of a cable with three loaded
CURRENTS IN FOUR-CORE AND FIVE-CORE                         conductors, will give the current-carrying capacity of
CABLES WITH FOUR CORES CARRYING                             a cable with four loaded conductors where the current
CURRENT                                                     in the fourth conductor is due to harmonics. The
                                                            reduction factors also take the heating effect of the
                                                                                                                                 SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
The subclause 5.2.6.6.3 states that where the neutral       harmonic current in the line conductors into account.
conductor carries current without a corresponding
reduction in load of the line conductors, the current       Where the neutral current is expected to be higher
flowing in the neutral conductor shall be taken into        than the line current then the cable size should be
account in ascertaining the current-carrying capacity       selected on the basis of the neutral current.
of the circuit.
                                                           204
                                                                                                                       IS 732 : 2019
reduction factor of 0.86 is applied and the design load               For this load a 10 mm2 cable is suitable.
becomes:
                                                                      If 50 per cent third harmonic is present, the cable size
                              39                                      is again selected on the basis of the neutral current,
                                   45A                               which is:
                             0.86
For this load, a 10 mm2 cable is necessary.                                                   39 × 0.5 × 3 = 58.5 A
If 40 percent third harmonic is present, the cable size               In this case, the reduction factor is 1 and a 16 mm2
selection is based on the neutral current which is:                   cable is required.
                       39 × 0.4 × 3 = 46.8 A                          All the above cable selections are based on the
                                                                      current-carrying capacity of the cable; voltage drop
and a reduction factor of 0.86 is applied, leading to a               and other aspects of design have not been considered.
                                                                                                                                          SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
design load of:
                            46.8
                                  54.4A
                            0.86
     NOTES
     1 These values are only a sample of the characteristics for conduit given in IS 14930 (Parts 1 & 2).
     2 According to resistance to flame propagation, conduit systems of orange colour are only permitted when embedded in concrete. For
     other methods for installation all colours are permitted with the exception of yellow, orange or red.
                                                                    205
IS 732 : 2019
                                                             ANNEX Y
                                                            (Clause 5.2)
                                                            (Normative)
                                VOLTAGE DROP IN CONSUMERS’ INSTALLATIONS
                                                                                                                                              SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
of the nominal voltage of the installation                               b        = the coefficient equal to 1 for three-
                                                                                    phases circuits, and equal to 2 for
      NOTES
                                                                                    single-phase circuits;
      1 A greater voltage drop may be accepted
                                                                                      NOTE  Three-phase circuits with the neutral
         – for motor during starting periods,
                                                                                      completely unbalanced (a single phase loaded)
         – for other equipment with high inrush current,
                                                                      206
                                                                                                           IS 732 : 2019
                                                      ANNEX Z
                                                    (Clause 5.2.6.7)
                                                     (Informative)
                        EXAMPLES OF CONFIGURATIONS OF PARALLEL CABLES
The special configurations referred in 5.2.6.7 can be:               2) above each other, see Fig. 82,
    a) for 4 three-core cables the connection                        3) in trefoil, see Fig. 83;
       scheme: L1L2L3, L1L2L3, L1L2L3, L1L2L3;                    d) for 12 single-core cables
       the cables may be touching;                                   1) in a flat plane, see Fig. 84,
    b) for 6 single-core cables                                      2) above each other, see Fig. 85,
                                                                                                                              SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
       1) in a flat plane, see Fig. 78,                              3) in trefoil, see Fig. 86.
       2) above each other, see Fig. 79,                     The distances          in   these     figures     shall    be
       3) in trefoil, see Fig. 80;                           maintained.
    c) for 9 single-core cables                                  NOTE  Where possible, the impedance differences between
                                                                 the phases are also limited in the special configurations.
       1) in a flat plane, see Fig. 81,
         FIG. 79 SPECIAL CONFIGURATION FOR 6 PARALLEL SINGLE-CORE CABLES ABOVE EACH OTHER
                                              (see 5.2.6.7)
FIG. 81 SPECIAL CONFIGURATION FOR 9 PARALLEL SINGLE-CORE CABLES IN A FLAT PLANE (see 5.2.6.7)
                                                           207
IS 732 : 2019
                                                                                                    SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                  ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
        FIG. 82 SPECIAL CONFIGURATION FOR 9 PARALLEL SINGLE-CORE CABLES ABOVE EACH OTHER
                                             (see 5.2.6.7)
FIG. 83 SPECIAL CONFIGURATION FOR 9 PARALLEL SINGLE-CORE CABLES IN TREFOIL (see 5.2.6.7)
FIG. 84 SPECIAL CONFIGURATION FOR 12 PARALLEL SINGLE-CORE CABLES IN A FLAT PLANE (see 5.2.6.7)
       FIG. 85 SPECIAL CONFIGURATION FOR 12 PARALLEL SINGLE-CORE CABLES ABOVE EACH OTHER
                                            (see 5.2.6.7)
                                                   208
                                                                                                                       IS 732 : 2019
                                                                                                                                       SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                          ANNEX AA
3   — Main earthing terminal or bar                             F1 — Protective device at the origin of the installation
4   — Surge protective devices providing protection against     F2 — Protective device required by the manufacturer of
      overvoltages of category II                                    the SPD
5   — Earthing connection of surge protective devices, either   RA — Earthing electrode (earthing resistance) of the installation
      5a or 5b
                                                                RB — Earthing electrode (earthing resistance) of the
6   — Equipment to be protected                                      supply system
                                                                  209
IS 732 : 2019
                                                         ANNEX BB
                                                         (Clause 5.3)
                                                           (Normative)
                  INSTALLATION OF SURGE PROTECTIVE DEVICES IN TT SYSTEMS
                                                                                                                                      SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                                                    ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
 3   — Main earthing terminal or bar                             F1 — Protective device at the origin of the installation
 4   — Surge protective devices providing protection against     F2 — Protective device required by the manufacturer of
       overvoltages of category II                                    the SPD
 5   — Earthing connection of surge protective devices, either   RA — Earthing electrode (earthing resistance) of the installation
       5a and/or 5b
                                                                 RB — Earthing electrode (earthing resistance) of the supply system
 6   — Equipment to be protected
 7   — Residual current protective device (RCD)
                                                                   210
                                                                                                            IS 732 : 2019
                                                                                                                            SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                                          ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
3   — Main earthing terminal or bar                       F1 — Protective device at the origin of the installation
4   — Surge protective devices                            F2 — Protective device required by the manufacturer
      4a Surge protective device                               of the SPD
      (a combination 4-4a, providing protection against
                                                          RA — Earthing electrode (earthing resistance)
      overvoltages of category II)
                                                               of the installation
5   — Earthing connection of surge protective devices,
                                                          RB — Earthing electrode (earthing resistance)
      either 5a and/or 5b
                                                               of the supply system
6   — Equipment to be protected
7   — Residual current protective device (RCD), placed
      either upstream or downstream of the busbars
                                                          211
IS 732 : 2019
                                                          ANNEX CC
                                                          (Clause 5.3)
                                                           (Normative)
                   INSTALLATION OF SURGE PROTECTIVE DEVICES IN IT SYSTEMS
                                                                                                                                        SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                                                      ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
3   — Main earthing terminal or bar                                F1 — Protective device at the origin of the installation
4   — Surge protective devices providing protection against        F2 — Protective device required by the manufacturer of the SPD
      overvoltages of category II
                                                                   RA — Earthing electrode (earthing resistance) of the installation
5   — Earthing connection of surge protective devices, either 5a
                                                                   RB — Earthing electrode (earthing resistance) of the supply system
      and/or 5b
6   — Equipment to be protected
7   — Residual current protective device (RCD)
                                                                   212
                                                                                                                          IS 732 : 2019
                                                          ANNEX DD
                                                           (Clause 5.3)
                                                           (Normative)
    INSTALLATION OF CLASS I, II AND III TESTED SPDS, FOR EXAMPLE IN TN-C-S SYSTEMS
                                                                                                                                          SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                                                        ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
1   —    Origin of the installation                                 7   — Fixed equipment to be protected
2   — Distribution board                                            8   — Surge protective device, test class II
3   — Distribution outlet                                           9   — Surge protective device, test class II or III
4   — Main earthing terminal or bar                                 10 — Decoupling element or line length
5   — Surge protective device, test class I                         F1, F2, F3 — Overcurrent protective devices
6   — Earthing connection (earthing conductor) of surge
      protective device
    NOTES
    1 Reference should be made to IS/ IEC 61643-12 for further information.
    2 SPD 5 and 8 can be combined in a single SPD.
                                                                    213
IS 732 : 2019
                                                                 ANNEX EE
                                                                 (Clause 5.4)
                                                                   (Normative)
                                  METHOD FOR DERIVING THE FACTOR k IN 5.4.3.1.2
                                         (see also IEC 60724 and IEC 60949)
                                                                                                                                        SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
       where
       Qc = the volumetric heat capacity of conductor material (J/K mm3) at 20 °C;
             = the reciprocal of temperature coefficient of resistivity at 0 °C for the conductor (°C);
       20 = the electrical resistivity of conductor material at 20 °C (.mm);
                                                                         214
                                                                                                                            IS 732 : 2019
             Table 59 Values of k for Bare Protective Conductors in Contact with Cable Covering
                                      but not Bunched with Other Cables
                                                                                                                                            SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                      Table 60 Values of k for Protective Conductors as a Core Incorporated
                        in a Cable or Bunched with Other Cables or Insulated Conductors
                                           Temperature                                           Material of Conductor
      Conductor
                                              °C 2)                              Copper               Aluminium               Steel
1)
   Temperature limits for various types of insulation are given in IEC 60724.
2)
   This value shall also be used for bare conductors exposed to touch or in contact with combustible material.
3)
   For the method of calculating k, see the formula at the beginning of this Annex.
                                                                           215
IS 732 : 2019
                                                                                                                          SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
 Normal
                       30            200             159              200           105          200              58
 conditions
 Fire risk             30            150             138              150            91          150              50
                                                              216
217
                                                                                                                                                           (Normative)
                                                                                                                                                           (Clause 5.4)
                                                                                                                                                           ANNEX FF
      SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                    ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
IS 732 : 2019
Key
      Symbol                                      Name                                                  Remark
        C        Extraneous-conductive-part
       C1        Water pipe, metal from outside                                     Or district heating pipe
       C2        Waste water pipe, metal from outside
       C3        Gas pipe with insulating insert, metal from outside
       C4        Air-conditioning
       C5        Heating system
       C6        Water pipe, metal e.g. in a bathroom                               See IEC 60364-7-701 701.4.2.15.2
                                                                                                                                SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
       C7        Waste water pipe, metal e.g. in a bathroom                         See IEC 60364-7-701 701.4.215.2
        D        Insulating insert
      MDB        Main distribution board
       DB        Distribution board                                                 Supplied from the main distribution board
       MET       Main earthing terminal                                             See 5.4.2.4
Where a lightning protection system is installed, the additional requirements are given in 6 of IS/IEC 62305-3 :
2006, in particular those given in 6.1 and 6.2.
  NOTE  Functional earthing conductors are not shown in this Figure.
                                                                   218
                                                                                                        IS 732 : 2019
                                      ANNEX GG
                                      (Clause 5.5)
                                      (Normative)
    EXPLANATION OF SYMBOLS USED IN LUMINAIRES, IN CONTROLGEAR
     FOR LUMINAIRES AND IN THE INSTALLATION OF THE LUMINAIRES
                                                                                                                        SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
              Luminaire not suitable for covering with thermally insulating material (IS 10322
              series)
              Recessed luminaire not suitable for direct mounting on normally flammable
              surfaces (IS 10322 series)
                 marked with the symbol            according to IS 10322 series). With the publication of IEC 60598-
                 1 : 2008 (7th edition), luminaires suitable for direct mounting have no special marking and only
                 luminaires not suitable for mounting on normally flammable surfaces are marked with symbols
              Luminaires suitable for direct mounting in/on normally flammable surfaces when
              thermally insulating material may cover the luminaire (IS 10322 series)
Luminaires designed for use with bowl mirror lamps (IS 10322 series)
                                               219
IS 732 : 2019
                                                                                                      SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                Luminaires for use with high pressure sodium lamp requiring external ignition
                system (IS 10322 series)
Replace any cracked protective screen (rectangular) or (circular) (IS 10322 series)
                Luminaires designed for use with self-shielded tungsten halogen lamps only
                (IS 10322 series), and lamps which can be used in open luminaires
                                             220
                                                                                                                           IS 732 : 2019
                                                             ANNEX HH
                                                             (Clause 5.6)
                                                             (Normative)
                                      GUIDANCE FOR EMERGENCY LIGHTING
The values in ISO 30061 should be considered but additional details of suitable systems are given in Table 63.
Annex HH serves as an informative guide for countries that do not have specific rules or their own guidelines.
                                                                                                                                              SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                            Requirements
                          1             2                3              4           5            6            7            8           9
                                                                                                                    Motor-
                       Extended                                                                           Motor-
   Examples of                                                                               Motor-                Generator
                        Duration  Escape Sign                         Low         Self-                 Generator
Assembly halls,
                          **            †                †             †            †            †            †            †           †
assembly rooms
Exhibition halls          **            †                †             †            †            †            †            †           †
Theatres, cinemas ** † † † † † † † †
Sports arenas ** † † † † † † † †
Sales areas ** † † † † † † † †
Restaurants               **            †                †             †            †            †            †            †           †
Hospitals,
                          **            †                †             †            †            †            †            †           †
treatment centres
Hotels, guest
                          **            †                †             †            †            †            †            †           †
houses *
Residential care
                          **            †                †             †            †            †            †            †           †
homes *
High-rise buildings
                          **            †                †             †            †            †            †            †           †
*
Schools                   **            †                †             †            †            †            †            †           †
Stages ** † † † † † † † †
                                                                     221
                                                            1)
                                                                                                                   equipment
                                                                                                                                               instructions
                                                                                                                                                                                                                                                                                                                                                                                                                                                                    IS 732 : 2019
                                                                                           CO warning equipment
                                                                                                                   Smoke and heat extraction
                                                                                                                                                                                                                                             Installations for fire pumps
                                                                                           1
                                                                                                                         3
                                                                                                                                                      3
                                                                                                                                                                               3
                                                                                                                                                                                                                 8
                                                                                                                                                                                                                                                                                                                                               1
                                                                                                                                                                                                                                             12
                                                                                                                                                                                                                                                                                        Rated operating time of the source, h
                                                                                                                                                                                                                                                                                                                                               2
                                                                                           15
                                                                                                                         15
                                                                                                                                                      15
                                                                                                                                                                               15
                                                                                                                                                                                                                 15
                                                                                                                                                                                                                                             15
                                                                                                                                                                                                                                                                                        Response time of the source, s, Max.
                                                                                           †
                                                                                                                         †
                                                                                                                                                      †
                                                                                                                                                                                                                                                                                                                                               4
222
                                                                                                                                                                                                                                                                                                                                                                                                                                                     ANNEX JJ
                                                                                                                                                                                                                                                                                                                                                                                                                                                     (Normative)
                                                                                                                                                                                                                                                                                                                                                                                                                                                     (Clause 5.6)
(Clause 5.6.8.4)
                                                                                           †
                                                                                                                         †
                                                                                                                                                                                                                                                                                                                                               5
                                                                                           †
                                                                                                                         †
                                                                                                                                                      †
                                                                                                                                                                               †
                                                                                                                                                                                                                 †
                                                                                                                                                                                                                                             †
                                                                                                                                                                                                                                                                                                                                               6
                                                                                           †
                                                                                                                         †
                                                                                                                                                      †
                                                                                                                                                                               †
                                                                                                                                                                                                                 †
                                                                                                                                                                                                                                             †
                                                                                                                                                                                                                                                                                                                                               7
                                                                                           †
                                                                                                                         †
                                                                                                                                                      †
                                                                                                                                                                               †
                                                                                                                                                                                                                 †
                                                                                                                                                                                                                                             †
                                                                                                                                                                                                                                                                                                                                               8
                                                                                           †
                                                                                                                         †
                                                                                                                                                      †
                                                                                                                                                                               †
                                                                                                                                                                                                                 †
                                                                                                                                                                                                                                             †
                                                                                                                                                                                                                                                                                                                                               9
                                                                                                                                                                               †
                                                                                                                                                                                                                 †
                                                                                                                                                                                                                                             †
                                                                                                                                                                                                                                                                                                                                               10
                                                                                           †1)
                                                                                                                         †1)
                                                                                                                                                      †1)
                                                                                                                                                                                                                                                                            Monitoring and changeover in the case of failure of the source
                                                                                                                  SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                                ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
                                                                                                     IS 732 : 2019
                                                ANNEX KK
                                               (Clause 6.2.3.5)
                                                 (Normative)
         METHODS FOR MEASURING THE INSULATION RESISTANCE/ IMPEDANCE OF
          FLOORS AND WALLS TO EARTH OR TO THE PROTECTIVE CONDUCTOR
                                                                                                                       SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
with a lower voltage of the same nominal frequency         electrode from the output of the voltage source or
combined with a measurement of insulation                  from the phase conductor L. The voltage UX at the
resistance. This may be done, for example, in              electrode is measured by means of a voltmeter with
accordance with the following methods of                   internal resistance of at least 1 M towards PE.
measurement:
                                                           The impedance of the floor insulation will then be:
                                                          223
IS 732 : 2019
                                                                                                  SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
                                                       All dimensions in millimetres.
(*) Protection against unintentional contact by a resistance limiting the current to 3.5 mA.
                                                                      224
                                                                                                              IS 732 : 2019
                                                        ANNEX LL
                                                      (Clause 6.2.3.6.2)
                                                         (Normative)
                                               METHOD LL1, LL2 AND LL3
LL-1 METHOD LL1 — MEASUREMENT OF                                     variable load resistance, and the fault loop impedance
EARTH ELECTRODE RESISTANCE                                           is calculated from the following formula:
As an example, the following procedure may be                                                      U1  U 2
                                                                                              Z
adopted when the measurement of the earth                                                            IR
resistance is to be made (see Fig. 95).
                                                                                                                              SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
An alternating current of a steady value is passed                   where
between the earth electrode, T, and an auxiliary earth                 Z = the fault loop impedance;
electrode, T1, placed at a distance from T such that                   U1 = the voltage measured without connection
the resistance areas of the two electrodes do not                           of the load resistance;
                                                                    225
IS 732 : 2019
                                                                                     SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                   ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
                                                           Resistance areas
                                                           (not overlapping)
Key
T — earth electrode under test, disconnected from all other sources of supply;
T1— auxiliary earth electrode;
T2— second auxiliary earth electrode;
X — alternative position of T2 for check measurement; and
Y — further alternative position of T2 for the other check measurement.
                                                                    226
                                                                                                     IS 732 : 2019
                                                                                                                       SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                                                     ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
   RT         —   earth-connection of transformer
   Rx         —   unknown earth-resistance to be measured
   R1 ...Rn   —   parallel earth-connections connected by an equipotential bonding or a PEN conductor
                                                  ANNEX MM
                                                   (Clause 6.2)
                                                   (Normative)
 GUIDANCE ON THE APPLICATION OF THE RULES OF CLAUSE 6.2 INITIAL VERIFICATION
The numbering of the clauses and subclauses of this                  The installation of the seals is verified to
Annex follows the numbering of 6.2.                                  confirm compliance with the erection
                                                                     instructions associated with IEC type test for
The absence of reference of clauses or subclauses
                                                                     the relevant product (under consideration by
means that no additional explanation is given to
                                                                     ISO).
them.
                                                                     No other test      is   required   after   this
MM-6.2.2 Inspection
                                                                     verification.
MM-6.2.2.2 This inspection is also intended to check
                                                                 –   protection against thermal effects (4.3)
that the installation of the equipment is in accordance
with the manufacturer’s instructions in order that its               The rules of 4.3 concerning the protection
performance is not adversely affected.                               against thermal effects apply for normal
                                                                     service, that is, in the absence of a fault.
MM-6.2.2.3
                                                                     The overcurrent protection of wiring
b) presence of fire barriers and other precautions                   systems is the object of 4.4 and of 5.3.4.
against propagation of fire and protection against
thermal effects (4.3 and 5.2.10)                                     The operation of a protective device
                                                                     resulting from a fault, including short
    –    presence of fire barriers (5.2.10.2)                        circuits, or from overloads, is considered as
                                                                     normal service.
                                                          227
IS 732 : 2019
    –    protection against fire (4.3.2)                        NOTE  The current used for testing should be sufficiently
                                                                low as not to cause a risk of fire or explosion.
        The requirements of 4.3.2 for locations with
        fire hazards assume that protection against        MM-6.2.3.3 Insulation resistance of the electrical
        overcurrent is in compliance with the rules        installation
        of 4.4.                                            The measurements shall be carried out with the
c) and d) Selection of conductors for current-carrying     installation isolated from the supply. Generally, the
capacity and voltage drop and choice and setting of        insulation measurement is carried out at the origin of
protective and monitoring devices.                         the installation.
        The selection of the conductors including          If the value measured is less than that specified in
        their materials, installation and cross-           Table 15, the installation may be divided into several
        sectional area, their erection and the setting     circuit groups and the insulation resistance of each
                                                                                                                             SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
        of the protective devices is verified              group shall be measured. If, for one group of circuits,
        according to the calculation of the designer       the measured value is less than that specified in
        of the installation in compliance with the         Table 15, the insulation resistance of each circuit of
        rules of this standard, particularly 4.2, 4.4,     this group shall be measured.
        5.2, 5.3 and 5.4.                                  When some circuits or parts of circuits are
                                                          228
                                                                                                 IS 732 : 2019
                                                                                                                  SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
Where the measured value of the fault loop                    e) the values of the resistance increased in
impedance exceeds 2Uo/3Ia, a more precise                        accordance with (d) are finally added to the
assessment of compliance with 4.2.11.4 may be                    value of the supply line conductor-earthed
made, evaluating the value of the fault loop                     neutral loop impedance, Ze, so obtaining a
impedance according to the following procedure:                  realistic value of Zs under fault conditions.
                                                        229
IS 732 : 2019
                                                      ANNEX NN
                                                    (Clause 6.2.3.10)
                                                      (Normative)
   EXAMPLE OF A DIAGRAM SUITABLE FOR THE EVALUATION OF THE VOLTAGE DROP
Maximum cable length for 4 percent voltage drop at 400 V a.c. nominal voltage and 55 °C wiring temperature.
Three-phase wiring system, PVC insulated cables, copper wiring
For single-phase wiring system (230 V a.c.): divide maximum cable length by 2
For aluminium wiring:        divide maximum cable length by 1.6
                                                                                                                        SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
        NOTE  The diagram above is not intended to give guidance on the current-carrying capacity of the conductors.                 ON 19/11/2022 17:07:39 (165.225.120.113) VALID UPTO 18/11/2023 00:00:00
FIG. 98 EXAMPLE OF A DIAGRAM SUITABLE FOR THE EVALUATION OF THE VOLTAGE DROP
                                                                230
                                                                                                        IS 732 : 2019
                                                           ANNEX PP
                                                            (Clause 6)
                                                           (Normative)
      RECOMMENDATION FOR ELECTRICAL EQUIPMENT, WHICH IS BEING RE-USED IN
                         ELECTRICAL INSTALLATIONS
Re-used equipment is equipment that has been                          b)   manufacturer;
previously installed.                                                 c)   relevant installation details;
For re-used equipment, documents should be                            d)   test instruments;
available, at the time of the verification, containing at             e)   results of inspection; and
least the following information:                                      f)   tests performed, including verification of
                                                                                                                        SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
     a)    type of re-used equipment;                                      disconnecting times for RCDs, and test
                                                                           results.
 Type of verification:
               Initial verification
               Periodic verification
 Client name and address:
 Installation address:
 Installer name and address:
 Installation:
               New                                                     Modification
               Extension                                               Existing
 Name of inspector:
 Description of installation work:
 Date of inspection:                                             Signature: ………………………………………..
 Identification of instruments used:
                                                                231
IS 732 : 2019
Supply characteristics and earthing arrangements Tick boxes and enter details, as appropriate
 Earthing arrangements              Number and type of live conductors                       Nature of supply parameters
                                                                                                                                                     Incoming supply
 Supply authority                                                                                                                                   protective device
 Consumer's                                                                                                                                          characteristics
 earth electrode          
 System types
 TN-C                              a.c                                   d.c.             Nominal voltage, U/Uo(1)...........................V    Type:...................
 TN-C-S                            1-phase, 2-wire (LN)                  2-pole           Nominal frequency, f
                                                                                             (1)
                                                                                                                                                     Nominal current
                                                                                                ......................Hz                             rating:...............A
 TN-S                              1-phase, 3-wire (LLM)                 3-pole    
                                                                                                                                                                                SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                             Prospective highest short-circuit                       RCD sensitivity,
 TT                                2-phase, 3-wire (LLN)                 other            current, Icc(2)……………                                    where applicable
 IT                                                                                         ……..............kA                                      ......................mA
                                    3-phase, 3-wire (LLL)                 other     
                                                                                             External earth fault loop
                                    3-phase, 4-wire (LLLN)                other            impedance, Ze (2)................................
                                                                                      232
                                                                                                                     IS 732 : 2019
                                                                                                                                     SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                 ANNEX RR
ii) Barriers
iii) Enclosures
B Equipment
                                                                      233
IS 732 : 2019
C Identification
                                                                                                                                               SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
 v)        Isolation devices
 vi)       Switching devices
 vii)      Diagrams and schedules
      NOTES
                                                                        234
                                                                                              IS 732 : 2019
                                                                                                               SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
❑ Prohibited core colours not used
❑ Joints to be made using cable couplers                ❑ Out of reach of a person using a bath or shower
❑ Final connections to other current-using              ❑ Correct rating of fuse fitted
    equipment properly secured or arranged to
                                                        Cooker control unit
    prevent strain on connections
❑ Mass supported by pendants not exceeding              ❑ Sited to the side and low enough for accessibility
                                                       235
IS 732 : 2019
Flexible metal conduit                                 ❑ No sharp edges on cable entries, screw heads etc.
❑ Separate protective conductor provided                 which could cause damage to cables
❑ Adequately supported and terminated                  ❑ All covers and equipment in place and secure
                                                       ❑ Adequate access and working space
Rigid non-metallic conduit                             ❑ Enclosure suitable for mechanical protection
❑ Provision for expansion and contraction                and, where applicable, for fire protection
❑ Boxes and fixings suitable for mass of luminaire     ❑ Protection against direct contact
    suspended at expected temperature                  ❑ Correct connection of equipment
❑ Protective conductor provided                        ❑ Choice and setting of protective devices
                                                         (protection against overcurrent)
4. Trunking
                                                       ❑ Protective device attributed individually for each
General                                                  circuit
                                                                                                              SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
❑ Visible indication of compliance with the            ❑ Wiring correctly fixed in distribution board
  appropriate product standard, where required in
  the relevant product standard                        6. Luminaires
❑ Securely fixed and adequately protected against      Lighting points
  mechanical damage                                    ❑ Correctly terminated in a suitable accessory or
                                                           fitting
                                                      236
                                                                                                               ANNEX SS
                                                                                                                (Clause 6)
                                                                                                                                                                                                                                                      SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                                                                               (Normative)
                                                                                              REPORT OF VERIFICATION
                                                                 Table 65 Model Form for Circuit Details and Test Results Schedule
                                                                                                                                                                                                                                      IS 732 : 2019
                                                                                                                        237
                                                                                                                                                                                    IS 732 : 2019
           NOTES
           1 By enquiry (manufacturer, name plate or technical doc.)
                                                                                                                                                                                                    SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
           2 By measurement or calculation
           3 Enter C if complies or NC if does not comply
           4 Complete test where appropriate shall be performed including touch voltage and tripping time at rated current
           5 Enter appropriate function code (see opposite)
           6 Only to be completed if the distribution board is not connected directly to the origin of the installation
                                                   ANNEX TT
                                                    (Clause 6)
            EXTRACTS FROM CENTRAL ELECTRICTTY AUTHORITY NOTIFICATION
                                    New Delhi, the 20th September, 2010
No. CEVl/59/CEA/EL - In exercise of the powers               name of such persons from the register.
conferred by section 177 of the Electricity Act, 2003
                                                             5. Electrical Safety Officer—(1) All suppliers of
(36 of 2003); the Central Electricity Authority hereby
                                                             electricity   including     generating   companies,
makes the following regulations for Measures
                                                             transmission companies and distribution companies
relating to Safety and Electric Supply, namely:-
                                                             shall designate an Electrical Safety Officer for
                      Chapter I                              ensuring observance of safety measures specified
                                                                                                                       SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
                                                             under these regulations in their organisation for
1. Short title and Commencement—(1) These                    construction, operation and maintenance of power
regulations may be called the Central Electricity            stations, sub-stations, transmission and distribution
Authority (Measures relating to Safety and Electric          lines.
Supply) Regulations, 2010
                                                            239
IS 732 : 2019
the Mean Sea level (MSL) as declared by local                        earthed neutral conductor, or the conductor
Municipal Authorities and where such equipment is                    which is to be connected thereto, to enable
to be installed in the basement, consumer shall ensure               such conductor to be distinguished from any
that the design of the basement should be such that                  live conductor and such indication shall be
there is no seepage or leakage or logging of water in                provided-
the basement.                                                        (a) where the earthed or earthed neutral
13. Service lines and apparatus on consumer’s                             conductor is the property of the
premises—(1) The supplier shall ensure that all                           supplier, at or near the point of
electric supply lines, wires, Fittings and apparatus                      commencement of supply;
belonging to him or under his control, which are on a                (b) where a conductor forming part of a
consumer’s premises, are in a safe-condition and in                       consumer’s system is to be connected to
all respects fit for supplying electricity and the                        the supplier’s earthed or earthed neutral
                                                                                                                      SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
supplier shall take precautions to avoid danger arising                   conductor, at the point where such
on such premises from such supply lines, wires,                           connection is to be made;
fittings and apparatus.                                              (c) in all other cases, at a point
                                                                          corresponding to the point of
(2) Service lines placed by the supplier on the
                                                                          commencement of supply or at such
                                                          240
                                                                                                      IS 732 : 2019
published by him in advance and where such                            supply lines having concentric cables, the
schedule of charges is not published, the procedure                   external conductor of such cables, shall be
laid down, in regulation 63 shall apply.                              earthed by two separate and distinct
                                                                      connections with earth.
Explanation—For the purposes of sub-regulation (1),
the expression "point of commencement of supply of             (v)    the connection with earth may include a link
electricity" shall mean the point at the incoming                     by means of which the connection may be
terminal of the switchgear installed by the consumer.                 temporarily interrupted for the purpose of
                                                                      testing or for locating fault.
17. Accessibility of bare conductors—Where bare                (vi)   in a direct current three wire system, the
conductors are used in a building, the owner of such                  middle conductor shall be earthed at the
conductors shall,—                                                    generating station only and the current from
    (a) ensure that they are inaccessible;                            the middle conductor to earth shall be
                                                                                                                        SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
    (b) provide in readily accessible position                        continuously recorded by means of a
        switches for rendering them dead whenever                     recording ammeter, and if at any time the
        necessary; and                                                current exceeds one-thousandth part of the
                                                                      maximum supply current, immediate steps
    (c) take such other safety measures as are                        shall be taken to improve the insulation of
                                                         241
IS 732 : 2019
         for regulating or controlling electricity, and                    works reasonably at earth potential and
         all electricity consuming apparatus, of                           to avoid dangerous contact potentials
         voltage exceeding 250 V but not exceeding                         being developed on such metal works;
         650 V shall be earthed by the owner by two                   b) limit earth resistance sufficiently low to
         separate and distinct connections with earth.                     permit adequate fault current for the
(xiii)   neutral point of every generator and                              operation of protective devices in time
         transformer shall be earthed by connecting it                     and to reduce neutral shifting;
         to the earthing system by not less than two                  c) be mechanically strong, withstand
         separate and distinct connections.                                corrosion      and     retain    electrical
(xiv)    all metal casing or metallic coverings                            continuity during the life of the
         containing or protecting any electric supply                      installation and all earthing systems
         line or apparatus shall be connected with                         shall be tested to ensure efficient
                                                                                                                         SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
         earth and shall be so joined and connected                        earthing, before the electric supply lines
         across all junction boxes and other openings                      or apparatus are energised.
         as to make good mechanical and electrical            (xvi) all earthing systems belonging to the
         connection throughout their whole length:                    supplier shall in addition, be tested for
         Provided that conditions mentioned in this                   resistance on dry day during the dry season
                                                            242
Bureau of Indian Standards
BIS is a statutory institution established under the Bureau of Indian Standards Act, 2016 to promote
harmonious development of the activities of standardization, marking and quality certification of goods
and attending to connected matters in the country.
Copyright
BIS has the copyright of all its publications. No part of these publications may be reproduced in any form
without the prior permission in writing of BIS. This does not preclude the free use, in the course of
implementing the standard, of necessary details, such as symbols and sizes, type or grade designations.
Enquiries relating to copyright be addressed to the Director (Publications), BIS.
                                                                                                                       SUPPLIED BY BOOK SUPPLY BUREAU UNDER THE LICENSE FROM BIS FOR LNTECC, MAHSR C4, SURAT
Review of Indian Standards
Amendments are issued to standards as the need arises on the basis of comments. Standards are also reviewed
periodically; a standard along with amendments is reaffirmed when such review indicates that no changes are
This Indian Standard has been developed from Doc No.: ETD 20 (10375).