KATHMANDU UNIVERSITY
SCHOOL OF ENGINEERING
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING
INSTRUMENTATION LABORARTORY WORK EEEG 306
LAB REPORT: 2
Use of Megger for Insulation Testing of a Transformer
Submitted By: Submitted To:
Prem Kr Yadav Aayush Bista
EE-Power & Control DoEEE, KU
III/I
Roll.no: 31246
Date: 2025/05/15
Experiment-II
Title: Use of Megger for Insulation testing of a transformer
Apparatus
S. No. Equipment Range Type Quantity
1 Megger 230V, 1-phase 1
2 Connecting wires 3/22, 15A Few
3 Transformer 2
Theory
Megger is used for insulation testing. The insulation should be high in MΩ for good equipment and
will lie in Ω range for damaged equipment.
Circuit diagram:
Figure 1: (a). Transformer (b) Transformer insulation testing using megger
Procedure:
1. Remove completely external supply to transformer.
2. Connect leads to megger and set the megger voltage to 1000V.
3. Measure the insulation resistance
Theory:
A megger test, also known as insulation resistance testing, measures the resistance of insulation in
electrical equipment to identify potential faults or degradation. It's a critical safety check for
electrical systems, ensuring proper insulation and preventing issues like electrical failures, shorts,
or fires.
Megger testing measures resistance between the phase windings of the motor under test and ground.
If there is an insulation breakdown, the resistance is negatively impacted and there is a departure
between phases or between one measurement and a previous one and a determination of motor
health is made.
Figure 2: Megger
Observation Table:
Phase- Ground Insulation Check:
S. No. Connection Resistance (MΩ)
1 1.2-Ground 16
2 1.1 Ground 24
3 2.1 Ground 56
4 2.2 Ground 105
5 3.1 Ground 621
6 3.2 Ground 726
Table 1: Phase-ground insulation resistance check
Phase-Phase Insulation Check:
S. No. Connection Resistance (MΩ)
1 1.2-2.1 32 MΩ
2 1.2-2.2 59 MΩ
3 1.2-3.1 93 MΩ
4 1.2-3.2 129 MΩ
5 1.1-2.1 485 MΩ
6 1.2-2.2 636 MΩ
7 1.2-3.1 386 MΩ
8 1.2-3.2 698 MΩ
9 1.3-2.1 769 MΩ
10 1.3-2.2 465 MΩ
Table 2: Phase-phase insulation resistance check
Conclusion:
From the above experiment, the resistance for phase to ground is less than that for the phase-to-
phase connection. We can also observe that the resistance increases as the phase-to-phase voltage
increases. Since, the resistance is in mega ohms, the transformer passes the insulation test.