EclypseTM I/O Modules
A range of I/O modules are available that have universal inputs and
               outputs, digital inputs with fast pulse support for use with energy meters
               and counters, 24VAC triac outputs for use with smaller load applications
               (up to 1 amp) such as electric fans and motors/actuators and relay
               outputs for larger load/high power applications such as electric heat and
               high power actuators.
               Features &Benefits
               • Universal inputs and outputs
               • Digital inputs with fast pulse support for use with energy meters and
                 counters
               • 24VAC triac outputs for use with smaller load applications (up to 1
                 amp) such as electric fans and motors/actuators and relay outputs
               • Override control outputs with optional Hand/Off/Auto (HOA) for
                 commissioning and maintenance
               • The I/O modules are hot-swappable for replacement without
                 interrupting power and communications to other modules
               • Status LEDs allow the user to confirm the status of the inputs/outputs,
                 facilitating commissioning and troubleshooting
               • The ECY-16DI module supports pulsed signals up to 120Hz for
                 equipment status monitoring and alarm point monitoring
               • Protection against miswiring and faults to prevent damage caused by
                 incorrect wiring or other mishaps
               • Plug & play devices equipped with HD-15 connectors that transmits
                 power and communications to the next module for fast and easy
                 assembly
Model Selection
Example: ECY-4UI4UO-HOA
        Series                                                       Model                                                             Hand-Off Auto Switch1
                           8UI : 8 Universal Inputs
                           16DI : 16 Digital Inputs
                           6UO : 6 Universal Outputs
                                                                                                                       [blank]: Without Hand-Off Auto Switch
       ECY-                8DOR : Digital Outputs (Relay)
                                                                                                                       -HOA : With Hand-Off Auto Switch
                           4UI4UO : 4 Universal Inputs and 4 Universal Outputs
                           8UI6UO : 8 Universal Inputs and 6 Universal Outputs
                           8UI6DOT : 8 Universal Inputs and 6 Digital Outputs (Triac)
1HOA    is only available for models with at least 1 output.
Product Specifications
ECY-8UI,  ECY-16DI,    ECY-6UO,    ECY-6UO-HOA, Standards and Regulations
ECY-4UI4UO,     ECY-4UI4UO-HOA,     ECY-8UI6UO,
ECY-8UI6UO-HOA, ECY-8UI6DOT, & ECY-8UI6DOT-HOA    CE Emission                                                                              EN61000-6-3: 2007; A1:2011
                                                                                                     CE Immunity                           EN61000-6-1: 2007
Power Supply Input
                                                                                                                                           Compliance with FCC rules part
                                                                                                     FCC
                                       Voltage        18VDC                                                                                15, subpart B, class B
            Basic Power Consumption1                  0.94 W                                                                               UL916 Energy management
                                                                                                     UL Listed (CDN and US)
1External  loads excluded. To calculate the number of Input/Output Extension Modules that can
                                                                                                                                           equipment
operate with a power supply, see the Product Selection Tool in Builder: https://builder.distech-
controls.com.
Hardware
                            Status Indicator          Green LEDs: inputs and outputs               Universal Inputs (UI)
                                                                                                   General
Mechanical
                                                                                                                         Input Type     Universal; software configurable
               Dimensions (H × W × D)                 4.74 × 3.20 × 2.31" (120.31 ×                   Current Input Option Selection    DIP switch
                                                      81.17 × 58.56mm)                                             Input Resolution     16-bit analog to digital converter
                           Shipping weight            0.85lbs (0.39kg)                                        Power Supply Output       18VDC; 20mA maximum per 0 to
                                     Mounting         DIN rail or screw mounting                                                        20 mA input
                             Hot-swappable            Yes
                       Enclosure Material             FR/ABS                                       Contact
                        Enclosure Rating1             Plastic housing, UL94-V0
                                                      flammability rating                                                      Type     Dry contact
1Allmaterials and manufacturing processes comply with the RoHS directive and are marked
according to the Waste Electrical and Electronic Equipment (WEEE) directive
                                                                                                   Counter
Environmental
                                                                                                                               Type     Dry contact
                 Operating Temperature                32 to 122°F (0 to 50°C)                                  Maximum Frequency        1Hz maximum
                    Storage Temperature               -22 to 158°F (-30 to 70°C)                               Minimum Duty Cycle       500milliseconds On /
                         Relative Humidity            0 to 90% non-condensing                                                           500milliseconds Off
              Ingress Protection Rating               IP20 in accordance with IEC
                                                      60537
                               Nema Rating            1
2                                                                                                                                                     Eclypse I/O Modules
0 to 10VDC                                                               PWM
                           Range    0 to 10VDC (40kΩ input                                        Range     Adjustable period from 2 to 65
                                    impedance)                                                              seconds
0 to 5VDC
                                                                         Floating
                           Range    0 to 5VDC (high input impedance)
                                                                               Minimum Pulse On/Off Time    500 milliseconds
                                                                                        Drive Time Period   Adjustable
0 to 20mA
                           Range    0 to 20mA, 249Ω DIP-switch           0 to 10VDC
                                    configurable internal resistor
                                                                                                  Range     0 to 10VDC linear
Resistance/Thermistor
                           Range    0 to 350 KΩ                          0 to 20mA
     Supported Thermistor Types     Any that operate in this range
                                                                                                  Range     0 to 20mA
                           Pre-configured Temperature Sensor Types:
                                                                                          Current Source    20mA maximum per 0 to 20 mA
                       Thermistor   10KΩ Type 2, 3 (10KΩ @ 77ºF;
                                                                                                            output
                                    25ºC)
                                                                           Ports UO1, UO2, and UO3 only     DIP switch
                         Platinum   Pt1000 (1KΩ @ 32ºF; 0ºC)
                           Nickel   RTD Ni1000 (1KΩ @ 32ºF; 0ºC)
                                    RTD Ni1000 (1KΩ @ 69.8ºF;
                                    21ºC)
                                                                         HOA
                                                                                     Hand-Off-Auto switch   When equipped
Digital Inputs (DI)                                                                                         Supervision allows control logic to
                                                                                                            read the current HOA switch and
                                                                                                            potentiometer settings
                                                                                               Threshold    Configurable
General
                                                                             Potentiometer Voltage Range    0 to 12VDC
                       Input Type   Dry contact or Open-Collector
                  Low Threshold     < 2.5V                               Digital Output (DOT)
                 High Threshold     > 3.0V                               General
Pulse/Counter                                                                                Output Type    24VAC Triac; software
                                                                                                            configurable
                      Pulse Input   S0 output compatible                                Maximum Current     0.5A continuous
            Maximum Frequency       120Hz                                                                   1A @ 15% duty cycle for a 10
            Minimum Duty Cycle      4.167milliseconds On /                                                  minute period
                                    4.167milliseconds Off                                  Power Source,    External power supply
Universal Outputs (UO)                                                   0 or 24VAC (On/Off)
General
                                                                                                  Range     0 or 24VAC
                      Output Type   Universal; software configurable
     Output Resolution Converter    10-bit digital to analog Converter
              Output Protection,    Built-in snubbing diode to protect   PWM
                                    against back-EMF, for example
                                    when used with a 12VDC relay                                  Range     Adjustable period from 2 to 65
                Load Resistance     Minimum 200Ω for 0 to 10VDC                                             seconds
                                    and 0 to 12VDC outputs Maximum
                                    500Ω for 0 to 20mA output
                Auto-reset Fuse     60mA @ 140ºF; 60ºC                   Floating
                                                                               Minimum Pulse On/Off Time    500 milliseconds
0 or 12VDC (On/Off)
                                                                                        Drive Time Period   Adjustable
                           Range    0 or 12VDC
3                                                                                                                        Eclypse I/O Modules
HOA
                    Hand-Off-Auto switch         When equipped
                                                 Supervision allows control logic
                                                 to read the current HOA switch
                                                 setting
Dimensions
                                               3.20" 81.17                                       2.31" 58.56
                                   Inter-Connection Gap: 0.01" 0.40
                                                                                                                                                                  0.83 21.08
            4.74" 120.31                                                                                                                                          3.18" 80.82
 4.80" 121.75
                                                                                                                                                                  0.73 18.54
                                                   Front                                              Profile                              Back
            0.06"    1.44                      2.95" 74.99                                                                                                  Inches Millimeters
Product Specifications
ECY-8DOR & ECY-8DOR-HOA                                                                                            Operating Voltage   0 to 277VAC or 0-30VDC
                                                                                                                                       ±10%, see HIG for mounting
Power Supply Input                                                                                                                     specifications
                                                                                                                      Resistive Load   Max 10A
                                    Voltage      18VDC                                                                Inductive Load   Max 6A
            Basic Power Consumption1             0.94 W                                                                  Motor Load    Max 3A
1External   loads excluded. To calculate the number of Input/Output Extension Modules that
can operate with a power supply, see the Product Selection Tool available in Builder: https://
                                                                                                                  Current Protection   Outputs must be protected with
builder.distech-controls.com.                                                                                                          max 10 A external circuit breaker
Hardware                                                                                         Digital
                            Status Indicator     Green LEDs: inputs and outputs                                              Range     On/Off
                                                                                                 HOA
Digital Output (DOR)
General                                                                                                         Hand-Off-Auto switch   When equipped
                                                                                                                                       Supervision allows control logic
                               Output Type       Relay contact                                                                         to read the current HOA switch
                                Relay Type       Form C                                                                                setting
                             Power Source        Dry contact (external power
                                                 supply)
4                                                                                                                                                  Eclypse I/O Modules
Mechanical                                                                                                      Pollution Degree    2
                                                                                                        Ingress Protection Rating   IP20
                Dimensions (H × W × D)            4.74 × 5.15 × 2.31" (120.31 ×                                                     (must be mounted in a protective
                                                  130.07 × 58.56mm)                                                                 enclosure to conform with
                         Shipping weight          0.75lbs (0.34kg)                                                                  electrical installation standards)
                                Mounting          DIN rail or screw mounting                                        Overvoltage     Category II - 2.5 kV
                          Hot-swappable           Yes (once high voltages have
                                                  been removed)
                                                                                             Standards and Regulations
                       Enclosure Material         FR/ABS
                       Enclosure Rating1          Plastic housing, UL94-5VB
                                                                                                 CE Electrical Safety                   EN 60730-1 : 2011
                                                  flammability rating
1Allmaterials and manufacturing processes comply with the RoHS directive and are marked
                                                                                                 CE Emission                            EN61000-6-3: 2007; A1:2011
according to the Waste Electrical and Electronic Equipment (WEEE) directive
                                                                                                 CE Immunity                            EN61000-6-1: 2007
                                                                                                                                        This device complies with FCC
                                                                                                 FCC
Environmental                                                                                                                           rules part 15, subpart B, class B
                                                                                                 UL Listed (CDN and US)                 UL 61010-1
                Operating Temperature             32 to 122°F (0 to 50°C)
                  Storage Temperature             -22 to 158°F (-30 to 70°C)
                        Relative Humidity         0 to 90% non-condensing
                                 Altitude         <6562ft (2000m)
Dimensions
                                             5.15" 130.07
                                                                                          2.31" 58.56
                                                  Inter-Connection Gap: 0.01" 0.40
                                                                                                                                                                  0.83 21.08
                                        O1   O2    O3   O4   O5   O6   O7   O8
                                                                                 MAN
                                                                                 AUTO
       4.74" 120.31                                                              OFF
                                                                                                                                                                  3.18" 80.82
 4.80" 121.75
                                                                                                                                                                  0.73 18.54
                                                      Front                                                                         Back
       0.06"    1.44                              4.94" 125.32                                                                                              Inches Millimeters
                                                              Specifications subject to change without notice.
    Eclypse, Distech Controls, the Distech Controls logo, EC-Net, Allure, and Allure Unitouch are trademarks of Distech Controls Inc. BACnet is a registered trademark of
 ASHRAE; BTL is a registered trademark of the BACnet Manufacturers Association. The Bluetooth® word mark and logos are registered trademarks owned by Bluetooth SIG,
                                Inc. and any use of such marks is under license. All other trademarks are property of their respective owners.
                                                             ©, , 2025 Distech Controls Inc. All rights reserved.
     Global Head Office - 4205 place de Java, Brossard, QC, Canada, J4Y 0C4EU Head Office - ZAC de Sacuny, 558 avenue Marcel Mérieux, 69530 Brignais, France
5                                                                                                                                       ECY IO Modules_SP_15_EN