IOM4711
IOM4711
MS-IOM4711-0U
Application
The IOM47 field controller is part of the Metasys® system North American Emissions
Field Equipment Controller family. Input/Output Module Compliance
(IOM) controller expand the number of points connected
to a Network Automation Engine (NAE), Field Equipment
Controller (FEC), or Advanced Application Field Canada
Equipment Controller (FAC) to monitor and control a wide This Class (A) digital apparatus meets all the
variety of HVAC equipment. requirements of the Canadian Interference-Causing
Equipment Regulations.
IOM controllers operate on an RS-485 BACnet® MS/TP
Cet appareil numérique de la Classe (A) respecte toutes
Bus as BACnet Application Specific Controllers (B-ASCs)
les exigences du Règlement sur le matériel brouilleur
and integrate into Johnson Controls® and third-party
du Canada.
BACnet systems.
Note: With CCT Release 10.3 and Release Module (RM)
United States
10.2, a new capability allows VMAs, FECs, and
FACs to communicate by using either the BACnet This equipment has been tested and found to comply
or the N2 field bus networking protocol. The I/O with the limits for a Class A digital device pursuant to
can be connected through the SA bus to a host Part 15 of the FCC Rules. These limits are designed to
controller that is using either the BACnet or the provide reasonable protection against harmful
N2 protocol. Only the BACnet protocol is interference when this equipment is operated in a
supported when the I/O is connected directly to commercial environment. This equipment generates,
the trunk using the FC bus. uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction
Important: The MS-IOM4711-0U model is used in manual, may cause harmful interference to radio
Metasys Release 8.1 smoke control communications. Operation of this equipment in a
applications and is UL 864 UUKL/UUKLC residential area may cause harmful interference, in which
10th Edition Smoke Control Listed. You case the users will be required to correct the interference
must refer to the Metasys® System UL 864 at their own expense.
10th Edition UUKL/ORD-C100-13 UUKLC
Smoke Control System Technical Bulletin
(LIT-12012487) for detailed requirements Installation
and procedures for installing, Observe these guidelines when installing a controller:
commissioning, and operating UL 864 • Transport the controller in the original container to
UUKL/UUKLC Listed Metasys system minimize vibration and shock damage.
devices. The UL 864 UUKL/UUKLC listing
for Smoke Control Equipment is voided if • Verify that all parts shipped with the controller.
(1) you do not use the required software • Do not drop the controller or subject it to physical
tools at the required versions; or (2) you do shock.
not meet the requirements or do not follow
the procedures as documented in the Parts Included
Metasys® System UL 864 10th Edition
• one controller with removable terminal blocks (Power
UUKL/ORD-C100-13 UUKLC Smoke
and SA/FC bus are removable)
Control System Technical Bulletin
(LIT-12012487). • one installation instructions sheet
Mounting
Observe these guidelines when mounting a controller:
• Ensure the mounting surface can support the
controller, DIN rail, and any user-supplied enclosure.
• Mount the controller horizontally on 35 mm DIN rail
whenever possible. DIN Rail Mount Applications
• Mount the controller in the proper mounting position Mounting the controller horizontal on 35 mm DIN rail is
(Figure 1). the preferred mounting method.
• Mount the controller on a hard, even surface To mount an IOM47 controller on 35 mm DIN rail:
whenever possible in wall-mount applications.
1. Securely mount a 20 cm (8 in.) or longer section of
• Use shims or washers to mount the controller securely 35 mm DIN rail horizontal and centered in the desired
and evenly on the mounting surface. space so that the controller mounts in the horizontal
• Mount the controller in an area free of corrosive position shown in Figure 1.
vapors and observe the Ambient Conditions 2. Pull the two bottom mounting clips outward from the
requirements in Table 10. controller to the extended position (Figure 2).
• Provide for sufficient space around the controller for 3. Hang the controller on the DIN rail by the hooks at
cable and wire connections for easy cover removal the top of the (DIN rail) channel on the back of the
and good ventilation through the controller (50 mm controller (Figure 2), and position the controller snugly
[2 in.] minimum on the top, bottom, and front of the against the DIN rail.
controller).
4. Push the bottom mounting clips inward (up) to secure
• Do not mount the controller on surfaces prone to the controller on the DIN rail.
vibration, such as duct work.
To remove the controller from the DIN rail, pull the
• Do not mount the controller in areas where
bottom mounting clips out to the extended position
electromagnetic emissions from other devices or
and carefully lift the controller off the DIN rail.
wiring can interfere with controller communication.
Observe these additional guidelines when mounting an
IOM47 controller in a panel or enclosure:
Wall Mount Applications
To mount a controller directly on a wall or other flat
• Mount the controller so that the enclosure walls do vertical surface:
not obstruct cover removal or ventilation through the
controller. 1. Pull the two bottom mounting clips outward and
ensure they are locked in the extended position as
• Mount the controller so that the power transformer shown in Figure 2.
and other devices do not radiate excessive heat to
the controller. 2. Mark the mounting hole locations on the wall using
the dimensions in Figure 2 and one of the mount
• Do not install the controller in an airtight enclosure. positions shown in Figure 1. Or, hold the controller
up to the wall or surface in a proper mount position
and mark the hole locations through the mounting
clips.
3. Drill holes in the wall or surface at the marked
locations, and insert appropriate wall anchors in the
holes (if necessary).
IOM4711 Input/Output Module Installation Instructions 2
4. Hold the controller in place, and insert the screws Figure 2: Back of Controller Showing Extended
through the mounting clips and into the holes (or Mounting Clips, DIN Rail Channel, and
anchors). Carefully tighten all of the screws. Mounting Dimensions, mm (in.)
Important: Use copper conductors only. Make all wiring When connecting the IOM to an SA bus, wire the bus
in accordance with local, national, and terminal block plugs on the controller and other SA bus
regional regulations. devices in a daisy-chain configuration using 4-wire
twisted, shielded cable as shown in Figure 5. See Table
Important: Electrostatic discharge can damage 3 for more information.
controller components. Use proper
Figure 5: SA Bus Terminal Block Wiring
electrostatic discharge precautions during
installation, setup, and servicing to avoid
damaging the controller.
For detailed information on configuring and wiring an
MS/TP Bus, FC bus, and SA bus, refer to the MS/TP
Communications Bus Technical Bulletin (LIT-12011034).
Incremental Control to CO or AO
Actuator (Switch Low,
Externally Sourced)
Incremental Control to BO
Actuator (Switch Low,
Externally Sourced)
Incremental Control to BO
Actuator (Switch High,
Externally Sourced)
UNIVERSAL +15 V 15 VDC Power Source for active (3-wire) input devices Same as (Universal) INn
connected to the Universal INn terminals.
(Inputs) Note: Use 3-wire cable for
Provides 100 mA total current devices that source power from
the +15V terminal.
INn Analog Input - Voltage Mode (0–10 VDC) See Guideline A in Table 4.
10 VDC maximum input voltage
Internal 75k ohm Pull-down
Analog Input - Current Mode (4–20 mA) See Guideline B in Table 4.
Internal 100 ohm load impedance
Note: A current loop fail-safe jumper can be positioned to
maintain a closed 4 to 20 mA current loop, even when the
power to the controller is interrupted or off. See UI Current
Loop Jumpers.
Analog Input - Resistive Mode (0–600k ohm) See Guideline A in Table 4.
Internal 12 V. 15k ohm pull up
Qualified Sensors: 0-2k ohm potentiometer, RTD (1k Nickel
[Johnson Controls® sensor], 1k Platinum, and A99B Silicon
Temperature Sensor) Negative Temperature Coefficient
(NTC) Sensor (10k Type L, 10k JCI Type II, 2.252k Type
II)
Binary Input - Dry Contact Maintained Mode See Guideline A in Table 4.
1 second minimum pulse width
Internal 12 V. 15k ohm pull up
ICOMn Universal Input Common for all Universal Input terminals Same as (Universal) INn
Note: All Universal ICOMn terminals share a common,
which is isolated from all other commons.
BINARY INn Binary Input - Dry Contact Maintained Mode See Guideline A in Table 4.
(Inputs) 0.01 second minimum pulse width
Internal 18 V. 3k ohm pull up
Binary Input - Pulse Counter/Accumulator Mode
0.01 second minimum pulse width
(50 Hz at 50% duty cycle)
Internal 18 V. 3k ohm pull up
ICOMn Binary Input Common for all Binary Input (IN) terminals
Note: All Binary ICOMn terminals share a common, which
is isolated from all other commons, except the Configurable
Output (CO) common (OCOMn) when the CO is defined
as an Analog Output.
ANALOG OUTn Analog Output - Voltage Mode (0–10 VDC) See Guideline C in Table 4.
(Outputs) 10 VDC maximum output voltage
10 mA maximum output current
Required an external load of 1,000 ohm or more.
Note: The Analog Output (AO) operates in the Voltage
Mode when connected to devices with impedances greater
than 1,000 ohm. Devices that drop below 1,000 ohm may
not operate as intended for Voltage Mode applications.
Analog Output - Current Mode (4–20 mA)
Requires and external load between 0 and 300 ohm.
Note: The Analog Output (AO) operates in the Current
Mode when connected to devices with impedances less
than 300 ohm. Devices that exceed below 300 ohm may
not operate as intended for Current Mode applications.
OCOMn Analog Output Signal Common for all Analog OUT
terminals.
Note: All Analog Output Common terminals (OCOMn) share
a common, which is isolated from all other commons.
BINARY OUTn Binary Output - 24 VAC Triac (External Power Source) See Guideline C in Table 4.
(Output) Connects OUTn to OCOMn when activated.
Power Selection External Power Source Requirements:
Jumper positioned to
30 VAC maximum output voltage
External (EXT) power.
0.5 A maximum output current
1.3 A at 25% duty cycle
40 mA minimum load current
OCOMn Binary Output Common (for OUTn terminal)
Note: Each Binary Output Common terminal (OCOMn) is
isolated from all other commons, including other Binary
Output Common terminals.
BINARY OUTn Binary Output - 24 VAC Triac (Internal Power Source) See Guideline C in Table 4.
(Output) Sources internal 24 VAC power (24~ HOT).
Power Selection OCOMn Binary Output - 24 VAC Triac (Internal Power Source)
Jumper positioned to
Connects OCOMn to 24~ when activated.
Internal (INT) power.
Internal Power Source:
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
40 mA minimum load current
CONFIGURABLE OUTn Analog Output - Voltage Mode (0–10 VDC) See Guideline A in Table 4.
(Outputs) 10 VDC maximum output voltage
10 mA maximum output current
Required an external load of 1,000 ohm or more.
Binary Output - 24 VAC Triac (External Power Source See Guideline C in Table 4.
only)
Connects OUTn to OCOMn when activated.
External Power Source Requirements:
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
40 mA minimum load current
OCOMn Analog Output Signal Common All Configurable Outputs Same as (Configurable) OUTn.
(COs) defined as Analog Outputs (AOs) share a common,
which is isolated from all other commons except the Binary
Input common.
Binary Output Signal Common All Configurable Outputs
(COs) defined as Binary Outputs are isolated from all other
commons, including other CO commons.
1 See Table 4 to determine wire size and cable lengths for cables.
1 See Table 4 to determine wire size and cable lengths for cables.
2 The SA Bus and FC Bus wiring recommendations in this table are for MS/TP bus communications at 38,400 baud. For more
information, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034).
Repair Information
The MS-IOM4711-0U model is UL 864 10th Edition UUKL/ORD-C100-13 UUKLC listed for smoke control. If a
controller fails to operate within its specifications, contact the Johnson Controls Repair Center in Louisville, Kentucky,
at 1-502-671-7312.
Accessories
See Table 9 for controller accessories ordering information.
Table 9: Accessories Ordering Information
Product Code Number Description
PAN-PWRSP-U Transformer, 120/24 VAC, 96 VA, with circuit breaker and 120 VAC outlet, approved for Smoke
Control
NS Series Network Sensors Refer to the NS Series Network Sensors Product Bulletin (LIT-12011574) for specific sensor
model descriptions.
Technical Specifications
Table 10: IOM4711-0U Technical Specifications
Product Code Number MS-IOM4711-0U Input/Output Module
Supply Voltage 24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, power supply
Class 2 (North America)
Power Consumption 14 VA maximum
Note: VA rating does not include any power supplied to the peripheral devices
connected to Binary Outputs (BOs) or Configurable Outputs (COs), which can
consume up to 12 VA for each BO or CO; for a possible total consumption of an
additional 84 VA (maximum).
Ambient Conditions Operating: 0° to 50°C (32° to 122°F); 10% to 90% RH noncondensing
Storage: -40° to 80°C (-40° to 176°F); 5% to 95% RH noncondensing
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions
beyond these specifications, consult the local Johnson Controls® office. Johnson Controls shall not be liable for
damages resulting from misapplication or misuse of its products.