ABB Drives

Users Manual
Analog I/O Extension
FIO-11

Analog I/O Extension


FIO-11
Users Manual

3AFE68784930 Rev C EN
EFFECTIVE: 1.2.2008
2008 ABB Oy. All Rights Reserved.

Safety instructions
Overview
This chapter states the general safety instructions that must be
followed when installing and operating the FIO-11 Analog I/O
Extension.
In addition to the safety instructions given below, read the
complete safety instructions of the specific drive you are working
on.
These warnings are intended for all who work on the drive.
Ignoring the instructions can cause physical injury or death, or
damage the equipment.

General safety instructions


Warning! All electrical installation and maintenance work on the
drive should be carried out by qualified electricians only.
The drive and adjoining equipment must be properly earthed.
Do not attempt any work on a powered drive. After switching off
the mains, always allow the intermediate circuit capacitors 5
minutes to discharge before working on the frequency converter,
the motor or the motor cable. It is good practice to check (with a
voltage indicating instrument) that the drive is in fact discharged
before beginning work.
The motor cable terminals of the drive are at a dangerously high
voltage when mains power is applied, regardless of motor
operation.
There can be dangerous voltages inside the drive from external
control circuits even when the drive mains power is shut off.
Exercise appropriate care when working on the unit.

Safety instructions

Safety instructions

Table of contents
Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
General safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table of contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Intended audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Before you start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
What this manual contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
The FIO-11 Analog I/O Extension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Input signal type selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal designations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

13
14
14
15
16

Fault tracing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Diagnostic LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Table of contents

Table of contents

Introduction
Intended audience
The manual is intended for the people who are responsible for
commissioning and using the FIO-11 Analog I/O Extension. The
reader is expected to have a basic knowledge of electrical
fundamentals, electrical wiring practices and how to operate the
drive.

Before you start


It is assumed that the drive is installed and the drive power supply
is switched off before starting the installation of the extension
module. Ensure that all dangerous voltages connected from
external control circuits to the inputs and outputs of the drive are
switched off.
In addition to conventional installation tools, have the drive
manuals available during the installation as they contain important
information not included in this manual. The drive manuals are
referred to at various points of this document.

What this manual contains


This manual contains information on the wiring, configuration and
use of the FIO-11 Analog I/O Extension.
Safety instructions are featured in the first few pages of this
manual.
Overview contains a short description of the FIO-11.
Installation contains instructions for hardware settings, mounting
and cabling.
Fault tracing explains LED indications.
Technical Data contains detailed technical information.

Introduction

10

Introduction

11

Overview
Overview
This chapter contains a short description of the FIO-11 Analog I/O
Extension.

The FIO-11 Analog I/O Extension


The FIO-11 is a general purpose analog and digital input/output
extension. It offers three analog inputs, one analog output and two
digital inputs or outputs. All inputs and outputs are in the same
potential and have a common isolation to control electronics.

FIO-11
ANALOG IO EXTENSION

Diagnostic LED

STATUS

SETTINGS
AI1

Voltage
input
Current
input

AI2

CHASSIS

AI3

AO1-

X71

X74

AI2-

DIO1

AI2+

COM

X72

X75

AI3-

DIO2

AI3+

COM

X73

X76

2 1

AO1+

AI1+

2 1

Slide switches for input


mode selection (under
the plugs)

AI1-

2 1

Fixing screw
Analog output
Digital inputs/outputs

Analog inputs

FIO-11 layout

Overview

12

Isolation areas
The following figure describes the different isolation areas of the
module.
Connection to the drive
X75

X76

X201

X74

Analog output

Digital inputs/outputs
Analog inputs
X71

X72

X73

CHASSIS
Fixing screw

The fixing screw connects the chassis to ground.

Overview

13

Installation
Warning! Follow the safety instructions given in this guide and in
the drives hardware manual.

Mounting
Warning! Before installation, switch off the drive power supply.
Wait for five minutes to ensure that the capacitor bank of the drive
is discharged. Switch off all dangerous voltages connected from
external control circuits to the inputs and outputs of the drive.
The FIO-11 is to be inserted into the option slot of the drive. The
module is held in place with plastic retaining clips and one screw.
On installation of the module, the signal and power connection to
the drive is automatically made through a 20-pin connector.
Mounting procedure:
Insert the module carefully into the option slot until the retaining
clips lock the module into position.
Fasten the screw (included) to the stand-off.
Note: Correct installation of the screw is essential for fulfilling the
EMC requirements and for proper operation of the module.

Installation

14

Input signal type selection


The three analog inputs can used with a current or voltage signal.
The selection is made by sliding the both slide switches next to the
input either up (current signal) or down (voltage signal).
Current signal

Voltage signal

Terminal designations
Marking

Description

X71

Analog input
Current input -2020 mA
Voltage input -1010 V

AI1+

AI1-

X72
1

AI2+

AI2-

X73
1

AI3+

AI3-

X74
1

AO1+

AO1-

Analog output
Current output: 020 mA

X75
1

DIO1

COM

X76

Installation

DIO2

COM

Digital input/output
24 V logic levels for input: 0 < 5 V, 1 > 15 V
Output current 50 mA source, 50 mA sink

15

Wiring
The diagram presents some typical output types.
Push-pull

Open collector
(Sinking)
+24 V

VCC

VCC

RL1

+24V

Open emitter
(Sourcing)
VCC

RL
DIOx

DIOx

DIOx
RL

RL2
COM

COM

COM

VCC = Digital I/O power supply voltage


RL = Load at output channel

Maximum 2.5 mm2 cable should be used for the signals. The
cable shields should be connected to the JCU-01 Control Unit.
See the drive Hardware Manual for more information.
+
-

AI+
AI-

Analog input description


VCC

AO1+
AO1-

RL = Max. 500 Ohms

Analog output description


Installation

16

+
-

DIOx

2 kOhms

0 / 1

COM

Digital I/O description


Note: Do not route signal cables parallel to power cables.
Tightening torque is 0.5 Nm (4.4 lbfin.) for the plugs.

Programming
The communication between the module and the drive is activated
by a drive parameter. See the drive Firmware Manual.

Installation

17

Fault tracing

STATUS LED

Diagnostic LEDs
Colour

Description

Green

OK

Orange

Not initialized or communication fault to


control unit

Red

Power fault & not initialized or


communication fault to control unit

Fault tracing

18

Fault tracing

19

Technical data
Dimensions
32 mm

1.26 in
FIO-11
ANALOG IO EXTENSION
STATUS

SETTINGS
Voltage
input
Current
input

AI2

2 1
2 1
2 1

AI1-

AO1+

AI1+

AO1-

X71

X74

AI2-

DIO1

AI2+

COM

X72

X75

AI3-

DIO2

AI3+

COM

X73

X76

23 mm

63 mm

0.91 in

2.48 in

2 1

AI3

2 1

CHASSIS

2 1

106 mm
4.17 in

AI1

General
Max. power consumption: 300 mA at 24 V
Degree of protection: IP20
Ambient conditions: The applicable ambient conditions
specified for the drive in its Hardware Manual are in effect
Connectors
20 pin socket
6 pcs. 2-pole detachable terminal plugs.

Technical data

20

Analog input
Input voltages: -1010 V
Input currents: -2020 mA
Differential inputs, common-mode voltage 20 V
Analog to digital conversion resolution 16 bit
Inaccuracy: 0.1% of FSR
Input signal bandwidth DC to 4 kHz (-3 dB)
Isolated from power supply.
Analog output
Output current: 020 mA, Rload < 500 ohms
Resolution 12 bit
Inaccuracy 2% FSR
Output signal bandwidth DC to 500 Hz (-3 dB).
Digital I/O
All DIOs programmable as
- Input (default)
- Push-pull output
- Open collector output
Input voltages max 30 V, reverse polarity protection
24 V logic levels for input: 0 < 5 V, 1 > 15 V (according to
standard IEC 61131-2)
Input impedance 2 kOhms
Output current 50 mA source, 50 mA sink
Outputs are short-circuit proof
Galvanic isolation as one group

Technical data

3AFE68784930 Rev C EN
EFFECTIVE: 1.2.2008
ABB Oy
AC Drives
P.O. Box 184
FIN-00381 HELSINKI
FINLAND
Telephone +358 10 22 11
Telefax
+358 10 22 22681
Internet
http://www.abb.com

ABB Inc.
Automation Technologies
Drives & Motors
16250 West Glendale Drive
New Berlin, WI 53151
USA
Telephone
262 785-3200
800-HELP-365
Telefax
262 780-5135

ABB Beijing Drive Systems


Co. Ltd.
No. 1, Block D,
A-10 Jiuxianqiao Beilu
Chaoyang District
Beijing, P.R. China, 100015
Telephone +86 10 5821 7788
Fax
+86 10 5821 7618

You might also like