A B C D A B C D
1 1
LEGEND:
2 S2
2
S2 CONVENIENCE OUTLET
S FLUORESCENT BULB
TAP TO SPARE
CIRCUIT
FLUORESCENT LAMP
S POLE SWITCH
3 S3 3 CIRCUIT BREAKER
SWITCH RUN
POWER RUN
4 4 GROUND
TAP TO SPARE
CIRCUIT WP
WEATHER PROOF OUTLET
S2 AC
AIRCON OUTLET
5 5
1 GROUND FLOOR LIGHTING LAYOUT 2 2ND FLOOR LIGHTING LAYOUT
E-01 SCALE 1:75 E-01 SCALE 1:75
GENERAL NOTES:
A B C D A B C D 1. ALL ELECTRICAL WORKS SPECIFIED HEREIN SHALL BE THW IN A 1-1/4" (32 mm) DIA. PIPE.
DONE IN ACCORDANCE WITH THE PROVISIONS OF C. BRANCH HOMERUN EXCEEDING, 200' - 0"
THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE, (60960mm) USE : # 6 AWG (14 sq. mm)
LAWS AND ORDINANCES OF THE LOCAL GOVERNMENT, THW IN A 1-1/2" (38 mm) DIA. PIPE.
RULES AND REGULATIONS OF THE LOCAL UTILITY POWER
1 1 COMPANY. D. METERING FACILITIES, 5' - 6' (1677mm) FROM
TOP OF METER BASE / SOCKET TO FINISH
2. INCOMING POWER SHALL BE 240 V, SINGLE FLOOR LEVEL AS A MAXIMUM HEIGHT FOR
PHASE,2-WIRES, 60 HERTZ.
7. ALL FLORESCENT LAMPS SHALL BE PROVIDED WITH RAPID
3. ALL WIRING SHALL BE IN PVC CONDUIT UNLESS START / PRE - HEAT BALLAST.
WP OTHERWISE SPECIFIED.
2 2 8. ALL MATERIALS SHALL BE NEW AND OF THE APPROVED
4. BRANCH CIRCUIT AND FEEDER WIRES SHALL BE CODED. TYPE FOR THE LOCATIONS AND PURPOSE INTENDED TO.
5. MOUNTING HEIGHT : 9. ALL WORKS SHALL BE EXECUTED UNDER THE DIRECT
A. WALL SWITCHES, 1'-6" (1372mm) - FROM CENTER SUPERVISIONS OF A DULLY
OF THE DEVICE TO FINISH FLOOR LEVEL, INCLUDING REGISTERED PROFESSIONAL ELECTRICAL, REGISTERED
3 3 INTERCOM UNITS.
B. CONVENIENCE OUTLETS, 1' - 0" (305mm) - FROM
ELECTRICAL ENGINEER, AND OR REGISTERED MASTER
TAP TO SPARE ELECTRICIAN.
CIRCUIT AC
CENTER OF DEVICE TO FINISH FLOOR LEVEL,
INCLUDING 10. CONFORM WITH THE ARCHITECT, THE TYPE AND COLOR
4 4 TELEPHONE OUTLET AND CATV OUTLET. RENDERING CATALOGS / INDEX OF LIGHTING FIXTURES
C. LIGHTING / POWER PANEL BOARDS, 5' - 6" (1677mm) BEFORE FINAL INSTALLATION.
FROM CENTER OF PANEL BOARDS TO FINISH
FLOOR LEVEL. 11. VERIFY ARCHITECTURAL DRAWINGS FOR LIGHTING
D. METERING FACILITIES, 5' - 6' (1677mm) FROM FIXTURES AND WIRING DEVICES INCLUDING EXACT LOCATION
TOP OF METER BASE / SOCKET TO FINISH AND MOUNTING HEIGHTS.
TAP TO SPARE FLOOR LEVEL AS A MAXIMUM HEIGHT FOR
5 5
CIRCUIT MULTI METERING.
6. LIGHTING BRANCHES CIRCUIT HOMERUNS SHALL BE
12. REFER ELECTRICAL TECHNICAL SPECIFICATIONS FOR
FURTHER INSTRUCTIONS.
WP GOVERNED BY THE FOLLOWING :
A. BRANCH HOMERUN EXCEEDING, 90' - 0" 13. NO REVISION IN THE DESIGN NOR ADDITIONAL LOADS
(27432mm) USE : # 10 AWG (5.5 sq. mm) SHALL BE DONE WITHOUT THE PRIOR KNOWLEDGE OR
THW IN A 1" (25 mm) DIA. PIPE. APPROVAL OF THE BUILDING ENGINEER AND THE DESIGNER.
B. BRANCH HOMERUN EXCEEDING, 140' - 0" ANY SUCH REVISIONS DONE WITHOUT APPROVAL SHALL
(4267mm) USE : # 8 AWG (8.0 sq. mm) CAUSE RESPONSIBILITY OF THE DESIGNER TO CEASE AS A
WHOLE.
3 GROUND FLOOR POWER LAYOUT 4 2ND FLOOR POWER LAYOUT
E-01 SCALE 1:75 E-01 SCALE 1:50
TWO STOREY RESIDENTIAL EXTENSION MR. SPENCER LANGIE JOHN B. AUSTRIA
E-01