This document provides general notes and schedules for electrical loads and wiring for a project. It specifies that all electrical work must comply with relevant codes and standards. A service entrance voltage of 230V, 1-phase power is noted. Wire and conduit sizes of 3.5mm THHN stranded wire and 15mm PVC are the minimums to be used. Lighting, convenience outlets, AC units, a refrigerator and range are included in the load schedule totaling 25,517 watts. Installation, testing and warranty standards are also outlined.

Uploaded by

Pocholo Severo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
50 views1 page

E2 Galang

This document provides general notes and schedules for electrical loads and wiring for a project. It specifies that all electrical work must comply with relevant codes and standards. A service entrance voltage of 230V, 1-phase power is noted. Wire and conduit sizes of 3.5mm THHN stranded wire and 15mm PVC are the minimums to be used. Lighting, convenience outlets, AC units, a refrigerator and range are included in the load schedule totaling 25,517 watts. Installation, testing and warranty standards are also outlined.

Uploaded by

Pocholo Severo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

GENERAL NOTES SCHEDULE OF LOADS ( PB ) ELECTRICAL

ALL ELECTRICAL WORKS HEREIN SHALL COMPLY WITH THE LATEST EDITION OF PHILIPPINE ELECTRICAL CODE THE RULES AND REGULATIONS OF THE
CKT. UNIT BRANCH AMPHERE SIZE OF WIRE SIZE OF CONDUIT
LOCAL UTILITY COMPANY AND THE LAWS AND ORDINANCES OF THE LOCAL ENFORCING AUTHORITIES CONCERNED. THE ELECTRICAL WORKS D E S C R I P T I O N QTY. LOAD (W) PROTECTION
SHALL BE UNDER THE IMMEDIATE SUPERVISION OF A COMPETENT, DULY LICENSED ELECTRICAL ENGINEER COMPLYING TO THE PSPC SAFETY
No. LOAD (A) ( THHN ) ( PVC )
STANDARDS.
01 10 - 100W LIGHTING OUTLET 100 10 1000 4.35 15 A 2 - 3.5 mm 2 15 mm DIA.
POWER SERVICE ENTRANCE VOTAGE SHALL BE 230 V, 60Hz, 1 - PHASE.
02 10 - 100W LIGHTING OUTLET 100 10 1000 4.35 15 A 2 - 3.5 mm 2 15 mm DIA.
MINIMUM SIZE OF CONDUCTOR AND CONDUIT TO BE USED SHALL BE 3.5mm TYPE THW / THHN, STRANDED AND 15mm NOMINAL DIAMETER, PVC 03 10 - 100W LIGHTING OUTLET 100 10 1000 4.35 15 A 2 - 3.5 mm 2 15 mm DIA.
MOLDFLEX PIPES RESPECTIVELY.
04 8 - 100W LIGHTING OUTLET 100 8 800 3.48 15 A 2 - 3.5 mm 2 15 mm DIA.
ALL PIPES SLEEVES SHALL BE PROVIDED WITH PROPER SUPPORT OR ANCHORAGE NECESSARY FOR PERMANENT CONNECTIONS WITH CONCRETE
WALLING AND BEAMS. 05 8 - 100W LIGHTING OUTLET 100 8 800 3.48 15 A 2 - 3.5 mm 2 15 mm DIA.

ALL SERVICE ENTRANCE EQUIPMENT, SWITCHES, PANEL BOARDS, LIGHTING FIXTURES AND ALL NON-CURRENT CARRYING METAL PARTS SHALL BE 06 8 - 100W LIGHTING OUTLET 100 8 800 3.48 15 A 2 - 3.5 mm 2 15 mm DIA.
PROPERLY GROUNDED IN ACCORDANCE TO THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE. 07 6 - 100W LIGHTING OUTLET 100 6 600 2.61 15 A 2 - 3.5 mm 2 15 mm DIA.
SERVICE ENTRANCE CONDUIT AND FEEDER LINES SHALL BE IN NELTEX CONDUIT AND SHALL BE A MINIMUM OF 1-1/2" dia. CONDUIT (OR LARGER 08 180W CONVENIENCE OUTLET 180 8 2880 12.52 20 A 2 - 3.5 mm 2 15 mm DIA.
AS THE LOAD MAY REQUIRED).
09 180W CONVENIENCE OUTLET 180 8 2880 12.52 20 A 2 - 3.5 mm 2 15 mm DIA.
NO BRANCH CIRCUIT, POWER AND SPECIAL OUTLETS SHALL HAVE A LOAD MORE THAN 80% OF ITS RATING.
10 180W CONVENIENCE OUTLET 180 2 720 3.13 20 A 2 - 3.5 mm 2 15 mm DIA.
GENERAL NOTES. LEGEND. COMPUTATIONS

UNLESS OTHERWISE SPECIFIED PULL BOXES OR JUNCTION BOXES SHALL BE PROVIDED WHENEVER REQUIRED AND NECESSARY, ALL THOUGH SUCH
11 1.0 HP SPLIT TYPE AC UNIT 1118.55 01 1118.55 6.08 30 A 2 - 5.5 mm 2 25 mm DIA.
BOXES ARE NOT INCATED ON PLANS.
12 1.0 HP SPLIT TYPE AC UNIT 1118.55 01 1118.55 6.08 30 A 2 - 5.5 mm 2 25 mm DIA.
ALL MATERIALS TO BE USED AND EQUIPMENT TO BE INSTALLED SHALL BE BRAND NEW, AND MUST BE OF THE APPROVED TYPE AND MODEL. ALL
DISCREPANCY IN LOCATIONS AND RATINGS OF EQUIPMENTS AND APPARATUS SHALL BE VERIFIED WITH THE OWNER OR HIS REPRESENTATIVES AND 13 REFRIGERATOR 1800 01 1800 7.83 30 A 2 - 5.5 mm 2 25 mm DIA.
THEN CHANGES SHALL BE MADE ACCORDINGLY.
14 RANGE (6.0 kW) 6000 01 6000 26.09 30 A 2 - 5.5 mm 2 25 mm DIA.
SPECIAL PURPOSE OUTLET, WEATHER PROOF, SHALL BE RATED 20A, OR 30A OR AS REQUIRED, SINGLE RECEPTACLE, GROUNDING TYPE. SPARE
15 1500 01 1500 6.52 30 A 2 - 5.5 mm 2 25 mm DIA.
THE CONTRACTOR SHALL GUARANTEE THAT ALL ELECTRICAL AND AUXILLARY WORKS ARE FREE FROM ALL FORMS OF DEFECTS IN MATERIAL AND 16 SPARE 1500 01 1500 6.52 30 A 2 - 5.5 mm 2 25 mm DIA.
WORKMANSHIP FOR A MINIMUM PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE ANY DEFECTS ARISING FROM THE CONTRACTORS
WORK SHALL BE REMINDED AT THE CONTRACTORS EXPENSE. T O T A L 25,517.10 WATTS

THE MINIMUM BURIAL DEPTHS OF DIRECT BURIAL CABLES OR EQUIVALENT CONDUIT RUN SHALL BE OF MINIMUM 600mm.
MOUNTING HEIGHTS :
LOAD COMPUTATIONS (PB)
A. KILOWATT HOUR METER - 1600mm ABOVE FLOOR FINISH
B. PANEL BOARD - 1600mm ABOVE FLOOR FINISH
C. SWITCHES - 1400mm ABOVE FLOOR FINISH
OTHERWISE REQUIRED BY FIELD CONDITION
I = W ( D.F ) POWER ENTRY
FROM SOURCE 230 V. 60 HZ
D. CONVENIENCE OUTLET - 300mm ABOVE FLOOR FINISH V
E. TABLE HEIGHT OUTLET - 1000mm ABOVE FLOOR FINISH
F. SPECIAL PURPOSE OUTLET
G. AIR CONDITION OUTLET
- 300mm ABOVE FLOOR FINISH
- 1800mm ABOVE FLOOR FINISH
I = 25,517.10 W ( 80 % DEMAND FACTOR )= 88.76 AMPERES
M
OTHERWISE REQUIRED BY FIELD CONDITION
230 V
PROTECTION
USE : 125 A, 2PST, MAIN CITCUIT BREAKER 2-50 mm 2 THHN ON
50 mm Ø RSC PIPE
6"Ø CIRCULAR DOWNLIGHT 3 watts GARDEN LIGHTS 125A, 2PST
6" USE 10 watts DAYLIGHT GL
USE: WARM LIGHT CONDUCTION
3 watts SWIMMING POOL LIGHTS 15 A 15 A
SPL
USE: WARM LIGHT USE: 2 - 50 MM. THHN STRANDED SERVICE ENTRY WIRE LIGHTING OUTLET 01 02 LIGHTING OUTLET
LED PINLIGHT
USE 5 watts LED PINLIGHT WARM WHITE SL
3 watts STAIR LIGHTS
USE: WARM LIGHT
ON 50 MM. Ø RIGID STEEL CONDUIT PIPE 15 A 15 A

RECESSED SINGLE DIRECTIONAL PINLIGHT 1 LIGHTING OUTLET 03 04 LIGHTING OUTLET


PB CIRCUIT HOME RUN 15 A 15 A
USE: 5 watts LED PINLIGHT
LIGHTING OUTLET 05 06 LIGHTING OUTLET
POWER/LIGHTING CIRCUIT LINE
RECESSED MULTIPLE DIRECTIONAL PINLIGHT 15 A 15 A
USE: 5 watts LED PINLIGHT LIGHTING OUTLET 07 08 CONVENIENCE
AIR CONDITION UNIT 15 A 15 A
OUTLET
A.C.U.
CONVENIENCE SPLIT TYPE CONVENIENCE 09
15 watts LED STRIP LIGHT
10 CONVENIENCE
for COVELIGHTING;USE WARM WHITE OUTLET 30 A 30 A OUTLET
REFRIGERATOR OUTLET ACU (1.0 HP)
REF 11 12 ACU (1.0 HP)
30 A 30 A
28 watts T5 FLUORESCENT BULBS;
USE DAY LIGHT RANGE OUTLET REFRIGERATOR 13 14 RANGE
RANGE 30 A 30 A
3 watts WALL LAMP
USE: WARM LIGHT
SPARE 15 16 SPARE

UP LIGHT
OVEN
OVEN OUTLET
MOUNTING HEIGHTS
UL
USE: WARM LIGHT
BD
BLOW DRYER
KILOWATTHOUR METER FROM CENTER OF DEVICE TO FINISH FLOOR LEVEL.
PB
18OO MM
PANELBOARD (VERIFY SIZE OF PANEL BOARD.)
UDL UP & DOWN LIGHT
USE: WARM LIGHT MULTI POINT WATER HEATER
WH
CONVENIENCE OUTLET
UNIVERSAL DUPLEX TELEPHONE OUTLET 4OO MM FROM CENTER OF DEVICE TO FINISH FLOOR LEVEL.
DECORATIVE LIGHT
CONVENIENCE OUTLET

30 watts FLOOD LIGHT


USE: DAY LIGHT LED
PANEL BOARD
EMERGENCY PANEL BOARD
WALL SWITCHES 15OO MM FROM CENTER OF DEVICE TO FINISH FLOOR LEVEL.
GALANG RESIDENCE
PB-1
EMERGENCY LIGHT 2300 MM FROM CENTER OF DEVICE TO FINISH FLOOR LEVEL.
TV OUTLET VARIES VERIFY WITH ARCHITECT RISER DIAGRAM
NOT TO SCALE

REPUBLIC ACT 8293


"INTELLECTUAL PROPERTY LAW" REPUBLIC ACT 9266
architect: PROJECT TITLE: OWNER: CONTENTS: SHEET NO:
Section 186 "ARCHITECTURE LAW OF THE
work of architecture - copyright in a PHILIPPINES" 1 GENERAL NOTES
work of architecture shall include the

E-2
Article 2 Section 25 (4)
right to control direction of any
building which reproduces the whole or
a substantial part of the work either in
drawing and specification duly signed,
stamp and sealed as instruments of -PROPOSED- MR. & MRS. GALANG 2
LAYOUT PLAN
LEGENDS
its original form recognizably derived
from the original.
service are the properties and
documents of the architect, whether AR. GINO VINCENT M. DIONGZON 3 MOUNTING HEIGHTS
PRESIDENTIAL DECREE No. 49
"PROTECTION OF INTELLECTUAL
the object for which they are made is
executed or not. it shall be unlawful
for any person, without the consent of
2-STOREY RESIDENCE W/ MEZZANINE OWNER'S APPROVAL:
4 SCHEDULE OF LOADS

2
PROPERTY" the architect or author of the said
NOVEMBER 14, 1972 documents or to make copies of said 5 COMPUTATIONS
works of art, architecture, models and documents for use in the repetition of
designs are creative work and considered and for other projects or building, REG. NO. 39491 PTR. NO. 3743498 LOCATION: PUROK 6, GAPAN CITY, NUEVA ECIJA 6 RISER DIAGRAM
as part of the intellectual property of whether executed partly or in whole.
the author duly protected under pd 49. TIN. 483-945-169-000 DATE ISS. 01-07-2021 SIGNATURE 7