0% found this document useful (0 votes)
85 views1 page

Stack Monitoring II

The report details stack emission monitoring conducted by M/s Kribhco Infrastructure Pvt. Ltd. at a DG Set area in Govindpuri, Haryana, from October 14 to October 19, 2022. The analysis included measurements of particulate matter, nitrogen dioxide, total hydrocarbons, carbon monoxide, and sulfur dioxide, all of which were within acceptable limits. The sampling was performed under calibrated conditions with clear meteorological conditions.

Uploaded by

Kushal Sharma
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
85 views1 page

Stack Monitoring II

The report details stack emission monitoring conducted by M/s Kribhco Infrastructure Pvt. Ltd. at a DG Set area in Govindpuri, Haryana, from October 14 to October 19, 2022. The analysis included measurements of particulate matter, nitrogen dioxide, total hydrocarbons, carbon monoxide, and sulfur dioxide, all of which were within acceptable limits. The sampling was performed under calibrated conditions with clear meteorological conditions.

Uploaded by

Kushal Sharma
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 1

Sample Number: DIG/KIPL/ST/01 Report No.

: DIG/ST/2210/14/001
Name & address of the M/s Kribhco Infrastructure Pvt. Ltd. Format No.: 7.8 F-03
Project: Village- Govindpuri, Riwari, (Harayana) Party Reference No.: NIL
Reporting Date: 19/10/2022
Period of Analysis: 14/10/2022 to 19/10/2022
Receipt Date: 14/10/2022

Sample Description : Stack Emission Monitoring

General Information
Sampling Location : DG Set Area (DG Set No.-01)
Sample Collected by : Sant Kumar (Field Analyst)
Date of Sampling : 12/10/2022
Sampling Duration (Minutes) : 40
Stack attached to : DG Set (250 KVA)
Make of stack : Metal
Diameter of stack (m) : 0.27 meter
Height of stack (m) : 2.0 meter
Instruments calibration status : Calibrated
Meteorological Condition : Clear Sky
Ambient Temperature – Ta (°C) : 27.0
Temperature of stack Gases – Ts (°C) : 134.0
Velocity of stack Gases (m/sec.) : 7.28
Flow rate of PM (LPM) : 26.0
Flow rate of Gas (LPM) : 2.0
Sampling condition : Isokinetic
Protocol used : IS :11255

RESULTS
S. No. Parameter Protocol Result Unit Limits
(As Per CPCB)
1. Particulate Matter (PM) IS 11255 (P-1), Gravimetric Method RA:2003 0.055 gm/Kw-hr ≤0.2
2. Nitrogen Dioxide (as NO2) IS 11255 (P-7), Colorimetric Method, RA:2012 1.06 gm/Kw-hr
≤4.0
3. Total Hydrocarbon (as HC) By Gas Chromatography Method 0.51 gm/Kw-hr
4. Carbon Monoxide (as CO) SOP, SP-74, Issue No.01:2018 0.35 gm/Kw-hr ≤3.5
5. Sulphur Dioxide (as SO2) IS 11255 (P-2), Titrimetric Method RA:2003 0.42 gm/Kw-hr --
**End of the Report**