Sample Number:                     DIG/KIPL/ST/01                                  Report No.
:             DIG/ST/2210/14/001
 Name & address of the              M/s Kribhco Infrastructure Pvt. Ltd.            Format No.:             7.8 F-03
 Project:                           Village- Govindpuri, Riwari, (Harayana)         Party Reference No.:    NIL
                                                                                    Reporting Date:         19/10/2022
                                                                                    Period of Analysis:     14/10/2022 to 19/10/2022
                                                                                    Receipt Date:           14/10/2022
  Sample Description :               Stack Emission Monitoring
                General Information
                Sampling Location                                     :    DG Set Area (DG Set No.-01)
                Sample Collected by                                   :    Sant Kumar (Field Analyst)
                Date of Sampling                                      :    12/10/2022
                Sampling Duration (Minutes)                           :    40
                Stack attached to                                     :    DG Set (250 KVA)
                Make of stack                                         :    Metal
                Diameter of stack (m)                                 :    0.27 meter
                Height of stack (m)                                   :    2.0 meter
                Instruments calibration status                        :    Calibrated
                Meteorological Condition                              :    Clear Sky
                Ambient Temperature – Ta (°C)                         :    27.0
                Temperature of stack Gases – Ts (°C)                  :    134.0
                Velocity of stack Gases (m/sec.)                      :    7.28
                Flow rate of PM (LPM)                                 :    26.0
                Flow rate of Gas (LPM)                                :    2.0
                Sampling condition                                    :    Isokinetic
                Protocol used                                         :    IS :11255
                                                                RESULTS
S. No.             Parameter                                 Protocol                         Result           Unit             Limits
                                                                                                                            (As Per CPCB)
    1.   Particulate Matter (PM)             IS 11255 (P-1), Gravimetric Method RA:2003       0.055          gm/Kw-hr            ≤0.2
    2.   Nitrogen Dioxide (as NO2)          IS 11255 (P-7), Colorimetric Method, RA:2012       1.06          gm/Kw-hr
                                                                                                                                  ≤4.0
    3.   Total Hydrocarbon (as HC)                 By Gas Chromatography Method                0.51          gm/Kw-hr
    4.   Carbon Monoxide (as CO)                    SOP, SP-74, Issue No.01:2018               0.35          gm/Kw-hr             ≤3.5
    5.   Sulphur Dioxide (as SO2)             IS 11255 (P-2), Titrimetric Method RA:2003       0.42          gm/Kw-hr              --
                                                          **End of the Report**
                  (Checked By)                                                                           (Approved By)