L&W Iaq Sensor - TDS

The document is a technical submittal for an Indoor Air Quality (IAQ) Sensor proposed by Blue Engineers for the L&W Bangalore project, with Honeywell as the selected manufacturer. It includes details on the sensor's specifications, features, and compatibility, along with submission dates and client information. The lead time for the product is estimated at 1-2 weeks.

Uploaded by

bewaha7743
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
26 views3 pages

L&W Iaq Sensor - TDS

The document is a technical submittal for an Indoor Air Quality (IAQ) Sensor proposed by Blue Engineers for the L&W Bangalore project, with Honeywell as the selected manufacturer. It includes details on the sensor's specifications, features, and compatibility, along with submission dates and client information. The lead time for the product is estimated at 1-2 weeks.

Uploaded by

bewaha7743
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Material Technical Submittal

Project Name L&W BANGALORE

Client L&W

HVAC Contractor Blue Engineers

Date of Submission 07-12-2023

Item Description IAQ SENSOR

Approved Makes AIE TECH/HONEYWELL

Proposed make HONEYWELL

Technical details As per Technical Annexure & Manufacturer Catalogue

Quantity and Size As per Approved Shop Drawing

Location of use As per Approved Shop Drawing

Lead time 1-2 Weeks

Remarks

Comments

For Blue Engineers ELECTRO CONSULTANTS

APV APV
AWC AWC
RST RST
REJ REJ
APV-Approved / AWC - Approved With Comments/ RST - Resubmit/ REJ - Rejected
Indoor Air Quality
Monitor
Honeywell Indoor Air Quality Monitor is advanced with
modular architecture design and configured with a
comprehensive array of multi-sensors to measure various
air quality parameters viz. Particulate Matter (PM2.5
and PM10), Carbon Dioxide (CO2), Total Volatile Organic
Compound (TVOC), Temperature (T), and Relative humidity
(Rh) in a single device.
The indoor air quality monitor uses an ‘active suction method’,
draws ‘air sample’ which enables laminar flow across the
array of sensors for better accuracy. The device is BMS
Compatible via RS-485 port using MODBUS protocol.
The indoor air quality monitor is pre-configurable with
optional sensors viz. Formaldehyde (HCHO), Ozone (O3)*,
NOx*, and SOx* apart from the standard configuration.
It is suitable for intelligent buildings and systems, air quality
data collection systems, green building evaluation systems,
and ventilation systems.
*Future release

FEATURES AND BENEFITS

Wide array of Modular Active sampling Advanced Large 3.5” TFT AQI parameter BMS
configurable architecture: with ‘Maglev’ fan Honeywell touchscreen display on compatible
hi-accuracy ‘5+2’ for for climate and particulate sensor. for clear visual screen
sensors optional gas sensors laser-based indication
configuration light scattering
particle sensing

PART NUMBER DESCRIPTION


H D 2 0 0 M H 1 W 0

Development Sequence
H Series 0 - 2021:Release-1
Colour
Display W - White
D - 3.5” TFT B - Black
N - No Display
Power Adaptor
Combination 0 - Without adaptor
2 -Temp, RH, PM2.5, TVOC, CO2 1 - With adaptor*
Certificate
H - RoHS
Optional sensor config
0 - No Sensor Communication
H - Formaldehyde M - MODBUS; RS-485
Z - Ozone
(* For Indian market only)
PRODUCT SPECIFICATION SENSOR SPECIFICATION - OPTIONAL
DETAIL SPECIFICATION PARAMETER DETAIL SPECIFICATION
5 in one standard sensor: Temperature , Relative humidity Sensor output resolution 100 ppb
(Rh.), Particulate Matter (PM2.5 and PM10), Total Volatile Measuring range 0 - 50,000 ppb
Organic Compound (TVOC), Carbon Dioxide (C02) Formaldehyde
Detection parameter Accuracy ± 15% full scale
(HCHO)
2 customer selectable optional sensors: Formaldehyde Performance check and re-
(HCHO), Ozone (O3)*, NOx*,and SOx* Yes / Replacement kit
calibration
Display Model: 3.5” Colour TFT touchscreen Sensor output resolution 1 ppb
Display
Non-Display Model: LED Indicators
Measuring range 0 to 1000 ppb
IAQ monitor power supply 12 VDC O3 (MEMS)* Accuracy ±1% full scale
Operating temperature 0 to 70 °C (32 to 158 °F)
Performance check and re-
Humidity 0 to 90% Rh. (Non-condensing) Yes / Replacement kit
calibration
Storage condition -10 to 50 °C (14 to 122 °F) Notes:
• Sensors specifications, accuracies are as per standard test procedures in lab conditions.
Output RS-485/RTU (MODBUS) The test conditions for each of the native sensors could vary depending on the type of
Without rear mounting plate: 160 mm × 160 mm × 55 mm native sensor.
Dimensions • PM Sensors are tested and calibrated with a smoke & dust mix in a proportion.
Mounting plate: 130 mm × 140 mm × 2.5 mm • For customized applications in specific or varying indoor environments, buyers are
Net weight 520 gms. (1.15 lbs.) required to provide corresponding end conditions for such specific calibrations.

Enclosure and IP level Polycarbonate (RoHS), IP20 MEASUREMENTS AND DIMENSIONS


Display Model: Air quality index value and status are
displayed on the touchscreen.
Air quality index (AQI) Non-Display Model: Air quality index status is indicated
using a LED {Green (Good), Yellow (Moderate), and Red
(Unhealthy)}.

SENSOR SPECIFICATION - BASE PACKAGE 117 mm 160 mm


PARAMETER DETAIL SPECIFICATION
Sensor output resolution 0.1 ⁰C
Measuring range -10 to 70 ⁰C
Temperature
Accuracy ± 0.3 ⁰C
160 mm
Performance check and re-calibration Yes / Replacement kit
Sensor output resolution ±2 %
Measuring range Upto 100 % 55 mm
Relative Humidity
Accuracy ±3%
Performance check and re-calibration Yes / Replacement kit
Sensor output resolution 5 μg/m³ MOUNTING
Measuring range 0-45000 μg/m³ WALL / CEILING
TVOC
Accuracy ±1 % full scale
Performance check and re-calibration Auto-calibration
Sensor output resolution 1 ppm
Measuring range up to 5000 ppm
CO2 (NDIR)
Accuracy ±1% full scale
SCREW
Performance check and re-calibration Auto-calibration
Sampling Type Active airflow
Sensor output resolution 1 μg/m3 BACKPLATE

PM2.5 and PM10 Measuring range 0 to 1000 μg/m3


INDOOR AIR QUALITY SENSOR
Accuracy ±5% full scale
Performance check and re-calibration Yes / Replacement kit

By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify
Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.

For more information,


www.honeywellbuildings.in,
Call: 000-8000-502167,
Email: HBT-Indiabuildings@honeywell.com 31-00510 | Rev. 01 | 01/22