gp030202 Com
gp030202 Com
Scope
[I] This Global Practice (GP) covers the design and installation of fire-fighting foam systems using high
or low back-pressure foam makers, for use with fixed roof tanks operating at approximately atmospheric
pressure (not exceeding 21/2 psig [17 kPag]) or with annular pontoon or double deck open-top floating
roof tanks. The systems also are applicable to tanks furnished with internal floating roofs or covers.
Copyright 2012r
ExxonMobil Development Company and ExxonMobil Pipeline Company hereby license the use of ExxonMobil Engineering Practices System (EMEPS) Global Practices (GPs) for
use by any ExxonMobil division, subsidiary, or more-than-50%-owned affiliate. The GPs may be downloaded and modified as necessary for project and affiliate use. Written
permission from ExxonMobil Development Company or ExxonMobil Pipeline Company is not required. However, any modified GPs must be renumbered to a project-specific or
affiliate-specific number to distinguish them from the GPs on the EMEPS web site. ExxonMobil operated joint ventures may utilize GPs to create project-specific or location-specific
specifications. It is the responsibility of individual affiliate or joint venture to ensure that the use of GPs and their derivatives is limited to joint venture related business and not
disclosed or used outside the JV without appropriate EM management approval.
GP 03-02-02 Foam Systems for Storage Tanks June 2012
Table of Contents
Table of Figures............................................................................................................. 3
1. Required References.............................................................................................4
1.1. Global Practices–ExxonMobil Engineering Practices....................................4
1.2. NFPA–National Fire Protection Association..................................................4
2. Materials................................................................................................................. 4
3. Design..................................................................................................................... 5
Record of Change........................................................................................................ 19
Table of Figures
Figure 3: Single Foam Outlet Station Layout of Foam Outlet Assembly and
Solution Piping (Schematic and Detailed)................................................14
Figure 4: Multiple Foam Outlet Locations Tanks over 75 ft Diameter Typical Layout of
Foam Outlets and Solution Piping (Schematic)............................................16
1. Required References
This Section lists the Practices, codes, standards, specifications, and publications that shall be used with
this document. Unless otherwise specified herein, use the latest edition.
2. Materials
1) [*] [A] Piping for risers, laterals, and distribution systems shall be carbon steel, Sch. 40 minimum
wall thickness, galvanized or lined with a heat-cured epoxy or phenolic-epoxy system with a
minimum dry film thickness of 8 mils (200 m). The Owner's Engineer shall approve use of unlined
pipe.
2) [S] Foam chambers, outlet assemblies, and deflectors shall be carbon steel, galvanized or epoxy lined.
Foam dams shall be fabricated from carbon steel. Pipe carrying foam concentrate shall not be
galvanized.
3) [S] Foam backboards shall be the same material specification and grade as the shell plate to which
they are attached.
4) [S] Frangible diaphragms, incorporated in the seal chamber of foam chambers, shall be 14 oz (0.061
in. [1.5 mm]) thick common soda lime glass, scored to facilitate breakage under foam pressure.
5) [S] Screening, installed at the foam deflector or air entry ports of foam makers, shall be 2 x 2 mesh
with 0.46 in. (12 mm) nominal opening.
3. Design
1) [S] Lateral terminal connection:
a) Laterals shall terminate outside the dike and on the roadside of all pipelines and drainage ditches.
b) The terminal connections shall be located in relation to fire hydrants such that the total length of
hose from the hydrant to fire truck does not exceed 25 ft (7.5 m), and the distance from the fire
truck to foam lateral terminals does not exceed 50 ft (15 m). The terminal connections shall be
located in at least one vessel diameter or 100 ft (30 m), but in no case less than 50 ft (15 m) from
the tank being protected, with a block valve, a check valve, and a 21/2 NPS (65 mm) hose
connection fitted with a pressure tight cap and a vent valve.
c) Terminal connections shall be from 2 ft to 4 ft (600 mm to 1200 mm) above grade and shall be
protected against collision. Where systems are located within 3 ft (1 m) of roadways or
accessways, in areas of high vehicular traffic, the systems shall be protected by concrete-filled
guards. Guards shall be NPS 4 (100 mm) Sch. 40 pipe, filed with concrete, and set in concrete
foundation.
d) A sign shall be installed at each lateral termination point to identify the tank served.
2) [S] Fire hose coupling type at terminal connections and at foam outlet stations shall be specified. In
some locations, the plant fire departments will provide the actual fire hose couplings.
3) [S] Coupling thread type shall be suitable for use with Owner's fire-fighting equipment. Couplings
shall be provided with dust caps or plugs.
4) [S] For tanks requiring multiple laterals, up to two laterals can be brought to a single location 4 ft
(1200 mm) apart. However, not more than two laterals from any one tank shall be brought to the
same location.
5) [S] The lateral terminals shall be located on the side of the tank lot that most directly faces the
prevailing wind, if any, consistent with good access.
6) [S] The terminal connections on foam makers shall be as follows:
a) Laterals to single foam outlets up to 250 gpm (0.95 m3/min) capacity shall terminate in one NPS
21/2 (65 mm) size mating hose coupling.
b) Laterals to single foam outlets greater than 250 gpm (0.95 m3/min) capacity or to multiple foam
outlets shall terminate in one NPS 21/2 (65 mm) size mating hose coupling for every 250 gpm
(0.95 m3/min) of lateral capacity or part thereof.
7) [S] The riser pipe size from the foam maker to the foam chamber shall be determined by hydraulic
calculation, but shall not be smaller than the foam chamber inlet flange size.
8) [S] Riser supports shall be 1/2 in. (12 mm) thick plate, 12 in. (300 mm) length, with the width
depending on riser dimension, but selected to maintain the riser a minimum of 4 in. (100 mm) clear
from the tank shell. Installation shall be as follows:
a) Each support shall be located on about 8 ft (2.4 m) centers and placed perpendicular to the tank
shell and centered on the riser pipe.
b) The edges of the plate shall be continuously welded on all sides to both tank shell and pipe with
1
/4 in. (6 mm) fillet welds to support the shell in event of a fire.
9) [S] Foam lateral size shall be determined by hydraulic calculation, but shall not be less than NPS 2 1/2
(65 mm) size. Laterals shall be installed as follows:
a) Slope continuously toward the termination point outside the dike. If this is impractical, a
(normally closed) NPS 3/4 (20 mm) drain valve shall be provided at the low point.
b) Not run through the dike area of any other tank, group of tanks, or paired tanks. However, piping
within a group of tanks may cross intermediate toe walls within that group.
c) Maintain a minimum elevation of 1 ft (300 mm) above finished grade.
10) [S] The ratio of the strainer's open basket area to its inlet pipe area shall be at least 10:1. The net
open area of the strainer shall be at least four times the area of the suction piping.
RFCH © ExxonMobil 2012 Version 3.1.0
11) [S] Underground carbon steel piping, and portions of aboveground carbon steel piping, that pass
through a dike or pipe sleeve shall be protected against external corrosion using a Single Coat-Single
Wrap or Double Coat-Double Wrap protective coating system.
12) [S] Permanent connections between the fire water system and any process system shall be prohibited.
< 20 <6 0
20 to 80 6 to 24 1
> 80 to 110 > 24 to 33 2
> 110 to 130 > 33 to 40 3
> 130 to 150 > 40 to 46 4
> 150 to 170 > 46 to 52 5
> 170 to 190 > 52 to 58 6
c) Tanks with a fixed roof and no internal floating cover or roof shall be designed such that the foam
chambers shall be shell mounted per Figure 1.
d) Tanks with a fixed roof and an internal floating cover or roof shall be designed such that the foam
chamber shall be tank-shell mounted per Table 1, provided the deflector does not interfere with
the specified upper travel limit of the internal floating cover or roof. Shell extension mounted per
Figure 2 is permitted for retrofits.
e) Exception 1: Fixed roof tanks shall meet the requirements for open-top floating roof tanks, per
Section 5, when the construction meets both the following conditions:
i) Provided with an internal floating roof that is either a pontoon-type floating roof or double
deck design floating roof.
ii) The fixed roof is aluminum, fiberglass, or other lightweight geodesic dome or external cone
roof.
f) Exception 2: The tank is provided with a SHE Critical nitrogen blanketing system.
RFCH © ExxonMobil 2012 Version 3.1.0
2) [S] Water-soluble flammable liquids: the Owner's Engineer and the plant Fire Chief shall specify the
need for foam chambers and the applicable details of design and installation.
3) [S] When multiple foam chambers are required, they shall be equally spaced around the tank.
Figure 3: Single Foam Outlet Station Layout of Foam Outlet Assembly and
Solution Piping (Schematic and Detailed)
3) [S] For open-top floating roof tanks larger than 75 ft (22.5 m) diameter, one foam station shall be
installed for each 80 ft (24 m), and fraction thereof, of tank circumference, equally spaced around the
circumference per Figure 4.
4) [S] [A] The foam outlet assembly, consisting of a foam maker, foam deflector, and mounting
assembly, shall be National Foam Systems, Inc., Type MBS-9SA/MCS-9FR or Company-approved
equivalent. The foam maker shall be furnished with an orifice diameter of 0.65 in. (16.5 mm). The
foam maker air entry ports and the foam deflector shall be provided with a bird screen per Section 2,
Item (5). See Section 4, Item (4c) for address of National Foam Systems.
5) [S] A single foam riser shall be used to deliver foam solution to the foam outlets. When multiple
foam outlets are installed, the distribution piping to individual outlets shall be located on top of the
wind girder to be accessible for inspection.
6) [S] The foam system including the lateral, riser, and distribution piping shall be sized to deliver 60
gpm (0.23 m3/min) foam solution to each foam maker inlet at a pressure of 60 psig (414 kPag), based
on a foam proportioning truck discharge pressure of 100 psig (700 kPag).
7) [S] Foam backboards and foam dams shall be designed for wind pressure. (Design wind velocity
shall be specified by the Owner's Engineer.) Foam dam bracing shall be on the outside of the dam,
away from the foam, so as not to impede the flow of foam. The foam dam shall extend completely
around the roof, and, except for drain slots per Figure 3, shall be continuously seal welded to the roof
for the full length of the dam.
8) [S] Foam backboards mounting and minimum dimensions shall comply with the following:
a) Foam backboards shall be mounted flush with the inside diameter (ID) of the shell.
b) The backboard shall be minimum height, but sufficient to have the foam deflector clear the
maximum travel of the roof seal weather shield and other protruding parts at the uppermost
position of the roof.
c) [A] The width of the backboard shall be 10 ft (3000 mm) minimum, unless otherwise dictated by
unusual wind conditions or experience at the plant location. The Owner's Engineer shall approve
deviation from this minimum width.
9) [S] Guard railings per GP 09-07-01 shall be installed on wind girders of open-top floating roof tanks,
completely around the tank, when one or more foam outlet stations are installed.
iii) Open-top floating roof tanks with multiple foam outlet system: Coverage of the complete
seal area shall be achieved within 10 minutes of application time.
2) [S] New and/or retrofitted foam systems shall be tested in accordance with NFPA 11 requirements
and the minimum testing requirements outlined above as part of the acceptance procedures.
Record of Change
Version 1.0.0 Date: 01/02
Location Action Description
Initial Publish.
Section 3, Item Modification Modified Rationale to include preventing a spill fire "at one tank" from
(8b) damaging the foam laterals of other tanks.
Section 3, Item Modification Modified Rationale to specify "safely" hooking up hoses to laterals.
(8c)
Section 3, Item Addition Added requirement that "The ratio of the strainer's open basket area to its
9 pipe area shall be at least 10:1. The net open area of the strainer shall be
at least four times the area of the suction piping."
Section 3, Item Modification Changed from 3.9. Modified to read "Underground carbon steel piping
(10) and portions of above ground carbon steel piping that pass through a dike
or pipe sleeve shall be protected against external corrosion using a Single
Coat Single Wrap or Double Coat Double Wrap protective coating
system."
Section 3, Item Modification Changed from 3.9. Modified Rationale to include "These portions can
(10) experience severe corrosion if not protected as described."
Section 3, Item Addition Added, "Permanent connections between the fire water system and any
(11) process system shall be prohibited" to prevent contamination of fire
water with process fluids.
Section 4, Item Modification Consolidated criteria for specifying fixed fire protection by incorporating
(1) information from former 5.10 and added provision to exclude internal
floating roof tanks with nitrogen blanketing from requiring foam systems
unless required by local codes. The nitrogen system should be "safety
critical."
Section 4, Item Modification Modified Rationale to note that foam concentrates for alcohol type fires
(2) "are often alcohol type specific."
Section 4, Item Modification Modified Rationale to include use of screens to prevent debris from
(4c) plugging the system.
Section 5, Item Modification Relocated the Note in Section 5, Item (2) to the Section 5, Item (2)
(2) Rationale.
Section 5, Item Modification Added a reference to GP 09-07-01 for guard railings.
(9)
Section 5, Item Deleted Deleted Section 5, Item (10). See Section 4, Item (1).
(10)
Section 6, Item Modification Added the plant Fire Chief's approval to acceptance testing.
(1)
Section 6, Item Modification Clarified the test requirements for foam systems.
(1a)
Section 6, Item Modification Modified Rationale to specify that these are the minimum requirements.
(1b)
General Modification Added references to NFPA 11 and NFPA 30 in Rationale. Removed
Pipelines from GP.