0% found this document useful (0 votes)
67 views8 pages

Prosense Psd25 Installation

The document provides installation instructions for the PSD25-0P-xxxxH electronic pressure sensor, detailing safety precautions, operational features, and technical specifications. It includes guidelines for electrical connections, mounting, and setting the device, emphasizing the importance of adhering to the specified parameters to avoid damage or injury. Additionally, it outlines the sensor's operational capabilities, including pressure detection and output switching based on set values.

Uploaded by

Dương Nguyen
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
67 views8 pages

Prosense Psd25 Installation

The document provides installation instructions for the PSD25-0P-xxxxH electronic pressure sensor, detailing safety precautions, operational features, and technical specifications. It includes guidelines for electrical connections, mounting, and setting the device, emphasizing the importance of adhering to the specified parameters to avoid damage or injury. Additionally, it outlines the sensor's operational capabilities, including pressure detection and output switching based on set values.

Uploaded by

Dương Nguyen
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

Installation Instructions

Electronic pressure sensor

PSD25-0P-xxxxH
02 / 2009

Set

Reset
704444 / 00
Contents
Safety instructions ........................................................................... 2
Function and features ...................................................................... 3
Installation ....................................................................................... 4
Electrical connection........................................................................ 4
Setting / Operation........................................................................... 5
Technical data.................................................................................. 6
Scale drawing .................................................................................. 7

Safety instructions
Please read the product description prior to installing the unit. Please check that
the product is suitable for your application without any restrictions.
If the operating instructions or the technical data are not adhered to, personal
injury and/or damage to property may occur.
Please check in all applications that the product materials (see Technical data) are
compatible with the media to be measured.

2
Function and features
The pressure monitor detects the system pressure and switches the two comple-
mentary outputs OUT1 (pin 4) / OUT2 (pin 2):
• In case of increasing pressure OUT1 closes / OUT2 opens when the set Set
value is reached.
• In case of decreasing pressure OUT1 opens / OUT2 closes when the set Reset
value is reached.

Applications (type of pressure: relative pressure)


Permissible
Resetpoint Bursting
Setpoint Scale overload
Order no. Scale pressure
pressure
bar PSI bar PSI bar PSI bar PSI
20 to 290 to 12 to 175 to
PSD25-0P-5800H 600 8700 1600 23200
4000 5800 392 5685
5 to 75 to 3 to 50 to
PSD25-0P-1450H 200 2900 1000 14500
100 1450 98 1420
0.5 to 7.5 to 0.3 to 5 to
PSD25-0P-0145H 25 362 300 4350
10 145 9.8 142
Avoid static and dynamic overpressure exceeding the given over-load
pressure.
Even if the bursting pressure is exceeded only for a short time the unit can
be destroyed (danger of injuries)!

3
Installation
Before mounting and removing the sensor, make sure that no pressure is
applied to the system.
Mount the pressure sensor on a suitable process connection (see type label “Port
Size”). Tightening torque 25 Nm.

Electrical connection
The unit must only be connected by an electrician.
The national and international regulations for the installation of electrical
equipment must be observed.
Voltage supply to EN50178, SELV, PELV.
The device shall be supplied from an isolating source and protected by
an overcurrent device in accordance with UL 248 such that the limited
voltage/current circuit requirements in accordance with UL 508 are met.
Disconnect power before connecting the unit as follows:
1
L+
2

4
4:
2: 3
L

Cable Assembly Wiring Colors:


Pin 1 - Brown
Pin 2 - White
Pin 3 - Blue
Pin 4 - Black
Note: wiring colors are based on AutomationDirect CD12L and CD12M 4-pole cable as-
semblies.

4
Setting / Operation

pnp
9.6 to
1 500mA 2 1 32DCV

pnp
3 4
500mA
Set
2
Reset
5

3 6

4
7

1. locking ring
2. setting rings (manually adjustable after unlocking)
3. LED green: supply voltage O. K.
4. process connection ¼ ” NPT; tightening torque 25 Nm
5. setting marks
6. LED yellow: Set value reached, OUT1 = ON / OUT2 = OFF
7. internal thread M5
• Minimum distance between Set and Reset = 2% of the final value of the
measuring range.
• To obtain the setting accuracy: Set both rings to the minimum value, then set
the requested values.

5
Technical data
Operating voltage [V] ........................................................................................ 9.6 to 32 DC
Current rating [mA] ..........................................................................................................500
Current consumption [mA] ..............................................................................................< 25
Switching frequency [Hz] .................................................................................................100
Setting accuracy [% of the end value of the measuring range] .............. < ± 2.5 / BFSL: 1.5
Repeatability [% of the end value of the measuring range] ....................................... < ± 0.5
Temperature drift [% of the end value of the measuring range/10 °C] ...................... < ± 0.5
in the temperature range [°C] .................................................................................. 0 to +80
Housing material........ PBT (Pocan); PC (Makrolon); FPM (Viton); stainless steel (316S12)
Materials (wetted parts) .................................................................. stainless steel (316S12)
Operating temperature [°C] .................................................................................. -25 to +80
Medium temperature [°C] ..................................................................................... -25 to +80
Storage temperature [°C].................................................................................... -40 to +100
Protection ..................................................................................................................... IP 67
Protection class ..................................................................................................................III
Insulation resistance [MΩ] ........................................................................> 100 (500 V DC)
Shock resistance [g] ............................................................... 50 (DIN / IEC 68-2-27, 11ms)
Vibration resistance [g] ................................................. 20 (DIN / IEC 68-2-6, 10 - 2000 Hz)
EMC
EN 61000-4-2 ESD: .................................................................................... 4 kV / 8 KV AD
EN 61000-4-3 HF radiated: ....................................................................................... 30 V/m
EN 61000-4-4 Burst: ......................................................................................................2 KV
EN 61000-4-6 HF conducted: ........................................................................................ 10 V
BFSL = Best Fit Straight Line

6
Scale drawing

27
M12 x1

70,6
60,6
7,5
13
1 M5
27
1 4" NPT

Dimensions are in millimeters (25.4 mm= 1 inch)


1: process connection 1/4 NPT, tigtening torque 25 Nm