Control Pi
Control Pi
l
tiona
Func cement
n
Enha
The contents of this Technical Information are subject to change without notice.
● Printed manual
Manual Name Manual Number Description
YS1500/YS1700 This manual describes the basic
IM 01B08B02-01EN
Operation Guide operation method.
This manual describes the basic
YS1310 Operation Guide IM 01B08D02-01EN
operation method.
YS1350/YS1360 This manual describes the basic
IM 01B08E02-01EN
Operation Guide operation method.
● Electronic manuals
Manual Name Manual Number Description
YS1500/YS1700
IM 01B08B02-01EN This is identical to the printed manual.
Operation Guide
This manual describes the usage of all
YS1500/YS1700
IM 01B08B02-02EN functions except the programming and
User’s Manual
communication functions.
YS1310
IM 01B08D02-01EN This is identical to the printed manual.
Operation Guide
YS1310 This manual describes the usage of all
IM 01B08D02-02EN
User’s Manual functions except the communication functions.
YS1350/YS1360
IM 01B08E02-01EN This is identical to the printed manual.
Operation Guide
YS1350/YS1360 This manual describes the usage of all
IM 01B08E02-02EN
User’s Manual functions except the communication functions.
This manual describes how to use
YS1000 Series
YS1000 in Ethernet, serial, and DCS-
Communication Interface IM 01B08J02-01EN
LCS communications. For communication
User’s Manual
wiring, see the Operation Guide.
YSS1000 Setting Software/ This manual describes how to use YSS1000
YS1700 Programmable IM 01B08K02-02EN and YS1700’s programmable function and
Function User’s Manual peer-to-peer communication function.
This manual. It describes the compatibility
YS1000 Series
IM 01B08H02-01EN of installation and wiring with YS100, YS80,
Replacement Manual
EBS, I, EK, HOMAC, and 100 line.
User’s manuals for YS1000 are available on the following web site: www.yokogawa.com/
ns/ys/im/
You need Adobe Reader 7.0 or later (but the latest version is recommended) installed on
the computer in order to open and read the manuals.
Notice
● The contents of this manual are subject to change without notice as a result of
continuing improvements to the instrument’s performance and functions.
● Every effort has been made to ensure accuracy in the preparation of this manual.
Should any errors or omissions come to your attention, however, please inform
YOKOGAWA Electric’s sales office or sales representative.
● Under no circumstances may the contents of this manual, in part or in whole, be
transcribed or copied without our permission.
TI 01B08A02-06EN i
Trademarks
● Our product names or brand names mentioned in this manual are the trademarks or
registered trademarks of YOKOGAWA Electric Corporation (hereinafter referred to as
YOKOGAWA).
● Microsoft, MS-DOS, Windows, Windows XP, and Windows NT are either registered
trademarks or trademarks of Microsoft Corporation in the United States and/or other
countries.
● Adobe, Acrobat, and Postscript are either registered trademarks or trademarks of
Adobe Systems Incorporated.
● Ethernet is a registered trademark of XEROX Corporation.
● We do not use the TM or ® mark to indicate these trademarks or registered
trademarks in this user's manual.
● All other product names mentioned in this user's manual are trademarks or registered
trademarks of their respective companies.
This symbol is used on the instrument. It indicates the possibility of injury to the user or
damage to the instrument, and signifies that the user must refer to the user’s manual for
special instructions. The same symbol is used in the user’s manual on pages that the
user needs to refer to, together with the term “WARNING” or “CAUTION.”
WARNING
Calls attention to actions or conditions that could cause serious or fatal injury to the user,
and indicates precautions that should be taken to prevent such occurrences.
CAUTION
Calls attention to actions or conditions that could cause injury to the user or damage
to the instrument or property and indicates precautions that should be taken to prevent
such occurrences.
Note
Identifies important information required to operate the instrument.
Indicates related operations or explanations for the user’s reference.
ii TI 01B08A02-06EN
Contents 1
Introduction.............................................................................................................................................. i 2
How to Use This Manual......................................................................................................................... ii
Chapter 1 Overview 3
1.1 Overview........................................................................................................................... 1-1
1.2 Models and Suffix Codes.................................................................................................. 1-3
1.3 Explanation of Terms and Replacement-related Descriptions........................................... 1-4 4
Chapter 3 Replacement with YS80 Internal Unit-compatible Type and EBS, I, EK,
or HOMAC-compatible Type
3.1 Replacement with YS80 Internal Unit-compatible Type and EBS, I, EK, or HOMAC-compatible
Type.......................................................................................................................................... 3-1
3.2 Panel Mounting Method.................................................................................................... 3-1
3.3 Housing Mounting Method................................................................................................ 3-1
3.3.1 Mounting to a Housing...............................................................................................................3-1
3.3.2 Removing the YS1000...............................................................................................................3-2
3.4 YS1oo0-o3o External Dimensions................................................................................ 3-3
3.5 External Dimensions and Terminals Layout of Housings.................................................. 3-4
3.5.1 SHUP-000*A (YS80 Housing), SHUP-000*A/A2ER (YS80 Housing, 220V Version Plug)............................... 3-4
3.5.2 SHUP-000*A/HTB (YS80 Housing, Power Terminal Type)........................................................3-5
3.5.3 SHUP-100*A (EBS or I Series-compatible Housing).................................................................3-6
3.5.4 Panel Cutout Dimensions
(SHUP-000*A, SHUP-000*A/A2ER, SHUP-000*A/HTB, SHUP-100*A)....................................3-7
3.5.5 SHUP-420*A (EK or HOMAC-compatible Housing)...................................................................3-8
3.5.6 Panel Cutout Dimensions (SHUP-420*A)..................................................................................3-8
3.6 Terminal Arrangement Table.............................................................................................. 3-9
3.6.1 SHUP-000*A (YS80 Housing), SHUP-000*A/A2ER (YS80 Housing, 220V Version Plug),
SHUP-000*A/HTB (YS80 Housing, Power Terminal Type), SHUP-100*A (EBS or I Series-compatible Housing).3-9
3.6.2 SHUP-420*A (EK or HOMAC-compatible Housing) ................................................................3-12
Revision Information.....................................................................................................i
iv TI 01B08A02-06EN
Chapter 1 Overview
1.1 Overview 1
Overview
This chapter specifies the external dimensions, panel cutout, terminal layout of the
compatible types for replacing the earlier single-loop controller models (EBS, I, EK, and
2
HOMAC), 100 line, YS80, and the YS100 series with the YS1000 and describes how
to mount and remove the YS1000. For operations of the YS1000, read through each
YS1000 series manual. 3
1965 1970 1975 1980 1985 1990 1995 2000
4
YS100
YS80
HOMAC
EK Series
I Series
EBS
Pneumatic100 Line
EBS
I Series
EK
TI 01B08A02-06EN 1-1
1.1 Overview
HOMAC
YS80
YS100
100 Line
1-2 TI 01B08A02-06EN
1.2 Models and Suffix Codes 1
Overview
Model Suffix Code
Optional
Remarks
2
Code
YS1700 Programmable indicating controller
YS1500
YS1360
Indicating controller
Manual Setter for MV Setting
3
YS1350 Manual Setter for SV Setting
YS1310 Indicator with Alarm
Use -1 In case of YS1700, YS1500 and YS1360: With hard manual unit 4
In case of YS1310 and YS1350: Always “-1”
-2 Without hard manual unit
0 Basic type
1 Basic type with expandable I/O (*1)
2 Compatible type for YS100 (with YS100 case)
3 Compatible type for YS80 internal unit/compatible type for
Type EBS, I, EK, and HOMAC (*2)
4 Compatible type for YS80 (compatible size for YS80 with
YS100 terminal)
5 Compatible type for pneumatic 100 line
(with YS100 terminal) (*3)
0 100 V AC, 24 V DC common power
Power supply
1 220 V AC power
/A01 mV input
/A02 Thermocouple input
/A03 RTD input
/A04 Potentiometer input
Direct input (*4) /A05 Isolator
/A06 Two-wire transmitter input (isolated)
/A07 Two-wire transmitter input (non-isolated)
/A08 Frequency input
/DF Direct input with Fahrenheit temperature range function (*5)
/A31 RS-485 communication (PC-link, Modbus, YS protocol, and
Peer-to-Peer) (*6)
Communication /A32 DCS-LCS communication (*7)
/A34 Ethernet communication (Modbus/TCP) (*8)
Standards /FM FM nonincendive approved (FM Class I, Div 2) (*9) (To be
approved)
/CSA CSA safety and nonincendive approved (Class I, Division 2)
(*10) (To be approved)
*1 Only YS1700 is compatible. The expandable I/O terminal (model YS010) and expandable
I/O cable (model YS011) (cable length: 3 m) are provided.
*2 This type can be connected to the YS80 housing (model SHUP-000).
(The EK/HOMAC-compatible housing (SHUP-420) and EBS/I series-compatible housing
(SHUP-100) are sold separately.)
*3 The 100 line-compatible housing (model YS006) is sold separately.
*4 Direct input options can be combined only with suffix codes “-o2o,” “-o4o,” or “-o5o.”
Selection of multiple options is not possible.
*5 Optional code /DF can be combined only with optional code /A02 or /A03.
*6 A combination with suffix code “-o3o” is not possible. Optional codes /A31 and /A32 cannot
be simultaneously specified.
*7 YS1310 cannot be specified.
Optional codes /A31 and /A32 cannot be simultaneously specified.
*8 Optional code /A34 can be specified only for suffix codes “-o0o” or “-o1o.”
*9 Optional code /FM can be combined only with suffix codes “-o0o” or “-o1o.”
*10 Optional code /CSA can be combined only with suffix codes “-o0o,” “-o1o,” or “-o2o.”
TI 01B08A02-06EN 1-3
1.3 Explanation of Terms and Replacement-related
Descriptions
Housings
(1) For the YS80, the enclosure containing the internal unit is called a “housing.”
(2) For the YS100 and the YS1000, it is regarded as a product with its internal unit
installed in an enclosure. This enclosure is not called “housing,” but is called a “case.”
(3) The types of housings also vary depending on the types of existing controllers to be
replaced.
(4) For the YS80, housing is required.
(5) For the YS1000, housings are used to re-use panel cutout and existing wiring the
same as when replacing the existing controllers. No housing is required if it is not
necessary to consider the panel cutout of an existing controller, etc. or for new
mounting.
Case
Terminals
Compatible Type for YS80 Internal Unit (YS1oo0-o3o)
Internal unit
Housing
Mounting Kits:
Components used to prevent the instrument from being horizontally shaken or used for
ornamenting panel cutout opening when mounting into a housing.
1-4 TI 01B08A02-06EN
Chapter 2 Replacement with YS100-compatible Type
Replace the YS100 with the YS1000. The model and suffix code are YS1oo0-o2o. 2
Replace the existing YS100 series and its case with the YS1000.
u Mounting and Removing: “Mounting the Instrument Main unit” of “Mounting Method” of
“Installation and Wiring” in each YS1000 Operation Guide.
67
When swung up 53 Note 1
60
13
136.4
(162.4)
144
13
72 22 320
Weight: 2.4 kg
Note 1: If a nameplate, etc. is installed within 60 mm above the instrument, the thickness of the
nameplate, etc. must be 30 mm or less from the panel surface.
Note 2: To ensure good air ventilation, allow space of 100 mm or more at the top and bottom of the
panel.
Note 3: General tolerance = ± (value of tolerance class IT18 based on JIS B 0401-1998) / 2
TI 01B08A02-06EN 2-1
2.3 YS1oo0-o2o External Dimensions
+2
0
137
220 or more
For Side-by-side Mounting
B
0
+2
137
220 or more
(Top view)
A
(Front)
Number of
Units 1 2 3 4 5 6 7
Location
A 72 144 216 288 360 432 504
B 68+1.0
0 140+1.0
0 212+1.0
0 284+1.0
0 356+1.0
0 428+1.0
0 500+1.0
0
Number of
Units 8 9 10 11 12 13 14
Location
A 576 648 720 792 864 936 1008
+1.0 +1.0 +1.0 +1.0 +1.0 +1.0 +1.0
B 572 0 644 0 716 0 788 0 860 0 932 0 1004 0
2-2 TI 01B08A02-06EN
2.4 Terminals Layout 1
1
2
22
23 2
24 3
25 4
26 5
TI 01B08A02-06EN 2-3
2.5 Terminal Arrangement Table
(1) YS1500/YS1700
User settings
Terminal Programmable mode
Single-loop mode Cascade mode Selector mode ( ) mode
number (YS1700 only)
(Note 10)
1 + Analog input 1 + Measurement input + Measurement input 1 + Measurement input 1
2 - (1-5V DC) - (1-5V DC) - (1-5V DC) - (1-5V DC)
3 + Analog input 2 + Cascade setting input (1- + Cascade setting input (1- + Cascade setting input 1
4 - (1-5V DC) - 5V DC) - 5V DC) - (1-5V DC)
5 + Analog input 3 + Input value for output + Measurement input 2 + Measurement input 2
6 - (1-5V DC) - tracking (1-5V DC) - (1-5V DC) - (1-5V DC)
7 + Analog input 4 + Feedforward input + Feedforward input + Cascade setting input 2
8 - (1-5V DC) - (1-5V DC) - (1-5V DC) (Note 1) - (1-5V DC) (Note 1)
9 + Analog input 5 + Output of the direct input + Output of the direct input + Output of the direct input
10 - (1-5V DC) (Note 2) - signal (1-5V DC) - signal (1-5V DC) - signal (1-5V DC)
11 + + + +
FAIL output (Note 3) FAIL output (Note 3) FAIL output (Note 3) FAIL output (Note 3)
12 - - - -
Connection of transmitter Connection of transmitter Connection of transmitter Connection of transmitter
13 supply power (24V DC) supply power (24V DC) supply power (24V DC) supply power (24V DC)
(Note 4) (Note 4) (Note 4) (Note 4)
14 Communication terminal SG Communication terminal SG Communication terminal SG Communication terminal SG
15 Communication terminal SDA (-) Communication terminal SDA (-) Communication terminal SDA (-) Communication terminal SDA (-)
16 Communication terminal SDB (+) Communication terminal SDB (+) Communication terminal SDB (+) Communication terminal SDB (+)
Communication terminal Communication terminal Communication terminal Communication terminal
17
RDA (-) or LCS (+) RDA (-) or LCS (+) RDA (-) or LCS (+) RDA (-) or LCS (+)
Communication terminal Communication terminal Communication terminal Communication terminal
18
RDB (+) or LCS (-) RDB (+) or LCS (-) RDB (+) or LCS (-) RDB (+) or LCS (-)
19 + + + +
Direct input terminals Direct input terminals Direct input terminals Direct input terminals
20 - - - -
(Note 5) (Note 5) (Note 5) (Note 5)
21
22 + Analog output 1 + Manipulated output variable 1 + Manipulated output variable 1 + Manipulated output variable 1
23 - (4 to 20mA DC) - (4 to 20mA DC) - (4 to 20mA DC) - (4 to 20mA DC)
24 + Analog output 2 + Manipulated output variable 2 + Manipulated output variable 2 + Manipulated output variable 2
25 - (1-5V DC) - (1-5V DC) (Note 6) - (1-5V DC) (Note 6) - (1-5V DC) (Note 6)
26 + Analog output 3 + + +
Setpoint value output Setpoint value output Setpoint value output
(4 to 20mA DC/1-5V DC)
27 - - (1-5V DC) (Note 6) - (1-5V DC) (Note 6) - (1-5V DC) (Note 6)
(Note 7)
28 + Digital output 1/Digital + High limit alarm setpoint + LOOP 1 alarm output + LOOP 1 alarm output
29 - input 6 (Note 8) - for PV output (Note 9) - (Note 9) - (Note 9)
30 + Digital output 2/Digital + Low limit alarm setpoint + LOOP 2 alarm output + LOOP 2 alarm output
31 - input 5 (Note 8) - for PV output (Note 9) - (Note 9) - (Note 9)
32 + Digital output 3/Digital + Velocity alarm setpoint for + O/C status output + L/R status output
33 - input 4 (Note 8) - PV output (Note 9) - (Note 9) - (Note 9)
34 + Digital output 4/Digital + C/A, M status output + C/A, M status output + C/A, M status output
35 - input 3 (Note 8) - (Note 9) - (Note 9) - (Note 9)
36 + Digital output 5/Digital + C, A/M status output + C, A/M status output + C, A/M status output
37 - input 2 (Note 8) - (Note 9) - (Note 9) - (Note 9)
38 + Digital output 6/Digital + No function (Factory + No function (Factory + No function (Factory
39 - input 1 (Note 8) - default) (Note 9) - default) (Note 9) - default) (Note 9)
L + + + +
Power supply Power supply Power supply Power supply
N - - - -
Grounding terminal Grounding terminal Grounding terminal Grounding terminal
Note
Do not use an unused terminal as a relaying terminal, etc.
2-4 TI 01B08A02-06EN
2.5 Terminal Arrangement Table
Note 1: These terminals can be used as output tracking input if feedforward input or cascade setting 1
input 2 is not used.
Note 2: For models with direct input (optional code /A0o), these terminals are treated as direct input
signal output (1-5 V DC).
Note 3: Using the terminals as fail output requires an external power supply. 2
Note 4: For a transmitter power supply, see “Wiring” of “Installation and Wiring” in each YS1000
Operation Guide.
Note 5: For models with direct input (optional code /A0o), the direct input terminals (19, 20, and 21)
TI 01B08A02-06EN 2-5
2.5 Terminal Arrangement Table
(2) YS1310/YS1350/YS1360
Terminal User settings
YS1310 YS1350 YS1360
number (Note 8)
1 + Measurement input 1 + Measurement input 1 + Measurement input 1
2 - (1-5V DC) - (1-5V DC) - (1-5V DC)
3 + Measurement input 2 + Cascade setting input + Cascade setting input (1-
4 - (1-5V DC) - (1-5V DC) - 5V DC)
5
6
7
8
9 + Direct input signal output + Direct input signal output + Direct input signal output
10 - (1-5V DC) (Note 1) - (1-5V DC) (Note 1) - (1-5V DC) (Note 1)
11 + + +
FAIL output (Note 2) FAIL output (Note 2) FAIL output (Note 2)
12 - - -
Connection of transmitter Connection of transmitter Connection of transmitter
13 supply power (24V DC) supply power (24V DC) supply power (24V DC)
(Note 3) (Note 3) (Note 3)
14 Communication terminal SG Communication terminal SG Communication terminal SG
15 Communication terminal SDA (-) Communication terminal SDA (-) Communication terminal SDA (-)
16 Communication terminal SDB (+) Communication terminal SDB (+) Communication terminal SDB (+)
Communication terminal Communication terminal
17 Communication terminal RDA (-)
RDA (-) or LCS (+) RDA (-) or LCS (+)
Communication terminal Communication terminal
18 Communication terminal RDB (+)
RDB (+) or LCS (-) RDB (+) or LCS (-)
19 + + +
Direct input terminals Direct input terminals Direct input terminals
20 - (Note 4)
- (Note 4)
- (Note 4)
21
22 + Manipulated output variable 1
23 - (4 to 20mA DC)
24 + Setpoint value output + Manipulated output variable 2
25 - (1-5V DC) - (1-5V DC)
26
27
28 + High limit alarm output for + High limit alarm output + High limit alarm output
29 - PV 1 (Note 5) - (Note 6) - (Note 6)
30 + Low limit alarm output for + Low limit alarm output + Low limit alarm output
31 - PV 1 (Note 5) - (Note 6) - (Note 6)
32 + High-high limit alarm
33 - output for PV 1 (Note 5)
34 + Low-low limit alarm output + C/M status output + C/M status output
35 - for PV 1 (Note 5) - (Note 6) - (Note 6)
OR output of high limit
36 + + +
alarm output for PV 2 and No function (Factory No function (Factory
low limit alarm output for default) (Note 7) default) (Note 7)
37 - PV 2 (Note 5) - -
OR output of high-high
38 + + +
limit alarm output for PV No function (Factory No function (Factory
2 and low-low limit alarm default) (Note 7) default) (Note 7)
39 - output for PV 2 (Note 5) - -
L + + +
Power supply Power supply Power supply
N - - -
Grounding terminal Grounding terminal Grounding terminal
Note
Do not use an unused terminal as a relaying terminal, etc.
2-6 TI 01B08A02-06EN
2.5 Terminal Arrangement Table
Note 1: For models with direct input (optional code /A0o), these terminals are treated as direct 1
input signal output (1-5 V DC).
Note 2: Using the terminals as fail output requires an external power supply.
Note 3: For a transmitter power supply, see “Wiring” of “Installation and Wiring” in each YS1000
Operation Guide. 2
Note 4: For models with direct input (optional code /A0o), the direct input terminals (19, 20, and
21) are used as input terminals. Connect the terminals as specified in Table 2.1, Connecting
Direct Input Terminals.
Terminal Symbol
19 21 20
mV input (optional code /A01)
Isolator (optional code /A05) + −
A B B
Note
Compatible type for YS100: YS1oo0-o2o/A02, an external RJC is connected. This is
different from the existing YS100s.
Connect the provided RJC to terminals 20 and 21. (Mount the RJC at the terminal 21 side.)
TI 01B08A02-06EN 2-7
Blank Page
Chapter 3 Replacement with YS80 Internal Unit-compatible Type and EBS, I, EK, or HOMAC-compatible Type
Replacement with YS80 Internal Unit-compatible Type and EBS, I, EK, or HOMAC-compatible Type
4
YS80 SHUP-000*A
EBS or I series SHUP-100*A
EK or HOMAC SHUP-420*A
Note
The YS1oo0-o31 of 220V AC power supply cannot be used with the SHUP housing of
100V power supply.
(2)
Cable connector (2)
Cable connector
Housing Housing
SHUP-000*A SHUP-420*A
(1) SHUP-100*A (1)
YS10-3 YS10-3
Figure 3.1 Connecting the Connector of SHUP-000*A (YS80 Housing) Figure 3.2 Connecting the Connector of SHUP-420*A
and SHUP-100*A (EBS or I Series-compatible Housing) (EK or HOMAC-compatible Housing)
TI 01B08A02-06EN 3-1
3.3 Housing Mounting Method
Figure 3.3 Inserting YS1000 into a Housing
Screwdriver
Figure 3.4 Inserting Screwdriver into Clearance
Figure 3.5 Pulling YS1000 out of the Housing
3-2 TI 01B08A02-06EN
3.4 YS1oo0-o3o External Dimensions 1
Unit: mm 2
65
3
When swung up 53 Note 1
Replacement with YS80 Internal Unit-compatible Type and EBS, I, EK, or HOMAC-compatible Type
4
60
70
144
136.4
149.2
9
22 345 5
Weight: 2.5 kg
Note 1: If a nameplate, etc. is installed within 60 mm above the instrument, the thickness of the
nameplate, etc. must be 30 mm or less from the panel surface.
Note 2: To ensure good air ventilation, allow space of 100 mm or more at the top and bottom of the
panel.
Note 3: General tolerance = ± (value of tolerance class IT18 based on JIS B 0401-1998) / 2
TI 01B08A02-06EN 3-3
3.5 External Dimensions and Terminals Layout of
Housings
3.5.1 SHUP-000*A (YS80 Housing), SHUP-000*A/A2ER (YS80 Housing, 220V Version Plug)
Unit: mm
9.5
182.5
170
*1
3
Recommended position of support angle 440 Support angle
19.5 480
Outline Drawing of 100V Version Plug Outline Drawing of 220V Version Plug (Optional Code: /A2ER)
11.9 21 32.2
6.35 10.0 19.0
17 4.8
4.0
11.18
14.22
32.0
19.0
35.5
3.1
Φ4
5.3
.75
Terminals Layout
A 1
2
B 3
4
C 5
6
D 7
8
F 9
10
H 11
12
J 13
14
K 15
16
L 17
18
M 19
20
N 21
Note
SHUP-000*A (YS80 Housing) is sold separately.
3-4 TI 01B08A02-06EN
3.5 External Dimensions and Terminals Layout of Housings
1
3.5.2 SHUP-000*A/HTB (YS80 Housing, Power Terminal Type)
Unit: mm
2
9.5
Replacement with YS80 Internal Unit-compatible Type and EBS, I, EK, or HOMAC-compatible Type
4
182.5
3170
Recommended position of support angle 440 Support angle
Front view 19.5 480 35 Rear view
Terminals Layout
A 1
2
B 3
4
C 5
6
D 7
8
F 9
10
H 11
12
J 13
14
K 15 Terminal Remarks
16 Symbol
L 17
18 L +
M 19 Power supply (DC or AC)
20 N −
N 21
Grounding
Note: Be aware that the signal terminals
L N
also have L and N terminals.
Note
SHUP-000*A/HTB (YS80 Housing Power Terminal Type) is sold separately.
TI 01B08A02-06EN 3-5
3.5 External Dimensions and Terminals Layout of Housings
9.5
182.5
170
Support
3
Recommended position of support angle 560 angle
Front view 19.5 642 35 Rear view
Terminals Layout
A 1
2
B 3
4
C 5
6
D 7
8
F 9
10
H 11
12
J 13
14
K 15 Terminal Remarks
16 Symbol
L 17
18 L +
M 19 Power supply (DC or AC)
20 N −
N 21
Grounding
Note: Be aware that the signal terminals
L N
also have L and N terminals.
Note
SHUP-100*A (EBS or I Series-compatible Housing) is sold separately.
3-6 TI 01B08A02-06EN
3.5 External Dimensions and Terminals Layout of Housings
1
3.5.4 Panel Cutout Dimensions
(SHUP-000*A, SHUP-000*A/A2ER, SHUP-000*A/HTB, SHUP-100*A)
For Single Mounting 2
140 or more
172±0.5
Replacement with YS80 Internal Unit-compatible Type and EBS, I, EK, or HOMAC-compatible Type
4
260 or more
80±0.5
For Side-by-side Mounting
B
172±0.5
(Top view)
260 or more
(Front)
MTS MTS
(Front view)
A
Number of
Units 1 2 3 4 5 6 7 8
Location
A* 87 157 227 297 367 437 507 577
B 80+10 150+10 220+10 290+10 360+10 430+10 500+10 570+10
Number of
Units 9 10 11 12 13 14 15
Location
A* 647 717 787 857 927 997 1067
B 640+10 710+10 780+10 850+10 920+10 990+10 1060+10
TI 01B08A02-06EN 3-7
3.5 External Dimensions and Terminals Layout of Housings
Unit: mm
73
76 172 Instrument panel thickness 3 to max. 12
152
Support
10.5
Front view Recommended position of support angle 380 to 470 angle Rear view
8 513
Terminals Layout
10 20 30
11 1 21 31
12 2 22 32
13 3 23 33
14 4 24 34
15 5 25 35
16 6 26 36
17 7 27 37
18 8 28 38
19 9 29 39
Screws: M3.5
Note
SHUP-420*A (EK or HOMAC-compatible Housing) is
sold separately.
250 or more
Note
If the YS1000 is mounted at an end in single mounting or side-by-side mounting, attach the
separately sold mounting kit (RA001) to the housing.
3-8 TI 01B08A02-06EN
3.6 Terminal Arrangement Table 1
3.6.1 SHUP-000*A (YS80 Housing), SHUP-000*A/A2ER (YS80 Housing, 220V Version Plug), 2
SHUP-000*A/HTB (YS80 Housing, Power Terminal Type),
SHUP-100*A (EBS or I Series-compatible Housing) 3
(1) YS1500/YS1700
User settings
Terminal Programmable mode
Single-loop mode Cascade mode Selector mode ( ) mode
Replacement with YS80 Internal Unit-compatible Type and EBS, I, EK, or HOMAC-compatible Type
number (YS1700 only)
(Note 8) 4
1 + Analog input 1 + Measurement input + Measurement input 1 + Measurement input 1
2 - (1-5V DC) - (1-5V DC) - (1-5V DC) - (1-5V DC)
3 + Analog input 2 + Cascade setting input + Cascade setting input + Cascade setting input 1
4 - (1-5V DC) - (1-5V DC) - (1-5V DC) - (1-5V DC)
5 + Analog input 3 + Input value for output + Measurement input 2 + Measurement input 2
6 - (1-5V DC) - tracking (1-5V DC) - (1-5V DC) - (1-5V DC)
7 + Analog input 4 + Feedforward input + Feedforward input + Cascade setting inpu 2
8 - (1-5V DC) - (1-5V DC) - (1-5V DC) (Note 2) - (1-5V DC) (Note 2)
9 + Analog input 5 + Output of the direct input + Output of the direct input + Output of the direct input
10 - (1-5V DC) - signal (1-5V DC) - signal (1-5V DC) - signal (1-5V DC)
N + + + +
FAIL output (Note 3) FAIL output (Note 3) FAIL output (Note 3) FAIL output (Note 3)
21 - - - -
Connection of transmitter Connection of transmitter Connection of transmitter Connection of transmitter
supply power (24V DC) supply power (24V DC) supply power (24V DC) supply power (24V DC)
Communication terminal SG Communication terminal SG Communication terminal SG Communication terminal SG
Communication terminal SDA (-) Communication terminal SDA (-) Communication terminal SDA (-) Communication terminal SDA (-)
Communication terminal SDB (+) Communication terminal SDB (+) Communication terminal SDB (+) Communication terminal SDB (+)
Communication terminal Communication terminal Communication terminal Communication terminal
17
RDA (-) or LCS (+) RDA (-) or LCS (+) RDA (-) or LCS (+) RDA (-) or LCS (+)
Communication terminal Communication terminal Communication terminal Communication terminal
18
RDB (+) or LCS (-) RDB (+) or LCS (-) RDB (+) or LCS (-) RDB (+) or LCS (-)
+ + + +
- Direct input terminals - Direct input terminals - Direct input terminals - Direct input terminals
A + Analog output 1 + Manipulated output variable 1 + Manipulated output variable 1 + Manipulated output variable 1
B - (4 to 20mA DC) - (4 to 20mA DC) - (4 to 20mA DC) - (4 to 20mA DC)
C + Analog output 2 + Manipulated output variable 2 + Manipulated output variable 2 + Manipulated output variable 2
D - (1-5V DC) - (1-5V DC) (Note 4) - (1-5V DC) (Note 4) - (1-5V DC) (Note 4)
F + Analog output 3 + + +
Setpoint value output Setpoint value output Setpoint value output
(4 to 20mA DC/1-5V DC)
H - - (1-5V DC) (Note 4) - (1-5V DC) (Note 4) - (1-5V DC) (Note 4)
(Note 5)
J + Digital output 1/Digital + High limit alarm setpoint + LOOP 1 alarm output + LOOP 1 alarm output
K - input 6 (Note 6) - for PV output (Note 7) - (Note 7) - (Note 7)
L + Digital output 2/Digital + Low limit alarm setpoint + LOOP 2 alarm output + LOOP 2 alarm output
M - input 5 (Note 6) - for PV output (Note 7) - (Note 7) - (Note 7)
19 + Digital output 3/Digital + Velocity alarm setpoint for + O/C status output + L/R status output
20 - input 4 (Note 6) - PV output (Note 7) - (Note 7) - (Note 7)
15 + Digital output 4/Digital + C/A, M status output + C/A, M status output + C/A, M status output
16 - input 3 (Note 6) - (Note 7) - (Note 7) - (Note 7)
13 + Digital output 5/Digital + C, A/M status output + C, A/M status output + C, A/M status output
14 - input 2 (Note 6) - (Note 7) - (Note 7) - (Note 7)
11 + Digital output 6/Digital + No function (Factory + No function (Factory + No function (Factory
12 - input 1 (Note 6) - default) (Note 7) - default) (Note 7) - default) (Note 7)
Note
Do not use an unused terminal as a relaying terminal, etc.
TI 01B08A02-06EN 3-9
3.6 Terminal Arrangement Table
Note 1: The functions in the shaded areas or those described in shaded characters are not available
in the YS80 housing or EBS or I series-compatible housing.
Note 2: These terminals can be used as output tracking input if feedforward input or cascade setting
input 2 is not used.
Note 3: Using the terminals as fail output requires an external power supply.
Note 4: For manipulated output variable 2 and setpoint output, the output types can be changed
using the analog output-2 selection Y2S and analog output-3 selection Y3S engineering
parameters.
Note 5: For analog output 3, the output type can be changed using the analog output-3 current/
voltage switching Y3TP engineering parameter.
Note 6: Using these terminals as digital output requires an external power supply. The function
of digital inputs or digital outputs can be set using the YSS1000 Setting Software (sold
separately).
Note 7: Using these terminals as digital output requires an external power supply. The settings in
the table are the factory defaults. Digital inputs or digital outputs can be appropriately used
by setting the DI/DO setting DIO16 to DIO61 engineering parameters. Functions can be set
using the DI1F to DI6F and DO1F to DO6F engineering parameters.
Note 8: If you change a function using the parameter concerned, enter the setting in the relevant
field in the User settings column.
3-10 TI 01B08A02-06EN
3.6 Terminal Arrangement Table
(2) YS1310/YS1350/YS1360 1
Terminal User settings
YS1310 YS1350 YS1360
number (Note 6)
1
2
+
-
Measurement input
(1-5V DC)
+
-
Measurement input 1
(1-5V DC)
+
-
Measurement input 1
(1-5V DC)
2
3 + Measurement input 2 + Cascade setting input + Cascade setting input
4 - (1-5V DC) - (1-5V DC) - (1-5V DC)
5 3
6
7
Replacement with YS80 Internal Unit-compatible Type and EBS, I, EK, or HOMAC-compatible Type
8
9 + + +
4
Output of the direct input Output of the direct input Output of the direct input
10 - signal (1-5V DC) - signal (1-5V DC) - signal (1-5V DC)
N + + +
FAIL output (Note 2) FAIL output (Note 2) FAIL output (Note 2)
21 - - -
Connection of transmitter Connection of transmitter Connection of transmitter
supply power (24V DC) supply power (24V DC) supply power (24V DC)
Communication terminal SG Communication terminal SG Communication terminal SG
Communication terminal SDA (-) Communication terminal SDA (-) Communication terminal SDA (-)
Communication terminal SDB (+) Communication terminal SDB (+) Communication terminal SDB (+)
Communication terminal Communication terminal Communication terminal
17
RDA (-) or LCS (+) RDA (-) or LCS (+) RDA (-) or LCS (+)
Communication terminal Communication terminal Communication terminal
18
RDB (+) or LCS (-) RDB (+) or LCS (-) RDB (+) or LCS (-)
+ + +
- Direct input terminals - Direct input terminals - Direct input terminals
Note 1: The functions in the shaded areas or those described in shaded characters are not available
in the YS80 housing or EBS or I series-compatible housing.
Note 2: Using the terminals as fail output requires an external power supply.
Note 3: Using these terminals as digital output requires an external power supply. The settings in
the table are the factory defaults. Digital inputs or digital outputs can be appropriately used
by setting the DI/DO setting DIO16 engineering parameter. Functions can be set using the
DI1F and DO1F to DO6F engineering parameters.
Note 4: Using these terminals as digital output requires an external power supply.
Note 5: The settings in the table are the factory defaults. Functions can be set using the DI1F and
DI2F engineering parameters.
Note 6: If you change a function using the parameter concerned, enter the setting in the relevant
field in the User settings column.
Note
Do not use an unused terminal as a relaying terminal, etc.
TI 01B08A02-06EN 3-11
3.6 Terminal Arrangement Table
37
38 + FAIL output (Note 7) + FAIL output (Note 7) + FAIL output (Note 7) + FAIL output (Note 7)
39 - Power supply L2 - Power supply L2 - Power supply L2 - Power supply L2
Note
Do not use an unused terminal as a relaying terminal, etc.
3-12 TI 01B08A02-06EN
3.6 Terminal Arrangement Table
Note 1: The functions in the shaded areas or those described in shaded characters are not available 1
in the EK or HOMAC-compatible housings.
Note 2: If analog output 1 is not used, short-circuit these terminals.
Note 3: Using these terminals as digital output requires an external power supply.
The function of digital inputs or digital outputs can be set using the YSS1000 Setting 2
Software (sold separately).
Note 4: For manipulated output variable 2 and setpoint output, the output types can be changed
using the analog output-2 selection Y2S and analog output-3 selection Y3S engineering
parameters. 3
Note 5: For analog output 3, the output type can be changed using the analog output-3 current/
voltage switching Y3TP engineering parameter.
Note 6: Using these terminals as digital output requires an external power supply. The settings in
Replacement with YS80 Internal Unit-compatible Type and EBS, I, EK, or HOMAC-compatible Type
the table are the factory defaults. Digital inputs or digital outputs can be appropriately used 4
by setting the DI/DO setting DIO16 to DIO61 engineering parameters. Functions can be set
using the DI1F to DI6F and DO1F to DO6F engineering parameters.
Note 7: Using the terminals as fail output requires an external power supply.
Note 8: These terminals can be used as output tracking input if feedforward input or cascade setting
input 2 is not used.
Note 9: If you change a function using the parameter concerned, enter the setting in the relevant
field in the User settings column.
TI 01B08A02-06EN 3-13
3.6 Terminal Arrangement Table
(2) YS1310/YS1350/YS1360
Terminal User settings
YS1310 YS1350 YS1360
number (Note 7)
1 + Measurement input 2 + Measurement input 2 + Measurement input 2
2 - (1-5V DC) - (1-5V DC) - (1-5V DC)
3
4
5 + Measurement input 1 + Measurement input 1 + Measurement input 1
6 - (1-5V DC) - (1-5V DC) - (1-5V DC)
7 + Manipulated output variable 1
8 - (4 to 20mA DC) (Note 2)
9
10
11 + High limit alarm setpoint + High limit alarm output + High limit alarm output
12 - for PV 1 output (Note 3) - (Note 4) - (Note 4)
13 + Low limit alarm setpoint + Low limit alarm output + Low limit alarm output
14 - for PV 1 output (Note 3) - (Note 4) - (Note 4)
15 + Setpoint value output + Manipulated output variable 2
16 - (1-5V DC) - (1-5V DC)
17
18
19 Grounding terminal Grounding terminal Grounding terminal
OR output of high-high
20 + + +
limit alarm output for PV No function (Factory No function (Factory
2 and low-low limit alarm default) (Note 3) default) (Note 3)
21 - output for PV 2 (Note 3) - -
OR output of high limit
22 + + +
alarm output for PV 2 and No function (Factory No function (Factory
low limit alarm output for default) (Note 3) default) (Note 3)
23 - PV 2 (Note 3) - -
24 + Low-low limit alarm output + C/M status output + C/M status output
25 - for PV 1 (Note 4) - (Note 5) - (Note 5)
26 + High-high limit alarm
27 - output for PV 1 (Note 4)
28 - FAIL output (Note 6) - FAIL output (Note 6) - FAIL output (Note 6)
29 + Power supply L1 + Power supply L1 + Power supply L1
30
31
32 + Output of the direct input + Output of the direct input + Output of the direct input
33 - signal (1-5V DC) - signal (1-5V DC) - signal (1-5V DC)
Connection of transmitter Connection of transmitter Connection of transmitter
34
supply power (24V DC) supply power (24V DC) supply power (24V DC)
Communication terminal SG Communication terminal SG Communication terminal SG
Communication terminal SDA (-) Communication terminal SDA (-) Communication terminal SDA (-)
Communication terminal SDB (+) Communication terminal SDB (+) Communication terminal SDB (+)
Communication terminal Communication terminal Communication terminal
35
RDA (-) or LCS (+) RDA (-) or LCS (+) RDA (-) or LCS (+)
Communication terminal Communication terminal Communication terminal
36
RDB (+) or LCS (-) RDB (+) or LCS (-) RDB (+) or LCS (-)
+ + +
- Direct input terminals - Direct input terminals - Direct input terminals
37
38 + FAIL output (Note 6) + FAIL output (Note 6) + FAIL output (Note 6)
39 - Power supply L2 - Power supply L2 - Power supply L2
Note
Do not use an unused terminal as a relaying terminal, etc.
3-14 TI 01B08A02-06EN
3.6 Terminal Arrangement Table
Note 1: The functions in the shaded areas or those described in shaded characters are not available 1
in the EK or HOMAC-compatible housings.
Note 2: If manipulated output variable 1 is not used, short-circuit these terminals.
Note 3: The settings in the table are the factory defaults. Functions can be set using the DI1F and
DI2F engineering parameters. 2
Note 4: Using these terminals as digital output requires an external power supply. The settings in
the table are the factory defaults. Digital inputs or digital outputs can be appropriately used
by setting the DI/DO setting DIO16 engineering parameter. Functions can be set using the
DI1F and DO1F to DO6F engineering parameters. 3
Note 5: Using these terminals as digital output requires an external power supply.
Note 6: Using the terminals as fail output requires an external power supply.
Note 7: If you change a function using the parameter concerned, enter the setting in the relevant
Replacement with YS80 Internal Unit-compatible Type and EBS, I, EK, or HOMAC-compatible Type
field in the User settings column. 4
TI 01B08A02-06EN 3-15
Blank Page
Chapter 4 Replacement with YS80-compatible Type
Replace the YS80 and its housing with the YS1000. The model and suffix codes are
YS1oo0-o4o.
2
3
4.2 Panel Mounting Method
Follow the same procedure as for the YS80. 4
If the YS1000 is installed at an end in single mounting or side-by-side mounting, the
separately sold mounting kit (MTY) is required.
Unit: mm
67
When swung up
53 Note 1
Instrument panel thickness 2.3 to max. 25
60
60
13
136.4
(186)
144
170
177
(33.6)
33
70 22 443.8
493.8 (6)
Note 1: If a nameplate, etc. is installed within 60 mm above the instrument, the thickness of the
nameplate, etc. must be 30 mm or less from the panel surface.
Note 2: To ensure good air ventilation, allow space of 100 mm or more at the top and bottom of the
panel.
Note 3: General tolerance = ± (value of tolerance class IT18 based on JIS B 0401-1998) / 2
TI 01B08A02-06EN 4-1
4.3 YS1oo0-o4o External Dimensions
172±0.5
260 or more
80±0.5
For Side-by-side Mounting
B
172±0.5
(Top view)
260 or more
(Front)
MTY MTY
(Front view)
Number of
Units 1 2 3 4 5 6 7 8
Location
A* 87 157 227 297 367 437 507 577
B 80+10 150+10 220+10 290+10 360+10 430+10 500+10 570+10
Number of
Units 9 10 11 12 13 14 15
Location
A* 647 717 787 857 927 997 1067
B 640+10 710+10 780+10 850+10 920+10 990+10 1060+10
4-2 TI 01B08A02-06EN
4.4 Terminals Layout 1
The terminal shapes and arrangements are the same as the YS1oo0-o2o.
► Terminals Layout: "2.4 Terminals Layout" and "2.5 Terminal Arrangment Table" in this manual.
2
Note 3
Compatible type for YS80: YS1oo0-o4o/A02, an external RJC is connected. This is different
from the existing YS100s.
Connect the provided RJC to terminals 20 and 21. (Mount the RJC at the terminal 21 side.)
4
TI 01B08A02-06EN 4-3
Blank Page
Chapter 5 Replacement with 100 Line-compatible Type
Replace the 100 line with the YS1000. The model and suffix codes are YS1oo0-o5o.
Install the YS1000 in the YS006 housing and then replace the 100 line with the YS1000.
2
The YS006 can be used with the YS1oo0-o50 (100V AC, 24V DC common power
supply) and YS1oo0-051 (220V AC power supply).
3
(2)
Cable connector
Housing YS006
(1)
YS10-5
Figure 5.1 Connecting the connector of YS006
TI 01B08A02-06EN 5-1
5.3 Housing Mounting Method
Figure 5.2 Inserting YS1000 into a Housing
Screwdriver
Figure 5.3 Inserting Screwdriver into Clearance
Figure 5.4 Pulling YS1000 out of the Housing
5-2 TI 01B08A02-06EN
5.4 YS1oo0-o5o External Dimensions 1
Unit: mm
2
65
When swung up 3
53 Note 1
4
60
70
136.4
144
22 345 5
Weight: 2.5 kg
Note 1: If a nameplate, etc. is installed within 60 mm above the instrument, the thickness of the
nameplate, etc. must be 30 mm or less from the panel surface.
Note 2: To ensure good air ventilation, allow space of 100 mm or more at the top and bottom of the
panel.
Note 3: General tolerance = ± (value of tolerance class IT18 based on JIS B 0401-1998) / 2
TI 01B08A02-06EN 5-3
5.5 YS006 (100 Line-compatible Housing) External
Dimensions
5.5.1 External Dimensions
Unit: mm
136
201.6
40
28.5
40.9
15
27
70 424 Support angle Rear view
Front view Recommended position of support angle 520 to 560
664
16.6 743
80±0.5
5-4 TI 01B08A02-06EN
5.5 YS006 (100 Line-compatible Housing) External Dimensions
2
(Top view)
191±0.5
(Front)
4
260 or more
MTP MTP
5
(Front view)
Number of
Units 1 2 3 4 5 6 7 8
Location
A* 90 160 230 300 370 440 510 580
B 80+10 150+10 220+10 290+10 360+10 430+10 500+10 570+10
Number of
Units 9 10 11 12 13 14 15
Location
A* 650 720 790 860 930 1000 1070
B 640+10 710+10 780+10 850+10 920+10 990+10 1060+10
Note
If the YS1000 is mounted at an end in single mounting or side-by-side mounting, attach the
separately sold mounting kit (MTP) to the housing.
Note
Compatible type for 100 line: YS1oo0-o5o/A02, an external RJC is connected. This is
different from the existing YS100s.
Connect the provided RJC to terminals 20 and 21. (Mount the RJC at the terminal 21 side.)
TI 01B08A02-06EN 5-5
Blank Page
i
Revision Information
Title : YS1000 Series Replacement Guide Installation and Wiring
Manual No. : TI 01B08A02-06EN