Control Pi

The YS1000 Series Replacement Guide provides detailed instructions for installing and wiring the YS1000 single-loop controller, including compatibility with earlier models such as EBS, I, EK, and HOMAC series. It outlines the necessary external dimensions, panel cutout, and terminal layouts for successful replacement and includes references to additional user manuals for operation and communication functions. The document emphasizes the importance of reading through the manual before installation and notes that its contents may change without notice.

Uploaded by

Edgar Duomingues
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
18 views45 pages

Control Pi

The YS1000 Series Replacement Guide provides detailed instructions for installing and wiring the YS1000 single-loop controller, including compatibility with earlier models such as EBS, I, EK, and HOMAC series. It outlines the necessary external dimensions, panel cutout, and terminal layouts for successful replacement and includes references to additional user manuals for operation and communication functions. The document emphasizes the importance of reading through the manual before installation and notes that its contents may change without notice.

Uploaded by

Edgar Duomingues
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 45

Technical

Information YS1000 Series Replacement Guide


Installation and Wiring
TI 01B08A02-06EN

l
tiona
Func cement
n
Enha

The contents of this Technical Information are subject to change without notice.

Yokogawa Electric Corporation TI 01B08A02-06EN


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan ©Copyright June. 2014
1st Edition June 13, 2014
Introduction
Thank you for purchasing the YS1000 series single-loop controller (hereinafter referred
to as “YS1000”).
This manual specifies the external dimensions, panel cutout, and terminal layout of the
compatible types for replacing the earlier single-loop controller models (EBS, I, EK, and
HOMAC series), pneumatic 100 line (100 line), YEWSERIES 80 (YS80), and the YS100
series with YS1000 and describes how to mount and remove the YS1000.
Please read through this user’s manual carefully before using the product.
Note that the manuals for the YS1000 comprise the following nine documents:

● Printed manual
Manual Name Manual Number Description
YS1500/YS1700 This manual describes the basic
IM 01B08B02-01EN
Operation Guide operation method.
This manual describes the basic
YS1310 Operation Guide IM 01B08D02-01EN
operation method.
YS1350/YS1360 This manual describes the basic
IM 01B08E02-01EN
Operation Guide operation method.

● Electronic manuals
Manual Name Manual Number Description
YS1500/YS1700
IM 01B08B02-01EN This is identical to the printed manual.
Operation Guide
This manual describes the usage of all
YS1500/YS1700
IM 01B08B02-02EN functions except the programming and
User’s Manual
communication functions.
YS1310
IM 01B08D02-01EN This is identical to the printed manual.
Operation Guide
YS1310 This manual describes the usage of all
IM 01B08D02-02EN
User’s Manual functions except the communication functions.
YS1350/YS1360
IM 01B08E02-01EN This is identical to the printed manual.
Operation Guide
YS1350/YS1360 This manual describes the usage of all
IM 01B08E02-02EN
User’s Manual functions except the communication functions.
This manual describes how to use
YS1000 Series
YS1000 in Ethernet, serial, and DCS-
Communication Interface IM 01B08J02-01EN
LCS communications. For communication
User’s Manual
wiring, see the Operation Guide.
YSS1000 Setting Software/ This manual describes how to use YSS1000
YS1700 Programmable IM 01B08K02-02EN and YS1700’s programmable function and
Function User’s Manual peer-to-peer communication function.
This manual. It describes the compatibility
YS1000 Series
IM 01B08H02-01EN of installation and wiring with YS100, YS80,
Replacement Manual
EBS, I, EK, HOMAC, and 100 line.

User’s manuals for YS1000 are available on the following web site: www.yokogawa.com/
ns/ys/im/
You need Adobe Reader 7.0 or later (but the latest version is recommended) installed on
the computer in order to open and read the manuals.
Notice
● The contents of this manual are subject to change without notice as a result of
continuing improvements to the instrument’s performance and functions.
● Every effort has been made to ensure accuracy in the preparation of this manual.
Should any errors or omissions come to your attention, however, please inform
YOKOGAWA Electric’s sales office or sales representative.
● Under no circumstances may the contents of this manual, in part or in whole, be
transcribed or copied without our permission.

1st Edition : June 2014 (YK)


All Rights Reserved, Copyright © 2014 Yokogawa Electric Corporation

TI 01B08A02-06EN i
Trademarks
● Our product names or brand names mentioned in this manual are the trademarks or
registered trademarks of YOKOGAWA Electric Corporation (hereinafter referred to as
YOKOGAWA).
● Microsoft, MS-DOS, Windows, Windows XP, and Windows NT are either registered
trademarks or trademarks of Microsoft Corporation in the United States and/or other
countries.
● Adobe, Acrobat, and Postscript are either registered trademarks or trademarks of
Adobe Systems Incorporated.
● Ethernet is a registered trademark of XEROX Corporation.
● We do not use the TM or ® mark to indicate these trademarks or registered
trademarks in this user's manual.
● All other product names mentioned in this user's manual are trademarks or registered
trademarks of their respective companies.

How to Use This Manual


Usage
First read through the Operation Guide to understand the basic operations and then
read this manual. For the programmable or communication functions, see the respective
manuals.
This User’s Manual is organized into Chapters 1 to 5 as shown below:
Chapter Title and Description
Overview
1 Provides transitions of the single-loop controllers, explanations of terms, and
descriptions on replacing with the YS1000.
Replacement with YS100-compatible Type
2
Describes replacing the YS100 with the YS1000.
Replacement with YS80 Internal Unit-compatible Type and EBS, I, EK, or
3 HOMAC-compatible Type
Describes replacing the YS80 and EBS, I, EK, or HOMAC with the YS1000.
Replacement with YS80-compatible Type
4
Describes replacing the YS80 with the YS1000 on a housing basis.
Replacement with 100 Line-compatible Type
5
Describes replacing the 100 line with the YS1000.

Symbols Used in This Manual


This symbol is used on the instrument. It indicates the possibility of injury to the user or
damage to the instrument, and signifies that the user must refer to the user’s manual for
special instructions. The same symbol is used in the user’s manual on pages that the
user needs to refer to, together with the term “WARNING” or “CAUTION.”

WARNING
Calls attention to actions or conditions that could cause serious or fatal injury to the user,
and indicates precautions that should be taken to prevent such occurrences.

CAUTION
Calls attention to actions or conditions that could cause injury to the user or damage
to the instrument or property and indicates precautions that should be taken to prevent
such occurrences.
Note
Identifies important information required to operate the instrument.


Indicates related operations or explanations for the user’s reference.

ii TI 01B08A02-06EN
Contents 1

Introduction.............................................................................................................................................. i 2
How to Use This Manual......................................................................................................................... ii

Chapter 1 Overview 3
1.1 Overview........................................................................................................................... 1-1
1.2 Models and Suffix Codes.................................................................................................. 1-3
1.3 Explanation of Terms and Replacement-related Descriptions........................................... 1-4 4

Chapter 2 Replacement with YS100-compatible Type


2.1 Replacement with YS100-compatible Type....................................................................... 2-1 5
2.2 Panel Mounting Method.................................................................................................... 2-1
2.3 YS1oo0-o2o External Dimensions................................................................................ 2-1
2.3.1 External Dimensions..................................................................................................................2-1 Index
2.3.2 Panel Cutout Dimensions..........................................................................................................2-2
2.4 Terminals Layout............................................................................................................... 2-3
2.5 Terminal Arrangement Table.............................................................................................. 2-4

Chapter 3 Replacement with YS80 Internal Unit-compatible Type and EBS, I, EK,
or HOMAC-compatible Type
3.1 Replacement with YS80 Internal Unit-compatible Type and EBS, I, EK, or HOMAC-compatible
Type.......................................................................................................................................... 3-1
3.2 Panel Mounting Method.................................................................................................... 3-1
3.3 Housing Mounting Method................................................................................................ 3-1
3.3.1 Mounting to a Housing...............................................................................................................3-1
3.3.2 Removing the YS1000...............................................................................................................3-2
3.4 YS1oo0-o3o External Dimensions................................................................................ 3-3
3.5 External Dimensions and Terminals Layout of Housings.................................................. 3-4
3.5.1 SHUP-000*A (YS80 Housing), SHUP-000*A/A2ER (YS80 Housing, 220V Version Plug)............................... 3-4
3.5.2 SHUP-000*A/HTB (YS80 Housing, Power Terminal Type)........................................................3-5
3.5.3 SHUP-100*A (EBS or I Series-compatible Housing).................................................................3-6
3.5.4 Panel Cutout Dimensions
(SHUP-000*A, SHUP-000*A/A2ER, SHUP-000*A/HTB, SHUP-100*A)....................................3-7
3.5.5 SHUP-420*A (EK or HOMAC-compatible Housing)...................................................................3-8
3.5.6 Panel Cutout Dimensions (SHUP-420*A)..................................................................................3-8
3.6 Terminal Arrangement Table.............................................................................................. 3-9
3.6.1 SHUP-000*A (YS80 Housing), SHUP-000*A/A2ER (YS80 Housing, 220V Version Plug),
SHUP-000*A/HTB (YS80 Housing, Power Terminal Type), SHUP-100*A (EBS or I Series-compatible Housing).3-9
3.6.2 SHUP-420*A (EK or HOMAC-compatible Housing) ................................................................3-12

Chapter 4 Replacement with YS80-compatible Type


4.1 Replacement with YS80-compatible Type......................................................................... 4-1
4.2 Panel Mounting Method.................................................................................................... 4-1
4.3 YS1oo0-o4o External Dimensions................................................................................ 4-1
4.3.1 External Dimensions..................................................................................................................4-1
4.3.2 Panel Cutout Dimensions..........................................................................................................4-2
4.4 Terminals Layout............................................................................................................... 4-3

Chapter 5 Replacement with 100 Line-compatible Type


5.1 Replacement with 100 Line-compatible Type.................................................................... 5-1
5.2 Panel Mounting Method.................................................................................................... 5-1
TI 01B08A02-06EN iii
5.3 Housing Mounting Method................................................................................................ 5-1
5.3.1 Mounting to a Housing...............................................................................................................5-1
5.3.2 Removing the YS1000...............................................................................................................5-2
5.4 YS1oo0-o5o External Dimensions................................................................................ 5-3
5.5 YS006 (100 Line-compatible Housing) External Dimensions............................................ 5-4
5.5.1 External Dimensions..................................................................................................................5-4
5.5.2 Panel Cutout Dimensions..........................................................................................................5-4
5.6 Terminals Layout............................................................................................................... 5-5

Revision Information.....................................................................................................i

iv TI 01B08A02-06EN
Chapter 1 Overview

1.1 Overview 1

Overview
This chapter specifies the external dimensions, panel cutout, terminal layout of the
compatible types for replacing the earlier single-loop controller models (EBS, I, EK, and
2
HOMAC), 100 line, YS80, and the YS100 series with the YS1000 and describes how
to mount and remove the YS1000. For operations of the YS1000, read through each
YS1000 series manual. 3
1965 1970 1975 1980 1985 1990 1995 2000

4
YS100

YS80

HOMAC

EK Series

I Series

EBS

Pneumatic100 Line


EBS


I Series


EK

TI 01B08A02-06EN 1-1
1.1 Overview


HOMAC


YS80


YS100

100 Line

1-2 TI 01B08A02-06EN
1.2 Models and Suffix Codes 1

Overview
Model Suffix Code
Optional
Remarks
2
Code
YS1700 Programmable indicating controller
YS1500
YS1360
Indicating controller
Manual Setter for MV Setting
3
YS1350 Manual Setter for SV Setting
YS1310 Indicator with Alarm
Use -1 In case of YS1700, YS1500 and YS1360: With hard manual unit 4
In case of YS1310 and YS1350: Always “-1”
-2 Without hard manual unit
0 Basic type
1 Basic type with expandable I/O (*1)
2 Compatible type for YS100 (with YS100 case)
3 Compatible type for YS80 internal unit/compatible type for
Type EBS, I, EK, and HOMAC (*2)
4 Compatible type for YS80 (compatible size for YS80 with
YS100 terminal)
5 Compatible type for pneumatic 100 line
(with YS100 terminal) (*3)
0 100 V AC, 24 V DC common power
Power supply
1 220 V AC power
/A01 mV input
/A02 Thermocouple input
/A03 RTD input
/A04 Potentiometer input
Direct input (*4) /A05 Isolator
/A06 Two-wire transmitter input (isolated)
/A07 Two-wire transmitter input (non-isolated)
/A08 Frequency input
/DF Direct input with Fahrenheit temperature range function (*5)
/A31 RS-485 communication (PC-link, Modbus, YS protocol, and
Peer-to-Peer) (*6)
Communication /A32 DCS-LCS communication (*7)
/A34 Ethernet communication (Modbus/TCP) (*8)
Standards /FM FM nonincendive approved (FM Class I, Div 2) (*9) (To be
approved)
/CSA CSA safety and nonincendive approved (Class I, Division 2)
(*10) (To be approved)
*1 Only YS1700 is compatible. The expandable I/O terminal (model YS010) and expandable
I/O cable (model YS011) (cable length: 3 m) are provided.
*2 This type can be connected to the YS80 housing (model SHUP-000).
(The EK/HOMAC-compatible housing (SHUP-420) and EBS/I series-compatible housing
(SHUP-100) are sold separately.)
*3 The 100 line-compatible housing (model YS006) is sold separately.
*4 Direct input options can be combined only with suffix codes “-o2o,” “-o4o,” or “-o5o.”
Selection of multiple options is not possible.
*5 Optional code /DF can be combined only with optional code /A02 or /A03.
*6 A combination with suffix code “-o3o” is not possible. Optional codes /A31 and /A32 cannot
be simultaneously specified.
*7 YS1310 cannot be specified.
Optional codes /A31 and /A32 cannot be simultaneously specified.
*8 Optional code /A34 can be specified only for suffix codes “-o0o” or “-o1o.”
*9 Optional code /FM can be combined only with suffix codes “-o0o” or “-o1o.”
*10 Optional code /CSA can be combined only with suffix codes “-o0o,” “-o1o,” or “-o2o.”

TI 01B08A02-06EN 1-3
1.3 Explanation of Terms and Replacement-related
Descriptions
Housings
(1) For the YS80, the enclosure containing the internal unit is called a “housing.”
(2) For the YS100 and the YS1000, it is regarded as a product with its internal unit
installed in an enclosure. This enclosure is not called “housing,” but is called a “case.”
(3) The types of housings also vary depending on the types of existing controllers to be
replaced.
(4) For the YS80, housing is required.
(5) For the YS1000, housings are used to re-use panel cutout and existing wiring the
same as when replacing the existing controllers. No housing is required if it is not
necessary to consider the panel cutout of an existing controller, etc. or for new
mounting.

Compatible Type for YS100 (YS1oo0-o2o)

Case

Terminals


Compatible Type for YS80 Internal Unit (YS1oo0-o3o)

Internal unit

Housing

Connector for connecting


the housing
Terminals


Mounting Kits:
Components used to prevent the instrument from being horizontally shaken or used for
ornamenting panel cutout opening when mounting into a housing.

1-4 TI 01B08A02-06EN
Chapter 2 Replacement with YS100-compatible Type

2.1 Replacement with YS100-compatible Type 1

Replace the YS100 with the YS1000. The model and suffix code are YS1oo0-o2o. 2
Replace the existing YS100 series and its case with the YS1000.

Replacement with YS100-compatible Type


3
2.2 Panel Mounting Method
4
Follow the same procedure for the YS1000 (suffix code “-o0o”, basic type).

u Mounting and Removing: “Mounting the Instrument Main unit” of “Mounting Method” of
“Installation and Wiring” in each YS1000 Operation Guide.

2.3 YS1oo0-o2o External Dimensions


2.3.1 External Dimensions

Unit: mm

67
When swung up 53 Note 1

Instrument panel thickness 2.3 to max. 25


60

60
13
136.4

(162.4)
144

13

72 22 320

Weight: 2.4 kg

Note 1: If a nameplate, etc. is installed within 60 mm above the instrument, the thickness of the
nameplate, etc. must be 30 mm or less from the panel surface.
Note 2: To ensure good air ventilation, allow space of 100 mm or more at the top and bottom of the
panel.
Note 3: General tolerance = ± (value of tolerance class IT18 based on JIS B 0401-1998) / 2

TI 01B08A02-06EN 2-1
2.3 YS1oo0-o2o External Dimensions

2.3.2 Panel Cutout Dimensions


For Single Mounting
+0.7
68 0

+2
0
137
220 or more


For Side-by-side Mounting
B

0
+2
137
220 or more

(Top view)

A
(Front)

Number of
Units 1 2 3 4 5 6 7
Location
A 72 144 216 288 360 432 504

B 68+1.0
0 140+1.0
0 212+1.0
0 284+1.0
0 356+1.0
0 428+1.0
0 500+1.0
0

Number of
Units 8 9 10 11 12 13 14
Location
A 576 648 720 792 864 936 1008
+1.0 +1.0 +1.0 +1.0 +1.0 +1.0 +1.0
B 572 0 644 0 716 0 788 0 860 0 932 0 1004 0

2-2 TI 01B08A02-06EN
2.4 Terminals Layout 1

1
2
22
23 2
24 3
25 4
26 5

Replacement with YS100-compatible Type


28
27
29
6
8
7 3
30 9
31 10
32 11
33 12
34
36
35 14
13
15
4
37 16
38 17
39 18
L 19
20
N 21

TI 01B08A02-06EN 2-3
2.5 Terminal Arrangement Table
(1) YS1500/YS1700
User settings
Terminal Programmable mode
Single-loop mode Cascade mode Selector mode ( ) mode
number (YS1700 only)
(Note 10)
1 + Analog input 1 + Measurement input + Measurement input 1 + Measurement input 1
2 - (1-5V DC) - (1-5V DC) - (1-5V DC) - (1-5V DC)
3 + Analog input 2 + Cascade setting input (1- + Cascade setting input (1- + Cascade setting input 1
4 - (1-5V DC) - 5V DC) - 5V DC) - (1-5V DC)
5 + Analog input 3 + Input value for output + Measurement input 2 + Measurement input 2
6 - (1-5V DC) - tracking (1-5V DC) - (1-5V DC) - (1-5V DC)
7 + Analog input 4 + Feedforward input + Feedforward input + Cascade setting input 2
8 - (1-5V DC) - (1-5V DC) - (1-5V DC) (Note 1) - (1-5V DC) (Note 1)
9 + Analog input 5 + Output of the direct input + Output of the direct input + Output of the direct input
10 - (1-5V DC) (Note 2) - signal (1-5V DC) - signal (1-5V DC) - signal (1-5V DC)
11 + + + +
FAIL output (Note 3) FAIL output (Note 3) FAIL output (Note 3) FAIL output (Note 3)
12 - - - -
Connection of transmitter Connection of transmitter Connection of transmitter Connection of transmitter
13 supply power (24V DC) supply power (24V DC) supply power (24V DC) supply power (24V DC)
(Note 4) (Note 4) (Note 4) (Note 4)
14 Communication terminal SG Communication terminal SG Communication terminal SG Communication terminal SG
15 Communication terminal SDA (-) Communication terminal SDA (-) Communication terminal SDA (-) Communication terminal SDA (-)
16 Communication terminal SDB (+) Communication terminal SDB (+) Communication terminal SDB (+) Communication terminal SDB (+)
Communication terminal Communication terminal Communication terminal Communication terminal
17
RDA (-) or LCS (+) RDA (-) or LCS (+) RDA (-) or LCS (+) RDA (-) or LCS (+)
Communication terminal Communication terminal Communication terminal Communication terminal
18
RDB (+) or LCS (-) RDB (+) or LCS (-) RDB (+) or LCS (-) RDB (+) or LCS (-)
19 + + + +
Direct input terminals Direct input terminals Direct input terminals Direct input terminals
20 - - - -
(Note 5) (Note 5) (Note 5) (Note 5)
21
22 + Analog output 1 + Manipulated output variable 1 + Manipulated output variable 1 + Manipulated output variable 1
23 - (4 to 20mA DC) - (4 to 20mA DC) - (4 to 20mA DC) - (4 to 20mA DC)
24 + Analog output 2 + Manipulated output variable 2 + Manipulated output variable 2 + Manipulated output variable 2
25 - (1-5V DC) - (1-5V DC) (Note 6) - (1-5V DC) (Note 6) - (1-5V DC) (Note 6)
26 + Analog output 3 + + +
Setpoint value output Setpoint value output Setpoint value output
(4 to 20mA DC/1-5V DC)
27 - - (1-5V DC) (Note 6) - (1-5V DC) (Note 6) - (1-5V DC) (Note 6)
(Note 7)
28 + Digital output 1/Digital + High limit alarm setpoint + LOOP 1 alarm output + LOOP 1 alarm output
29 - input 6 (Note 8) - for PV output (Note 9) - (Note 9) - (Note 9)
30 + Digital output 2/Digital + Low limit alarm setpoint + LOOP 2 alarm output + LOOP 2 alarm output
31 - input 5 (Note 8) - for PV output (Note 9) - (Note 9) - (Note 9)
32 + Digital output 3/Digital + Velocity alarm setpoint for + O/C status output + L/R status output
33 - input 4 (Note 8) - PV output (Note 9) - (Note 9) - (Note 9)
34 + Digital output 4/Digital + C/A, M status output + C/A, M status output + C/A, M status output
35 - input 3 (Note 8) - (Note 9) - (Note 9) - (Note 9)
36 + Digital output 5/Digital + C, A/M status output + C, A/M status output + C, A/M status output
37 - input 2 (Note 8) - (Note 9) - (Note 9) - (Note 9)
38 + Digital output 6/Digital + No function (Factory + No function (Factory + No function (Factory
39 - input 1 (Note 8) - default) (Note 9) - default) (Note 9) - default) (Note 9)
L + + + +
Power supply Power supply Power supply Power supply
N - - - -
Grounding terminal Grounding terminal Grounding terminal Grounding terminal

Note
Do not use an unused terminal as a relaying terminal, etc.

2-4 TI 01B08A02-06EN
2.5 Terminal Arrangement Table

Note 1: These terminals can be used as output tracking input if feedforward input or cascade setting 1
input 2 is not used.
Note 2: For models with direct input (optional code /A0o), these terminals are treated as direct input
signal output (1-5 V DC).
Note 3: Using the terminals as fail output requires an external power supply. 2
Note 4: For a transmitter power supply, see “Wiring” of “Installation and Wiring” in each YS1000
Operation Guide.
Note 5: For models with direct input (optional code /A0o), the direct input terminals (19, 20, and 21)

Replacement with YS100-compatible Type


are used as input terminals. Connect the terminals as specified in Table 2.1, Connecting 3
Direct Input Terminals.
Note 6: For manipulated output variable 2 and setpoint output, the output types can be changed
using the analog output-2 selection Y2S and analog output-3 selection Y3S engineering
parameters. 4
Note 7: For analog output 3, the output type can be changed using the analog output-3 current/
voltage switching Y3TP engineering parameter.
Note 8: Using these terminals as digital output requires an external power supply. The function
of digital inputs or digital outputs can be set using the YSS1000 Setting Software (sold
separately).
Note 9: Using these terminals as digital output requires an external power supply. The settings in
the table are the factory defaults. Digital inputs or digital outputs can be appropriately used
by setting the DI/DO setting DIO16 to DIO61 engineering parameters. Functions can be set
using the DI1F to DI6F and DO1F to DO6F engineering parameters.
Note 10: If you change a function using the parameter concerned, enter the setting in the relevant
field in the User settings column.

TI 01B08A02-06EN 2-5
2.5 Terminal Arrangement Table

(2) YS1310/YS1350/YS1360
Terminal User settings
YS1310 YS1350 YS1360
number (Note 8)
1 + Measurement input 1 + Measurement input 1 + Measurement input 1
2 - (1-5V DC) - (1-5V DC) - (1-5V DC)
3 + Measurement input 2 + Cascade setting input + Cascade setting input (1-
4 - (1-5V DC) - (1-5V DC) - 5V DC)
5
6
7
8
9 + Direct input signal output + Direct input signal output + Direct input signal output
10 - (1-5V DC) (Note 1) - (1-5V DC) (Note 1) - (1-5V DC) (Note 1)
11 + + +
FAIL output (Note 2) FAIL output (Note 2) FAIL output (Note 2)
12 - - -
Connection of transmitter Connection of transmitter Connection of transmitter
13 supply power (24V DC) supply power (24V DC) supply power (24V DC)
(Note 3) (Note 3) (Note 3)
14 Communication terminal SG Communication terminal SG Communication terminal SG
15 Communication terminal SDA (-) Communication terminal SDA (-) Communication terminal SDA (-)
16 Communication terminal SDB (+) Communication terminal SDB (+) Communication terminal SDB (+)
Communication terminal Communication terminal
17 Communication terminal RDA (-)
RDA (-) or LCS (+) RDA (-) or LCS (+)
Communication terminal Communication terminal
18 Communication terminal RDB (+)
RDB (+) or LCS (-) RDB (+) or LCS (-)
19 + + +
Direct input terminals Direct input terminals Direct input terminals
20 - (Note 4)
- (Note 4)
- (Note 4)
21
22 + Manipulated output variable 1
23 - (4 to 20mA DC)
24 + Setpoint value output + Manipulated output variable 2
25 - (1-5V DC) - (1-5V DC)
26
27
28 + High limit alarm output for + High limit alarm output + High limit alarm output
29 - PV 1 (Note 5) - (Note 6) - (Note 6)
30 + Low limit alarm output for + Low limit alarm output + Low limit alarm output
31 - PV 1 (Note 5) - (Note 6) - (Note 6)
32 + High-high limit alarm
33 - output for PV 1 (Note 5)
34 + Low-low limit alarm output + C/M status output + C/M status output
35 - for PV 1 (Note 5) - (Note 6) - (Note 6)
OR output of high limit
36 + + +
alarm output for PV 2 and No function (Factory No function (Factory
low limit alarm output for default) (Note 7) default) (Note 7)
37 - PV 2 (Note 5) - -
OR output of high-high
38 + + +
limit alarm output for PV No function (Factory No function (Factory
2 and low-low limit alarm default) (Note 7) default) (Note 7)
39 - output for PV 2 (Note 5) - -
L + + +
Power supply Power supply Power supply
N - - -
Grounding terminal Grounding terminal Grounding terminal

Note
Do not use an unused terminal as a relaying terminal, etc.

2-6 TI 01B08A02-06EN
2.5 Terminal Arrangement Table

Note 1: For models with direct input (optional code /A0o), these terminals are treated as direct 1
input signal output (1-5 V DC).
Note 2: Using the terminals as fail output requires an external power supply.
Note 3: For a transmitter power supply, see “Wiring” of “Installation and Wiring” in each YS1000
Operation Guide. 2
Note 4: For models with direct input (optional code /A0o), the direct input terminals (19, 20, and
21) are used as input terminals. Connect the terminals as specified in Table 2.1, Connecting
Direct Input Terminals.

Replacement with YS100-compatible Type


Note 5: Using these terminals as digital output requires an external power supply. The settings in 3
the table are the factory defaults. Digital inputs or digital outputs can be appropriately used
by setting the DI/DO setting DIO16 engineering parameter. Functions can be set using the
DI1F and DO1F to DO6F engineering parameters.
Note 6: Using these terminals as digital output requires an external power supply. 4
Note 7: The settings in the table are the factory defaults. Functions can be set using the DI1F and
DI2F engineering parameters.
Note 8: If you change a function using the parameter concerned, enter the setting in the relevant
field in the User settings column.

Table 2.1 Connecting Direct Input Terminals

Terminal Symbol
19 21 20
mV input (optional code /A01)
Isolator (optional code /A05) + −

Thermocouple input (optional code /A02) + RJC −

A B B

RTD input (optional code /A03)


Match the wiring resistances of terminals 19 and 21
with each other.

Potentiometer input (optional code /A04) 100% 0%


Match the wiring resistances of terminals 19 and 20
with each other.
Two-wire type
(voltage, contact) + −
Frequency input
Power feed type,
(optional code two-wired Signal Power supply
/A08)
Power feed type,
three-wired + Power supply −

Two-wire Supply voltage


required + −
transmitter input
(optional codes Case of 4 to 20 mA
/A06, /A07) signal not requiring + −
power supply

Note
Compatible type for YS100: YS1oo0-o2o/A02, an external RJC is connected. This is
different from the existing YS100s.
Connect the provided RJC to terminals 20 and 21. (Mount the RJC at the terminal 21 side.)

TI 01B08A02-06EN 2-7
Blank Page
Chapter 3 Replacement with YS80 Internal Unit-compatible Type and EBS, I, EK, or HOMAC-compatible Type

3.1 Replacement with YS80 Internal Unit-compatible 1


Type and EBS, I, EK, or HOMAC-compatible Type
Replace the YS80 internal unit or EBS, I, EK, or HOMAC controller with the YS1000. The 2
model and suffix codes are YS1oo0-o3o.
Install the YS1000 in an SHUP housing and then replace the internal unit or controller
with the YS1000. For replacement of the EBS, I, EK, or HOMAC controller, the 3
separately sold SHUP housing corresponding to the model is required.

Model to be Replaced Corresponding Housing

Replacement with YS80 Internal Unit-compatible Type and EBS, I, EK, or HOMAC-compatible Type
4
YS80 SHUP-000*A
EBS or I series SHUP-100*A
EK or HOMAC SHUP-420*A

Note
The YS1oo0-o31 of 220V AC power supply cannot be used with the SHUP housing of
100V power supply.

3.2 Panel Mounting Method


Follow the same procedure as for the YS80.
If the YS1000 is installed at an end in single mounting or side-by-side mounting, the
separately sold mounting kit (MTS for the YS80, EBS, or I series/RA001 for the EK or
HOMAC) is required.
► Mounting: Installation Manual for Panel-mounted Instruments (IM 1B4F1-01E)

3.3 Housing Mounting Method


3.3.1 Mounting to a Housing
1. Connect the housing’s cable connector to the connector at the back of the YS1000.
2. Insert the YS1000 into the mounting kit by moving it along the housing frame until you
hear a click, which means the case is now fitted into and fastened to the housing.

(2)
Cable connector (2)
Cable connector

Housing Housing
SHUP-000*A SHUP-420*A
(1) SHUP-100*A (1)

YS10-3 YS10-3

Figure 3.1 Connecting the Connector of SHUP-000*A (YS80 Housing) Figure 3.2 Connecting the Connector of SHUP-420*A
and SHUP-100*A (EBS or I Series-compatible Housing) (EK or HOMAC-compatible Housing)

TI 01B08A02-06EN 3-1
3.3 Housing Mounting Method


Figure 3.3 Inserting YS1000 into a Housing

3.3.2 Removing the YS1000


Prepare a flat-blade screwdriver (with an end size of 7 mm or less).
1. Insert the screwdriver into the clearance at the lower part of the stopper key. This
causes the stopper key to be lifted up.
2. With the screwdriver inserted, pull out the YS1000 from the housing.
3. Disconnect the cable connector of the housing from the connector at the back of the
YS1000.
Stopper key

Screwdriver


Figure 3.4 Inserting Screwdriver into Clearance


Figure 3.5 Pulling YS1000 out of the Housing

3-2 TI 01B08A02-06EN
3.4 YS1oo0-o3o External Dimensions 1

Unit: mm 2

65
3
When swung up 53 Note 1

Replacement with YS80 Internal Unit-compatible Type and EBS, I, EK, or HOMAC-compatible Type
4
60

70
144

136.4

149.2
9
22 345 5

Weight: 2.5 kg

Note 1: If a nameplate, etc. is installed within 60 mm above the instrument, the thickness of the
nameplate, etc. must be 30 mm or less from the panel surface.
Note 2: To ensure good air ventilation, allow space of 100 mm or more at the top and bottom of the
panel.
Note 3: General tolerance = ± (value of tolerance class IT18 based on JIS B 0401-1998) / 2

TI 01B08A02-06EN 3-3
3.5 External Dimensions and Terminals Layout of
Housings
3.5.1 SHUP-000*A (YS80 Housing), SHUP-000*A/A2ER (YS80 Housing, 220V Version Plug)
Unit: mm

Instrument panel thickness 3.2 to max. 20


70

9.5
182.5

170
*1

3
Recommended position of support angle 440 Support angle
19.5 480

*1:Cable length 300


Front view Weight: 2.0 kg (excluding mounting kit) Rear view

Outline Drawing of 100V Version Plug Outline Drawing of 220V Version Plug (Optional Code: /A2ER)
11.9 21 32.2
6.35 10.0 19.0
17 4.8
4.0
11.18
14.22

32.0

19.0
35.5

3.1
Φ4

5.3
.75

Ground contact hole Ground contact


JIS C 8303 15A, 125 V Grounding Type Two-prong Attachment Plug CEE PUBLICATION 7 STANDARD SHEET VII
10/16A 250V TWO-POLE PLUG WITH DUAL-EARTHING CONTACTS

Terminals Layout

A 1
2
B 3
4
C 5
6
D 7
8
F 9
10
H 11
12
J 13
14
K 15
16
L 17
18
M 19
20
N 21

Note
SHUP-000*A (YS80 Housing) is sold separately.

3-4 TI 01B08A02-06EN
3.5 External Dimensions and Terminals Layout of Housings

1
3.5.2 SHUP-000*A/HTB (YS80 Housing, Power Terminal Type)
Unit: mm
2

Instrument panel thickness 3.2 to max. 20


3
70

9.5

Replacement with YS80 Internal Unit-compatible Type and EBS, I, EK, or HOMAC-compatible Type
4
182.5

3170
Recommended position of support angle 440 Support angle
Front view 19.5 480 35 Rear view

Weight: 2.0 kg (excluding mounting kit)

Terminals Layout

A 1
2
B 3
4
C 5
6
D 7
8
F 9
10
H 11
12
J 13
14
K 15 Terminal Remarks
16 Symbol
L 17
18 L +
M 19 Power supply (DC or AC)
20 N −
N 21
Grounding
Note: Be aware that the signal terminals
L N
also have L and N terminals.

Note
SHUP-000*A/HTB (YS80 Housing Power Terminal Type) is sold separately.

TI 01B08A02-06EN 3-5
3.5 External Dimensions and Terminals Layout of Housings

3.5.3 SHUP-100*A (EBS or I Series-compatible Housing)


Unit: mm

Instrument panel thickness 3.2 to max. 20


70

9.5
182.5

170
Support

3
Recommended position of support angle 560 angle
Front view 19.5 642 35 Rear view

Weight: 3.0 kg (excluding mounting kit)

Terminals Layout

A 1
2
B 3
4
C 5
6
D 7
8
F 9
10
H 11
12
J 13
14
K 15 Terminal Remarks
16 Symbol
L 17
18 L +
M 19 Power supply (DC or AC)
20 N −
N 21
Grounding
Note: Be aware that the signal terminals
L N
also have L and N terminals.

Note
SHUP-100*A (EBS or I Series-compatible Housing) is sold separately.

3-6 TI 01B08A02-06EN
3.5 External Dimensions and Terminals Layout of Housings

1
3.5.4 Panel Cutout Dimensions
(SHUP-000*A, SHUP-000*A/A2ER, SHUP-000*A/HTB, SHUP-100*A)
For Single Mounting 2
140 or more

172±0.5

Replacement with YS80 Internal Unit-compatible Type and EBS, I, EK, or HOMAC-compatible Type
4
260 or more

80±0.5


For Side-by-side Mounting
B

172±0.5
(Top view)
260 or more

(Front)
MTS MTS

(Front view)

A

Number of
Units 1 2 3 4 5 6 7 8
Location
A* 87 157 227 297 367 437 507 577
B 80+10 150+10 220+10 290+10 360+10 430+10 500+10 570+10

Number of
Units 9 10 11 12 13 14 15
Location
A* 647 717 787 857 927 997 1067
B 640+10 710+10 780+10 850+10 920+10 990+10 1060+10

*: The numerical values in line A include the MTS’s bezels.


Note
If the YS1000 is mounted at an end in single mounting or side-by-side mounting, attach the
separately sold mounting kit (MTS) to the housing.

TI 01B08A02-06EN 3-7
3.5 External Dimensions and Terminals Layout of Housings

3.5.5 SHUP-420*A (EK or HOMAC-compatible Housing)

Unit: mm

73
76 172 Instrument panel thickness 3 to max. 12

152
Support

10.5
Front view Recommended position of support angle 380 to 470 angle Rear view
8 513

Weight: 2.4 kg (excluding mounting kit)

Terminals Layout

10 20 30
11 1 21 31
12 2 22 32
13 3 23 33
14 4 24 34
15 5 25 35
16 6 26 36
17 7 27 37
18 8 28 38
19 9 29 39
Screws: M3.5
Note
SHUP-420*A (EK or HOMAC-compatible Housing) is
sold separately.

3.5.6 Panel Cutout Dimensions (SHUP-420*A)


+1 0.8R or less 89 or more 0.8R or less
13 or more 90 0
0
+3
152.5

250 or more

For single mounting in


combination with bezels

W’ = W – 7 mm “W” shows the front panel width (including bezels) for


side-by-side mounting of the YS1000.
Note that dimension W is 16 + 919.2 mm or less (12
units or less as the number of “3 × 6” type instruments).
W = (76.6 × N) + (152.4 + M) + 23 +1 13 or more +2
74 0 W’ 0
where N: Number of “3 × 6” type instruments mounted
M: Number of “6 × 6” type instruments mounted For single mounting For side-by-side mounting

Note
If the YS1000 is mounted at an end in single mounting or side-by-side mounting, attach the
separately sold mounting kit (RA001) to the housing.

3-8 TI 01B08A02-06EN
3.6 Terminal Arrangement Table 1

3.6.1 SHUP-000*A (YS80 Housing), SHUP-000*A/A2ER (YS80 Housing, 220V Version Plug), 2
SHUP-000*A/HTB (YS80 Housing, Power Terminal Type),
SHUP-100*A (EBS or I Series-compatible Housing) 3
(1) YS1500/YS1700
User settings
Terminal Programmable mode
Single-loop mode Cascade mode Selector mode ( ) mode

Replacement with YS80 Internal Unit-compatible Type and EBS, I, EK, or HOMAC-compatible Type
number (YS1700 only)
(Note 8) 4
1 + Analog input 1 + Measurement input + Measurement input 1 + Measurement input 1
2 - (1-5V DC) - (1-5V DC) - (1-5V DC) - (1-5V DC)
3 + Analog input 2 + Cascade setting input + Cascade setting input + Cascade setting input 1
4 - (1-5V DC) - (1-5V DC) - (1-5V DC) - (1-5V DC)
5 + Analog input 3 + Input value for output + Measurement input 2 + Measurement input 2
6 - (1-5V DC) - tracking (1-5V DC) - (1-5V DC) - (1-5V DC)
7 + Analog input 4 + Feedforward input + Feedforward input + Cascade setting inpu 2
8 - (1-5V DC) - (1-5V DC) - (1-5V DC) (Note 2) - (1-5V DC) (Note 2)
9 + Analog input 5 + Output of the direct input + Output of the direct input + Output of the direct input
10 - (1-5V DC) - signal (1-5V DC) - signal (1-5V DC) - signal (1-5V DC)
N + + + +
FAIL output (Note 3) FAIL output (Note 3) FAIL output (Note 3) FAIL output (Note 3)
21 - - - -
Connection of transmitter Connection of transmitter Connection of transmitter Connection of transmitter
supply power (24V DC) supply power (24V DC) supply power (24V DC) supply power (24V DC)
Communication terminal SG Communication terminal SG Communication terminal SG Communication terminal SG
Communication terminal SDA (-) Communication terminal SDA (-) Communication terminal SDA (-) Communication terminal SDA (-)
Communication terminal SDB (+) Communication terminal SDB (+) Communication terminal SDB (+) Communication terminal SDB (+)
Communication terminal Communication terminal Communication terminal Communication terminal
17
RDA (-) or LCS (+) RDA (-) or LCS (+) RDA (-) or LCS (+) RDA (-) or LCS (+)
Communication terminal Communication terminal Communication terminal Communication terminal
18
RDB (+) or LCS (-) RDB (+) or LCS (-) RDB (+) or LCS (-) RDB (+) or LCS (-)
+ + + +
- Direct input terminals - Direct input terminals - Direct input terminals - Direct input terminals

A + Analog output 1 + Manipulated output variable 1 + Manipulated output variable 1 + Manipulated output variable 1
B - (4 to 20mA DC) - (4 to 20mA DC) - (4 to 20mA DC) - (4 to 20mA DC)
C + Analog output 2 + Manipulated output variable 2 + Manipulated output variable 2 + Manipulated output variable 2
D - (1-5V DC) - (1-5V DC) (Note 4) - (1-5V DC) (Note 4) - (1-5V DC) (Note 4)
F + Analog output 3 + + +
Setpoint value output Setpoint value output Setpoint value output
(4 to 20mA DC/1-5V DC)
H - - (1-5V DC) (Note 4) - (1-5V DC) (Note 4) - (1-5V DC) (Note 4)
(Note 5)
J + Digital output 1/Digital + High limit alarm setpoint + LOOP 1 alarm output + LOOP 1 alarm output
K - input 6 (Note 6) - for PV output (Note 7) - (Note 7) - (Note 7)
L + Digital output 2/Digital + Low limit alarm setpoint + LOOP 2 alarm output + LOOP 2 alarm output
M - input 5 (Note 6) - for PV output (Note 7) - (Note 7) - (Note 7)
19 + Digital output 3/Digital + Velocity alarm setpoint for + O/C status output + L/R status output
20 - input 4 (Note 6) - PV output (Note 7) - (Note 7) - (Note 7)
15 + Digital output 4/Digital + C/A, M status output + C/A, M status output + C/A, M status output
16 - input 3 (Note 6) - (Note 7) - (Note 7) - (Note 7)
13 + Digital output 5/Digital + C, A/M status output + C, A/M status output + C, A/M status output
14 - input 2 (Note 6) - (Note 7) - (Note 7) - (Note 7)
11 + Digital output 6/Digital + No function (Factory + No function (Factory + No function (Factory
12 - input 1 (Note 6) - default) (Note 7) - default) (Note 7) - default) (Note 7)

Note
Do not use an unused terminal as a relaying terminal, etc.

TI 01B08A02-06EN 3-9
3.6 Terminal Arrangement Table

Note 1: The functions in the shaded areas or those described in shaded characters are not available
in the YS80 housing or EBS or I series-compatible housing.
Note 2: These terminals can be used as output tracking input if feedforward input or cascade setting
input 2 is not used.
Note 3: Using the terminals as fail output requires an external power supply.
Note 4: For manipulated output variable 2 and setpoint output, the output types can be changed
using the analog output-2 selection Y2S and analog output-3 selection Y3S engineering
parameters.
Note 5: For analog output 3, the output type can be changed using the analog output-3 current/
voltage switching Y3TP engineering parameter.
Note 6: Using these terminals as digital output requires an external power supply. The function
of digital inputs or digital outputs can be set using the YSS1000 Setting Software (sold
separately).
Note 7: Using these terminals as digital output requires an external power supply. The settings in
the table are the factory defaults. Digital inputs or digital outputs can be appropriately used
by setting the DI/DO setting DIO16 to DIO61 engineering parameters. Functions can be set
using the DI1F to DI6F and DO1F to DO6F engineering parameters.
Note 8: If you change a function using the parameter concerned, enter the setting in the relevant
field in the User settings column.

3-10 TI 01B08A02-06EN
3.6 Terminal Arrangement Table

(2) YS1310/YS1350/YS1360 1
Terminal User settings
YS1310 YS1350 YS1360
number (Note 6)
1
2
+
-
Measurement input
(1-5V DC)
+
-
Measurement input 1
(1-5V DC)
+
-
Measurement input 1
(1-5V DC)
2
3 + Measurement input 2 + Cascade setting input + Cascade setting input
4 - (1-5V DC) - (1-5V DC) - (1-5V DC)
5 3
6
7

Replacement with YS80 Internal Unit-compatible Type and EBS, I, EK, or HOMAC-compatible Type
8
9 + + +
4
Output of the direct input Output of the direct input Output of the direct input
10 - signal (1-5V DC) - signal (1-5V DC) - signal (1-5V DC)
N + + +
FAIL output (Note 2) FAIL output (Note 2) FAIL output (Note 2)
21 - - -
Connection of transmitter Connection of transmitter Connection of transmitter
supply power (24V DC) supply power (24V DC) supply power (24V DC)
Communication terminal SG Communication terminal SG Communication terminal SG
Communication terminal SDA (-) Communication terminal SDA (-) Communication terminal SDA (-)
Communication terminal SDB (+) Communication terminal SDB (+) Communication terminal SDB (+)
Communication terminal Communication terminal Communication terminal
17
RDA (-) or LCS (+) RDA (-) or LCS (+) RDA (-) or LCS (+)
Communication terminal Communication terminal Communication terminal
18
RDB (+) or LCS (-) RDB (+) or LCS (-) RDB (+) or LCS (-)
+ + +
- Direct input terminals - Direct input terminals - Direct input terminals

A + Manipulated output variable 1


B - (4 to 20mA DC)
C + Setpoint value output + Manipulated output variable 2
D - (1-5V DC) - (1-5V DC)
F
H
J + High limit alarm setpoint + High limit alarm output + High limit alarm output
K - for PV 1 output (Note 3) - (Note 4) - (Note 4)
L + Low limit alarm setpoint + Low limit alarm output + Low limit alarm output
M - for PV 1 output (Note 3) - (Note 4) - (Note 4)
19 + High-high limit alarm
20 - output for PV 1 (Note 3)
15 + Low-low limit alarm output + C/M status output + C/M status output
16 - for PV 1 (Note 3) - (Note 4) - (Note 4)
OR output of high limit
13 + + +
alarm output for PV 2 and No function (Factory No function (Factory
low limit alarm output for default) (Note 5) default) (Note 5)
14 - PV 2 (Note 3) - -
OR output of high-high
11 + + +
limit alarm output for PV No function (Factory No function (Factory
2 and low-low limit alarm default) (Note 5) default) (Note 5)
12 - output for PV 2 (Note 3) - -

Note 1: The functions in the shaded areas or those described in shaded characters are not available
in the YS80 housing or EBS or I series-compatible housing.
Note 2: Using the terminals as fail output requires an external power supply.
Note 3: Using these terminals as digital output requires an external power supply. The settings in
the table are the factory defaults. Digital inputs or digital outputs can be appropriately used
by setting the DI/DO setting DIO16 engineering parameter. Functions can be set using the
DI1F and DO1F to DO6F engineering parameters.
Note 4: Using these terminals as digital output requires an external power supply.
Note 5: The settings in the table are the factory defaults. Functions can be set using the DI1F and
DI2F engineering parameters.
Note 6: If you change a function using the parameter concerned, enter the setting in the relevant
field in the User settings column.
Note
Do not use an unused terminal as a relaying terminal, etc.
TI 01B08A02-06EN 3-11
3.6 Terminal Arrangement Table

3.6.2 SHUP-420*A (EK or HOMAC-compatible Housing)


(1) YS1500/YS1700
User settings
Terminal Programmable mode
Single-loop mode Cascade mode Selector mode ( ) mode
number (YS1700 only)
(Note 9)
1 + Analog input 2 + Cascade setting input + Cascade setting input + Cascade setting input 1
2 - (1-5V DC) - (1-5V DC) - (1-5V DC) - (1-5V DC)
3 + Analog input 3 + Input value for output + Measurement input 2 + Measurement input 2
4 - (1-5V DC) - tracking (1-5V DC) - (1-5V DC) - (1-5V DC)
5 + Analog input 1 + Measurement input + Measurement input 1 + Measurement input 1
6 - (1-5V DC) - (1-5V DC) - (1-5V DC) - (1-5V DC)
7 + Analog output 1 + Manipulated output variable 1 + Manipulated output variable 1 + Manipulated output variable 1
8 - (4 to 20mA DC) (Note 2) - (4 to 20mA DC) - (4 to 20mA DC) - (4 to 20mA DC)
9
10
11 + Digital output 1/Digital + High limit alarm setpoint + +
LOOP 1 alarm output LOOP 1 alarm output
12 - input 6 (Note 3) - for PV output - -
13 + Digital output 2/Digital + Low limit alarm setpoint + +
LOOP 2 alarm output LOOP 2 alarm output
14 - input 5 (Note 3) - for PV output - -
15 + Analog output 2 + Manipulated output variable 2 + Manipulated output variable 2 + Manipulated output variable 2
16 - (1-5V DC) - (1-5V DC) (Note 4) - (1-5V DC) (Note 4) - (1-5V DC) (Note 4)
17 + Analog output 3 + + +
Setpoint value output Setpoint value output Setpoint value output
(4 to 20mA DC/1-5V DC)
18 - - (1-5V DC) - (1-5V DC) (Note 4) - (1-5V DC) (Note 4)
(Note 5)
19 Grounding terminal Grounding terminal Grounding terminal Grounding terminal
20 + Digital output 6/Digital + No function (Factory + No function (Factory + No function (Factory
21 - input 1 (Note 3) - default) (Note 6) - default) (Note 6) - default) (Note 6)
22 + Digital output 5/Digital + C, A/M status output + C, A/M status output + C, A/M status output
23 - input 2 (Note 3) - (Note 6) - (Note 6) - (Note 6)
24 + Digital output 4/Digital + C/A, M status output + C/A, M status output + C/A, M status output
25 - input 3 (Note 3) - (Note 6) - (Note 6) - (Note 6)
26 + Digital output 3/Digital + Velocity alarm setpoint for + O/C status output + L/R status output
27 - input 4 (Note 3) - PV output (Note 6) - (Note 6) - (Note 6)
28 - FAIL output (Note 7) - FAIL output (Note 7) - FAIL output (Note 7) - FAIL output (Note 7)
29 + Power supply L1 + Power supply L1 + Power supply L1 + Power supply L1
30 + Analog input 4 + Feedforward input + Feedforward input + Cascade setting input 2
31 - (1-5V DC) - (1-5V DC) (Note 8) - (1-5V DC) (Note 8) - (1-5V DC)
32 + Analog input 5 + Output of the direct input + Output of the direct input + Output of the direct input
33 - (1-5V DC) - signal (1-5V DC) - signal (1-5V DC) - signal (1-5V DC)
Connection of transmitter Connection of transmitter Connection of transmitter Connection of transmitter
34
supply power (24V DC) supply power (24V DC) supply power (24V DC) supply power (24V DC)
Communication terminal SG Communication terminal SG Communication terminal SG Communication terminal SG
Communication terminal SDA (-) Communication terminal SDA (-) Communication terminal SDA (-) Communication terminal SDA (-)
Communication terminal SDB (+) Communication terminal SDB (+) Communication terminal SDB (+) Communication terminal SDB (+)
Communication terminal Communication terminal Communication terminal Communication terminal
35
RDA (-) or LCS (+) RDA (-) or LCS (+) RDA (-) or LCS (+) RDA (-) or LCS (+)
Communication terminal Communication terminal Communication terminal Communication terminal
36
RDB (+) or LCS (-) RDB (+) or LCS (-) RDB (+) or LCS (-) RDB (+) or LCS (-)
+ + + +
- Direct input terminals - Direct input terminals - Direct input terminals - Direct input terminals

37
38 + FAIL output (Note 7) + FAIL output (Note 7) + FAIL output (Note 7) + FAIL output (Note 7)
39 - Power supply L2 - Power supply L2 - Power supply L2 - Power supply L2

Note
Do not use an unused terminal as a relaying terminal, etc.

3-12 TI 01B08A02-06EN
3.6 Terminal Arrangement Table

Note 1: The functions in the shaded areas or those described in shaded characters are not available 1
in the EK or HOMAC-compatible housings.
Note 2: If analog output 1 is not used, short-circuit these terminals.
Note 3: Using these terminals as digital output requires an external power supply.
The function of digital inputs or digital outputs can be set using the YSS1000 Setting 2
Software (sold separately).
Note 4: For manipulated output variable 2 and setpoint output, the output types can be changed
using the analog output-2 selection Y2S and analog output-3 selection Y3S engineering
parameters. 3
Note 5: For analog output 3, the output type can be changed using the analog output-3 current/
voltage switching Y3TP engineering parameter.
Note 6: Using these terminals as digital output requires an external power supply. The settings in

Replacement with YS80 Internal Unit-compatible Type and EBS, I, EK, or HOMAC-compatible Type
the table are the factory defaults. Digital inputs or digital outputs can be appropriately used 4
by setting the DI/DO setting DIO16 to DIO61 engineering parameters. Functions can be set
using the DI1F to DI6F and DO1F to DO6F engineering parameters.
Note 7: Using the terminals as fail output requires an external power supply.
Note 8: These terminals can be used as output tracking input if feedforward input or cascade setting
input 2 is not used.
Note 9: If you change a function using the parameter concerned, enter the setting in the relevant
field in the User settings column.

TI 01B08A02-06EN 3-13
3.6 Terminal Arrangement Table

(2) YS1310/YS1350/YS1360
Terminal User settings
YS1310 YS1350 YS1360
number (Note 7)
1 + Measurement input 2 + Measurement input 2 + Measurement input 2
2 - (1-5V DC) - (1-5V DC) - (1-5V DC)
3
4
5 + Measurement input 1 + Measurement input 1 + Measurement input 1
6 - (1-5V DC) - (1-5V DC) - (1-5V DC)
7 + Manipulated output variable 1
8 - (4 to 20mA DC) (Note 2)
9
10
11 + High limit alarm setpoint + High limit alarm output + High limit alarm output
12 - for PV 1 output (Note 3) - (Note 4) - (Note 4)
13 + Low limit alarm setpoint + Low limit alarm output + Low limit alarm output
14 - for PV 1 output (Note 3) - (Note 4) - (Note 4)
15 + Setpoint value output + Manipulated output variable 2
16 - (1-5V DC) - (1-5V DC)
17
18
19 Grounding terminal Grounding terminal Grounding terminal
OR output of high-high
20 + + +
limit alarm output for PV No function (Factory No function (Factory
2 and low-low limit alarm default) (Note 3) default) (Note 3)
21 - output for PV 2 (Note 3) - -
OR output of high limit
22 + + +
alarm output for PV 2 and No function (Factory No function (Factory
low limit alarm output for default) (Note 3) default) (Note 3)
23 - PV 2 (Note 3) - -
24 + Low-low limit alarm output + C/M status output + C/M status output
25 - for PV 1 (Note 4) - (Note 5) - (Note 5)
26 + High-high limit alarm
27 - output for PV 1 (Note 4)
28 - FAIL output (Note 6) - FAIL output (Note 6) - FAIL output (Note 6)
29 + Power supply L1 + Power supply L1 + Power supply L1
30
31
32 + Output of the direct input + Output of the direct input + Output of the direct input
33 - signal (1-5V DC) - signal (1-5V DC) - signal (1-5V DC)
Connection of transmitter Connection of transmitter Connection of transmitter
34
supply power (24V DC) supply power (24V DC) supply power (24V DC)
Communication terminal SG Communication terminal SG Communication terminal SG
Communication terminal SDA (-) Communication terminal SDA (-) Communication terminal SDA (-)
Communication terminal SDB (+) Communication terminal SDB (+) Communication terminal SDB (+)
Communication terminal Communication terminal Communication terminal
35
RDA (-) or LCS (+) RDA (-) or LCS (+) RDA (-) or LCS (+)
Communication terminal Communication terminal Communication terminal
36
RDB (+) or LCS (-) RDB (+) or LCS (-) RDB (+) or LCS (-)
+ + +
- Direct input terminals - Direct input terminals - Direct input terminals

37
38 + FAIL output (Note 6) + FAIL output (Note 6) + FAIL output (Note 6)
39 - Power supply L2 - Power supply L2 - Power supply L2


Note
Do not use an unused terminal as a relaying terminal, etc.

3-14 TI 01B08A02-06EN
3.6 Terminal Arrangement Table

Note 1: The functions in the shaded areas or those described in shaded characters are not available 1
in the EK or HOMAC-compatible housings.
Note 2: If manipulated output variable 1 is not used, short-circuit these terminals.
Note 3: The settings in the table are the factory defaults. Functions can be set using the DI1F and
DI2F engineering parameters. 2
Note 4: Using these terminals as digital output requires an external power supply. The settings in
the table are the factory defaults. Digital inputs or digital outputs can be appropriately used
by setting the DI/DO setting DIO16 engineering parameter. Functions can be set using the
DI1F and DO1F to DO6F engineering parameters. 3
Note 5: Using these terminals as digital output requires an external power supply.
Note 6: Using the terminals as fail output requires an external power supply.
Note 7: If you change a function using the parameter concerned, enter the setting in the relevant

Replacement with YS80 Internal Unit-compatible Type and EBS, I, EK, or HOMAC-compatible Type
field in the User settings column. 4

TI 01B08A02-06EN 3-15
Blank Page
Chapter 4 Replacement with YS80-compatible Type

4.1 Replacement with YS80-compatible Type 1

Replace the YS80 and its housing with the YS1000. The model and suffix codes are
YS1oo0-o4o.
2

3
4.2 Panel Mounting Method
Follow the same procedure as for the YS80. 4
If the YS1000 is installed at an end in single mounting or side-by-side mounting, the
separately sold mounting kit (MTY) is required.

Replacement with YS80-compatible Type


► Mounting: Installation Manual for Panel-mounted Instruments (IM 1B4F1-01E)

4.3 YS1oo0-o4o External Dimensions


4.3.1 External Dimensions

Unit: mm

67
When swung up
53 Note 1
Instrument panel thickness 2.3 to max. 25
60
60

13
136.4

(186)
144

170
177

(33.6)
33

70 22 443.8
493.8 (6)

Weight: 3.4 kg (excluding mounting kit)

Note 1: If a nameplate, etc. is installed within 60 mm above the instrument, the thickness of the
nameplate, etc. must be 30 mm or less from the panel surface.
Note 2: To ensure good air ventilation, allow space of 100 mm or more at the top and bottom of the
panel.
Note 3: General tolerance = ± (value of tolerance class IT18 based on JIS B 0401-1998) / 2

TI 01B08A02-06EN 4-1
4.3 YS1oo0-o4o External Dimensions

4.3.2 Panel Cutout Dimensions


For Single Mounting
140 or more

172±0.5
260 or more

80±0.5


For Side-by-side Mounting
B

172±0.5
(Top view)
260 or more

(Front)
MTY MTY

(Front view)

Number of
Units 1 2 3 4 5 6 7 8
Location
A* 87 157 227 297 367 437 507 577
B 80+10 150+10 220+10 290+10 360+10 430+10 500+10 570+10

Number of
Units 9 10 11 12 13 14 15
Location
A* 647 717 787 857 927 997 1067
B 640+10 710+10 780+10 850+10 920+10 990+10 1060+10

*: The numerical values in line A include the MTY’s bezels.


Note
If the YS1000 is mounted at an end in single mounting or side-by-side mounting, attach the
separately sold mounting kit (MTY) to the housing.

4-2 TI 01B08A02-06EN
4.4 Terminals Layout 1

The terminal shapes and arrangements are the same as the YS1oo0-o2o.
► Terminals Layout: "2.4 Terminals Layout" and "2.5 Terminal Arrangment Table" in this manual.
2

Note 3
Compatible type for YS80: YS1oo0-o4o/A02, an external RJC is connected. This is different
from the existing YS100s.
Connect the provided RJC to terminals 20 and 21. (Mount the RJC at the terminal 21 side.)
4

Replacement with YS80-compatible Type

TI 01B08A02-06EN 4-3
Blank Page
Chapter 5 Replacement with 100 Line-compatible Type

5.1 Replacement with 100 Line-compatible Type 1

Replace the 100 line with the YS1000. The model and suffix codes are YS1oo0-o5o.
Install the YS1000 in the YS006 housing and then replace the 100 line with the YS1000.
2
The YS006 can be used with the YS1oo0-o50 (100V AC, 24V DC common power
supply) and YS1oo0-051 (220V AC power supply).
3

5.2 Panel Mounting Method 4


Follow the same procedure as the YS80.
If the YS1000 is installed at an end in single mounting or side-by-side mounting, the
separately sold mounting kit (MTP) is required.
5
► Mounting: Installation Manual for Panel-mounted Instruments (IM 1B4F1-01E)

Replacement with 100 Line-compatible Type


5.3 Housing Mounting Method
5.3.1 Mounting to a Housing
1. Connect the housing’s cable connector to the connector at the back of the YS1000.
2. Insert the YS1000 into the mounting kit by moving it along the housing frame until you
hear a click, which means the case is now fitted into and fastened to the housing.

(2)
Cable connector

Housing YS006
(1)

YS10-5


Figure 5.1 Connecting the connector of YS006

TI 01B08A02-06EN 5-1
5.3 Housing Mounting Method


Figure 5.2 Inserting YS1000 into a Housing

5.3.2 Removing the YS1000


Prepare a flat-blade screwdriver (with an end size of 7 mm or less).
1. Insert the screwdriver into the clearance at the lower part of the stopper key. This
causes the stopper key to be lifted up.
2. With the screwdriver inserted, pull out the YS1000 from the housing.
3. Disconnect the cable connector of the housing from the connector at the back of the
YS1000.
Stopper key

Screwdriver


Figure 5.3 Inserting Screwdriver into Clearance


Figure 5.4 Pulling YS1000 out of the Housing

5-2 TI 01B08A02-06EN
5.4 YS1oo0-o5o External Dimensions 1
Unit: mm
2

65
When swung up 3
53 Note 1

4
60

70

136.4
144

Replacement with 100 Line-compatible Type


8.5
13.9

22 345 5
Weight: 2.5 kg

Note 1: If a nameplate, etc. is installed within 60 mm above the instrument, the thickness of the
nameplate, etc. must be 30 mm or less from the panel surface.
Note 2: To ensure good air ventilation, allow space of 100 mm or more at the top and bottom of the
panel.
Note 3: General tolerance = ± (value of tolerance class IT18 based on JIS B 0401-1998) / 2

TI 01B08A02-06EN 5-3
5.5 YS006 (100 Line-compatible Housing) External
Dimensions
5.5.1 External Dimensions
Unit: mm

Instrument panel thickness 2.3 to max. 25


150

136
201.6

40
28.5
40.9

15
27
70 424 Support angle Rear view
Front view Recommended position of support angle 520 to 560

664
16.6 743

Weight: 4.3 kg (excluding mounting kit)

5.5.2 Panel Cutout Dimensions


For Single Mounting
140 or more
191±0.5
260 or more

80±0.5

5-4 TI 01B08A02-06EN
5.5 YS006 (100 Line-compatible Housing) External Dimensions

For Side-by-side Mounting


1
B

2
(Top view)

191±0.5
(Front)
4

260 or more
MTP MTP

5
(Front view)

Replacement with 100 Line-compatible Type


A

Number of
Units 1 2 3 4 5 6 7 8
Location
A* 90 160 230 300 370 440 510 580
B 80+10 150+10 220+10 290+10 360+10 430+10 500+10 570+10

Number of
Units 9 10 11 12 13 14 15
Location
A* 650 720 790 860 930 1000 1070
B 640+10 710+10 780+10 850+10 920+10 990+10 1060+10

*: The numerical values in line A include the MTP’s bezels.

Note
If the YS1000 is mounted at an end in single mounting or side-by-side mounting, attach the
separately sold mounting kit (MTP) to the housing.

5.6 Terminals Layout


The terminal shapes and arrangements are the same as the YS1oo0-o2o.
► Terminals Layout: "2.4 Terminals Layout" and "2.5 Terminal Arrangement Table" in this manual.

Note
Compatible type for 100 line: YS1oo0-o5o/A02, an external RJC is connected. This is
different from the existing YS100s.
Connect the provided RJC to terminals 20 and 21. (Mount the RJC at the terminal 21 side.)

TI 01B08A02-06EN 5-5
Blank Page
i

Revision Information
 Title : YS1000 Series Replacement Guide Installation and Wiring
 Manual No. : TI 01B08A02-06EN

June 2014/1st Edition


Newly published

n Written by Yokogawa Electric Corporation


n Published by Yokogawa Electric Corporation
2-9-32 Nakacho, Musashino-shi, Tokyo 180-8750, JAPAN