J 3688
J 3688
     
   
                          
                     
                  
              
                
                
        
                           
                 
                    
                     
                
      
                                                                                                                           I
                                                        
          
           Module Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AĆ1
          
           Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . BĆ1
          
           Sample AutoMate Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CĆ1
II
                                                
Figure 1.1 Ć Analog Rail Module Hardware Configuration . . . . . . . . . . . . . . . 1Ć3
                                                                                                                   III
                    
      The products described in this instruction manual are manufactured
      by Reliance Electric Industrial Company.
      The 4 Input 0Ć10 Volt Analog Rail module allows you to connect four
      input 0Ć10V analog signals to AutoMater, AutoMaxr and DCS 5000
      systems. Typically, the Analog Rail module is used with
      potentiometers, valve actuators, pressure or flow transducers, and
      meters in both drive control systems and process control systems.
      The Analog Rail module is hardwareĆconfigurable by means of a
      faceplate switch to emulate one of two types of devices, AutoMate
      Rails or AutoMate Local Heads. In some hardware configurations, the
      type of interface device available for the Analog Rail module will
      determine the mode of operation that can be selected (see
      figure 1.1).
      The Analog Rail module operates in Local Head mode when it is
      connected directly to one of the processor's four I/O ports in
      AutoMate systems, to an AutoMate Local I/O Processor, or to one of
      the four I/O ports of the DCS 5000/AutoMax Remote I/O Head in DCS
      5000/AutoMax systems. The Analog Rail data will take up four
      registers in the host when operating in Local Head mode.
      The module operates in Rail mode when it is connected to one I/O
      port of a Local I/O Head, which in turn is connected to one I/O port of
      an AutoMate processor. The Analog Rail module will occupy one
      register of the host in Rail mode. The Rail mode is used to expand
      the I/O address space available through the front I/O port of the
      processor by multiplexing each group of four analog points through
      one register. Note that the Analog Rail module cannot be used with
      the Local I/O Head in DCS 5000/AutoMax systems.
      The Analog Rail module operates in Rail mode when it is connected
      to one I/O port of the Power Module Interface (PMI) Processor
      (B/M 60000), which is in turn connected to a Universal Drive
      Controller (UDC) module (M/N 57552) which resides in an AutoMax
      rack.
      The remainder of this manual describes the functions and
      specifications of the module. It also includes a detailed overview of
      installation and troubleshooting procedures, as well as examples of
      configuration and programming.
                                                                                1Ć1
         JĆ3141    AutoMate 40 CONTROL PROCESSOR INSTRUCTION
                    MANUAL
         JĆ3150    AutoMate 30/40 SOFTWARE REFERENCE MANUAL
         JĆ3649    DCS 5000/AutoMax CONFIGURATION TASK
                    INSTRUCTION MANUAL
         JĆ3630    AutoMax PROGRAMMING EXECUTIVE INSTRUCTION
                    MANUAL
         JĆ3600    DCS 5000 ENHANCED BASIC LANGUAGE
                    INSTRUCTION MANUAL
         JĆ3675    AutoMax ENHANCED BASIC LANGUAGE
                    INSTRUCTION MANUAL
         JĆ3601    DCS 5000 CONTROL BLOCK LANGUAGE
                    INSTRUCTION MANUAL
         JĆ3676    AutoMax CONTROL BLOCK LANGUAGE
                    INSTRUCTION MANUAL
         JĆ3602    DCS 5000 LADDER LOGIC LANGUAGE
                    INSTRUCTION MANUAL
         JĆ3677    AutoMax LADDER LOGIC LANGUAGE INSTRUCTION
                    MANUAL
         JĆ3671    AutoMate LOCAL I/O HEAD INSTRUCTION MANUAL
         JĆ3750    ReSource AutoMax PROGRAMMING EXECUTIVE
                    INSTRUCTION MANUAL, VERSION 3.0
         J2Ć3045 AutoMax PROGRAMMING EXECUTIVE VERSION 3.3
         SĆ3006    DĆC DRIVE CONFIGURATION AND PROGRAMMING
                    INSTRUCTION MANUAL
         SĆ3008    POWER MODULE INTERFACE RACK INSTRUCTION
                    MANUAL
         Your personal computer and DOS operating system manual(s).
         IEEE 518 GUIDE FOR THE INSTALLATION OF ELECTRICAL
          EQUIPMENT TO MINIMIZE ELECTRICAL NOISE INPUTS TO
          CONTROLLERS
1Ć2
          The Analog Rail module can be configured with the hardware
          (purchased separately) listed in figure 1.1.
                                                          
DCS 5000/AutoMax
                          M/N 57C330                 Local Head
Remote I/O Head
                          M/N 45C20, 45C21,
AutoMate 20, 20E          45C220, 45C221,            Local Head or Rail *
                          45C224, 45C225
                          M/N 45C301, 45C305,
AutoMate 30, 30E                                     Local Head or Rail *
                          45C307
AutoMate 40, 40E          M/N 45C410, 45C411         Local Head or Rail *
AutoMate Local            M/N 45C200B
                                                     Local Head
I/O Processor             (and later versions)
AutoMate
                          M/N 45C37, 45C38           Local Head
Remote I/O Head
Power Module
                          B/M 60000                  Rail
Interface Processor
* Direct connection to the Processors (Local Head mode) or connection through
  an AutoMate Local I/O Head, M/N 45C22, 61C22, 61C22A, or 61C23 (Rail
  mode). Note that it is also permissible to configure the Analog Rail module for
  Rail mode even if it is connected directly to an AutoMate 20, 30, or 40
  Processor.
           Figure 1.1 ĆAnalog Rail Module Hardware Configuration
                                                                               1Ć3
2.0 MECHANICAL/ELECTRICAL
    DESCRIPTION
      The following sections describe the mechanical and electrical
      characteristics of the Analog Rail module.
                                                                          2Ć1
                                             
                          Analog Rail
                             61C346
                          0 to 10V Input
Input
                           PWR COM
                            OK  OK
                             Mode
                     Local
                     Head     Rail
                      Analog Inputs
                                  VĆIN
                     CH           Common
                      0
                                 
                                  VĆIN
                     CH           Common
                      1
                                 
                                  VĆIN
                     CH               Common
                      2
                                  VĆIN
                     CH           Common
                      3
                                 
                          Input Power
                                 DC-
                                            24
                                           VDC
                                 DC+
                                     L2
                                           120
                                           VAC
                                     L1
                     Fuse Type
                     250V MDQ
                                     24 VDC:
                                     Use 0.75A
                                     120 VAC:
                                     Use 0.25A
GND
2Ć2
The faceplate of the module contains three electrical connectors
labeled Input", Analog I/O", and Input Power" (reading top to
bottom). The top connector is used for connection to the I/O port. A
cable (M/N 45C5) is provided for this purpose. The second
connector, labeled Analog I/O", is a numbered, 12Ćpoint removable
plug connector with screwĆtype terminal points. Three successive
terminal points are reserved for each channel's connection to
external hardware. The Analog Inputs" terminals are designed for
14Ć22 AWG wire.
The third connector on the faceplate, also a removable plug
connector with screwĆtype terminal points, is used for input power.
The terminal points are labeled. The top two points are used if the
power source is 24 VDC. The bottom two points are used if the power
source is 120 VAC. The Input Power" terminals are designed to use
14 AWG wire. A terminal stud for connecting a grounding conductor
is provided on the bottom of the rightĆhand mounting flange.
The module faceplate also contains two LEDs, a mode switch, and a
fuse holder and fuse. The LED labeled PWR OK" indicates that the
I/O port, the external power source, and the internallyĆgenerated
voltages necessary for operation of the module are present. The
COM OK" LED indicates whether all four channels are successfully
communicating with the host.
The switch labeled Mode" is used to select between Local Head"
and Rail" mode. Note that the position of the switch is read only
once at the time power is turned on to the Reliance device that is
connected to the Analog Rail module. The mode will remain fixed as
long as this device is powered up.
As shipped from the factory, the fuse holder on the bottom of the
faceplate contains a .25A fuse for 120 VAC input power. If input
power will be 24 VDC, you need to replace the fuse with the .75A
fuse included along with the Analog Rail module.
                                                                       2Ć3
               
              The Analog Rail module contains four analog input channels that
              convert 0Ć10V analog input signals to proportional values between 0
              and 4095, equal to 12 bits of digital data. Input signals are filtered
              through a second order lowĆpass filter.
              The A/D conversions are triggered by the actual I/O update
              sequences. The conversion rate is therefore dependent upon the
              scan time of the application task. See figure 2.2 for a typical input
              circuit.
                    90K                                                   to A/D
      VĆIN                                                               converter
                                   90K
      VĆOUT
2Ć4
3.0 INSTALLATION
         This section describes how to install and replace the Analog Rail
         module. Note that analog signals are sensitive to variations in
         temperature. The Analog Rail module is designed to perform
         optimally at room temperature, approximately 25oC. In all cases, the
         ambient temperature of the installation must be maintained in the
         range specified in Appendix A to ensure the highest possible
         accuracy.
                          DANGER
THE USER IS RESPONSIBLE FOR CONFORMING WITH THE NATIONAL
ELECTRICAL CODE AND ALL OTHER APPLICABLE LOCAL CODES. WIRING
PRACTICES, GROUNDING, DISCONNECTS, AND OVERĆCURRENT
PROTECTION ARE OF PARTICULAR IMPORTANCE. FAILURE TO OBSERVE
THIS PRECAUTION COULD RESULT IN SEVERE BODILY INJURY OR LOSS OF
LIFE.
                          DANGER
DO NOT TOUCH THE CONNECTORS ON THE FACEPLATE IF THERE IS
POWER ON THE WIRES ATTACHED TO THE PLUG CONNECTOR SCREW
TERMINALS. ALWAYS TURN OFF POWER BEFORE HANDLING A
CONNECTOR THAT IS WIRED. FAILURE TO OBSERVE THIS PRECAUTION
COULD RESULT IN SEVERE BODILY INJURY OR LOSS OF LIFE.
                           CAUTION
THE ANALOG RAIL MODULE IS DESIGNED TO BE POWERED BY EITHER 24
VDC OR 120 VAC. CONNECT THE PROPER POWER SOURCE TO THE
MODULE. FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN
DAMAGE TO OR DESTRUCTION OF THE EQUIPMENT.
3.1      Wiring
         To reduce the possibility of electrical noise interfering with the proper
         operation of the control system, exercise care when installing the
         wiring between the module and the external hardware.
         Use shielded twisted pair for all wiring between the Analog Rail
         module and the external hardware. Belden 8761 or an equivalent
         cable type is recommended. Cable lengths should be limited to 50
         feet maximum. For detailed recommendations refer to IEEE 518.
                                                                                     3Ć1
               
        Use the following procedure to install the Analog Rail module.
        Step 1.   Using the mounting dimensions shown in figure 3.1,
                  prepare the necessary mounting provisions on the panel.
                  The module is designed to be mounted vertically using
                  four #10 or M5 bolts or studs. Multiple modules should be
                  mounted side by side. The flange width of two modules
                  side by side is sufficient to dissipate the heat produced by
                  the modules. The modules can also be mounted one
                  above the other, but since this hardware configuration
                  does not allow the most efficient heat dissipation, the
                  minimum clearance between the module chassis is 3".
                  See figure 3.1.
2.44"
7.0" 9.25"
2.94"
3.0"
                                          Depth: 7.75"
                                          Diameter of mounting holes: 7/32"
3Ć2
            Step 2.   If the power supply you are using is 24 VDC, replace the
                      factoryĆinstalled .25A fuse with the .75A fuse that came in
                      the shipping box with the module. Use a screwdriver to
                      release the fuse holder located on the Analog Rail module
                      faceplate. Pull the fuse holder out of the module.
                      Take the .25A fuse out of the fuse holder and replace it
                      with the .75A fuse. ReĆinsert the fuse holder into the
                      module. Turn the screwdriver clockwise while pressing
                      down on the fuse holder. The fuse holder must be flush
                      against the faceplate.
            Step 3.   Mount the Analog Rail on the panel and attach it securely
                      with #10 (M5) studs or bolts.
            Step 4.   Make certain that no voltage is present on the wires that
                      will be used to provide 120 VAC or 24 VDC power to the
                      Analog Rail module. Use either a 120 VAC or 24 VDC
                      power supply, but not both.
            Step 5.   Using 14 AWG wire, connect input power to the screw
                      terminals on the Input Power" plug connector on the
                      faceplate as shown below. Strip off approximately 5/16" of
                      insulation from the wires.
                               24 VDC Power
Signal                      Terminal Label                      Terminal Number
24 VDC -                        DC-                                    1
24 VDC +                        DC+                                    2
            Step 6.   Use the stud marked GND" (ground) on the bottom right
                      flange of the module to connect a ground wire.
                           DANGER
 THE USER IS RESPONSIBLE FOR CONFORMING WITH THE NATIONAL
 ELECTRICAL CODE AND ALL OTHER APPLICABLE LOCAL CODES. WIRING
 PRACTICES, GROUNDING, DISCONNECTS, AND OVERĆCURRENT
 PROTECTION ARE OF PARTICULAR IMPORTANCE. FAILURE TO OBSERVE
 THIS PRECAUTION COULD RESULT IN SEVERE BODILY INJURY OR LOSS OF
 LIFE.
            Step 7.   Turn off all power to any external hardware that will
                      provide input signals to the module or be powered by the
                      module.
            Step 8.   Attach a retainer clip to the connector at each end of the
                      I/O Rail cable (M/N 45C5). Note that faceplate connectors
                      have slots that correspond to the part of the retainer clip
                      that protrudes away from the cable connector. The retainer
                      clip is used to assure a tight connection between the cable
                      and faceplate connectors.
                                                                                    3Ć3
               Step 9.     Using 14Ć22AWG wire, connect external hardware to the
                           Analog Inputs" plug connector on the faceplate as shown
                           below. Strip off approximately 5/16" insulation from the
                           wires.
                                   
                                                    
         0                 1              VĆIN       0Ć10V+ input
                           2           Common        common
                           3           (no label)    (shield; no connection)*
         1                 4              VĆIN       0Ć10V+ input
                           5           Common        common
                           6           (no label)    (shield; no connection)*
         2                 7              VĆIN       0Ć10V+ input
                           8           Common        common
                           9           (no label)    (shield; no connection)*
         3                 10             VĆIN       0Ć10V+ input
                           11          Common        common
                           12          (no label)    (shield; no connection)*
  * This pin makes no electrical connection to the Analog Rail printed circuit
    board.
               Step 10.    For the four input channels, connect a shield wire from the
                           external hardware to the third terminal (terminals 3, 6, 9
                           and 12, respectively) on each channel. The shield wire at
                           the external hardware end of the cable should be
                           connected to the source reference point. See figure 3.2.
3Ć4
                                                                                     Source
            VĆIn        1
Channel 0                                                                            +   -
            Common 2
                                                                                 I
                        3
                                                                                     Source
            VĆIn        4
Channel 1                                                                            +   -
            Common 5
                                                                                 I
                                                                                     Source
            VĆIn        7
Channel 2                                                                            +   -
            Common 8
                                                                                 I
                                                                                     Source
            VĆIn    10
Channel 3                                                                            +   -
            Common 11
                                                                                 I
12
             Step 11.       Turn off power to the Reliance device that will be
                            connected to the Analog Rail module.
             Step 12.       Set the Mode" switch on the faceplate of the module to
                            the desired position.
             Step 13.       Connect the I/O Rail cable between the Analog Rail
                            connection labeled Input" and an I/O port on the
                            Reliance device that will communicate with the module.
                            Turn on power to the Reliance device that will
                            communicate with the module. Recall that the Mode
                            switch is read each time the Reliance device connected to
                            the Analog Rail module is powered up.
             Step 14.       The Analog Rail installation is now ready for testing.
                            Inspect all work to assure that the installation has been
                            performed properly.
             Step 15.       Turn on power to the Input Power" wiring. Turn on power
                            to the external hardware. See Appendix A for power
                            supply specifications.
             Step 16.       Verify that the hardware has been installed correctly.
                            Before testing, insure that the external hardware will not
                            respond to output signals from the Analog Rail module.
                                                                                          3Ć5
                   For AutoMate systems, you must configure the AutoMate
                   processor using the AutoMate Programming Executive
                   (APX) before testing. See section 4.0 for more information.
                   After configuring the module, use the APX Point Monitor
                   function to test the module. You can test the Analog Rail
                   module input channels by verifying that the input signal in
                   the channel (0 to 10V) is proportional to a voltmeter
                   reading at the terminal points.
                   For DCS 5000, AutoMax, or Distributed Power DĆC Drive
                   systems, use the DCS 5000 or AutoMax Programming
                   Executive software I/O Monitor function, respectively. To
                   test the input channels, verify that the input signal in the
                   channel (0 to 10V) is proportional to a voltmeter reading at
                   the terminal points.
                               
        Use the following procedure to replace the module.
        Step 1.    Stop any application programs that are running.
        Step 2.    Turn off power to the external hardware connected to the
                   input channels on the faceplate of the module.
        Step 3.    Turn off power to the Analog Rail module (120 VAC or
                   24 VDC).
        Step 4.    Turn off power to the Reliance device connected to the
                   Analog Rail module.
        Step 5.    Disconnect the I/O Rail cable from the Analog Rail module.
        Step 6.    Without disconnecting the wiring, remove the 12Ćpoint
                   terminal from the faceplate and set aside.
        Step 7.    Without disconnecting the wiring, remove the 4Ćpoint
                   terminal from the faceplate and set aside. Disconnect the
                   ground wire from the bottom rightĆhand flange.
        Step 8.    Loosen the screws that hold the Analog Rail module to the
                   panel and remove the module.
        Step 9.    If the power supply you are using is 24 VDC, you need to
                   replace the factoryĆinstalled .25A fuse in the new module
                   with the .75A fuse that came in the shipping box with the
                   module. Use a screwdriver to release the fuse holder
                   located on the Analog Rail module faceplate. Pull the fuse
                   holder out of the module.
                   Take the .25A fuse out of the fuse holder and replace it
                   with the .75A fuse. ReĆinsert the fuse holder into the
                   module. Turn the screwdriver clockwise while pressing
                   down on the fuse holder at the same time. The fuse holder
                   must be flush against the faceplate.
        Step 10.   Remove the two plug connectors from the faceplate of the
                   new module by pulling them firmly away from the
                   faceplate.
        Step 11.   Place the new module over the pattern drilled and attach it
                   securely to the wall with #10 or M5 studs or bolts.
        Step 12.   Attach the original 12Ćpoint and 4Ćpoint connectors with
                   wiring to the faceplate of the module. Use the stud marked
                   GND" (ground) on the bottom right flange of the module
                   to connect a ground wire.
3Ć6
Step 13.   Set the Mode" switch on the faceplate of the module to
           the desired position.
Step 14.   Connect the I/O Rail cable between the Analog Rail
           connection labeled Input" and any rail connector on the
           Reliance device that will communicate with the module.
           Turn on power to the Reliance device connected to the
           module. Recall that the Mode switch is read each time the
           Reliance device connected to the Analog Rail module is
           powered up. If applicable, reĆconnect the cable between
           the Local I/O Head, or the DCS/AutoMax Remote I/O
           Head, and the host.
Step 15.   Turn on power to the Analog Rail module Input Power"
           connections.
Step 16.   Turn on power to the external hardware connected to the
           Analog Rail module.
Step 17.   Verify that the hardware has been installed correctly.
           For AutoMate systems, use the APX Point Monitor function
           to test the module. To test the input channels, verify that
           the input signal in the channel (0 to 10V) is proportional to
           a voltmeter reading at the terminal points.
           For DCS 5000, AutoMax, or Distributed Power DĆC Power
           systems, use the DCS 5000 or AutoMax Programming
           Executive software I/O Monitor function, respectively. To
           test the input channels, verify that the input signal in the
           channel (0 to 10V) is proportional to a voltmeter reading at
           the terminal points.
                                                                           3Ć7
4.0 PROGRAMMING
              This section describes how the data is organized in the module and
              provides examples of how the module is accessed by application
              programs.
              When creating application programs, the programmer should
              estimate the magnitude of input signals because they must be in the
              specified range of the Analog Rail module (0Ć10V). Input signals
              greater than 10V will be clamped at 4095. Input signals greater than
              approximately 11.3V will also cause the overĆrange bit (12 decimal;
              14 octal) to be set to 1. Signals less than 0V are clamped at zero (0).
              Signals less than approximately -1V will also cause the underĆrange
              bit (13 decimal; 15 octal) to be set to 1. See figure 4.1.
 Counts
                                                            >11.3 = overĆrange
       4095
                                                                        Volts
       -1     0   1   2     3   4   5   6   7   8   9 10 11
      <-1 = underĆrange
                                                                                        4Ć1
                
                        
               Configuration is the process of describing in software how the
               hardware and software in the system are related. The Analog Rail
               module is configured using the AutoMate Programming Executive
               (APX) software, M/N 45C130 or 45C131. Select CONFIGURE
               SYSTEM from the main menu to create the configuration.
               Note that the Analog Rail module can also be configured using the
               AutoMate Programming System (APS) software, M/N 45C134,
               45C141, 45C142, or 45C143. Refer to instruction manual J2Ć3041 for
               additional information.
               The Analog Rail module is configured depending upon the mode in
               which it is being used. See figures 4.2, 4.3, 4.4, 4.5, and 4.6 for how
               to configure the Analog Rail for use with AutoMate processors. The
               sample configurations are shown as they appear on the APX screen.
               Unless otherwise noted, all references to the AutoMate 20, 30, and 40
               will also apply to the 20E, 30E and the 40E, respectively.
                                       Rail Mode
  Enter the value 16XX for the register representing the port to which the Analog Rail
  module is connected, where XX is a value from 00Ć17*. The XX value
  represents the register that will be used to multiplex data through the I/O port.
  *Values are in octal notation.
4Ć2
          Analog Rail Module Connected Directly to AutoMate 30 or 40
                       (Local Head Mode or Rail Mode)
 The following sample configuration shows two Analog Rail modules connected
 directly to an AutoMate 30 or 40 Processor in Local Head mode:
 MSLT DROP TYP RSLT CARD CH0 REGISTER CH1 REGISTER CH2 REGISTER CH3 REGISTER
 ă1                 A/M  LHD ăă0Ć3    LHD ăă4-7    NU           NU
 The following sample configuration shows two Analog Rail modules connected
 directly to an AutoMate 30 or 40 Processor in Rail Mode :
 MSLT DROP TYP RSLT CARD CH0 REGISTER CH1 REGISTER CH2 REGISTER CH3 REGISTER
 ă1                 A/M  RAIL ăăă0    RAIL ăăăă1   NU           NU
Figure 4.3 Ć Sample Configurations for Analog Rail Module Connected Directly
             to AutoMate 30 or 40
                                                                               4Ć3
      Analog Rail Module Connected to AutoMate 30 or 40 Through a Local I/O Head
                                  (Rail Mode Only)
 The following sample configuration shows two Analog Rail modules connected to
 an AutoMate 30 or 40 through a Local I/O Head:
 MSLT DROP TYP RSLT CARD CH0 REGISTER CH1 REGISTER CH2 REGISTER CH3 REGISTER
 ă1                 A/M  LHD ăăă0Ć3   NU           NU           NU
4Ć4
Analog Rail Module with AutoMate Local I/O Processor (Local Head Mode Only)
The following sample configuration shows three Analog Rail modules connected to
a Local I/O Processor in a remote rack:
MSLT DROP TYP RSLT CARD CH0 REGISTER CH1 REGISTER CH2 REGISTER CH3 REGISTER
ă2   ă1   RRK ăă2 LIOP LHD ăăă0-3    LHD ăăă4Ć7   LHD ăă10Ć13  NU
     Figure 4.5 Ć Sample Configuration for Analog Rail Module with AutoMate
                  Local I/O Processor
                                                                                  4Ć5
      Analog Rail Module with AutoMate Remote I/O Head (Local Head Mode Only)
 The following sample configuration shows one Analog Rail module connected to
 an AutoMate Remote I/O Head:
 MSLT DROP TYP RSLT CARD CH0 REGISTER CH1 REGISTER CH2 REGISTER CH3 REGISTER
 ă2   ă0   RHD           LHD ăăă0-3   NU           NU           NU
         Figure 4.6 Ć Sample Configuration for Analog Rail Module with AutoMate
                      Remote I/O Head
4Ć6
                              
          In Rail mode, the Analog Rail module is imaged in one I/O register of
          the processor. Data from one of the four channels will occupy the
          register as a function of the channel select bits. The active channel is
          updated at the end of each scan. For input channels, the two channel
          select bits in the register must be set to the appropriate input channel
          number. After the I/O update, the register contains the data in the
          format shown in figure 4.7.
Octal 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0
          The Analog Rail module data may also be accessed in the middle of
          the scan (as opposed to the end of the scan, which is the normal
          mode of operation for digital rail I/O) using the appropriate number of
          Analog In (AIN) blocks. The AIN block will check whether the
          overĆrange or underĆrange bits have been set by the module and the
          error coil will be energized, if applicable. See section 4.1.4 for more
          information about the AIN block.
          Note that the AIN block is supported by the AutoMate 20E
          M/N 45C224 and 45C225, but not the AutoMate 20 (M/N 45C20,
          45C21, 45C220, 45C221) by APX Version 3.0 and later.
          For processors that do not support the AIN block, you can use the
          MOVE block to move data in and out of the registers assigned and to
          determine the channel select bits. OverĆrange and underĆrange bits
          should be used as inputs to error coils. The I/O update will occur
          automatically at the end of each scan. See Appendix C for a sample
          AutoMate program that reads from the Analog Rail module without
          using AIN blocks.
                                                                                     4Ć7
  4.1.3      AutoMate Programming in Local Head Mode
             In Local Head mode, the module is imaged in four I/O registers of the
             processor. Data from all four channels is always available and will be
             updated at the end of each scan. It is not necessary to select the
             channel. After the I/O update, the register contains the data in the
             format shown in figure 4.8.
Octal 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0
             The Analog Rail module data may also be accessed in the middle of
             the scan (as opposed to the end of the scan) using the appropriate
             number of Analog In (AIN) blocks. The AIN block will set the
             overĆrange or underĆrange bits if applicable. See section 4.1.4 for
             more information about the AIN block.
             Note that the AIN block is supported by the AutoMate 20E
             M/N 45C224 and 45C225, but not the AutoMate 20 (M/N 45C20,
             45C21, 45C220, 45C221) by APX Version 3.0.
             For processors that do not support the AIN block, you can use the
             MOVE block to move data in and out of the registers assigned.
             OverĆrange and underĆrange bits should be used as inputs to error
             coils. The I/O update will occur automatically at the end of each scan.
             See Appendix C for a sample AutoMate program that reads from the
             Analog Rail module without using the AIN block.
4Ć8
                      
           The AIN block is used to read inputs from the Analog Rail module.
           AIN is supported for the A20E. The AIN block makes it possible to
           update the channels on the Analog Rail module during the scan
           instead of at the end of the scan (the standard AutoMate I/O update).
           The block also makes it possible to update all four channels during
           the scan in Rail mode, a hardware configuration which would
           otherwise allow only one channel on the module to be updated. The
           format of the AIN block is shown in figure 4.9.
AIN
    12                                                                         13
   .01                                                                        .01
   [ ]                                             EN                    EN   ( )
                                                            AIN
                                                      IOPORT:     2
                                                      LHPORT:     0
                                                        CHAN:     3            76
                                                        DEST:     2000        .00
                                                       VALUE:            ER   ( )
                                                                                    4Ć9
   4.2     Analog Rail Module in DCS 5000/AutoMax
           Systems
           This section describes how the Analog Rail module is used with
           DCS 5000/AutoMax systems.
           where:
           nnnnn Ć Configuration task line number; range 1Ć32767.
           name Ć Symbolic name of channel, ending with % (integer) for
                  registers, @ (booleans) for bits.
           m        Ć Slot in rack containing DCS 5000/AutoMax master remote
                      I/O module; range 0Ć15.
           d        Ć Drop number of DCS 5000/AutoMax Remote I/O Head;
                      range 1Ć7.
           s        Ć Communication port on the DCS 5000/AutoMax Remote
                      I/O Head to which the Analog Rail module or Local I/O
                      Head is connected; range 0Ć3.
           r        Ć Register number; range 0Ć3.
           b        Ć Optional field defining the bit position within the register
                      number; range 0Ć15.
4Ć10
4.2.3   DCS 5000/AutoMax Programming
        When programming the Analog Rail module, it is recommended that
        you monitor the state of the overĆrange and underĆrange bits for the
        input channels. You can check the status of the appropriate bits
        directly if they were defined in the configuration. You can also use the
        BASIC expression AND with the variable name assigned to the input
        channel to mask off the 12 bits of analog data and read the values in
        the overĆrange and underĆrange bits. Any nonĆzero result means that
        the value is out of range. See the following three statements for
        examples of how to detect values out of range. Use the hexadecimal
        values shown to mask off the analog data.
        The value in the channel defined as CHANNEL_2 is either overĆrange
        or underĆrange:
            10000 RANGE_ERROR@ = CHANNEL_2 AND 3000H
        The value in the channel defined as CHANNEL_2 is overĆrange:
            11000 OVER_ERROR@ = CHANNEL_2 AND 1000H
        The value in the channel defined as CHANNEL_2 is underĆrange:
            12000 UNDER_ERROR@ = CHANNEL_2 AND 2000H
                                                                              4Ć11
5.0 DIAGNOSTICS AND
    TROUBLESHOOTING
                           DANGER
THE REMAINING STEPS ARE MADE WITH POWER ON. EXERCISE EXTREME
CAUTION BECAUSE HAZARDOUS VOLTAGE EXISTS. FAILURE TO OBSERVE
THIS PRECAUTION COULD RESULT IN SEVERE BODILY INJURY OR LOSS OF
LIFE.
                                WARNING
ONLY QUALIFIED ELECTRICAL PERSONNEL FAMILIAR WITH THE
CONSTRUCTION AND OPERATION OF THIS EQUIPMENT AND THE HAZARDS
INVOLVED SHOULD INSTALL, ADJUST, OPERATE, AND/OR SERVICE THIS
EQUIPMENT. READ AND UNDERSTAND THIS MANUAL IN ITS ENTIRETY
BEFORE PROCEEDING. FAILURE TO OBSERVE THIS PRECAUTION COULD
RESULT IN BODILY INJURY.
                                WARNING
INSERTING OR REMOVING THIS PRODUCT OR ITS CONNECTING CABLES
MAY RESULT IN UNEXPECTED MACHINE MOTION. POWER TO THE MACHINE
SHOULD BE TURNED OFF BEFORE INSERTING OR REMOVING THE PRODUCT
OR ITS CONNECTING CABLES. FAILURE TO OBSERVE THIS PRECAUTION
COULD RESULT IN BODILY INJURY.
                                                                                 5Ć1
                                   DANGER
  VOLTAGE IS PRESENT ON THE PLUG CONNECTOR TERMINALS. DISCONNECT
  THE POWER AT THE SOURCE BEFORE TOUCHING THE PLUG CONNECTOR
  TERMINALS. FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN
  SEVERE BODILY INJURY OR LOSS OF LIFE.
                                   DANGER
  DO NOT TOUCH THE CONNECTORS ON THE FACEPLATE IF THERE IS POWER
  ON THE WIRES ATTACHED TO THE PLUG CONNECTOR SCREW TERMINALS.
  ALWAYS TURN OFF POWER BEFORE HANDLING A CONNECTOR THAT IS
  WIRED. FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN SEVERE
  BODILY INJURY OR LOSS OF LIFE.
            Step 2.   Turn off power to the module. Verify that the input power
                      connector is connected securely to the faceplate. Verify
                      that the I/O Rail cable connections are tight at both ends.
            Step 3.   Turn on power to the module. If the LEDs are still off, try
                      replacing the I/O Rail cable. Check that the input
                      connector pins are not bent.
            Step 4.   If the LEDs are still off, turn off power to the module and
                      replace the power supply fuse on the front panel following
                      the directions below.
                                   CAUTION
  MAKE CERTAIN THAT THE ANALOG RAIL MODULE CONTAINS THE PROPER
  FUSE FOR THE POWER SUPPLY BEING USED. USE A .25 A FUSE FOR 120 VAC
  POWER AND A .75A FUSE FOR 24 VDC POWER. FAILURE TO OBSERVE THIS
  PRECAUTION COULD RESULT IN DAMAGE TO OR DESTRUCTION OF THE
  EQUIPMENT.
5Ć2
5.2       The COM OK" LED is Off
          Problem: The COM OK" LED on the faceplate is off. This LED
          signifies whether there is communication between the Analog Rail
          and the host. The LED should be on if communication is taking
          place. The possible causes of this problem are incorrect
          configuration, a disconnected or malfunctioning I/O Rail cable, a
          malfunctioning host, or a malfunctioning Analog Rail module. After
          verifying that the configuration of the Analog Rail is correct, follow the
          steps below to isolate the problem.
          Step 1.    Stop any application programs or tasks that are running
                     and turn off power to the Analog Rail module.
                                   DANGER
VOLTAGE IS PRESENT ON THE PLUG CONNECTOR TERMINALS. DISCONNECT
THE POWER AT THE SOURCE BEFORE TOUCHING THE PLUG CONNECTOR
TERMINALS. FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN
SEVERE BODILY INJURY OR LOSS OF LIFE.
                                   DANGER
DO NOT TOUCH THE CONNECTORS ON THE FACEPLATE IF THERE IS POWER
ON THE WIRES ATTACHED TO THE PLUG CONNECTOR SCREW TERMINALS.
ALWAYS TURN OFF POWER BEFORE HANDLING A CONNECTOR THAT IS
WIRED. FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN SEVERE
BODILY INJURY OR LOSS OF LIFE.
          Step 2.    Verify that the connections on both ends of the I/O Rail
                     cable are tight. Check that the input connector pins are
                     not bent.
          Step 3.    Turn on power to the module. The COM OK" LED should
                     be illuminated if communication is taking place. If the LED
                     still does not illuminate, turn off power to the module and
                     replace the I/O Rail cable.
          Step 4.    If applicable, try to reset the condition by disconnecting
                     and then reĆconnecting the cable between the host and
                     the Local I/O Head, the AutoMate Remote I/O Head, or the
                     DCS 5000/AutoMax Remote I/O Head. Troubleshoot the
                     host if necessary. If the problem is still not corrected,
                     replace the Analog Rail module.
                                                                                       5Ć3
        Step 1.    Verify that the application program(s) is correct. Check to
                   see that the program is referencing the correct registers
                   (AutoMate) or symbolic names (DCS 5000/AutoMax).
                   In DCS 5000/AutoMax applications, make certain that the
                   program is not attempting to write to the input channels.
        Step 2.    Stop any application tasks that are running. Turn off power
                   to the Analog Rail module.
        Step 3.    Try to clear the condition by disconnecting and then
                   reĆconnecting the I/O Rail cable. Make certain the
                   connections are tight. If applicable, check the connections
                   between the host and the Local I/O Head, the AutoMate
                   Remote I/O Head, or the DCS 5000/AutoMax Remote I/O
                   Head. Check that the input connector pins are not bent.
        Step 4.    Turn off power to the external hardware. Verify that the
                   wiring to the external hardware is tight and functioning
                   correctly.
        Step 5.    Turn on power to the external hardware.
                   Use the Executive software to read the value on the input
                   channels. Use a voltmeter to read the input signal and
                   compare the two. If the signal is being converted correctly,
                   there is a problem with the external hardware or wiring.
        Step 6.    Troubleshoot the external hardware, the wiring, and the
                   host.
5Ć4
                         Appendix A
                 Technical Specifications
Ambient Conditions
  D Storage temperature: -40oC to 85oC
                         -40oF to 185oF
  D Operating temperature (at the module): 0_C to 60_C
                                           32_F to 140_F
  D Humidity: 5Ć90% nonĆcondensing
Dimensions
  D Height: 9.25 inches (23.5 cm)
  D Width: 2.94 inches (7.5 cm)
  D Depth: 7.75 inches (19.1 cm including plugĆin connectors)
  D Weight: 4.5 lbsă(2.1 kg)
                                                                AĆ1
                                           
                                    
                 
         Operating range: 0Ć10 VDC
         Number of channels: 4 (singleĆended)
         Number of commons: 1 (shared among all 4 channels)
         Resolution: 12 bits binary
         NonĆlinearity: + 1 LSB maximum
         Accuracy: +.33% of full scale at 25oC maximum
         Thermal drift: + 50 ppm/degree C
         Type of converter: Successive approximation
         Speed of conversion: 13 usec
         Impedance: 180K Ohm + 0.2%
         Input filter: 2nd order 160Hz low pass
         Input overvoltage protection: + 115 VDC continuous
         Isolation of analog section from host and input power: 2500V RMS
AĆ2
                                    LOCAL HEAD OR RAIL MODE SWITCH
                                                                                          RESET
                  GND                                                                   CIRCUITRY
                                                                                                                 ISOLATION
        12 PNT.                                                                            MAIN                  BOUNDARY
                                                             HOST                       CONTROL
         HOST           SERIAL HOST INTERFACE             INTERFACE
      CONNECTOR                                                                         CIRCUITRY
                                                          CIRCUITRY
                                COMMUNICATION LED
                Vcc
                                POWER LED
                                                                                       PRECISION
                                                                                      VOLTAGE REF
                        ISOLATED                                                         VREF
                                                                                                          VREF
                        CONTROL
                        CIRCUITRY
                                                                                                                  AMP
                                                                                                                             +
                                                                       OVER/UNDER
                                                                      RANGE DETECT                                           0-10V IN
                                                                        CIRCUITRY
                        PARALLELĆ         A/D CONTROL                                                                        -
                         SERIAL
                        REGISTER                     S
                                                      I
                                         DATABUS     G
                                                     N
                                                     A
                                                     L
                                                     S                                                            AMP
                                                                                                      FILTER                 +
                                                                                                                             0-10V IN
                                                                                                                                            
                                                                                                      FILTER
         DĆC+                                                                                MUX                             -
                                                                                                                                                        
                                                          ISOLATED POWER
                                                                                                      FILTER
         DĆC-              ISOLATED
         AĆC                ANALOG
                            POWER                                                                     FILTER
                                                                                                                  AMP
         AĆC                                                                                                                 +
                                                                                                                             0-10V IN
                                                                       ANALOG
                                                                        DIGITAL                                              -
                                                                      CONVERTER
                                                                                            SAMPLE/
                                                                                             HOLD
                                                                                                                  AMP
                                                                                                                             +
0-10V IN
BĆ1
                                 
                                 
The following AutoMate program sequences can be used to interface to an
AutoMate Processor that does not support the AIN block. Over a period of four
scans, the program below inputs four channels from an Analog Rail module in
Rail mode.
Registers Used
0           Register that is configured to be updated at the end of scan.
40          Value input from channel 0
41          Value input from channel 1
42          Value input from channel 2
43          Value input from channel 3
44          Counter to select channel to operate this scan
45          Coils
                                                                                     CĆ1
                                         
                                                
  If channel 2 was read in, put the data in register 42.
                                     Ă44.00    Ăă0.16
                                      [ăă]      (ăă)
                                     Ă44.01    Ăă0.17
                                      [ăă]      (ăă)
                                                                           Ă45.10
                                                    EN      ADD      EN     (ăă)
                                                    LENGTH: 1
                                                        SRC: 44
                                                      SCR 2: K1
                                                       DEST: 44
                                                                           Ă45.11
                                                    EN      ADD      EN     (ăă)
                                                    LENGTH: 1
                                                        SRC: 44
                                                      SCR 2: K3
                                                       DEST: 44
CĆ2
    / 24703 Euclid Avenue / Cleveland, Ohio 44117 / 216Ć266Ć7000