FBs 2LC Datasheet en

The FBs-2LC is a dual-channel load cell input module designed for FATEK FBs series PLCs, featuring a resolution of 16 bits and a conversion rate of 1/3/5/8 Hz. It supports weight measurement with configurable sensitivity options and includes features for noise filtering and calibration. The module requires specific software for configuration and is compatible with certain versions of PLC OS and Winproladder.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
6 views3 pages

FBs 2LC Datasheet en

The FBs-2LC is a dual-channel load cell input module designed for FATEK FBs series PLCs, featuring a resolution of 16 bits and a conversion rate of 1/3/5/8 Hz. It supports weight measurement with configurable sensitivity options and includes features for noise filtering and calibration. The module requires specific software for configuration and is compatible with certain versions of PLC OS and Winproladder.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

FBs-2LC Dual-Channel Load Cell Input Module

Specifications
Total Channels - 2
Resolution- 16 bits (include signed bit)
I/O Points Occupied - 1 RI(Input Register) and 8 DO
Conversion Rate- 1/3/5/8 Hz
Non-Linearity- 0.01% F.S. (@25℃)
Zero Drift- 0.2 µV/℃
Gain Drift- 10 ppm/℃
Excitation Voltage – 5V with 100Ω driving capability
Sensitivity - 2mV/V, 5mV/V, 10mV/V, 20mV/V
Software Filter- Moving average
Introduction Average Samples- 1~8 configurable
FBs-2LC is one of the analog input modules Isolation- Transformer(Power) and photo-coupler(Signal)
of FATEK FBs series PLC. It supports two Indicator(s) - 5V PWR LED
channels of load cell input for weight Supply Power- 24V-15%/+20%, 2VA
measurement. The raw conversion result is Internal Power Consumption- 5V, 100mA
represented by a signed 16 bit integer value. Operating Temperature- 0 ~ 60 ℃
In order to filter out the field noise imposed Storage Temperature- -20 ~ 80 ℃
Dimensions- 40(W)x90(H)x80(D) mm
on the signal, it also provides the average of
sample input function.

Dimensions

1/3
FBs-2LC Dual-Channel Load Cell Input Module

Wiring Diagram

24V+
24V
24V-

+5V +EXC

CH0+ R R

16-Bit Data 24-Bit +


Δ-Σ -
A/D
CH0- R R

-EXC
Load Cell #0

+5V +EXC

CH1+
16-Bit Data 24-Bit
Δ-Σ Load Cell #1
A/D CH1-

-EXC

The raw conversion result is represented by a 16-bit signed value. After setting the full range engineering
value and perform the zero and full scale calibration procedure, the system will automatically convert the
raw conversion reading value into engineering weight value for user application.

2/3
FBs-2LC Dual Channel Load Cell Input Module

PLC Control

Before FBs-2LC module can be working, the configuration of the module should be set by the
Winproladder software tool. The picture shown at above is the I/O configuration page for “LC module”
setup.
Starting register of configuration table : Please input the starting register number of a block register
that allocated for load cell module configuration in this field. The size of configuration table depends on
the total installed load cell modules. The actual number of register allocated for configuration can be
seen following the field entry, in this case it takes 5 registers for configuration.
Starting register of reading/control registers: Please input the starting register number of a block
register that were allocated for receiving the measurement value and control parameters for load cell.
Starting register of working registers: Please input the starting register number of a block register that
were allocated for internal process.
Span Ch0: The sensitivity of incorporated load cell or measurement range for channel 0. There are
2mV/V, 5mV/V, 10mV/V and 20mV/V can be set. The corresponding measurement range are 0~10mV,
0~25mV, 0~50mV and 0~100mV.
Span Ch1: The sensitivity of incorporated load cell or measurement range for channel 1
Scan Rate: Conversion rate. There are 1Hz, 3Hz, 5Hz and 8Hz can be set
Times of Average: There are No, 2 times, 4 times and 8 times average can be set.
The processing capability of load cell module for one PLC is 16 in total.

Please refer the user’s manual for more detail explanation.

Note: The supporting for FBs-2LC module is available only for PLC OS V4.71 and Winproladder V3.22