FBs-2LC                                      Dual-Channel Load Cell Input Module
Specifications
                                                 Total Channels - 2
                                                 Resolution- 16 bits (include signed bit)
                                                 I/O Points Occupied - 1 RI(Input Register) and 8 DO
                                                 Conversion Rate- 1/3/5/8 Hz
                                                 Non-Linearity- 0.01% F.S. (@25℃)
                                                 Zero Drift- 0.2 µV/℃
                                                 Gain Drift- 10 ppm/℃
                                                 Excitation Voltage – 5V with 100Ω driving capability
                                                 Sensitivity - 2mV/V, 5mV/V, 10mV/V, 20mV/V
                                                 Software Filter- Moving average
Introduction                                     Average Samples- 1~8 configurable
FBs-2LC is one of the analog input modules       Isolation- Transformer(Power) and photo-coupler(Signal)
of FATEK FBs series PLC. It supports two         Indicator(s) - 5V PWR LED
channels of load cell input for weight           Supply Power- 24V-15%/+20%, 2VA
measurement. The raw conversion result is        Internal Power Consumption- 5V, 100mA
represented by a signed 16 bit integer value.    Operating Temperature- 0 ~ 60 ℃
In order to filter out the field noise imposed   Storage Temperature- -20 ~ 80 ℃
                                                 Dimensions- 40(W)x90(H)x80(D) mm
on the signal, it also provides the average of
sample input function.
Dimensions
                                                    1/3
FBs-2LC                                                   Dual-Channel Load Cell Input Module
Wiring Diagram
                                                  24V+
                                                                         24V
                                                  24V-
                                        +5V       +EXC
                                                  CH0+                           R            R
        16-Bit Data    24-Bit                                             +
                        Δ-Σ                                               -
                        A/D
                                                  CH0-                           R            R
                                                   -EXC
                                                                               Load Cell #0
                                        +5V       +EXC
                                                  CH1+
        16-Bit Data    24-Bit
                        Δ-Σ                                                    Load Cell #1
                        A/D                       CH1-
                                                   -EXC
The raw conversion result is represented by a 16-bit signed value. After setting the full range engineering
value and perform the zero and full scale calibration procedure, the system will automatically convert the
raw conversion reading value into engineering weight value for user application.
                                                    2/3
FBs-2LC                                                    Dual Channel Load Cell Input Module
PLC Control
Before FBs-2LC module can be working, the configuration of the module should be set by the
Winproladder software tool. The picture shown at above is the I/O configuration page for “LC module”
setup.
Starting register of configuration table : Please input the starting register number of a block register
that allocated for load cell module configuration in this field. The size of configuration table depends on
the total installed load cell modules. The actual number of register allocated for configuration can be
seen following the field entry, in this case it takes 5 registers for configuration.
Starting register of reading/control registers: Please input the starting register number of a block
register that were allocated for receiving the measurement value and control parameters for load cell.
Starting register of working registers: Please input the starting register number of a block register that
were allocated for internal process.
Span Ch0: The sensitivity of incorporated load cell or measurement range for channel 0. There are
2mV/V, 5mV/V, 10mV/V and 20mV/V can be set. The corresponding measurement range are 0~10mV,
0~25mV, 0~50mV and 0~100mV.
Span Ch1: The sensitivity of incorporated load cell or measurement range for channel 1
Scan Rate: Conversion rate. There are 1Hz, 3Hz, 5Hz and 8Hz can be set
Times of Average: There are No, 2 times, 4 times and 8 times average can be set.
The processing capability of load cell module for one PLC is 16 in total.
Please refer the user’s manual for more detail explanation.
Note: The supporting for FBs-2LC module is available only for PLC OS V4.71 and Winproladder V3.22
or later version.
                                                     3/3