Electric Panel

The document provides technical data for the GPx Series Full Service Electric Fire Pump Controller, including specifications, starting methods, and various models offered. It outlines features such as ambient temperature ratings, surge suppression, and alarm systems, as well as compliance with industry standards like NFPA 20 and UL218. Additionally, it includes information on optional accessories, electrical ratings, and operational capabilities of the controllers.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
35 views15 pages

Electric Panel

The document provides technical data for the GPx Series Full Service Electric Fire Pump Controller, including specifications, starting methods, and various models offered. It outlines features such as ambient temperature ratings, surge suppression, and alarm systems, as well as compliance with industry standards like NFPA 20 and UL218. Additionally, it includes information on optional accessories, electrical ratings, and operational capabilities of the controllers.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 15

Project: 233200223

Customer: BUNGE
Engineer: Erick Morais
Pump Manufacturer: RUHRPUMPEN

Technical Data
Submittal Document

GPx Series
Full Service
Electric Fire Pump Controller

Contents:
Data Sheets
Dimensional Data
Wiring Schematics
Field Connections

MEMBER
2019 -2020 MEMBER
2019 -2020

Note: The drawings included in this package are for controllers


covered under our standard offering. Actual AS BUILT
drawings may differ from what is shown in this package. MEMBER
2019 -2020
MEMBER
2019 -2020

May 2024
Technical Data
GPx Series Full Service Electric Fire Pump Controller

Select starting method

Model GPA Model GPP


Across the line Partwinding
1M 1M T3
3L3
3L3 T3

*
3L2 T2

M
3L2 T2
*
3L1 T1

3L1 T1 CR4
1M 2M T9
M
CR4 CR5 T8
2M
1M T7
3L1

3L1 3L2 3L2

Model GPS Model GPR


Soft Start Soft Stop Autotransformer
1M 1M
3L3 3L3 T3
T3

* M
3L2 T2
3L2

* 3L1
T2

T1
M CR4 CR5 2S
3L1 T1

1S 100%
1M
0% ATR
CR5 1M CR5
1M 2S

3L1 65%
1S
2S
3L1

3L2 Soft Starter 3L2

Model GPY Model GPW


Wye-Delta Open Wye-Delta Closed
1M 3L3
1M
3L3 T3 T3

* *
3L2 T2 3L2 T2

3L1 T1
3L1 T1

M
CR4

M
CR4 1M 2M
1M 2M T5 CR5 1S
T5

T4
CR5 1S T4
2M

2M(LB) CR3A T6
2M
T6 3L1 2S
CR5 2M 2S(LB) 2M(LB) CR3A
3L1
1S
1S 1S

1S

3L2

3L2
2S
RES
RES
RES

MEMBER
2019 -2020 MEMBER
2019 -2020

*From normal incoming power through Disconnecting Means (IS/CB)


MEMBER MEMBER
2019 -2020 2019 -2020

This is a Marketing document. Please consult factory for more information.


May 2024 2
Manufacturer reserves the right to modify this information without notice
Technical Data
GPx Series Full Service Electric Fire Pump Controller

Built to NFPA 20 (latest edition)


Underwriters Laboratory
UL218 - Fire Pump Controllers
(UL)
Standard, FM Global Class 1321/1323
Listings,
Approvals and New York City Accepted for use in the City of New York by the Department of Buildings
Certifications CE Mark Various EN, IEC & CEE directives and standards
Built in Canada or U.A.E Built in Europe
CE Mark Option Supplied as Standard
Protection Rating

Built in Canada or U.A.E Built in Europe

Standard: NEMA 2 Standard: IP55


Optional

NEMA 12 NEMA 4X-304 sst painted IP54

Enclosure NEMA 3 NEMA 4X-304 sst brushed finish IP55

NEMA 3R NEMA 4X-316 sst painted IP65

NEMA 4 NEMA 4X-316 sst brushed finish IP66

Accessories Paint Specifications


• Bottom entry gland plate • Red RAL3002
• Lifting Lugs • Powder coating
• Keylock handle • Glossy textured finish

Shortcircuit 200V to 208V 220V to 240V 380V to 415V 440V to 480V 575V to 600V
Withstand 60Hz 60Hz 50 Hz / 60Hz 60Hz 60Hz
Rating
HP (kw)

Standard 100kA
5 - 150 (3.7 - 110) 5 - 200 (3.7 - 149) 5 - 300 (3.7 - 223) 5 - 400 (3.7 - 298) N/A
Optional 150kA

Standard 50kA 200 (149) 250 (186) 350 - 450 (261 - 335) 450 - 500 (335 - 373)
5 - 500 (3.7- 373)
Optional 100kA N/A N/A 350 - 500 (261 - 373) 450 - 500 (335 - 373)

Optional 200kA 5 - 150 (3.7 - 110) 5 - 200 (3.7 - 149) 5 - 300 (3.7 - 223) 5 - 400 (3.7 - 298) N/A

*Please see Disconnecting Means details on page 4

May 2024 This is a Marketing document. Please consult factory for more information.
Manufacturer reserves the right to modify this information without notice 3
Technical Data
GPx Series Full Service Electric Fire Pump Controller

Ambient Standard: Optional:


Temperature 4°C to 40°C / 39°F to 104°F 4°C to 55°C / 39°F to 131°F
Rating
Controllers built in Dubai, UAE (Tornatech FZE) are supplied standard with 55°C rating.
Surge
Surge arrestor rated to suppress surges above line voltage
Suppression
• Isolating switch and circuit breaker assembly:
- Door interlocked in the ON position
- Isolating switch rated not less than 115% of motor full load current
Disconnecting
- Circuit breaker continuous rating not less than 115% of motor full load current
Means
- Overcurrent sensing non-thermal type, magnetic only
- Instantaneous trip setting of not more than 20 times the motor full load current
• Common flange mounted operating handle
Service Entrance
Suitable as service entrance equipment
Rating

Emergency Start • Flange mounted • Integrated limit switch


Handle • Pull and latch activation • Across the line start (direct on line)

Locked Rotor • Operate shunt trip to open circuit breaker • Trip between 8 and 20 seconds
Protector • Factory set at 600% of motor full load current

Electrical • Voltage phase to phase (normal power)


Readings • Amperage of each phase when motor is running
Pressure • Continuous system pressure display
Readings • Cut-in and Cut-out pressure settings
• Pressure readings with date stamp
• Event recording with date stamp
Pressure and
• Under regular maintained operation, events are stored in memory for the life of the controller.
Event recorder
• Data viewable on operator interface display screen
• Downloadable by USB port to external memory device
• Pressure transducer and run test solenoid valve assembly for fresh water application
• Pressure sensing line connection 1/2” Female NPT
Pressure Sensing • Drain connection 3/8”
• Rated for 0-500PSI working pressure (standard display at 0-300PSI)
• Externally mounted with protective cover

This is a Marketing document. Please consult factory for more information.


May 2024 4
Manufacturer reserves the right to modify this information without notice
Technical Data
GPx Series Full Service Electric Fire Pump Controller

Audible Alarm Alarm buzzer - 85dB at 3 meters


• Power available • Deluge valve start • Pump on demand/Automatic start
• Motor run • Remote automatic start • Pump room temperature (ºF or ºC)
Visual Indications
• Periodic test • Remote manual start • Lockout
• Manual start • Emergency start
Visual
• Control voltage not healthy • Overcurrent • Pump on demand
• Invalid cut-in • Overvoltage • Pump room alarm
• Lock rotor current • Phase loss L1 • Service required
• Loss of power • Phase loss L2 • Undercurrent
Visual & Audible • Phase loss L3 • Undervoltage
• Low ambient temperature
Alarms • Phase unbalanced • Check weekly test solenoid
• Low water level
• Motor trouble • Pressure transducer fault detected • Weekly test cut-in reached
• Phase reversal (normal power)
Visual and audible
• Fail to start

DPDT-8A-250V.AC
• Power available
• Phase reversal
• Motor run
• Common pump room alarm (field re-assignable)**
• Overvoltage
• Undervoltage
Remote Alarm • Phase unbalance
Contacts • Low pump room temperature
• High Pump room temperature
• Common motor trouble (field re-assignable)**
• Overcurrent
• Fail to start
• Undercurrent
• Ground fault
• Free (field programmable)**

**Tornatech reserves the right to use any of these three alarm points for special specific application requirements.

May 2024 This is a Marketing document. Please consult factory for more information.
Manufacturer reserves the right to modify this information without notice 5
Technical Data
GPx Series Full Service Electric Fire Pump Controller

• Embedded microcomputer with software PLC logic


ViZiTouch V2.1 • 7.0” color touch screen (HMI technology)
Operator Interface • Upgradable software
• Multi-language
• Protocol: Modbus
Communication
• Connection type: Shielded female connector RJ45
Protocol
• Frame Format: TCP/IP
Capability
• Addresses: See bulletin MOD-GPx
• Start on pressure drop
Automatic Start • Remote start signal from automatic device
• Deluge valve start
• Start pushbutton
Manual Start • Run test pushbutton
• Remote start from manual device
• Manual with Stop pushbutton
Stopping
Operation • Automatic after expiration of minimum run timer ***
• Minimum run timer ***(off delay)
Field Adjustable &
Timers • Sequential start timer (on delay)
Visual Countdown
• Periodic test timer
• Pressure
Actuation
• Non-pressure
Visual Indication
• Automatic
Mode
• Non-automatic

***Can only be used if approved by the AHJ

This is a Marketing document. Please consult factory for more information.


May 2024 6
Manufacturer reserves the right to modify this information without notice
Technical Data
GPx Series Full Service Electric Fire Pump Controller

A4 Flow switch provision C19 Emergency start alarm contact (DPDT)


Foam pump application w/o pressure C20 Manual start alarm contact (DPDT)
A8
transducer and run test solenoid valve.
C21 Deluge valve start alarm contact (DPDT)
A9 Low zone pump control function
C22 Remote automatic start alarm contact (DPDT)
A10 Middle zone pump control function
C23 Remote manual start alarm contact (DPDT)
A11 High zone pump control function
High pump room temperature alarm contact
Non-pressure actuated controller w/o pressure C24
A13 (DPDT)
transducer and run test solenoid valve
Second set of standard alarm contacts (DPDT)
Lockout/interlock circuit from equipment C25
A16 (Typical for city of Los Angeles and Denver)
installed inside the pump room
Additional visual and alarm contact (Specify
Built in alarm panel (120V.AC supervisory Cx
function) (DPDT)
power) providing indication for:
• Audible alarm & silence pushbutton for motor Low suction pressure transducer for fresh
B11 D1 water rated at 0-300PSI with visual indication
run, phase reversal, loss of phase.
• Pilot lights for loss of phase & supervisory and alarm contact
power available Low suction pressure transducer for sea water
Built in alarm panel same as B11 but 220- D1A rated at 0-300PSI with visual indication and
B11B alarm contact
240VAC supervisory power
High motor temperature c/w thermoster relay Pressure transducer and run test solenoid
B19A D5 valve for fresh water rated for 0-500PSI (for
and alarm contacts (DPDT)
factory calibration purposes only)
High motor temperature c/w PT100 relay and
B19B Pressure transducer and run test solenoid
alarm contacts (DPDT) D5D
valve for sea water rated for 0-500PSI
Ground fault alarm detection c/w visual
B21 D10 Omit mounting feet (when applicable)
indication and alarm contact (DPDT)
C1 Extra motor run alarm contact (DPDT) High withstand rating for:
• 200V to 208V @ 150HP max. = 150kA*
C4 Periodic test alarm contact (DPDT) • 200V to 208V @ 200HP = 100kA*
C6 Low discharge pressure alarm contact (DPDT) • 220V to 240V @ 200HP max. = 150kA*
• 220V to 240V @ 250HP = 100kA*
Low pump room temperature alarm contact D13
C7 • 380V to 415V @ 300HP max. = 150kA*
(DPDT) • 380V to 415V @ 350HP to 450HP = 100kA*
Low water reservoir level alarm contact • 440V to 480V @ 400HP max. = 150kA*
C10 • 440V to 480V @ 450HP to 500HP = 100kA*
(DPDT)
• 600V @ 500HP max. = 100kA*
High electric motor temperature alarm contact
C11 High withstand rating for:
(DPDT)
D13A • 380V to 480V = 65kA*
High electric motor vibration c/w visual
C12 • 600V = 25kA*
indication and alarm contact (DPDT)
High withstand rating for:
Pump on demand / automatic start alarm
C14 • 200V to 208V @ 150HP max. = 200kA*
contact (DPDT)
D13B • 220V to 240V @ 200HP max. = 200kA*
C15 Pump fail to start alarm contact (DPDT) • 380V to 415V @ 300HP max. = 200kA*
• 440V to 480V @ 400HP max. = 200kA*
C16 Control voltage healthy alarm contact (DPDT)
D14 Anti-condensation heater & thermostat
Flow meter valve loop open c/w visual
C17 D14A Anti-condensation heater & humidistat
indication and alarm contact (DPDT)
High water reservoir level c/w visual indication Anti-condensation heater & thermostat &
C18 D14B
and alarm contact (DPDT) humidistat

*For fire pump controller section only.


Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

May 2024 This is a Marketing document. Please consult factory for more information.
Manufacturer reserves the right to modify this information without notice 7
Technical Data
GPx Series Full Service Electric Fire Pump Controller

D15 Tropicalization L01 Other language and English (bilingual)


D18 CE Mark with factory certificate L02 French
Modbus with RTU frame format and RS485 L03 Spanish
D26
connection
L04 German
Motor heater connection (external single
D27 phase power source and heater on/off L05 Italian
contact)
L06 Polish
Motor heater connection (internal single
D27A phase power source and heater on/off L07 Romanian
contact)
L08 Hungarian
D28 Customized drawing set
L09 Slovakian
Field programmable I/O board -
D34A L10 Croatian
5 Input / 5 output
Redundant pressure transducer for fresh L11 Czech
D36
water rated for 0-500PSI
L12 Portuguese
Redundant pressure transducer for sea
D36A
water rated for 0-500PSI L13 Dutch
Seismic Certification compliant to CBC 2019, L15 Turkish
D43
IBC 2018 rigid base/wall mounted only
L16 Swedish
Special Seismic Certification compliant to
D44
OSHPD rigid base/wall mounted only L21 Danish
L25 Chinese
L28 Finnish
L29 Norwegian

Additional Options:

Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

This is a Marketing document. Please consult factory for more information.


May 2024 8
Manufacturer reserves the right to modify this information without notice
Technical Data
GPx Series Full Service Electric Fire Pump Controller

ViZiTouch V2.1 Operator Interface

1
2

4 5 6 8 7

1 - Color touch screen 3 - Power LED (3 colors)


2 - Onscreen menu 4 - START button
• HOME page 5 - STOP button
• ALARM page 6 - Not Used
• CONFIGURATION page 7 - RUN TEST button
• HISTORY page 8 - Alarm buzzer
• SERVICE page
• MANUAL page
• LANGUAGES page

May 2024 This is a Marketing document. Please consult factory for more information.
Manufacturer reserves the right to modify this information without notice 9
0 1 2 3 4 5 6 7 8

BY DD/MM/YY MODEL: GPS


BUILT TO THE LATEST EDITION OF THE NFPA20 & NFPA70
A
DRAWN BY DDS 22/02/23 ELECTRIC FIRE PUMP CONTROLLER DRAWING NUMBER
CDL
A
© Tornatech, Inc. Not for construction.
NYC
Dpt of Building
THIRD ANGLE GPX-DI851 /E
FINAL Approved
PROJECTION DWG REV. 0
Subject to change without notice. FC 23/02/23
APPROVAL SHEET 1 OF 1

39 1/4" [998]
B B

1/2" [12] 21 7/8" [554] 36" [914]


18" [457] 34 1/2" [876]
Ø7/8" [Ø23] X2 Ø3/8" [Ø10] X4

C C

See Notes

69 1/8" [1756]
D D

68" [1727]
65 7/8" [1673]

E E

Voltage / Power Table

Voltage Min HP Max HP


F
28 3/8" [720] F
208 75 125 22 3/4" [576]
33 5/8" [854]
220 - 240 100 150
1" [25] Adjustable Feet
380 - 400 - 415 150 250

G 440 - 480 200 300 G


40" [1016]
600 250 350 Sensing Line Connection - 1/2 " F.NPT
38" [965]
Ø1/2" [Ø13] X4 11" [279] 1" [25]
Drain - 3/8 " M.TUBE

H H
Notes: 11 1/8" [284] Normal
11" [279]
Power and
- Standard NEMA: NEMA 2 Motor Leads 16" [406]
- Standard paint : textured red RAL 3002. Entrance
- All dimensions are in inches [millimeters].
- Center of screen: 61-5/8" [1564] from bottom.
- Bottom conduit entrance through removable gland plate recommended.
I 3 1/2" [89] 3" [76] I
- Use watertight conduit and connector only. 1 1/4" [31] 1" [25]
- Protect equipment against drilling chips.
- Door swing equal to door width.

0 1 2 3 4 5 6 7 8
Copyright © 2024 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
0 1 2 3 4 5 6 7 8

BY DD/MM/YY MODEL: GPS


DRAWN BY ACD 11/01/24
ELECTRIC FIRE PUMP CONTROLLER BUILT TO THE LATEST EDITION OF THE NFPA20 & NFPA70
CDL
A DRAWING NUMBER A
REDUCED VOLTAGE / SOFT STARTER NYC GPS-WS800/E
© Tornatech, Inc. Not for construction. FINAL
Dpt of Building
Approved DWG REV. 1
Subject to change without notice. FC 11/01/24
APPROVAL SHEET 1 OF 2

IS1
1L3
B 1L2 B
1L1
SA1
To I/O
Electric Board
4
To J45 VMB1 UP
CB1 ST1 (P.2 / F4) (P.2 / E2)
C 2 C

I/O

D J14 J8 J5 D

COM

COM

COM

COM
3L1

DI0

DI1

DI2

DI3
3L2 -

+
3L3
To
J2/J3/J4 (P.2/F8) (D1)
3L1 3L2

1M
E E
H1 H2

3L3
XTR4
3L2
3L1 44 X2 X1
230

17
F CR5 47 F
50
49 (P.2/H2)
46
CR4
CR5
3L1 (P.2/E8)
48
CT3 68 Black
69 White
G G
CT2 66 Black
CL1 LI1 LI2 +24V CL2
67 White To J76 (P.2/F6)

CT1 64 Black
65 White Legend
R1B 1M Contactor
AB Alarm Bell
R1C RUN / TRIP
CB Circuit Breaker
H NO (Programmable)
CR Control Relay H
R1A
CT Current Transformer
EB Electric I/O Board
195 NC IS Isolating Switch
1M** SSS1 (P.2/H7) 198
R2B
J Jumper
R2C OVERLOAD / FAILURE LS Limit Switch
NO (Fail Safe) PT Pressure Transducer
R2A SA Surge Arrester

I ATS22....6S SSS
ST
Soft Starter
Shunt Trip I
T1 T2 T3 SV Solenoid Valve

M
VMB Main Board
XTR Transformer

0 1 2 3 4 5 6 7 8
Copyright © 2024 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
0 1 2 3 4 5 6 7 8

BY DD/MM/YY MODEL: GPS


DRAWN BY ACD 11/01/24
ELECTRIC FIRE PUMP CONTROLLER BUILT TO THE LATEST EDITION OF THE NFPA20 & NFPA70
CDL
A DRAWING NUMBER A
REDUCED VOLTAGE / SOFT STARTER NYC GPS-WS800/E
© Tornatech, Inc. Not for construction. FINAL
Dpt of Building
Approved DWG REV. 1
Subject to change without notice. FC 11/01/24
APPROVAL SHEET 2 OF 2

B B

C C

SV1
XTR1
1
LS1 ** LS1-1 X1 H2

Brown
D LS1-2 24VAC D
3L2

Blue
X2 H1
3 3L1
Sensing Line
Connection To
3L1-2-3
PT1 To ST1
To
(P.1 / D1)

E
(P.1 / C8)
(P.1 / C1)
CR4 CR5 CT1-2-3
(P.1 / G2)
To E
To 3L1 CR4
VMB1 (P.1 / G2)

CR4-1
CR4-2

CR5-1
CR5-2
SV1-1
SV1-2
I/O
White
Black

3L3

3L2
3L2

3L1
3L1
Red

4
2

1
3

67
69
68

66
65
64
7 5 3 1

24V OUT

24VAC
24V IN
UP DOWN 8 6 4 2 2 1 2 1 2 1
F F
LS1
AI4

AI3

AI2

AI1

NO

NO
NC

NC
AB

SV

ST
L3 L2 L1

C
IGF I3 I2 I1
+

+
-

J76 J53 J4 J3 J2
J14 J15 J16 J17 J54 J46 J43 J45 J44 J47 J36 J38
CR4 CR5

I/O Electric Board EB1


G J40 J42 J37 J39 J41 J55 G
TB1 TB2 TB3 TB4 TB5 TB6
J25
NO

NO

NO

NO

NO

NO
NC

NC

NC

NC

NC

NC

2 2 2 2 2 2
C

C
NO

NO

NO

NO

NO

NO
NC

NC

NC

NC

NC

NC

1 1 1 1 1 1
C

IN1 IN2 IN3 IN4 IN5 IN6 IN7 IN8

H H
47
46

195
198
J1* J2*
ve e

rm
n

le
ble

Re Phas
l
Ru

rsa

ub

e
al

l
to
ut
Ala

ve
ila

(P.1/F5)
alv
nu

Au
cko

(P.1/H3)
Tro

Le
tor

va

eV
Ma
r

om

te
Lo
we

ter
Mo

rA

mo

lug
tor

ote

Wa
Ro
Po

Re
we

De
Mo

w
Re
mp
al
Po

Lo
rm

Pu
No

I I

* Remove jumper to use this feature


** Contact closes when emergency start is in "ON" position
0 1 2 3 4 5 6 7 8
Copyright © 2024 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
0 1 2 3 4 5 6 7 8

BY DD/MM/YY MODEL: GPX


BUILT TO THE LATEST EDITION OF THE NFPA20 & NFPA70
A
DRAWN BY ACD 28/02/23 ELECTRIC FIRE PUMP CONTROLLER DRAWING NUMBER
CDL
A
© Tornatech, Inc. Not for construction.
NYC
Dpt of Building
GPX-TD800 /E
FINAL Approved DWG REV. 0
Subject to change without notice. FC 28/02/23
APPROVAL SHEET 1 OF 1

COPPER CONDUCTORS for Isolating Switch (IS1).


Field Wiring According to Bending Space (AWG or MCM). Terminals L1 - L2 - L3
B
Bending
5 " (127 mm) 8 " (203 mm)
Power Terminals B
Space
3 Phases
HP 5 7.5 10 15 20 25 30 40 50 60 Bonding Incoming Power
Voltage
Ground
208 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (2 to 1/0) 1x (1/0 to 3/0) 1x (3/0 to 250) 1x (4/0 to 250)

220 to 240 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (1 to 3/0) 1x (2/0 to 3/0) 1x (3/0 to 250)
L1 L2 L3
380 to 416 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (3 to 1/0) IS1
C C
440 to 480 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0)

600 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0)

Bending
Space 12 " (305 mm) 16 " (406 mm)

HP 75 100 125 150 200 250 300 350 400 450 500
Voltage
D D
208 2x (1/0 to 500) 2x (2/0 to 500) 2x (4/0 to 500) 2x (250 to 500) 3x (4/0 to 500) -------- -------- -------- -------- -------- --------

220 to 240 1x (250) 2x (2/0 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (350 to 500) 3x (250 to 500) -------- -------- -------- -------- --------

380 to 416 1x (1/0 to 3/0) 1x (3/0 to 250) 1x (250) 2x (1/0 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (300 to 500) 2x (400 to 500) 3x (250 to 500) 3x (300 to 500) --------

440 to 480 1x (1 to 3/0) 1x (2/0 to 3/0) 1x (3/0 to 250) 1x (4/0 to 250) 2x (1/0 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (300 to 500) 2x (350 to 500) 2x (400 to 500) 3x (250 to 500)

E 600 1x (3 to 1/0) 1x (1 to 3/0) 1x (2/0 to 3/0) 1x (3/0 to 250) 1x (250) 2x (2/0 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (250 to 500) 2x (300 to 500) 2x (350 to 500) E
Bending
Space 5 " (127 mm) 8 " (203 mm) 12 " (305 mm)

ALUMINUM CONDUCTORS for Isolating Switch (IS1).


Field Wiring According to Bending Space (AWG or MCM). Terminals L1 - L2 - L3
Bending
Space 5 " (127 mm) 8 " (203 mm) 10 " (254 mm)
F F
HP 5 7.5 10 15 20 25 30 40 50 60
Voltage
1x (300) ** or
208 1x (10 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (1 to 1/0) 1x (1/0) 1x (3/0) 1x (4/0 to 250)
1x (250) 90°C *
220 to 240 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (2 to 1/0) 1x (1 to 1/0) 1x (2/0 to 3/0) 1x (3/0) 90°C * 1x (250)

380 to 416 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (2 to 1/0) 1x (1 to 1/0) 1x (1/0)

G 440 to 480 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (2 to 1/0) 1x (1 to 1/0) G

600 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (2 to 1/0)

Bending
Space 12 " (305 mm) 16 " (406 mm)

HP 75 100 125 150 200 250 300 350 400 450 500
Voltage

H 208 2x (2/0 to 500) 2x (4/0 to 500) 2x (300 to 500) 2x (350 to 500) 3x (300 to 500) -------- -------- -------- -------- -------- -------- H
1x (350) ** Notes:
220 to 240 2x (3/0 to 500) 2x (250 to 500) 2x (300 to 500) 2x (500) 3x (400 to 500) -------- -------- -------- -------- --------
N/A 1 - For proper wire sizing, refer to NFPA70 and NEC (USA) or CEC (Canada)
1x (350) ** 3x (300 to 500)**
380 to 416 1x (3/0) 1x (250 to 350) 2x (3/0 to 500) 2x (4/0 to 500) 2x (300 to 500) 2x (500)
2x (500) 90°C *
3x (350 to 500) 3x (400 to 500) -------- or local code.
N/A
1x (300 to 350)** 2 - Controller suitable for service entrance in USA.
440 to 480 1x (1/0 to 3/0) 1x (3/0) 1x (250) 2x (3/0 to 500) 2x (250 to 500) 2x (300 to 500) 2x (400 to 500) 2x (500) 2x (500) 90°C * 3x (350 to 500)
1x (250) 90°C * 3 - For more accurate motor connections refer to motor manufacturer or
600 1x (1 to 1/0) 1x (2/0 to 3/0) 1x (3/0) 90°C * 1x (4/0 to 250) 1x (350 to 500) 2x (3/0 to 500) 2x (4/0 to 250) 2x (300 to 500) 2x (350 to 500) 2x (400 to 500) 2x (500) motor nameplate.
I
4 - Controller is phase sensitive. Incoming lines must be connected in ABC I
Bending sequence.
Space 5 " (127 mm) 8 " (203 mm) 12 " (305 mm)

Drawing for information only.


* For standard enclosure, use 90°C aluminium wire. Consult Factory for Use of Conductors Rated Lower than 90°C. Manufacturer reserves the right to modify this drawing without notice.
** Consult Factory Contact manufacturer for "As Built" drawing.

0 1 2 3 4 5 6 7 8
Copyright © 2024 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
0 1 2 3 4 5 6 7 8

BY DD/MM/YY MODEL: GPA/GPR/GPS


BUILT TO THE LATEST EDITION OF THE NFPA20 & NFPA70
A
DRAWN BY ACD 28/02/23 ELECTRIC FIRE PUMP CONTROLLER DRAWING NUMBER
CDL
A
© Tornatech, Inc. Not for construction.
NYC
Dpt of Building
GPX-TD801 /E
FINAL Approved DWG REV. 0
Subject to change without notice. FC 28/02/23
APPROVAL SHEET 1 OF 1

COPPER CONDUCTORS for Motor Connection (1M).


Field Wiring According to Bending Space (AWG or MCM). Terminals T1 - T2 - T3
HP
B 5 7.5 10 15 20 25 30 40 50 60 B
Voltage
208 1x (10 to 2) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (4 to 2) 1x (3 to 2/0) 1x (2 to 2/0) 1x (1/0 to 3/0) 1x (3/0) 1x (4/0 to 300) Motor Terminals
220 to 240 1x (10 to 2) 1x (10 to 2) 1x (8 to 2) 1x (6 to 2) 1x (4 to 2) 1x (4 to 2/0) 1x (3 to 2/0) 1x (1/0 to 3/0) 1x (2/0 to 3/0) 1x (3/0)

380 to 416 1x (10 to 2) 1x (10 to 2) 1x (10 to 2) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (6 to 1/0) 1x (4 to 2) 1x (3 to 2/0) 1x (1 to 2/0) 1M


T1 T2 T3
440 to 480 1x (10 to 2) 1x (10 to 2) 1x (10 to 2) 1x (10 to 2) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (6 to 2) 1x (4 to 2/0) 1x (3 to 2/0)
C C
600 1x (10 to 2) 1x (10 to 2) 1x (10 to 2) 1x (10 to 2) 1x (10 to 2) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (6 to 2) 1x (4 to 2/0)

HP M
75 100 125 150 200 250 300 350 400 450 500
Voltage
208 1x (300) 2x (2/0 to 300) 2x (4/0 to 300) 2x (250 to 300) 2x (400 to 600) -------- -------- -------- -------- -------- -------- Models:GPA/GPR/GPS

220 to 240 1x (250 to 300) 2x (2/0 to 300) 2x (3/0 to 300) 2x (4/0 to 300) 2x (350 to 500) 2x (500 to 600) -------- -------- -------- -------- --------
D D
380 to 416 1x (1/0 to 3/0) 1x (3/0) 1x (250 to 300) 1x (300) 2x (3/0 to 300) 2x (4/0 to 300) 2x (300) 2x (400 to 500) 2x (500 to 600) 2x (600)

440 to 480 1x (1 to 1/0) 1x (2/0 to 3/0) 1x (3/0) 1x (4/0 to 300) 2x (1/0 to 300) 2x (3/0 to 300) 2x (4/0 to 300) 2x (300) 2x (350 to 500) 2x (400 to 600) 2x (500 to 600)

600 1x (3 to 1/0) 1x (1 to 1/0) 1x (2/0 to 3/0) 1x (3/0) 1x (250 to 300) 2x (2/0 to 300) 2x (3/0 to 300) 2x (4/0 to 300) 2x (250 to 300) 2x (300) 2x (350 to 500)

E E

ALUMINUM CONDUCTORS for Contactor (1M).


Field Wiring According to Bending Space (AWG or MCM). Terminals T1 - T2 - T3
HP
5 7.5 10 15 20 25 30 40 50 60
Voltage
208 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (6 to 2/0) ** 1x (4 to 2/0) ** 1x (2 to 2/0) ** 1x (1 to 2/0) ** 1x (1/0 to 2/0) ** 1x (2/0) 90°C * Consult Factory 1x (300)

F 220 to 240 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (8 to 2/0) ** 1x (4 to 2/0) ** 1x (3 to 2/0) ** 1x (2 to 2/0) ** 1x (1 to 2/0) ** 1x (2/0) 1x (3/0) 90°C * Consult Factory F

380 to 416 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (10 to 2/0) ** 1x (8 to 2/0) ** 1x (6 to 2/0) ** 1x (6 to 2/0) ** 1x (4 to 2/0) ** 1x (2 to 2/0) ** 1x (1 to1/0) 1x (1/0)

440 to 480 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (8 to 2/0) ** 1x (6 to 2/0) ** 1x (6 to 2/0) ** 1x (4 to 2/0) ** 1x (2 to 1/0) 1x (1 to 1/0)

600 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (8 to 2/0) ** 1x (8 to 2/0) ** 1x (4 to 2/0) ** 1x (4 to 2/0) ** 1x (2 to 1/0)

HP
G 75 100 125 150 200 250 300 350 400 450 500 G
Voltage
208 1x (300) 90°C * 2x (4/0 to 300) 2x (300) 2x (300) 90°C * 2x (600) -------- -------- -------- -------- -------- --------

220 to 240 1x (300) 90°C * 2x (3/0 to 300) 2x (250 to 300) 2x (300) 2x (500) 2x (600) -------- -------- -------- -------- --------

380 to 416 1x (3/0) Consult Factory 1x (300) 90°C * Consult Factory 2x (4/0 to 300) 2x (300) Consult Factory 2x (600) 2x (600) 90°C * 2x (600) 90°C * --------

440 to 480 1x (1/0) 1x (3/0) Consult Factory 1x (300) 2x (3/0 to 300) 2x (250 to 300) 2x (300) 2x (300) 90°C * 2x (500) 2x (600) 2x (600) 90°C *
H H
600 1x (1 to 1/0) Consult Factory 1x (3/0) 90°C * Consult Factory 1x (300) 90°C * 2x (3/0 to 300) 2x (4/0 to 300) 2x (300) 2x (300) 90°C * 2x (300) 90°C * Consult Factory
Notes:
1 - For proper wire sizing, refer to NFPA70 and NEC (USA) or CEC (Canada)
* For standard enclosure, use 90°C aluminium wire. Consult Factory for Use of Conductors Rated Lower than 90°C.
or local code.
** Option V659 required.
2 - Controller suitable for service entrance in USA.
3 - For more accurate motor connections refer to motor manufacturer or
motor nameplate.
I
4 - Controller is phase sensitive. Incoming lines must be connected in ABC I
sequence.

Drawing for information only.


Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.

0 1 2 3 4 5 6 7 8
Copyright © 2024 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
0 1 2 3 4 5 6 7 8

BY DD/MM/YY MODEL: GPX


BUILT TO THE LATEST EDITION OF THE NFPA20 & NFPA70
A
DRAWN BY ACD 18/12/23 ELECTRIC FIRE PUMP CONTROLLER DRAWING NUMBER
CDL
A
© Tornatech, Inc. Not for construction.
NYC
Dpt of Building
GPX-TD803 /E
FINAL Approved DWG REV. 0
Subject to change without notice. FC 19/12/23
APPROVAL SHEET 1 OF 1

Field Connections Alarm Contacts


Terminals Wire Size: Terminals Wire Size:
B 24 - 12 AWG 24 - 12 AWG B
0.5 Nm 0.5 Nm
I/O Electric Board
I/O Electric Board
Normally Opened

IN 1
Remote Manual NO
Closes to alarm
Normally Closed C

IN 2
Lockout Opens to alarm NC
Motor Run TB1
Normally Opened NO

Controller Terminal Strip


C C

IN 3
Remote Auto J1* Closes to alarm
Normally Closed C
Opens to alarm NC

IN 4
Deluge Valve J2*
J25 Normally Opened
Closes to alarm NO

IN 5
Low Water Level Normally Closed C
Opens to alarm NC
IN 6 Power Available TB2
Normally Opened NO
Closes to alarm
D Normally Closed C D
IN 7

Opens to alarm NC
IN 8

Normally Opened
Closes to alarm NO
Normally Closed C
Opens to alarm
Network Connections Normal Power
Phase Reversal Normally Opened
NC
NO
TB3
Closes to alarm
Terminals Wire Size: Normally Closed C
E Shielded Female Connector RJ45 Opens to alarm NC
E

Located on Main Board Normally Opened


Closes to alarm NO

Modbus TCP/IP RJ45 Normally Closed


Opens to alarm NC
C

Pump Room Alarm** TB4


Normally Opened NO
Closes to alarm
Normally Closed C
Opens to alarm NC
F F
Normally Opened
Closes to alarm NO
Normally Closed C
Opens to alarm NC
Motor Trouble** TB5
Normally Opened NO
Closes to alarm
Normally Closed C
Opens to alarm NC
G G
Normally Opened
Closes to alarm NO
Normally Closed C
Opens to alarm NC
(Field
Programmable***) TB6
Normally Opened NO
Closes to alarm
Normally Closed C
Opens to alarm NC

H H

I I

* Remove jumper to use this feature


** Re-assignable
*** Not available on GPS models

0 1 2 3 4 5 6 7 8
Copyright © 2024 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.