Data sheet                                                                                                         6ES7314-6BH04-0AB0
SIMATIC S7-300, CPU 314C-2 PTP Compact CPU with MPI, 24 DI/16 DO, 4 AI, 2
                                                                     AO, 1 Pt100, 4 high-speed counters (60 kHz), integrated interface RS485, Integr.
                                                                     power supply 24 V DC, work memory 192 KB, Front connector (2x 40-pole) and
                                                                     Micro Memory Card required
General information
 Product type designation                                             CPU 314C-2 PtP
 HW functional status                                                 01
 Firmware version                                                     V3.3
 Engineering with
       ● Programming package                                          STEP 7 as of V5.5 + SP1 or STEP 7 V5.3 + SP2 or higher with HSP 204
Supply voltage
 Rated value (DC)                                                     24 V
 permissible range, lower limit (DC)                                  19.2 V
 permissible range, upper limit (DC)                                  28.8 V
 external protection for power supply lines (recommendation)          Miniature circuit breaker, type C; min. 2 A; miniature circuit breaker type B, min.
                                                                      4A
 Mains buffering
       ● Mains/voltage failure stored energy time                     5 ms
       ● Repeat rate, min.                                            1s
 Load voltage L+
       Digital inputs
           — load voltage / at digital input / at DC / rated value    24 V
           — Reverse polarity protection                              Yes
       Digital outputs
           — Rated value (DC)                                         24 V
           — Reverse polarity protection                              No
Input current
 Current consumption (rated value)                                    660 mA
 Current consumption (in no-load operation), typ.                     150 mA
 Inrush current, typ.                                                 5A
 I²t                                                                  0.7 A²·s
 Digital inputs
       ● from load voltage L+ (without load), max.                    80 mA
 Digital outputs
       ● from load voltage L+, max.                                   50 mA
Power loss
 Power loss, typ.                                                     13 W
Memory
 Work memory
       ● integrated                                                   192 kbyte
       ● expandable                                                   No
 Load memory
       ● Plug-in (MMC)                                                Yes
       ● Plug-in (MMC), max.                                          8 Mbyte
6ES73146BH040AB0                                                                                                  Subject to change without notice
                                                                     6/26/2025
Page 1/11                                                                                                                    © Copyright Siemens
      ● Data management on MMC (after last programming),    10 a
      min.
 Backup
      ● present                                             Yes; Guaranteed by MMC (maintenance-free)
      ● without battery                                     Yes; Program and data
CPU processing times
 for bit operations, typ.                                   0.06 µs
 for word operations, typ.                                  0.12 µs
 for fixed point arithmetic, typ.                           0.16 µs
 for floating point arithmetic, typ.                        0.59 µs
CPU-blocks
 Number of blocks (total)                                   1 024; (DBs, FCs, FBs); the maximum number of loadable blocks can be
                                                            reduced by the MMC used.
 DB
      ● Number, max.                                        1 024; Number range: 1 to 16000
      ● Size, max.                                          64 kbyte
 FB
      ● Number, max.                                        1 024; Number range: 0 to 7999
      ● Size, max.                                          64 kbyte
 FC
      ● Number, max.                                        1 024; Number range: 0 to 7999
      ● Size, max.                                          64 kbyte
 OB
      ● Number, max.                                        see instruction list
      ● Size, max.                                          64 kbyte
      ● Number of free cycle OBs                            1; OB 1
      ● Number of time alarm OBs                            1; OB 10
      ● Number of delay alarm OBs                           2; OB 20, 21
      ● Number of cyclic interrupt OBs                      4; OB 32, 33, 34, 35
      ● Number of process alarm OBs                         1; OB 40
      ● Number of startup OBs                               1; OB 100
      ● Number of asynchronous error OBs                    4; OB 80, 82, 85, 87
      ● Number of synchronous error OBs                     2; OB 121, 122
 Nesting depth
      ● per priority class                                  16
      ● additional within an error OB                       4
Counters, timers and their retentivity
 S7 counter
      ● Number                                              256
      Retentivity
            — adjustable                                    Yes
            — preset                                        Z 0 to Z 7
      Counting range
            — lower limit                                   0
            — upper limit                                   999
 IEC counter
      ● present                                             Yes
      ● Type                                                SFB
      ● Number                                              Unlimited (limited only by RAM capacity)
 S7 times
      ● Number                                              256
      Retentivity
            — adjustable                                    Yes
            — preset                                        No retentivity
      Time range
            — lower limit                                   10 ms
            — upper limit                                   9 990 s
 IEC timer
      ● present                                             Yes
      ● Type                                                SFB
      ● Number                                              Unlimited (limited only by RAM capacity)
6ES73146BH040AB0                                                                                       Subject to change without notice
                                                           6/26/2025
Page 2/11                                                                                                         © Copyright Siemens
Data areas and their retentivity
 Retentive data area (incl. timers, counters, flags), max.    64 kbyte
 Flag
        ● Size, max.                                          256 byte
        ● Retentivity available                               Yes; MB 0 to MB 255
        ● Retentivity preset                                  MB 0 to MB 15
        ● Number of clock memories                            8; 1 memory byte
 Data blocks
        ● Retentivity adjustable                              Yes; via non-retain property on DB
        ● Retentivity preset                                  Yes
 Local data
        ● per priority class, max.                            32 kbyte; Max. 2048 bytes per block
Address area
 I/O address area
        ● Inputs                                              1 024 byte
        ● Outputs                                             1 024 byte
        of which distributed
            — Inputs                                          none
            — Outputs                                         none
 Process image
        ● Inputs                                              1 024 byte
        ● Outputs                                             1 024 byte
        ● Inputs, adjustable                                  1 024 byte
        ● Outputs, adjustable                                 1 024 byte
        ● Inputs, default                                     128 byte
        ● Outputs, default                                    128 byte
        Default addresses of the integrated channels
            — Digital inputs                                  124.0 to 126.7
            — Digital outputs                                 124.0 to 125.7
            — Analog inputs                                   752 to 761
            — Analog outputs                                  752 to 755
 Digital channels
        ● Inputs                                              1 016
            — of which central                                1 016
        ● Outputs                                             1 008
            — of which central                                1 008
 Analog channels
        ● Inputs                                              253
            — of which central                                253
        ● Outputs                                             250
            — of which central                                250
Hardware configuration
 Number of expansion units, max.                              3
 Number of DP masters
        ● integrated                                          none
        ● via CP                                              4
 Number of operable FMs and CPs (recommended)
        ● FM                                                  8
        ● CP, PtP                                             8
        ● CP, LAN                                             10
 Rack
        ● Racks, max.                                         4
        ● Modules per rack, max.                              8; In rack 3 max. 7
Time of day
 Clock
        ● Hardware clock (real-time)                          Yes
        ● retentive and synchronizable                        Yes
        ● Backup time                                         6 wk; At 40 °C ambient temperature
        ● Deviation per day, max.                             10 s; Typ.: 2 s
        ● Behavior of the clock following POWER-ON            Clock continues running after POWER OFF
6ES73146BH040AB0                                                                                    Subject to change without notice
                                                             6/26/2025
Page 3/11                                                                                                      © Copyright Siemens
      ● Behavior of the clock following expiry of backup period     the clock continues at the time of day it had when power was switched off
 Operating hours counter
      ● Number                                                      1
      ● Number/Number range                                         0
      ● Range of values                                             0 to 2^31 hours (when using SFC 101)
      ● Granularity                                                 1h
      ● retentive                                                   Yes; Must be restarted at each restart
 Clock synchronization
      ● supported                                                   Yes
      ● to MPI, master                                              Yes
      ● on MPI, device                                              Yes
      ● in AS, master                                               Yes
      ● in AS, device                                               No
Digital inputs
 Number of digital inputs                                           24
      ● of which inputs usable for technological functions          16
 integrated channels (DI)                                           24
 Input characteristic curve in accordance with IEC 61131, type 1    Yes
 Number of simultaneously controllable inputs
      horizontal installation
           — up to 40 °C, max.                                      24
           — up to 60 °C, max.                                      12
      vertical installation
           — up to 40 °C, max.                                      12
 Input voltage
      ● Rated value (DC)                                            24 V
      ● for signal "0"                                              -3 to +5V
      ● for signal "1"                                              +15 to +30 V
 Input current
      ● for signal "1", typ.                                        8 mA
 Input delay (for rated value of input voltage)
      for standard inputs
           — parameterizable                                        Yes; 0.1 / 0.3 / 3 / 15 ms (You can reconfigure the input delay of the standard
                                                                    inputs during program runtime. Please note that under certain circumstances
                                                                    your newly set filter time may not be effective until the next filter cycle.)
           — Rated value                                            3 ms
      for technological functions
           — at "0" to "1", max.                                    8 µs; Minimum pulse width/minimum pause between pulses at maximum
                                                                    counting frequency
 Cable length
      ● shielded, max.                                              1 000 m; 50 m for technological functions
      ● unshielded, max.                                            600 m; for technological functions: No
      for technological functions
           — shielded, max.                                         50 m; at maximum count frequency
           — unshielded, max.                                       not allowed
Digital outputs
 Number of digital outputs                                          16
      ● of which high-speed outputs                                 4; Notice: You cannot connect the fast outputs of your CPU in parallel
 integrated channels (DO)                                           16
 Short-circuit protection                                           Yes; Clocked electronically
      ● Response threshold, typ.                                    1A
 Limitation of inductive shutdown voltage to                        L+ (-48 V)
 Controlling a digital input                                        Yes
 Switching capacity of the outputs
      ● on lamp load, max.                                          5W
 Load resistance range
      ● lower limit                                                 48 Ω
      ● upper limit                                                 4 kΩ
 Output voltage
      ● for signal "1", min.                                        L+ (-0.8 V)
 Output current
6ES73146BH040AB0                                                                                                Subject to change without notice
                                                                   6/26/2025
Page 4/11                                                                                                                  © Copyright Siemens
     ● for signal "1" rated value                                    500 mA
     ● for signal "1" permissible range, min.                        5 mA
     ● for signal "1" permissible range, max.                        0.6 A
     ● for signal "1" minimum load current                           5 mA
     ● for signal "0" residual current, max.                         0.5 mA
 Parallel switching of two outputs
     ● for uprating                                                  No
     ● for redundant control of a load                               Yes
 Switching frequency
     ● with resistive load, max.                                     100 Hz
     ● with inductive load, max.                                     0.5 Hz
     ● on lamp load, max.                                            100 Hz
     ● of the pulse outputs, with resistive load, max.               2.5 kHz
 Total current of the outputs (per group)
     horizontal installation
          — up to 40 °C, max.                                        3A
          — up to 60 °C, max.                                        2A
     vertical installation
          — up to 40 °C, max.                                        2A
 Cable length
     ● shielded, max.                                                1 000 m
     ● unshielded, max.                                              600 m
Analog inputs
 Number of analog inputs                                             5
     ● For voltage/current measurement                               4
     ● For resistance/resistance thermometer measurement             1
 integrated channels (AI)                                            5; 4x current/voltage, 1x resistance
 permissible input voltage for current input (destruction limit),    5 V; Permanent
 max.
 permissible input voltage for voltage input (destruction limit),    30 V; Permanent
 max.
 permissible input current for voltage input (destruction limit),    0.5 mA; Permanent
 max.
 permissible input current for current input (destruction limit),    50 mA; Permanent
 max.
 Electrical input frequency, max.                                    400 Hz
 No-load voltage for resistance-type transmitter, typ.               3.3 V
 Constant measurement current for resistance-type transmitter,       1.25 mA
 typ.
 Technical unit for temperature measurement adjustable               Yes; Degrees Celsius / degrees Fahrenheit / Kelvin
 Input ranges
     ● Voltage                                                       Yes; ±10 V / 100 kΩ; 0 V to 10 V / 100 kΩ
     ● Current                                                       Yes; ±20 mA / 100 Ω; 0 mA to 20 mA / 100 Ω; 4 mA to 20 mA / 100 Ω
     ● Resistance thermometer                                        Yes; Pt 100 / 10 MΩ
     ● Resistance                                                    Yes; 0 Ω to 600 Ω / 10 MΩ
 Input ranges (rated values), voltages
     ● 0 to +10 V                                                    Yes
          — Input resistance (0 to 10 V)                             100 kΩ
 Input ranges (rated values), currents
     ● 0 to 20 mA                                                    Yes
          — Input resistance (0 to 20 mA)                            100 Ω
     ● -20 mA to +20 mA                                              Yes
          — Input resistance (-20 mA to +20 mA)                      100 Ω
     ● 4 mA to 20 mA                                                 Yes
          — Input resistance (4 mA to 20 mA)                         100 Ω
 Input ranges (rated values), resistance thermometer
     ● Pt 100                                                        Yes
          — Input resistance (Pt 100)                                10 MΩ
 Input ranges (rated values), resistors
     ● 0 to 600 ohms                                                 Yes
          — Input resistance (0 to 600 ohms)                         10 MΩ
 Thermocouple (TC)
6ES73146BH040AB0                                                                                                 Subject to change without notice
                                                                    6/26/2025
Page 5/11                                                                                                                   © Copyright Siemens
     Temperature compensation
          — parameterizable                                             No
 Characteristic linearization
     ● parameterizable                                                  Yes; by software
          — for resistance thermometer                                  Pt 100
 Cable length
     ● shielded, max.                                                   100 m
Analog outputs
 integrated channels (AO)                                               2
 Voltage output, short-circuit protection                               Yes
 Voltage output, short-circuit current, max.                            55 mA
 Current output, no-load voltage, max.                                  14 V
 Output ranges, voltage
     ● 0 to 10 V                                                        Yes
     ● -10 V to +10 V                                                   Yes
 Output ranges, current
     ● 0 to 20 mA                                                       Yes
     ● -20 mA to +20 mA                                                 Yes
     ● 4 mA to 20 mA                                                    Yes
 Connection of actuators
     ● for voltage output two-wire connection                           Yes; Without compensation of the line resistances
     ● for voltage output four-wire connection                          No
     ● for current output two-wire connection                           Yes
 Load impedance (in rated range of output)
     ● with voltage outputs, min.                                       1 kΩ
     ● with voltage outputs, capacitive load, max.                      0.1 µF
     ● with current outputs, max.                                       300 Ω
     ● with current outputs, inductive load, max.                       0.1 mH
 Destruction limits against externally applied voltages and currents
     ● Voltages at the outputs towards MANA                             16 V; Permanent
     ● Current, max.                                                    50 mA; Permanent
 Cable length
     ● shielded, max.                                                   200 m
Analog value generation for the inputs
 Measurement principle                                                  Actual value encryption (successive approximation)
 Integration and conversion time/resolution per channel
     ● Resolution with overrange (bit including sign), max.             12 bit
     ● Integration time, parameterizable                                Yes; 16.6 / 20 ms
     ● Interference voltage suppression for interference                50 / 60 Hz
     frequency f1 in Hz
     ● Time constant of the input filter                                0.38 ms
     ● Basic execution time of the module (all channels                 1 ms
     released)
Analog value generation for the outputs
 Integration and conversion time/resolution per channel
     ● Resolution with overrange (bit including sign), max.             12 bit
     ● Conversion time (per channel)                                    1 ms
 Settling time
     ● for resistive load                                               0.6 ms
     ● for capacitive load                                              1 ms
     ● for inductive load                                               0.5 ms
Encoder
 Connection of signal encoders
     ● for voltage measurement                                          Yes
     ● for current measurement as 2-wire transducer                     Yes; with external supply
     ● for current measurement as 4-wire transducer                     Yes
     ● for resistance measurement with two-wire connection              Yes; Without compensation of the line resistances
     ● for resistance measurement with three-wire connection            No
     ● for resistance measurement with four-wire connection             No
 Connectable encoders
     ● 2-wire sensor                                                    Yes
6ES73146BH040AB0                                                                                                 Subject to change without notice
                                                                       6/26/2025
Page 6/11                                                                                                                   © Copyright Siemens
             — permissible quiescent current (2-wire sensor), max.      1.5 mA
Errors/accuracies
 Temperature error (relative to input range), (+/-)                     0.006 %/K
 Crosstalk between the inputs, min.                                     60 dB
 Repeat accuracy in steady state at 25 °C (relative to input            0.06 %
 range), (+/-)
 Output ripple (relative to output range, bandwidth 0 to 50 kHz),       0.1 %
 (+/-)
 Linearity error (relative to output range), (+/-)                      0.15 %
 Temperature error (relative to output range), (+/-)                    0.01 %/K
 Crosstalk between the outputs, min.                                    60 dB
 Repeat accuracy in steady state at 25 °C (relative to output           0.06 %
 range), (+/-)
 Operational error limit in overall temperature range
       ● Voltage, relative to input range, (+/-)                        1%
       ● Current, relative to input range, (+/-)                        1%
       ● Resistance, relative to input range, (+/-)                     1%
       ● Voltage, relative to output range, (+/-)                       1%
       ● Current, relative to output range, (+/-)                       1%
 Basic error limit (operational limit at 25 °C)
       ● Voltage, relative to input range, (+/-)                        0.8 %; Linearity error ±0.06 %
       ● Current, relative to input range, (+/-)                        0.8 %; Linearity error ±0.06 %
       ● Resistance, relative to input range, (+/-)                     0.8 %; Linearity error ±0.2 %
       ● Resistance thermometer, relative to input range, (+/-)         0.8 %
       ● Voltage, relative to output range, (+/-)                       0.8 %
       ● Current, relative to output range, (+/-)                       0.8 %
 Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
       ● Series mode interference (peak value of interference <         30 dB
       rated value of input range), min.
       ● Common mode interference, min.                                 40 dB
Interfaces
 Number of PROFINET interfaces                                          0
 Number of RS 485 interfaces                                            1; MPI
 Number of RS 422 interfaces                                            1; RS 422 / 485 combined
 Point-to-point connection
       ● Cable length, max.                                             1 200 m
       Integrated protocol driver
             — 3964 (R)                                                 Yes
             — ASCII                                                    Yes
             — RK 512                                                   Yes
       Transmission rate, RS 422/485
             — with 3964 (R) protocol, max.                             19.2 kbit/s; 38.4 kbit/s half duplex; 19.2 kbit/s full duplex
             — with ASCII protocol, max.                                19.2 kbit/s; 38.4 kbit/s half duplex; 19.2 kbit/s full duplex
             — with RK 512 protocol, max.                               19.2 kbit/s; 38.4 kbit/s half duplex; 19.2 kbit/s full duplex
1. Interface
 Interface type                                                         Integrated RS 485 interface
 Isolated                                                               No
 Interface types
       ● RS 485                                                         Yes
       ● Output current of the interface, max.                          200 mA
 Protocols
       ● MPI                                                            Yes
       ● PROFIBUS DP master                                             No
       ● PROFIBUS DP device                                             No
       ● Point-to-point connection                                      No
 MPI
       ● Transmission rate, max.                                        187.5 kbit/s
       Services
             — PG/OP communication                                      Yes
             — Routing                                                  No
             — Global data communication                                Yes
             — S7 basic communication                                   Yes
6ES73146BH040AB0                                                                                                      Subject to change without notice
                                                                       6/26/2025
Page 7/11                                                                                                                        © Copyright Siemens
            — S7 communication                                       Yes; Only server, configured on one side
            — S7 communication, as client                            No; but via CP and loadable FB
            — S7 communication, as server                            Yes
2. Interface
 Interface type                                                      Integrated RS 422/ 485 interface
 Isolated                                                            Yes
 Interface types
      ● RS 485                                                       Yes; RS 422 / 485 (X.27)
      ● Output current of the interface, max.                        No
 Protocols
      ● MPI                                                          No
      ● PROFINET IO Controller                                       No
      ● PROFINET IO Device                                           No
      ● PROFINET CBA                                                 No
      ● PROFIBUS DP master                                           No
      ● PROFIBUS DP device                                           No
      ● Point-to-point connection                                    Yes
 Point-to-point connection
      ● Transmission rate, max.                                      19.2 kbit/s; 38.4 kbit/s half duplex; 19.2 kbit/s full duplex
      ● Interface controllable from the user program                 Yes
      ● Interface can trigger alarm/interrupt in the user program    Yes; Message on break - identification
Protocols
 PROFIsafe                                                           No
communication functions / header
 PG/OP communication                                                 Yes
 Data record routing                                                 No
 Global data communication
      ● supported                                                    Yes
      ● Number of GD loops, max.                                     8
      ● Number of GD packets, max.                                   8
      ● Number of GD packets, transmitter, max.                      8
      ● Number of GD packets, receiver, max.                         8
      ● Size of GD packets, max.                                     22 byte
      ● Size of GD packet (of which consistent), max.                22 byte
 S7 basic communication
      ● supported                                                    Yes
      ● User data per job, max.                                      76 byte
      ● User data per job (of which consistent), max.                76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET
                                                                     as server)
 S7 communication
      ● supported                                                    Yes
      ● as server                                                    Yes
      ● as client                                                    Yes; Via CP and loadable FB
      ● User data per job, max.                                      180 kbyte; With PUT/GET
      ● User data per job (of which consistent), max.                240 byte; as server
 S5 compatible communication
      ● supported                                                    Yes; via CP and loadable FC
 Number of connections
      ● overall                                                      12
      ● usable for PG communication                                  11
            — reserved for PG communication                          1
            — adjustable for PG communication, min.                  1
            — adjustable for PG communication, max.                  11
      ● usable for OP communication                                  11
            — reserved for OP communication                          1
            — adjustable for OP communication, min.                  1
            — adjustable for OP communication, max.                  11
      ● usable for S7 basic communication                            8
            — reserved for S7 basic communication                    0
            — adjustable for S7 basic communication, min.            0
            — adjustable for S7 basic communication, max.            8
6ES73146BH040AB0                                                                                                   Subject to change without notice
                                                                    6/26/2025
Page 8/11                                                                                                                     © Copyright Siemens
S7 message functions
 Number of login stations for message functions, max.    12; Depending on the configured connections for PG/OP and S7 basic
                                                         communication
 Process diagnostic messages                             Yes
 simultaneously active Alarm_S blocks, max.              300
Test commissioning functions
 Status block                                            Yes; Up to 2 simultaneously
 Single step                                             Yes
 Number of breakpoints                                   4
 Status/control
     ● Status/control variable                           Yes
     ● Variables                                         Inputs, outputs, memory bits, DB, times, counters
     ● Number of variables, max.                         30
           — of which status variables, max.             30
           — of which control variables, max.            14
 Forcing
     ● Forcing                                           Yes
     ● Forcing, variables                                Inputs, outputs
     ● Number of variables, max.                         10
 Diagnostic buffer
     ● present                                           Yes
     ● Number of entries, max.                           500
           — adjustable                                  No
           — of which powerfail-proof                    100; Only the last 100 entries are retained
     ● Number of entries readable in RUN, max.           499
           — adjustable                                  Yes; From 10 to 499
           — preset                                      10
 Service data
     ● can be read out                                   Yes
Interrupts/diagnostics/status information
 Diagnostics indication LED
     ● Status indicator digital input (green)            Yes
     ● Status indicator digital output (green)           Yes
Integrated Functions
 Counter
     ● Number of counters                                4; See "Technological Functions" manual
     ● Counting frequency, max.                          60 kHz
 Frequency measurement                                   Yes
     ● Number of frequency meters                        4; up to 60 kHz (see "Technological Functions" manual)
 controlled positioning                                  Yes
 integrated function blocks (closed-loop control)        Yes; PID controller (see "Technological Functions" manual)
 PID controller                                          Yes
 Number of pulse outputs                                 4; Pulse width modulation up to 2.5 kHz (see "Technological Functions"
                                                         Manual)
 Limit frequency (pulse)                                 2.5 kHz
Potential separation
 Potential separation digital inputs
     ● Potential separation digital inputs               Yes
     ● between the channels                              No
     ● between the channels and backplane bus            Yes
 Potential separation digital outputs
     ● Potential separation digital outputs              Yes
     ● between the channels                              Yes
     ● between the channels, in groups of                8
     ● between the channels and backplane bus            Yes
 Potential separation analog inputs
     ● Potential separation analog inputs                Yes; common for analog I/O
     ● between the channels                              No
     ● between the channels and backplane bus            Yes
 Potential separation analog outputs
     ● Potential separation analog outputs               Yes; common for analog I/O
6ES73146BH040AB0                                                                                       Subject to change without notice
                                                        6/26/2025
Page 9/11                                                                                                         © Copyright Siemens
      ● between the channels                                       No
      ● between the channels and backplane bus                     Yes
Isolation
 Isolation tested with                                             600 V DC
Ambient conditions
 Ambient temperature during operation
      ● min.                                                       0 °C
      ● max.                                                       60 °C
configuration / header
 Configuration software
      ● STEP 7                                                     Yes; STEP 7 V5.5 + SP1 or higher or STEP 7 V5.3 + SP2 or higher with HSP
                                                                   203
      ● STEP 7 Lite                                                No
 configuration / programming / header
      ● Command set                                                see instruction list
      ● Nesting levels                                             8
      ● System functions (SFC)                                     see instruction list
      ● System function blocks (SFB)                               see instruction list
      Programming language
            — LAD                                                  Yes
            — FBD                                                  Yes
            — STL                                                  Yes
            — SCL                                                  Yes
            — CFC                                                  Yes
            — GRAPH                                                Yes
            — HiGraph®                                             Yes
 Know-how protection
      ● User program protection/password protection                Yes
      ● Block encryption                                           Yes; With S7 block Privacy
Dimensions
 Width                                                             120 mm
 Height                                                            125 mm
 Depth                                                             130 mm
Weights
 Weight, approx.                                                   680 g
Classifications
                                                                                                        Version             Classification
                                                                               eClass                     14                 27-24-22-07
                                                                               eClass                     12                 27-24-22-07
                                                                               eClass                     9.1                27-24-22-07
                                                                               eClass                      9                 27-24-22-07
                                                                               eClass                      8                 27-24-22-07
                                                                               eClass                     7.1                27-24-22-07
                                                                               eClass                      6                 27-24-22-07
                                                                                ETIM                       9                  EC000236
                                                                                ETIM                       8                  EC000236
                                                                                ETIM                       7                  EC000236
                                                                                IDEA                       4                     3565
                                                                              UNSPSC                      15                 32-15-17-05
Approvals / Certificates
  General Product Approval
     Miscellaneous         Manufacturer Declara-                                                                         Metrological Approval
                                   tion
  General Product Ap-      EMV                     For use in hazardous locations
6ES73146BH040AB0                                                                                          Subject to change without notice
                                                                 6/26/2025
Page 10/11                                                                                                           © Copyright Siemens
 proval
                                                                  FM
 For use in hazardous locations                           Maritime application
                          Miscellaneous   CCC-Ex
 Maritime application
                                                         CCS (China Classifica-
                                                             tion Society)
last modified:                                     4/7/2025
6ES73146BH040AB0                                                                  Subject to change without notice
                                                   6/26/2025