Product datasheet LC1K0610M7
Characteristics TeSys K contactor - 3P(3 NO) - AC-3 - <= 440 V 6 A
- 220...230 V AC coil
Main
Range of product TeSys K
Product or component type Contactor
Device short name LC1K
Contactor application Motor control
Utilisation category AC-3
AC-4
Poles description 3P
Pole contact composition 3 NO
[Ue] rated operational voltage 690 V AC 50/60 Hz for power circuit
<= 690 V AC 50/60 Hz for signalling circuit
[Ie] rated operational current 6 A at <= 440 V AC AC-3 for power circuit
Motor power kW 3 kW at 440 V AC 50/60 Hz
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
3 kW at 500...600 V AC 50/60 Hz
3 kW at 660...690 V AC 50/60 Hz
1.5 kW at 220...230 V AC 50/60 Hz
2.2 kW at 380...415 V AC 50/60 Hz
3 kW at 480 V AC 50/60 Hz
Control circuit type AC 50/60 Hz
Control circuit voltage 220...230 V AC 50/60 Hz
Auxiliary contact composition 1 NO
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
[Uimp] rated impulse withstand 8 kV
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
voltage
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Overvoltage category III
[Ith] conventional free air thermal 20 A at <= 50 °C for power circuit
current 10 A at <= 50 °C for signalling circuit
Irms rated making capacity 110 A AC for power circuit conforming to NF C 63-
110
110 A AC for power circuit conforming to IEC
60947
110 A AC for signalling circuit conforming to IEC
60947
Rated breaking capacity 110 A at 415 V conforming to IEC 60947
110 A at 440 V conforming to IEC 60947
80 A at 500 V conforming to IEC 60947
110 A at 220...230 V conforming to IEC 60947
110 A at 380...400 V conforming to IEC 60947
70 A at 660...690 V conforming to IEC 60947
[Icw] rated short-time withstand 90 A <= 50 °C 1 s power circuit
current 85 A <= 50 °C 5 s power circuit
80 A <= 50 °C 10 s power circuit
60 A <= 50 °C 30 s power circuit
45 A <= 50 °C 1 min power circuit
40 A <= 50 °C 3 min power circuit
80 A 1 s signalling circuit
90 A 500 ms signalling circuit
110 A 100 ms signalling circuit
20 A <= 50 °C >= 15 s power circuit
Associated fuse rating 25 A gG at <= 440 V for power circuit
25 A aM for power circuit
10 A gG for signalling circuit conforming to IEC
60947
10 A gG for signalling circuit conforming to VDE
0660
Average impedance 3 mOhm at 50 Hz - Ith 20 A for power circuit
[Ui] rated insulation voltage 690 V for power circuit conforming to IEC 60947-4-
1
600 V for power circuit conforming to UL 508
690 V for signalling circuit conforming to IEC
60947-4-1
1/3
690 V for signalling circuit conforming to IEC
60947-5-1
600 V for signalling circuit conforming to UL 508
600 V for power circuit conforming to CSA C22.2
No 14
600 V for signalling circuit conforming to CSA
C22.2 No 14
Electrical durability 1.3 Mcycles 6 A AC-3 at Ue <= 440 V
Mounting support Plate
Rail
Standards BS 5424
IEC 60947
NF C 63-110
VDE 0660
Product certifications CSA
UL
Connections - terminals Screw clamp terminals 1 cable(s) 1.5...4 mm² -
cable stiffness: solid
Screw clamp terminals 1 cable(s) 0.75...4 mm² -
cable stiffness: flexible - without cable end
Screw clamp terminals 1 cable(s) 0.34...2.5 mm² -
cable stiffness: flexible - with cable end
Screw clamp terminals 2 cable(s) 1.5...4 mm² -
cable stiffness: solid
Screw clamp terminals 2 cable(s) 0.75...4 mm² -
cable stiffness: flexible - without cable end
Screw clamp terminals 2 cable(s) 0.34...1.5 mm² -
cable stiffness: flexible - with cable end
Tightening torque 1.3 N.m - on screw clamp terminals - with
screwdriver Philips No 2
1.3 N.m - on screw clamp terminals - with
screwdriver flat Ø 6 mm
Operating time 10...20 ms coil de-energisation and NO opening
10...20 ms coil energisation and NO closing
Safety reliability level B10d = 1369863 cycles contactor with nominal
load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with
mechanical load conforming to EN/ISO 13849-1
Mechanical durability 10 Mcycles
Operating rate 3600 cyc/h
Complementary
Control circuit voltage limits 0.2...0.75 Uc at <= 50 °C drop-out
0.8...1.15 Uc at <= 50 °C operational
Inrush power in VA 30 VA at 20 °C
Hold-in power consumption in VA 4.5 VA at 20 °C
Heat dissipation 1.3 W
Auxiliary contacts type Type instantaneous (1 NO)
Signalling circuit frequency <= 400 Hz
Minimum switching current 5 mA for signalling circuit
Minimum switching voltage 17 V for signalling circuit
Non overlap distance 0.5 mm
Insulation resistance > 10 MOhm for signalling circuit
Environment
IP degree of protection IP2x conforming to VDE 0106
Protective treatment TC conforming to IEC 60068
TC conforming to DIN 50016
Ambient air temperature for operation -25...50 °C
Ambient air temperature for storage -50...80 °C
Operating altitude 2000 m without derating in temperature
Flame retardance V1 conforming to UL 94
Requirement 2 conforming to NF F 16-101
Requirement 2 conforming to NF F 16-102
Mechanical robustness Shocks contactor closed, on X axis 10 Gn for 11 ms IEC 60068-2-27
2/3
Shocks contactor closed, on Y axis 15 Gn for 11 ms IEC 60068-2-27
Shocks contactor closed, on Z axis 15 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on X axis 6 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on Y axis 10 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on Z axis 10 Gn for 11 ms IEC 60068-2-27
Vibrations contactor closed 4 Gn, 5...300 Hz IEC 60068-2-6
Vibrations contactor opened 2 Gn, 5...300 Hz IEC 60068-2-6
Height 58 mm
Width 45 mm
Depth 57 mm
Product weight 0.18 kg