0% found this document useful (0 votes)
18 views5 pages

6ES75317QF000AB0 Datasheet en

The document provides detailed specifications for the SIMATIC S7-1500 Analog input module (AI 8xU/I/R/RTD BA), which features 8 channels with 16-bit resolution and 0.5% accuracy. It outlines various input ranges for current, voltage, and resistance measurements, along with diagnostics capabilities and environmental conditions for operation. Additionally, it includes information on power consumption, dimensions, weight, and compliance with ecological standards.

Uploaded by

usmanmushtaq769
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
18 views5 pages

6ES75317QF000AB0 Datasheet en

The document provides detailed specifications for the SIMATIC S7-1500 Analog input module (AI 8xU/I/R/RTD BA), which features 8 channels with 16-bit resolution and 0.5% accuracy. It outlines various input ranges for current, voltage, and resistance measurements, along with diagnostics capabilities and environmental conditions for operation. Additionally, it includes information on power consumption, dimensions, weight, and compliance with ecological standards.

Uploaded by

usmanmushtaq769
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

Data sheet 6ES7531-7QF00-0AB0

SIMATIC S7-1500 Analog input module, AI 8xU/I/R/RTD BA, 16 bit resolution,


Accuracy 0.5%, 8 channels in groups of 8; Common mode voltage 4 V DC,
Diagnostics; Hardware interrupts; Delivery including infeed element, shield bracket
and shield terminal: Front connector (screw terminals or push-in) to be ordered
separately

General information
Product type designation AI 8xU/I/R/RTD BA
HW functional status FS01
Firmware version V1.0.0
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No
● Prioritized startup No
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V15.1 / V16
● STEP 7 configurable/integrated from version V5.5 SP3 / -
● PROFIBUS from GSD version/GSD revision V1.0 / V5.1
● PROFINET from GSD version/GSD revision V2.3 / -
Operating mode
● Oversampling No
● MSI Yes
CiR - Configuration in RUN
Reparameterization possible in RUN Yes
Calibration possible in RUN No
Power
Power consumption from the backplane bus 0.85 W
Power loss
Power loss, typ. 0.9 W
Analog inputs
Number of analog inputs 8
● For current measurement 8
● For voltage measurement 8
● For resistance/resistance thermometer measurement 8
permissible input voltage for voltage input (destruction limit), 12 V; 12 V continuous, 30 V for max. 1 s
max.
permissible input current for current input (destruction limit), 40 mA
max.
Constant measurement current for resistance-type transmitter, 230 ... 370 µA
typ.
Technical unit for temperature measurement adjustable Yes; °C/°F/K
Input ranges (rated values), voltages
● 0 to +5 V No

6ES75317QF000AB0 Subject to change without notice


7/15/2025
Page 1/5 © Copyright Siemens
● 0 to +10 V No
● 1 V to 5 V Yes
— Input resistance (1 V to 5 V) 10 MΩ
● -1 V to +1 V Yes
— Input resistance (-1 V to +1 V) 10 MΩ
● -10 V to +10 V Yes
— Input resistance (-10 V to +10 V) 10 MΩ
● -2.5 V to +2.5 V No
● -25 mV to +25 mV No
● -250 mV to +250 mV No
● -5 V to +5 V Yes
— Input resistance (-5 V to +5 V) 10 MΩ
● -50 mV to +50 mV Yes
— Input resistance (-50 mV to +50 mV) 10 MΩ
● -500 mV to +500 mV Yes
— Input resistance (-500 mV to +500 mV) 10 MΩ
● -80 mV to +80 mV No
Input ranges (rated values), currents
● 0 to 20 mA Yes
— Input resistance (0 to 20 mA) 25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
● -20 mA to +20 mA Yes
— Input resistance (-20 mA to +20 mA) 25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
● 4 mA to 20 mA Yes
— Input resistance (4 mA to 20 mA) 25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
Input ranges (rated values), thermocouples
● Type B No
● Type C No
● Type E No
● Type J No
● Type K No
● Type L No
● Type N No
● Type R No
● Type S No
● Type T No
● Type U No
● Type TXK/TXK(L) to GOST No
Input ranges (rated values), resistance thermometer
● Cu 10 No
● Cu 10 according to GOST No
● Cu 50 No
● Cu 50 according to GOST No
● Cu 100 No
● Cu 100 according to GOST No
● Ni 10 No
● Ni 10 according to GOST No
● Ni 100 Yes; Standard/climate
— Input resistance (Ni 100) 10 MΩ
● Ni 100 according to GOST No
● Ni 1000 Yes; Standard/climate
— Input resistance (Ni 1000) 10 MΩ
● Ni 1000 according to GOST No
● LG-Ni 1000 Yes; Standard/climate
— Input resistance (LG-Ni 1000) 10 MΩ
● Ni 120 No
● Ni 120 according to GOST No
● Ni 200 No
● Ni 200 according to GOST No
● Ni 500 No
● Ni 500 according to GOST No
● Pt 10 No

6ES75317QF000AB0 Subject to change without notice


7/15/2025
Page 2/5 © Copyright Siemens
● Pt 10 according to GOST No
● Pt 50 No
● Pt 50 according to GOST No
● Pt 100 Yes; Standard/climate
— Input resistance (Pt 100) 10 MΩ
● Pt 100 according to GOST No
● Pt 1000 Yes; Standard/climate
— Input resistance (Pt 1000) 10 MΩ
● Pt 1000 according to GOST No
● Pt 200 No
● Pt 200 according to GOST No
● Pt 500 No
● Pt 500 according to GOST No
Input ranges (rated values), resistors
● 0 to 150 ohms No
● 0 to 300 ohms No
● 0 to 600 ohms Yes
— Input resistance (0 to 600 ohms) 10 MΩ
● 0 to 3000 ohms No
● 0 to 6000 ohms Yes
— Input resistance (0 to 6000 ohms) 10 MΩ
● PTC Yes
— Input resistance (PTC) 10 MΩ
Cable length
● shielded, max. 200 m; 50 m at 50 mV
Analog value generation for the inputs
Measurement principle integrating
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
● Integration time, parameterizable Yes
● Integration time (ms) 2,5 / 16,67 / 20 / 100 ms
● Basic conversion time, including integration time (ms) 10 / 24 / 27 / 107 ms
— additional conversion time for wire-break monitoring 4 ms (to be considered in R/RTD/U 1 to 5 V measurement)
— additional conversion time for resistance 8 ms
measurement
● Interference voltage suppression for interference 400 / 60 / 50 / 10 Hz
frequency f1 in Hz
Smoothing of measured values
● parameterizable Yes
● Step: None Yes
● Step: low Yes
● Step: Medium Yes
● Step: High Yes
Encoder
Connection of signal encoders
● for voltage measurement Yes
● for current measurement as 2-wire transducer Yes; with external supply
● for current measurement as 4-wire transducer Yes
● for resistance measurement with two-wire connection Yes; Only for PTC
● for resistance measurement with three-wire connection Yes; All measuring ranges except PTC; internal compensation of the cable
resistances
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.1 %
Temperature error (relative to input range), (+/-) 0.006 %/K
Crosstalk between the inputs, max. -50 dB
Repeat accuracy in steady state at 25 °C (relative to input 0.1 %
range), (+/-)
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-) 0.5 %
● Current, relative to input range, (+/-) 0.5 %
● Resistance, relative to input range, (+/-) 0.5 %
● Resistance thermometer, relative to input range, (+/-) Ptxxx Standard: ±1.2 K, Ptxxx Climate: ±0.8 K, Nixxx Standard: ±0.8 K, Nixxx

6ES75317QF000AB0 Subject to change without notice


7/15/2025
Page 3/5 © Copyright Siemens
Climate: ±0.8 K
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-) 0.3 %
● Current, relative to input range, (+/-) 0.3 %
● Resistance, relative to input range, (+/-) 0.3 %
● Resistance thermometer, relative to input range, (+/-) Ptxxx Standard: ±1.0 K, Ptxxx Climate: ±0.5 K, Nixxx Standard: ±0.5 K, Nixxx
Climate: ±0.5 K
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < 40 dB
rated value of input range), min.
● Common mode voltage, max. 4V
● Common mode interference, min. 60 dB
Interrupts/diagnostics/status information
Diagnostics function Yes
Alarms
● Diagnostic alarm Yes
● Limit value alarm Yes; two upper and two lower limit values in each case
Diagnoses
● Monitoring the supply voltage No
● Wire-break Yes; Only for 1 ... 5 V, 4 ... 20 mA, R, and RTD
● Short-circuit No
● Group error No
● Overflow/underflow Yes
Diagnostics indication LED
● RUN LED Yes; green LED
● ERROR LED Yes; red LED
● MAINT LED No
● Monitoring of the supply voltage (PWR-LED) No
● Channel status display Yes; green LED
● for channel diagnostics Yes; red LED
● for module diagnostics Yes; red LED
Potential separation
Potential separation channels
● between the channels No
● between the channels, in groups of 8
● between the channels and backplane bus Yes
Permissible potential difference
between the inputs (UCM) 8 V DC
Between the inputs and MANA (UCM) 4 V DC
Isolation
Isolation tested with 707 V DC (type test)
Standards, approvals, certificates
Siemens Eco Profile (SEP) Siemens EcoTech
Ecological footprint
● environmental product declaration Yes
Global warming potential
— global warming potential, (total) [CO2 eq] 38.6 kg
— global warming potential, (during production) [CO2 14.4 kg
eq]
— global warming potential, (during operation) [CO2 24.6 kg
eq]
— global warming potential, (after end of life cycle) -0.44 kg
[CO2 eq]
product functions / security / header
signed firmware update No
data integrity No
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -30 °C; From FS05
● horizontal installation, max. 60 °C
● vertical installation, min. -30 °C; From FS05
● vertical installation, max. 40 °C

6ES75317QF000AB0 Subject to change without notice


7/15/2025
Page 4/5 © Copyright Siemens
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Dimensions
Width 35 mm
Height 147 mm
Depth 129 mm
Weights
Weight, approx. 250 g
Classifications
Version Classification

eClass 14 27-24-22-01
eClass 12 27-24-22-01
eClass 9.1 27-24-22-01
eClass 9 27-24-22-01
eClass 8 27-24-22-01
eClass 7.1 27-24-22-01
eClass 6 27-24-22-01
ETIM 9 EC001420
ETIM 8 EC001420
ETIM 7 EC001420
IDEA 4 3562
UNSPSC 15 32-15-17-05

Approvals / Certificates
General Product Approval For use in hazardous locations

For use in hazard-


Test Certificates Maritime application
ous locations

Miscellaneous Special Test Certific- Type Test Certific-


ate ates/Test Report

Maritime application other

Confirmation

other Railway Environment

Miscellaneous Special Test Certific- Environmental Con-


ate firmations

last modified: 5/14/2025

6ES75317QF000AB0 Subject to change without notice


7/15/2025
Page 5/5 © Copyright Siemens