Differential Voltage
Differential Voltage
Differential Voltage
Applications
■ Bus differential high z voltage
■ Shunt reactor differential protection
■ Transformer high z ground differential
GE Multilin 1
PVD Differential Voltage
Description
Current Transformer
The PVD21 relay is available in
four models. All models include a Requirements
high-speed voltage sensing unit The PVD21 relays can be applied
(87L) that operates from the volt- for bus protection in most cases
age provided by the differentially where CT’s having negligible
connected CT’s during an internal leakage reactance are used. This
fault. In addition, a high seismic generally includes any kind of
instantaneous overcurrent unit current transformer with a
(87H) is included in the PVD21B toroidal core if the windings (on
and 21D models The overcurrent the taps used) are completely
unit 87H, which has an electrically distributed about the core. It is
separate output contact, may be preferable that all the CT’s in the
used to supplement the voltage bus differential circuit have the
Connection Diagram
Fig. 2. Simplified internal connection diagram for PVD21A and PVD21C Fig. 3. Simplified internal connection diagram for PVD21B and PVD21D
* * * * * * * * * * * *
1 3 5 7 9
1 3 5 7 2 4 6 8 10
2 6 8 Shorting bar
Shorting bar
2 www.GEindustrial.com/Multilin
PVD Differential Voltage
Ratings
The voltage unit 87L has a contin-
uous rating of 150 V.
The current unit 87H is a Hi-G,
high seismic instantaneous unit
with the following ratings for the
coil:
87H UNIT (2-50 A RANGE)
Continuous One Sec
Link Range Rating Rating
Position (A) (A) (A)
Low 2-10 3.7
130
High 10-50 7.5
20
10
www.GEindustrial.com/pm
0
0 2 3 4 5 6
Multilples of pickup setting
SELECTION GUIDE
Single-phase (3 Required)
Continuous Frequency Voltage Unit Current Unit Approx. Wt.
Rating (87L) (87H) Thyrite® Model Case in lbs (kg)
(Hz) Stacks Number Size
(V) Min Max Min Max Net Ship
}
60 --- --- PVD21A1A
50 --- --- A2A
1
60 2A 50A PVD21B1A
50 2A 50A B2A
}
150 60 75V 500V --- --- PVD21C1A M1 20(9) 27( 1 2.2)
50 --- --- C2A
2
60 2A 50A PVD21D1A
50 2A 50A D2A
60 4A 100A 2 PVD21D3A
NOTE: All PVD relays include a 0.2/2.0 A T. & SI Unit used in conjunction with the 87L Unit.
www.GEindustrial.com/Multilin 3