The document summarizes the technical specifications of the MC30 three phase overcurrent and earth fault relay. The MC30 provides protective functions like overcurrent protection, earth fault protection, and breaker failure protection. It has measurement and control capabilities including digital/analog inputs and outputs. The MC30 has communication ports for interfacing and can be expanded with optional input/output modules. It has configurable time-current protection curves and settings.

Uploaded by

vural
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
367 views3 pages

MC 30 Eng

The document summarizes the technical specifications of the MC30 three phase overcurrent and earth fault relay. The MC30 provides protective functions like overcurrent protection, earth fault protection, and breaker failure protection. It has measurement and control capabilities including digital/analog inputs and outputs. The MC30 has communication ports for interfacing and can be expanded with optional input/output modules. It has configurable time-current protection curves and settings.

Uploaded by

vural
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

MC Line

MC30
THREE PHASE OVERCURRENT & EARTH FAULT RELAY

Three phase overcurrent & earth fault relay with


programmable timecurrent curves suitable for protection
of power distribution systems with insulated, resistance
earthed or compensated neutral.

Rated input current selectable 1A or 5A, 50/60 Hz.

Connection through 3 CTs.

Protective Functions Communications


• F49 : One Thermal Image element • 1 RS485 Serial communication port on rear side
• F50/51 : Three independent overcurrent elements • 1 RS232 Serial communication port on front panel
• F50N/51N : Three Earth Fault elements • Modbus RTU / IEC870-5-103 Communication Protocols
• F51BF : Breaker Failure protection
Expansion Modules (optional)
Measurements The relay support only one expansion module
• Real Time Measurements (IA - IB - IC - Io) • “UX10-4” 10 Digital Input and 4 Outputs Relay
• Maximum Demand and Inrush Recording (IA - IB - IC - Io) • “14DI” 14 Digital Inputs
• Trip Recording (last 20 trips with date & time) • “14DO” 14 Output Relays
Control Mounting
• 4 Output Relays (programmable) • 1 Module box (2 modules with expansion), totally draw-out execution
• 3 Digital Inputs • IP44 protection case (on request IP54)
• Time tagged multiple event recording
Power Supply Ratings
• Oscillographic wave form capture
• Type 1 : 24V(-20%) / 110V(+15%) a.c. - 24V(-20%) / 125V(+20%) d.c.
• Blocking Outputs and Blockings Input for pilot wire
• Type 2 : 80V(-20%) / 220V(+15%) a.c. - 90V(-20%) / 250V(+20%) d.c.
MC07-ING-Rev.06

selectivity coordination
Software
Technical Characteristics
• MSCom2 Program interface for device management
• Complete autodiagnostic program
• Display LCD 16 (2x8) characters
• 4 Leds for signalization
2

MC30

Programmable Input Quantities


In : Rated primary current of phase CTs : (1 ÷ 9999)A step 1A
Fn : System frequency : (50 ÷ 60)Hz

F49 (T>): Thermal Image


Function enabling : Enable/Disable
Temperature prealarm : Tal = (50 ÷ 110)%Tb step 1%Tb
Thermal Image reset level : Tst = (10 ÷ 100)%Tb step 1%Tb
Continuous admissible current : Ib = (50 ÷ 130) step 1 %In
Warming-up Time constant : TW = (1 ÷ 60)min step 1min
1F - 50/51 (I>): First Overcurrent Element
Function enabling : Enable/Disable
Current setting range : I> = (0.20 ÷¸ 4)In step 0.01In
Definite trip time delay (10x[I>] in inverse time operation modes) : tI> = (0.05 ÷ 60)s step 0.01s
Instantaneous output : ≤ 0.03s
Time current curves : Indep.Definite Time (D), IEC (A / B / C), IEEE (MI / VI / I / EI / SI)
2F - 50/51 (I>>): Second Overcurrent Element
Function enabling : Enable/Disable
Current setting range : I>> = (0.50 ÷ 40)In step 0.01In
Definite trip time delay : tI>> = (0.05 ÷ 60)s step 0.01s
Instantaneous output : ≤ 0.03s
Automatic threshold doubling on inrush : 2xI = Enable/Disable
3F - 50/51 (IH): Third Overcurrent Element
Function enabling : Enable/Disable
Current setting range : IH = (0.50 ÷ 40)In step 0.01In
Definite trip time delay : tIH = (0.05 ÷ 60)s step 0.01s
Instantaneous output : ≤ 0.03s
Automatic threshold doubling on inrush : 2xI = Enable/Disable
1F - 50N/51N (Io>): First Earth Fault Element
Function enabling : Enable/Disable
Current setting range : Io> = (0.01 ÷ 4)Ion, step 0.01Ion
Definite trip time delay (10x[Io>] in inverse time operation modes) : tIo> = (0.05 ÷ 60)s step 0.01s
Instantaneous output : ≤ 0.04s
Time current curves : Indep.Definite Time (D), IEC (A / B / C), IEEE (MI / VI / I / EI / SI)
2F - 50N/51N (Io>>): Second Earth Fault Element
Function enabling : Enable/Disable
Current setting range : Io>> = (0.01 ÷ 9.99)Ion step 0.01Ion
MC07-ING-Rev.06

Definite trip time delay : tIo>> = (0.05 ÷ 60)s step 0.01s


Instantaneous output : ≤ 0.04s
3F - 50N/51N (IoH): Third Earth Fault Element
Function enabling : Enable/Disable
Current setting range : IoH = (0.01 ÷ 9.99)Ion step 0.01Ion
Definite trip time delay : tIoH = (0.05 ÷ 60)s step 0.01s
Instantaneous output : ≤ 0.04s
Breaker Failure Element
Trip time delay : tBF = (0.05 ÷ 0.75)s step 0.01s
3

MC30

Connection Diagram

Typical Characteristics
Accuracy at reference value of influencing factors 2% In - 0.2% On for measurements
2% + (to = 20 ÷ 30ms @ 2xIs) for times
Rated Current In = 1A/5A - On = 1A/5A
Current Overload 400A for 1 sec; 20A continuous
Burden on current input 0.1VA a In = 1A; 0.3VA a In = 5A
Average power supply consumption ≤ 7 VA
Output relays rating 6 A; Vn = 250 V
A.C. resistive switching = 1500W (400V max)
make = 30 A (peak) 0.5 sec.;
break = 0.3 A, 110 Vcc,
L/R = 40 ms (100.000 op.)

Order code - Example :


MC07-ING-Rev.06

MC30 1 2 1 1
Power Supply Phase Rated Zero sequence Output Options
Input Current Input Current
1 = Type 1 1 = 1A 1 = 1A 1 = Standard (with R4)
2 = Type 2 2 = 5A 2 = 5A 2 = UX10-4
3 = 14DI
4 = 14DO
btsadv.com