MC Line
MC30
                                                            THREE PHASE OVERCURRENT & EARTH FAULT RELAY
                                                            Three phase overcurrent & earth fault relay with
                                                            programmable timecurrent curves suitable for protection
                                                            of power distribution systems with insulated, resistance
                                                            earthed or compensated neutral.
                                                            Rated input current selectable 1A or 5A, 50/60 Hz.
                                                            Connection through 3 CTs.
Protective Functions                                        Communications
• F49        : One Thermal Image element                    • 1 RS485 Serial communication port on rear side
• F50/51     : Three independent overcurrent elements       • 1 RS232 Serial communication port on front panel
• F50N/51N : Three Earth Fault elements                     • Modbus RTU / IEC870-5-103 Communication Protocols
• F51BF      : Breaker Failure protection
                                                            Expansion Modules (optional)
Measurements                                                The relay support only one expansion module
• Real Time Measurements (IA - IB - IC - Io)                • “UX10-4” 10 Digital Input and 4 Outputs Relay
• Maximum Demand and Inrush Recording (IA - IB - IC - Io)   • “14DI”     14 Digital Inputs
• Trip Recording (last 20 trips with date & time)           • “14DO”     14 Output Relays
Control                                                     Mounting
• 4 Output Relays (programmable)                            • 1 Module box (2 modules with expansion), totally draw-out execution
• 3 Digital Inputs                                          • IP44 protection case (on request IP54)
• Time tagged multiple event recording
                                                            Power Supply Ratings
• Oscillographic wave form capture
                                                            • Type 1 : 24V(-20%) / 110V(+15%) a.c. - 24V(-20%) / 125V(+20%) d.c.
• Blocking Outputs and Blockings Input for pilot wire
                                                            • Type 2 : 80V(-20%) / 220V(+15%) a.c. - 90V(-20%) / 250V(+20%) d.c.
                                                                                                                                    MC07-ING-Rev.06
  selectivity coordination
                                                            Software
Technical Characteristics
                                                            • MSCom2 Program interface for device management
• Complete autodiagnostic program
• Display LCD 16 (2x8) characters
• 4 Leds for signalization
2
                                                                                                                                       MC30
    Programmable Input Quantities
    In : Rated primary current of phase CTs                               : (1 ÷ 9999)A                               step 1A
    Fn : System frequency                                                 : (50 ÷ 60)Hz
    F49 (T>): Thermal Image
    Function enabling                                                     : Enable/Disable
    Temperature prealarm                                                  : Tal = (50 ÷ 110)%Tb                       step 1%Tb
    Thermal Image reset level                                             : Tst = (10 ÷ 100)%Tb                       step 1%Tb
    Continuous admissible current                                         : Ib = (50 ÷ 130)                           step 1 %In
    Warming-up Time constant                                              : TW = (1 ÷ 60)min                          step 1min
    1F - 50/51 (I>): First Overcurrent Element
    Function enabling                                                     : Enable/Disable
    Current setting range                                                 : I> = (0.20 ÷¸ 4)In                     step 0.01In
    Definite trip time delay (10x[I>] in inverse time operation modes)    : tI> = (0.05 ÷ 60)s                     step 0.01s
    Instantaneous output                                                  : ≤ 0.03s
    Time current curves                                                   : Indep.Definite Time (D), IEC (A / B / C), IEEE (MI / VI / I / EI / SI)
    2F - 50/51 (I>>): Second Overcurrent Element
    Function enabling                                                     : Enable/Disable
    Current setting range                                                 : I>> = (0.50 ÷ 40)In                       step 0.01In
    Definite trip time delay                                              : tI>> = (0.05 ÷ 60)s                       step 0.01s
    Instantaneous output                                                  : ≤ 0.03s
    Automatic threshold doubling on inrush                                : 2xI = Enable/Disable
    3F - 50/51 (IH): Third Overcurrent Element
    Function enabling                                                     : Enable/Disable
    Current setting range                                                 : IH = (0.50 ÷ 40)In                        step 0.01In
    Definite trip time delay                                              : tIH = (0.05 ÷ 60)s                        step 0.01s
    Instantaneous output                                                  : ≤ 0.03s
    Automatic threshold doubling on inrush                                : 2xI = Enable/Disable
    1F - 50N/51N (Io>): First Earth Fault Element
    Function enabling                                                     : Enable/Disable
    Current setting range                                                 : Io> = (0.01 ÷ 4)Ion,                   step 0.01Ion
    Definite trip time delay (10x[Io>] in inverse time operation modes)   : tIo> = (0.05 ÷ 60)s                    step 0.01s
    Instantaneous output                                                  : ≤ 0.04s
    Time current curves                                                   : Indep.Definite Time (D), IEC (A / B / C), IEEE (MI / VI / I / EI / SI)
    2F - 50N/51N (Io>>): Second Earth Fault Element
    Function enabling                                                     : Enable/Disable
    Current setting range                                                 : Io>> = (0.01 ÷ 9.99)Ion                   step 0.01Ion
                                                                                                                                                     MC07-ING-Rev.06
    Definite trip time delay                                              : tIo>> = (0.05 ÷ 60)s                      step 0.01s
    Instantaneous output                                                  : ≤ 0.04s
    3F - 50N/51N (IoH): Third Earth Fault Element
    Function enabling                                                     : Enable/Disable
    Current setting range                                                 : IoH = (0.01 ÷ 9.99)Ion                    step 0.01Ion
    Definite trip time delay                                              : tIoH = (0.05 ÷ 60)s                       step 0.01s
    Instantaneous output                                                  : ≤ 0.04s
    Breaker Failure Element
    Trip time delay                                                       : tBF = (0.05 ÷ 0.75)s                      step 0.01s
3
                                                                                                                                        MC30
                                                          Connection Diagram
    Typical Characteristics
    Accuracy at reference value of influencing factors           2% In - 0.2% On                        for measurements
                                                                 2% + (to = 20 ÷ 30ms @ 2xIs)           for times
    Rated Current                                                In = 1A/5A - On = 1A/5A
    Current Overload                                             400A for 1 sec; 20A continuous
    Burden on current input                                      0.1VA a In = 1A; 0.3VA a In = 5A
    Average power supply consumption                             ≤ 7 VA
    Output relays                                                rating 6 A; Vn = 250 V
                                                                 A.C. resistive switching = 1500W (400V max)
                                                                 make = 30 A (peak) 0.5 sec.;
                                                                 break = 0.3 A, 110 Vcc,
                                                                 L/R = 40 ms (100.000 op.)
    Order code - Example :
                                                                                                                                                            MC07-ING-Rev.06
    MC30                                   1                     2                           1                           1
                                           Power Supply          Phase Rated                 Zero sequence               Output Options
                                                                 Input Current               Input Current
                                           1 = Type 1            1 = 1A                      1 = 1A                      1 = Standard (with R4)
                                           2 = Type 2            2 = 5A                      2 = 5A                      2 = UX10-4
                                                                                                                         3 = 14DI
                                                                                                                         4 = 14DO
                                                                                                                                                            btsadv.com
The performances and the characteristics reported in this document are not binding and can modified at any moment without notice.
                                                                       Microelettrica Scientifica S.p.A. - 20089 Rozzano (MI) - Via Alberelle 56/58 Italy
                                                                       Tel. +39 02 575731 - Fax +39 02 57510940 - E-Mail: sales.relays@microelettrica.com