NIVOCONT
2.3 ACCESSORIES
Thank you for choosing a NIVELCO instrument.
We are sure that you will be satisfied throughout its use!
KRK - 512 CONDUCTIVE
LEVEL SWITCH
Users manual
Certificate of Warranty
Declaration of Conformity
Sealing (2 mm thick)
(KLINGER OILIT)
1 pc. 3/8 (for KSP-201,
KSS -201, KSN-201)
1 pc. 1 for a KSH-20_
M6 nut (standard SW):
3 pcs. for KSH-202
4 pcs. for KSH-203, KSH-204
M6 nut (non-st. SW):
1pc. for KSH-204
1. APPLICATION
The conductive measuring principle can be applied to liquids with specific conductivity over
10 S/cm. The switching unit can sense the resistance between probes. Conductivity
measurement is suitable only for detecting the presence of liquid at a given level of the
tank. This level is represented by the length of the probe.
The level switch consists of a NIVOCONT KRK-512-5 type switching unit and the
KLN-2 type probes selected according to the task. Probes are to be connected to the
NIVOCONT KS-0 type probe socket head that can be screwed into the tank. If the
material of the tank or its internal insulation is not conductive then a reference probe
should be used in addition to the one, two, three or four probe(s), if the material of the tank
is conductive, the tank can be used as a reference probe.
The conductive switch is suitable for filling / emptying control or level limit.
USER'S MA NUAL
Manufac tu rer
NIVELCO Proc ess Contro l Co.
H-104 3 Buda pest, Du gonics u. 1 1.
Phon e: 88 9-010 0 Fa x: 889 -0200
e -mail: sa les@nivelco.com www.nivelc o.co m
2. TECHNICAL DATA
2.1 GENERAL DATA
2.1.1 TECHNICAL DATA OF THE SWITCHING UNIT
Type
2.1.2 TECHNICAL DATA OF PROBE SOCKETS
KRK-512-5
Probe voltage
Probe current
Sensitivity
Max. cable capacity
Response
Setting accuracy (mech.)
Delay
t1 delay
Relay output
Switching voltage
Switching current
Switching power
Electrical strength
Mechanical life-span
Electrical life-span
Power supply Un
3.5 V AC
< 0.2 mA AC
Adjustable: 5 k ... 100 k
800 nF
max. 400 ms
5%
Adjustable: 0.5 10 s
1.5 s
1x SPDT
250 V AC1, 24 V DC
8 A AC1
2500 VA AC1, 240 W DC
3.75 kV
3 x107 switches
0,7x105 switches
24 V 240 V AC / DC
nominal voltage
15% ... +10%
max 2.5 VA / W
-20 C ... +55 C
max. 2.5 mm2 / with insulation 1.5 mm2
Class II.
IP 20
DIN EN 60715 rail
72 g
Voltage range allowed
Power consumption
Ambient temperature
Electrical connection
Electrical protection
Ingress protection
Mechanical connection
Mass
KSK- KSP201 201
Type
Nr. of probes
Insulation of
socket
Cable
gland
Process
connection
KSS201
KSN201
1
ABS
PP
KSH203
KSH204
KSH301
KSH302
2+r
3+r
4+r
1+r
2+r
PFA
PP
Housing material
Medium
max 80C
temperature
Max. pressure
0.3MPa
Ingress protection
Mass
0.05 kg
KSH304
3+r
4+r
M20x1.5
cable diameter 6 ... 12 mm
3/8 BSP
KSH303
M4 nut,
rubber cap protected
Pg 9
Socket material
KSH202
1 BSP
A44
c. steel
KO35
stainless steel (1.4571)
Paint coated aluminium cast
KLN2
KLP201
KLP204
M6
KO35
1.4571
PP
PBT
max 200 C
max 80C
1.6 MPa
0.3 MPa
0.22 kg/m
IP 20
0.1 kg
IP 65
0.4 kg
PP
max
80C
PVDF
max
130C
r =reference probe
2.2 ORDER CODES
NIVOCONT
KRK 512
Power supply
24-240 V AC/DC
NIVOCONT KS
CODE
5
TYPE
Cable probe
SINGLE PROBE
PP socket
Carbon steel socket
St. steel socket
MULTIPLE PROBES
St. steel socket
NIVOCONT KLN 2
Probe length*
0.5 m 3 m
CODE
05 30
CODE
K
HOUSING MAT.
Aluminium
Plastic
0
CODE
2
3
CODE
1
2
3
4
PROBE NUMBER
1 + ref. probe*
2 + ref. probe
3 + ref. probe
4 + ref. probe
P
S
N
* only plastic version
Separator:
NIVOCONT KLP 201
NIVOCONT KLP 204
* to be ordered in 0.5 m units
for plastic version
for aluminium version
2.4 DIMENSIONS
17,6
64
35
14
~ 114
16
M20x1.5
35
90
67,5
45
Lt.55
3/8" BSP
42
~ 147
85
S=22
M6 nut
M6 nut
1 BSP
3,4
SWITCHING UNIT
CABLE PROBE
PROBE SOCKET
PROBE SOCKET
PROBE
KRK-512-5
KSK-201
KSH-20
KSP-201 / KSS-201 / KSN-201
KLN-2
89
M20x1,5
38
121
22
Uninsulated reference probe
1 BSP
80
33
22
38
M6
PROBE SOCKET
KSH-202
KSH-203
SEPARATOR
KSH-204
KLP-204
PROBE SOCKET
SEPARATOR
KSH-30
KLP-201
3. INSTALLATION
5.4. LEVEL CONTROL
KRK-512-5 switching unit can be mounted on DIN EN 60715 rail.
It is recommended that the KLN-2 type probes are cut to the length required for level
detection on site. The probes should be screwed into the KS-20 type sockets.
NIVOCONT KRK-512-5 can be
used for control of filling or
emptying.
During filling control the PUMP
switch should be in position UP
and during emptying control in
position DOWN. That way in
case a power supply outage
occurs
(energised
relay)
overfilling or unwanted emptying
is prevented.
ALWAYS REMEMBER TO TIGHTEN THE PROBE WITH AN M6 NUT!
When using KSH-204 type probe sockets the reference probes should be tightened with
special SW hexagonal M6 nuts!
It is suggested that KLP- type separators be used at every 0.5m for multiple probe
devices to keep the probes apart.
A KSK-201 single probe, attached to an insulated cable, can be lowered into pits and wells
without running the risk of a short circuit. When a measurement is needed in a well or in a
plastic pipe 2 of them have to be used.
4. ELECTRICAL CONNECTION
If the wall of the tank is
conductive no reference probe
is needed. In this case terminal
C is to be connected to the
tank. On multiple probe units
E1 and E2 are marked with
14, the reference probe is
marked with C. Admissible
length of cable between signal
processor and probes depends
on cable capacity and
conductivity.
Un
E2
E1
A1
A2
E1
E2
16
15
18
max
min
FILLING
Un
Un
A1
A2
E1
E2
max
A1, A2 - power supply
C - reference probe
E1 - upper level probe
E2 - bottom level probe
15, 16, 18 - relay output
min
16
15
18
max
level
min
t1
EMPTYNG
Un
max
level
min
t1
Connections for NIVOCONT KRK-512-5
5. PUTTING INTO OPERATION
5.1. ADJUSTMENT
6. MAINTENANCE, REPAIR
The green LED (Un) shows that the unit is on, and the energised state of the relay is
indicated by the red LED. Operating mode and delay time (ON and OFF) can be set with
the rotary selector switch and potentiometer on the front panel.
To set the sensitivity using SENS potentiometer do the following: submerge all probes into
the fluid. Set a minimal delay time (t). Adjust the sensitivity from min. to max. value until the
relay becomes energised. Now set the sensitivity a little higher, but dont set a higher
sensitivity than needed.
krk5121a0600h_02
July 2008.
Nivelco reserves the right to change technical data without notice!
max
Function
3
t 2
[s ]
1
4 5 6 7
8
9
10
Probe connection terminal
15
18
Output terminals
Front panel of NIVOCONT KRK-512-5
5.2. LED INDICATION
Green LED is on
Red LED is on
Red LED is off
Red LED blinking
power supply is on
relay is switched on (contacts 15 and 18 are closed)
relay is disconnected (contacts 15 and 16 are closed)
output delay indication
5.3. SINGLE-LEVEL MONITORING LIMIT SWITCHING
If KRK-512-5 is monitoring only one
level, the sensor probe should be
connected to both E1 and E2
terminals. For High Fail-safe mode
indication the PUMP switch should be
in UP position and for Low level alarm
indication in DOWN position. Level
alarm conditions are indicated in the
same way (by de-energised relay
state) as when a power cut-off occurs.
8. WARRANTY
Output indicator (red LED)
Probe sensitivity adjustment
16
Relative humidity: max. 85%
E2
Un
Delay adjustment
Ambient temperature: -30 70 C
Probe connection terminals
A2
E1
Power supply indicator
(green) LED
7. STORAGE
All Nivelco products are warranted free of defects in materials or workmanship for a period
of two years from the date of purchase, as indicated in the Certificate of Warranty.
Power supply terminals
A1
The device does not require regular maintenance.
Repair within and beyond the warranty period is carried out at the Manufacturers location.
Un
A1
A2
E1
E2
16
15
18
max