Technical Specifications:
Wireless Network Equipment
Sr.               Name of Equipment & Specifications            Qty.   Unit Price   Total
 1    WLC (Gateway)
         It can manage up to 500+ APs, meeting requirements     02
         of medium and enterprise campuses.
         2 x 25G SFP28 ports with Transceivers
         2 x 10G SPF+ with Transceivers
         2 x 2.5 GbE RJ45 ports
         At least 12.5 Gbit/s Throughput
        Automatic channel optimization
        AAA supported active directory / RADIUS/ LDAP support
        Must support High Availability
        Must support SD-WAN
        Must support Network Monitoring
        Wi-Fi 7 / Wi-Fi 8 Ready
     Management and Security Features
      Next Day Inspection (NDI)
      SSL Certificates:
      Firewall Insights
      Granular Control
      Threat Protection
      Should be able to Run Network for full-stack network
      management
     WLC Gateway Compliance requirements.
     Should be compactable with the following Compliance
       International Organization for Standardization 27001
       (ISO 27001)
       General Data Protection Regulation (GDPR)
       International regulations
       University Record & Data Retention
     Software Requirements.
       Support 3rd Pary syslog servers like Kiwi etc.
       Support UIPATH AI
       Built-in Ticket creation for emergency support
       Should be compactable with XDR and SIEM
       Endpoint Visibility using Observium or Zabbix
       Ability to run Automations using Automation tools like
       NETBOX
       Ability to run Standalone & offline in absence of
       authentication assessment server
     Storage Hardware Requirements
       (16) 3.5" HDD / SSD support
       (2) 10G SFP+ uplinks and (1) 10 GbE RJ45 port
       Data protection with RAID Storage Technology
      (2) included hot-swap PSUs for power redundancy
      Dedicated AI Chipset for AI Utilization
      Storage: 8TB HDD (Total 8 HDDs)
      3.5 Inch SATA 6Gb/s 7200 RPM 256MB Cache
      High Availability Ready: Shadow Mode High Availability
      with automatic failover provides uninterrupted
      connectivity (VRRP)
      Must Support Built-in Touch Display Bezel
      With Mounting Railing Kits
2   Access Point Indoor
       WiFi IEEE 802.11a/b/g/n/ac/ax/be (WiFi 6/6E, WiFi 7)
       WPA-PSK, WPA-Enterprise (WPA/WPA2/WPA3/PPSK)
       Can support min 500 plus Concurrent users
       Channel Bandwidth upto 320 MHz                              200
       Frequency Band Range 2.4Ghz, 5Ghz and 6 GHz
       2.4 Ghz 2 x 2 (DL/UL MU-MIMO)
       5 Ghz 4 x 4 (DL/UL MU-MIMO)
       6 Ghz 2 x 2 (DL/UL MU-MIMO)
       Network Interface Upto 2.5 GbE RJ45
3   10G Core Switch                                                02
       32 Port Layer Switch with High Capacity 10G SFP+ and
       25G SFP28 Connections
       28 10G SFP+, 4 25G SFP28 ports with Transceivers
       Switching Capacity at least 760 Gbps, Throughput 380
       Gbps with Forwarding rate 565 Mpps
       Dual Power Supply
       Must support Storm Control, Multicast/Broadcast rate
       limiting, STP/RSTP, DHCP snooping/guarding, DHCP
       Relay, Inter VLAN routing, Network Loop Protection
       Wi-Fi 7 / Wi-Fi 8 Ready
4   Layer 3 24 ports PoE Network Switch
       24 Ports, Layer 3 Switch with 2.5 GbE PoE+, 2 10G SFP+
       Ports                                                       20
       GbE PoE 12 Ports, 2.5 GbE RJ45 12 Ports, 2 10G SFP+ ports
       Switching Capacity at least 120 Gbps with Forwarding
       rate 90 Mpps
       PoE Power 400W
       Must support Storm Control, STP/RSTP, DHCP
       snooping/guarding, DHCP Relay, Inter VLAN routing,
       Network Isolation with ACLs
       Wi-Fi 7 / Wi-Fi 8 Ready
5   Layer 2 Non PoE 48 Ports Network Switch                        15
       48 GbE RJ 45 Ports, 4 1G SFP Ports
       Switching Capacity at least 104 Gbps, Throughput 52
       Gbps with Forwarding rate 75 Mpps
       Must support Storm Control, STP/RSTP, DHCP
       snooping/guarding
6   Layer 2 Non PoE 24 Ports Network Switch                        12
       24 GbE RJ 45 Ports, 2 1G SFP Ports
         Switching Capacity at least 52 Gbps, Throughput 26 Gbps
         with Forwarding rate 38 Mpps
         Must support Storm Control, STP/RSTP, DHCP
         snooping/guarding
6     SFP Transceivers 10GE Single Mode                                20
      Single Mode 10 GE SFP +
7     SFP Transceivers 1GE Single Mode                                 15
      Single Mode 1GE SFP +
8     Fiber Single Mode Patch Cords
         Fiber Single Mode Patch Cords Single Mode                     80
9     Network Cabinet
         10U Network Cabinet with Fan with 600mm Depth                 30
10    Power Backup.                                                    15
      At least 950W DC Power Availability with at least 6 DC
      Smart Power ports with 1 G RJ45 ports with maximum
      power consumption 995W with Surge Protection
      DC Output Direct to Gateways & Switches.
11    PDU (Rack Mount)                                                 2
      At least 16 Power Control Outlets with Maximum Output
      Current 1875W with Surge protection.
      Network Managed PDU Solution
12    Ethernet Surge Protector                                         30
      Protects Ethernet Devices with 2 Passive, surge
      protected RJ45 connections compatible with 2.5 GbE
      networks with ESD/EMP Protection, Absorbing transient
      current with response to surge voltage from 100V/s to
      1kV/us, PoE Support, Data Line protection upto 2.5 Gbps
13    Patch Cord:
      1 Meter, Pure Copper (Branded)                                  50
17    96 Core Single Fiber Optic Cable (LTE) Laying based on       Around 4
      ground survey for backbone DC connectivity with on-            KM
      campus departmental/hostel, and Department buildings.
18   LAN Networking/Power Work:
      Connectivity mounting and installation of all Access
      points with Switches existing and current purchase.            As per
      Duct and PVC pipe for connectivity of Access point           actual/ per
      throughout the campus including Pure Copper Cat 6              meter
      Cable Roll
      Complete End to End Connectivity of network switches
      with Core switches And Wireless LAN controller with
      Access Points.
      Power Socket with Power Cable for Network Cabinets
      wherever Required
19    Estimation of Passive (Structure Cabling accessories and       As per
      Fiber Optic Backbone network connectivity) BoQ is              actual
      separately attached.                                           Survey
           Total cost of Wi-Fi Equipment
                  (Turnkey Basis)
      Data Center Facility Equipment
1     Cabinets                                                                      QTY   UOM
                                 42U Closed Cabinet kit, dimension
                                 600mm(W)*1400mm(D)*2000mm(H). Including
                                 9-folded support frame, mounting flange, top
                                 panel with brush, bottom panel with brush,
                                 wheels and cups, front cold air management
1.1   Closed Cabinet Kit                                                             6    No
                                 channel, and rear hot air management channel,
                                 sandwich type transparent front door with
                                 thermal insulation, split rear doors, emergency
                                 ventilation system to open doors upon over
                                 temperature.
                                 Side door with insulation and side air channel
1.2   Side Door                  sealing panels with insulation, for Closed          2    No
                                 Cabinet of 1100mm(D)*2000mm(H).
                                 Lights for mdc, red light at rear side and blue
1.3   Environment Lights                                                             6    No
                                 light at front side.
                                 Quick installation type tool free blanking panel
1.4   Blanking Panel                                                                180   No
                                 1U height.
                                 Vertical cable organizer, 42U height. Including
1.5   Vertical Cable Organizer                                                      12    No
                                 cable plate, and cable rings.
                                 Top cable management system, seperation of
1.6   Top Cable Management       power and signal wiring. Dimension                  6    No
                                 600mm(W)*360mm(D)*150mm(H)
      Thermal
2
      Management System
                                 12.7kW or ghier Inrow type, cooling with
      Inrow DX 12.7kW Cooling
2.1                              humidification, inverter compressor, condenser      2    No
      or higher
                                 included.
3     Power System
                                 UPS rack mount, 20kVA high frequency type,
3.1   Rack Mount UPS-20kVA                                                           2    No
                                 220V/220V, 3U height
                                 Rack mount PDM, 63A 3P power input,
                                 including power meters, surge protection, and
      Power Distribution
3.2                              power distribution & management braces of 2*        2    No
      Module
                                 UPS, 2* Cooling, 1* ups bypass, 4* PDU, and
                                 1* surge protection. 6U height.
3.3   Basic PDU-16 Sockets       PDU C13 and C19 Sockets type                       10    No
                                 Rack mount battery package, VRLA type, 40*
3.4   Rack Mount Batteries                                                           2    No
                                 12V/9AH batteries. 2U height.
4     Monitoring System
                                 Integrated monitoring host with built in 10-inch
                                 display, communicates with sensors
      Monitoring Host- All in    (temperature & humidity, smoke, leaking, door
4.1                                                                                  1    No
      One Type                   open) and equipment (cooling, ups and power
                                 meters). Web portal and Modbus-TCP port.
                                 Wall mounting type.
      Sensor - Temperature &
4.2                                Temperature and humidity sensor, RS-485 type       6       No
      Humidity
4.3   Sensor - Smoke               Smoke sensor, dry contact type with alarm light.   6       No
      Sensor - Leaking none
4.4                                Water flooding sensor, none positioning type.      2       No
      Positioning Type
4.5   Security System
                                   Access controller, management of users, logs
4.6   Access controller
                                   and access authorization
                                   3 in 1 access control reader, supporting
      Supporting                   fingerprint, RFID card, and pin both side front    1      LOT
                                   and back side sides of racks
                                   Door locking system Kit assembly, including
4.7   Door Locking
                                   magnetic type locks, and hydraulic open poles
5     LOCAL PORTION
      Electrical Cables
                                                                                          Total Meter
      Main Output Cable from                                                              as per site
5.1                                4cx50mm+Earth PVC/PVC Cable on cable try           1
      ATS to UPS PDM                                                                      Survey by
                                                                                            Vendor
                                                                                          Total Meter
      UPS Output Cable from
                                                                                          as per site
5.2   PDM to Each IT rack with     3cx6mm PVC/PVC cable on cable try                  1
                                                                                          Survey by
      path A+B
                                                                                            Vendor
                                                                                          Total Meter
      Main Input cable for In-     4cx6mm PVC/PVC cable + Earth Cable on                  as per site
5.3                                                                                   1
      row cooling units            cable try                                              Survey by
                                                                                            Vendor
6     Earthing
                                   Earth pit for Data Center equipment/Generator
      Main Earth Pit for Data
                                   to attain less than 1 Ohm value with all
6.1   Center                                                                          1      Job
                                   chemical, copper rope, Copper rod or plate, GI
      equipment/Generator
                                   for watering, main hole, complete in all respect
                                                                                          Total Meter
      Earth Wire from Earth pits                                                          as per site
6.2                                1cx35mm PVC/PVC Earth cable                        1
      to Power room                                                                       Survey by
                                                                                            Vendor
                                                                                          Total Meter
                                   1x6mm earth cable to SRG earth fo Each IT              as per site
6.3   SRG Earthing                                                                    1
                                   racks/Cable try with Earth Bar                         Survey by
                                                                                            Vendor
       Cable Management
 7
       System
                                                                                  Total Meter
                             G I Cable try Size 8"x3" perforated without
       Data/Power/                                                                as per site
7.1    Cooling cable try
                             cover including powder coated paint, hanging     1
                                                                                  Survey by
                             rod, bend, through and accessories
                                                                                    Vendor
       FM200 Fire
 8     Suppression System
       (Datacenter)
8.1                          Extinguishing Control Panel with batteries
8.2                          Optical Smoke detector with base
8.3                          First Stage Fire Alarm Sounder
8.4                          Second Stage Fire Alarm Sounder Flasher
8.5                          Abort Switch                                     1      LOT
8.6                          Gas Discharge Nozzle 360*
8.7                          FM200 gas in kgs UL Listed & FM Approved.
                             cylinder with electrical Actuator and cylinder
8.8
                             holding bracket.
        Conventional fire
 9     detection alarm
       system (Power Room)
                             Control Panel with batteries
9.1                          12 Volt 3.2 Ah
9.2                          Optical Smoke detector with base                 1      LOT
9.3                          Manual Call Point
9.4                          Fire Alarm Sounder flasher
       Security and
10
       Surveillance
                             IP Cameras
                             8 Port NVR including 2x16 TB Surveillance
10.1
                             Storage Drive                                    1      No.
10.2                         Indoor IP cameras                                6      No.
10.3                         Management Software                              1      No.
10.4                         Network Cable                                    6      Job
10.5                         Conduiting with installation                     6      Job
                             Access Control
                             Touchless 3 in 1 Biometric access control
10.6                                                                          3      No.
                             system
10.7                         EM Locks 600 Lbs.                                3      No.
10.8                         Exit Buttons with Back Box Touch less            3      No.
10.9                           Cabling / Conduiting                                1        Job
10.10                          Management Software                                 1        No.
        In-row Precision air
 11
        conditioning
                               TO INSTALL NEW IN-ROW COOLING
11.1
                               UNITS
                               Final positioning & installing 12.7kW or higher.
                               (Liquid and Hot gas copper piping c/w all
11.2
                               accessories and fittings covering distance from
                               indoor to outdoor condenser units,
                               Refrigerant Hard copper Hot Gas Line, Liquid
11.3
                               Line including Bend, Gas brazing (single circuit)
11.4                           Install air cooled condenser bracket support
                               Drainage system for condensate water c/w
11.5
                               insulation.
                               N2 Pressure test at 300 psi for 24 hours for
11.6                                                                               1       LOT
                               copper piping.
                               Control cabling Conducting from indoor to
                               outdoor condenser. (To supply and install 3 x
11.7
                               2.5mm2 + E + 1 Spare PVC cables from indoor
                               to outdoor condenser unit.)
11.8                           Refrigerant gas, R410A.
                               Water tank with PPR Pipe and water filter for
11.9                           humidification water supply (Supply &
                               Installation included)
11.10                          Testing and commissioning.
 12     Civil Work
                               Data Center Partitioning wall with blocks and
12.1                           plaster including tempered glass 12mm looking       1        Job
                               window size 3ftx6 ft
                               60min fire rated door Size 3'-6''X 7' with all
12.2                           Accessories door closer, lock, fireproof glass      1        Job
                               window.
                               Paint work to whole facility, datacenter, power
12.3                           room, NOC and entrance Lobby with filling,          1        Job
                               rubbing.
                               SMD Panel light size 1ftx4ft with cabling size
12.4                                                                               1        Job
                               3x029x2 with motion sensor switch.
        ESD (Anti-Static)
 13
        Flooring
                               ESD Size 2x2 with anti-static vinal flooring with
13.1                                                                               1        Job
                               earthing strip mesh for datacenter Power room
        Ultrasonic Anti-
 14
        rodent
                                                                                       Qty as per
14.1                           Ultrasonic Dou Pro-Pest rappeler                    1   site survey
                                                                                                Required
                           Servers Requirements (Qty: 5 Servers)                                CPU
                                                                                                Generation
                                                                                                on Servers
Chassis               Rack-Mountable 2U Server Chassis
Total Cores           At least 440 Cores in 5 Servers
                      4 x Intel® Xeon E5-4669 v4 (2.2GHz/22Cores) CPU Module or
PROCESSOR             Higher
MEMORY                1 TB PC4-17000-R (2133Mhz) ECC Registered Server Memory per
                      Server
                      2 x 256GB SSD - SATA OS Drive 2 Each Server (Total OS SSD 10 x 256 SSD
SYSTEM DISK           in 5 Servers) Read Intensive SSD or Higher with RAID1 Support for OS
                      Installation
STORAGE               2 x 2 TB SSD SATA Storage Drive for each server
                      2 x 10 TB SSD DATA Storage for each server or Higher
Combined SSDs Size    100 TB
                                                                                               At least 440
                      1 x 4-Port 1GE Copper Interface OCP3.0 Ethernet Adapter or Higher         Cores Intel
ETHERNET
                      2 x 2-Port 10GE Fiber Interface Ethernet Adapter With 4 x 10GSFP+           based
                      Optical Transceiver Module (850nm,300m, LC)                              Servers and
RAID Controller       1 x P460-B4 12G SAS RAID Controller Module (Supporting 8 SAS             Virtualizatio
                      Ports,4GB Cache, PCIe, No Supercapacitor)                                n Software
Power Supply          2 x 1600W 80+ Platinum PSU for each server, the power module
                      can support overclocking for scalability and future GPU
                      requirements.
Rack Mount Rail       Complete Sliding Rail Kit for each server in Rack Mounting
Front Bezel           Front Security Bezel should be installed
MANAGEMENT            Embedded Server Management Software as per standard
SOFTWARE              requirement for RAID and other configurations.
Virtualization        Virtualization Software with CPU Socket based licensing with 3
Software (Optional)   Years Support Service, licenses should be perpetual
                      3 Years with warranty including replacement of parts
Hardware WARRANTY
                                                                                              QTY
                                   UPS 10KVA Online
 UPS 10KVA Online
 Max Configurable Power (Watts) 10.0kWatts /10.0kVA (Rack Mount/Tower Convertible)
 Input Voltage Configurable for 220V
 Input Voltage Range = 110-300Vac
 Input Frequency (sync to mains) 46 - 54 Hz For 50 Hz
 Unity Power Factor
 Efficiency at Full Load 94%                                                                      01
 Output Voltage Distortion Less than 5 % at full load
 Harmonic Distortion (Less than 1% on Linear Load)
 Charging Current = 4A
 Dimensions (438*600*88(2U))
 Battery Backup = 12V 9Ah*16 Nos Batteries with Third Party Battery Bank
                              3 Years 5x9 NBD with warranty including replacement of parts
 Hardware WARRANTY
Terms & Conditions of Quoted Solution
        Participated vendors must have OEM Manufacturer support with respect to quoted Hardware,
        Software and related warranties.
        Complete LAN/WLAN Turn-Key solution with High performing Wireless LAN solution is required.
        All the quoted equipment i.e. switches, controllers/gateways and AP should be from the same
        OEM.
        The bidder shall be responsible for complete end-to-end connectivity and the network shall be
        fully converged.
        The bidders would be required to conduct a detailed survey of the existing network and must
        submit heat maps with respect to the quoted Wi-Fi equipment along with diagrams of the
        Technical Survey Report (TSR), prior to submission of the tender document.
        Solution must provide Blanket Coverage of Wi-Fi signal at each and every building to give
        maximum coverage and SNR ratio shall be -70 DB to users through expansion of the existing Wi-
        Fi network.
        The bidder must be responsible for providing Network Cat 6 Cable Roll, Duct Power for newly
        installed Switches, Access Points, Uplinks, and Cabinets.
        CAT6 Copper Testing requirement: The Power Draw Test must be under 5% for a 1000 FT roll, and
        the cable must be shielded.
        Complete Cabling Solution including Racks, PDU and
        etc. must be from a single premium quality manufacturer / brand.
        The bidder must do the survey for the data center in order to fulfill the requirements of
        civil/power work and requirements for the installation of the Smart Racks solution.
        The specified quantity of items is based on internal assessment. Each bidder must verify the
        exact requirements through a physical survey before submitting the tender document within
        the designated deadline.
        The procurement authority reserves the right to adjust the quantity of equipment during the
        purchase order stage.
        The Bidders must have a minimum of 10 years of experience in implementing this type of
        solution in Pakistan and provide at least three references for similar work within the country