LEVEL SWITCH
UNITS : Flow- Liquid - m3/hr, Gas - Nm3/hr, Steam - kg/hr, Pressure - kg/Cm2g, Temp.- C , Level / Length - mm
Tag No. Customer to specify
GENERAL Service Level switch for TS3
Internal / External Internal Top Mounted
Interface NA
Body or Cage Material Cast Aluminium
Flange Material NA
Conn., Size, Type & Rating 3/4" BSP (M)
Flange Facing & Finish NA
BODY/ Location Upper NA
CAGE Location Lower NA
Case Orientation NA
Rotatable Head Yes
Finned / Extension NA
Vent / Drain Conn. Size NA
C/C Distance NA
Displacer or Float Float
Dia. or Length (Low / High) Dia 52 X 51mm
DISPLACER/ Guide tube length (GTL) 375mm
FLOAT PRESET LEVEL (L1) 325mm
Displacer / Float Material SS316
Spring Material NA
Other wetted Parts material SS 316
Function Switch
Output Potential Free Contact
Differential Fixed (min.)
Controller Action NA
Elect. Area Classification Zone1,Gas Gr. IIA/IIB,T6.
Switch Type Hermetically Sealed Reed Switch
Qty. / Form 1 C/O
SWITCH Contact Rating / Plating / Load 60 VA
On Level Inc. Contact - High NA
On Level Dec. Contact - Low Open
Cable Entry single/dual 1/2" NPT (F) Dual* entry required
Enclosure Cast AL, Ex-proof Gr. IIA & IIB x 1/2" NPT Double comp'n
Intrinsically Safe No
OPTIONS Jacketing - Medium / Conn NA
Hydrotesting NO
Upper Fluid Air
Lower Fluid Oil
SERVICE Sp. Gr. of Fluid 0.8 to 0.9
CONDITIONS Operating Pressure Test Pressure Atm 10 kg/cm²-(g)
Operating Temp. Max Temp Amb 100 °C
Set Point - Low / High 325 Low
Tag Plate Required with Tag No.
Certification Material Compliance Certificate,IP66, Material Test Certificate
CMRI, CCOE
SS.Tag plate required.
(1) One entry with explosion-proof double compression SS 304 cable gland and other entry plugged with explosion-proof SS
304 plug. The cable glands should be with PVC hoods.Cable gland shall be WP to IP66 certified
Notes for Plan (2) Float has to be insert from bottom of guide tube.
(3) Internal set point adjustment is required.
(4) Model : FGSO-E-2-1-O-1-W-W-W
FGSO-Float Operated Guide Level Switch, E-Cast AL, Ex-proof Gr. IIA & IIB x 1/2" NPT Double comp'n (ENCLOSURE), 2-
Model 60VA X 1C/O (REED SWITCH RATING X FORM), 1- One (NO. OF PRESET LEVELS), O-Non-std (FLOAT x PROCESS
Docodification CONN. COMBINE), 1- One(NO.OF FLOATS), W-None(SPECIAL FEATURES),W-Without (ACCESSORIES), W-Not
provided (LEVEL CONTROLLER (TLC))
Notes for Spares -
Hydrotest Pr. NA Item No. -
Qty. (Plan/Spares) 2/- Pump Type - VENDOR'S SIGNATURE
Model REFER NOTE 3 Client P.O. No. PL-005092 Date 24.07.12
Make PUNE TECHTROL Service - Approved by PRP
GA Drg. No. 6G920 Work Order No. - Checked by AUK
DOR No. - Project No. - Prepared by NCM
SO No. 12300234 (A1) CLIENT EAGLE BURGMANN MIDDLE EAST. DATASHEET NUMBER
END CLIENT JBF INDUSTRIES DUBAI.
CONSULTANT -
850A070
PROJECT - LS6G920 REV : 0 / 24.07.12
PLANT DUBAI
MRP CODE - 058800161
VENDOR EAGLEBURGMANN INDIA PVT LTD.