Model: IPS1675C
Frequency: 50
Fuel Type: Diesel
» Generator set data sheet
1500 kVA Prime Power
Empowering your world
Spec sheet: SS16-IPSUK
Noise data sheet (Open/enclosed): ND50-OSHHP/ND50-CSHHP
Airflow data sheet: AF50-HHP
Derate data sheet (Open/enclosed): DD50-OSHHP/DD50-CSHHP
Transient data sheet: RTF
Standby Prime
Fuel consumption kVA (kW) kVA (kW)
Ratings 1675 (1340) 1500 (1200)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
US gph 24.3 43.7 66..8 91.2 23.3 44.1 62.8 81.6
L/hr 92 165 253 345 88 167 238 309
Engine Standby rating Prime rating
Engine manufacturer Cummins
Engine model KTA50G8
Configuration Cast Iron, 60° V16 Cylinder
Aspiration Turbo Charged and Low Temperature After-Cooled
Gross engine power output, kWm 1429 1200
BMEP at set rated load, kPa 2275 1910
Bore, mm 159
Stroke, mm 159
Rated speed, rpm 1500
Piston speed, m/s 7.9
Compression ratio 14.9:1
Lube oil capacity, L 178
Overspeed limit, rpm 1850 ±50
Regenerative power, kW 116
Governor type Electronic
Starting voltage 24V Volts DC
Fuel flow
Maximum fuel flow, L/hr 570
Maximum fuel inlet restriction, mm Hg 203
Maximum fuel inlet temperature (°C) 70
Air
Combustion air, m3/min 99.2 90.2
Maximum air cleaner restriction, kPa 6.2
©2009 | Integrated Power Solutions Ltd. | All rights reserved | Specifications subject to change without notice | Integrated Power Solutions and
IPS are trademarks of Integrated Power Solutions Ltd. PowerControl and “Empowering your world” are trademarks of Integrated Power
Solutions Ltd. Other company, product, or service names may be trademarks or service marks of others.
Exhaust Standby rating Prime rating
3
Exhaust gas flow at set rated load, m /min 261 231
Exhaust gas temperature, °C 510 485
Maximum exhaust back pressure, kPa 6.7
Standard set-mounted radiator cooling
Ambient design, °C 40
Fan load, KW m 29.7
Coolant capacity (with radiator), L 310
Cooling system air flow, m3/min @ 12.7mmH2O 21.7
Total heat rejection, BTU/min 52430 42210
Maximum cooling air flow static restriction mmH2O 0.12
Open set derating factors kVA (kW)
Note: Standard open genset options running at 400V, 150m above sea level. For enclosed product derates, please refer to datasheet - DD50-
CSHHP.
27°C 40°C 45°C 50°C 55°C
Standby 1675 (1340) RTF RTF RTF RTF
Prime 1500 (1200) RTF RTF RTF RTF
Weights* Open Enclosed
Unit dry weight kgs 10324 RTF
Unit wet weight kgs 10626 RTF
* Weights represent a set with standard features. See outline drawing for weights of other configurations
Dimensions Length Width Height
Standard open set dimensions 5690 2033 2330
Enclosed set standard dimensions RTF RTF RTF
Genset outline
Open set
Enclosed set
Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.
©2009 | Integrated Power Solutions Ltd. | All rights reserved | Specifications subject to change without notice | Integrated Power Solutions
and IPS are trademarks of Integrated Power Solutions Ltd. PowerControl and “Empowering your world” are trademarks of Integrated Power
Solutions Ltd. Other company, product, or service names may be trademarks or service marks of others.
Alternator data
Feature code Connection1 Temp rise degrees C Duty2 Alternator Voltage
B668 Wye, 3 Phase 125/105 S/P P7C 380-440V
Ratings definitions
Emergency Standby Power (ESP) Limited-Time running Power Prime Power (PRP): Base Load (Continuous) Power
Applicable for supplying power to Applicable for supplying power to a Applicable for supplying power to Applicable for supplying power
varying electrical load for the constant electrical load for limited varying electrical load for unlimited continuously to a constant electrical
duration of power interruption of a hours. Limited Time Running hours. Prime Power (PRP) is in load for unlimited hours.
reliable utility source. Emergency Power (LTP) is in accordance with accordance with ISO 8528. Ten Continuous Power (COP) in
Standby Power (ESP) is in ISO 8528. percent overload capability is accordance with ISO 8528, ISO
accordance with ISO 8528. Fuel available in accordance with ISO 3046, AS 2789, DIN 6271 and BS
Stop power in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514.
3046, AS 2789, DIN 6271 and BS 5514.
5514.
Formulas for calculating full load currents:
Three phase output Single phase output
kWx1000 kWxSingleP haseFactor x1000
Voltagex1. 73x0.8 Voltage
See your distributor for more information.
Integrated Power Solutions Ltd
Suite 72, Cariocca Business Park
2 Sawley Road, Manchester
Lancashire M40 8BB, UK
Telephone: +44 (0) 1612 970145
Fax: +44 (0) 1612 970146
E-Mail: info@integratedpowersolutions.co.uk
©2009 | Integrated Power Solutions Ltd. | All rights reserved | Specifications subject to change without notice | Integrated Power Solutions
and IPS are trademarks of Integrated Power Solutions Ltd. PowerControl and “Empowering your world” are trademarks of Integrated Power
Solutions Ltd. Other company, product, or service names may be trademarks or service marks of others.