This document outlines the electrical general notes for a construction project, detailing the responsibilities of the contractor, including coordination of lighting fixtures, grounding requirements, and testing protocols. It includes specific abbreviations for various electrical components and systems, as well as instructions for labeling and documenting changes during the project. The contractor is also required to maintain accurate records and ensure compliance with safety and fire regulations throughout the installation process.

Uploaded by

nchau
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
21 views10 pages

05 Electrical

This document outlines the electrical general notes for a construction project, detailing the responsibilities of the contractor, including coordination of lighting fixtures, grounding requirements, and testing protocols. It includes specific abbreviations for various electrical components and systems, as well as instructions for labeling and documenting changes during the project. The contractor is also required to maintain accurate records and ensure compliance with safety and fire regulations throughout the installation process.

Uploaded by

nchau
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

ELECTRICAL GENERAL NOTES LIGHTING POWER FIRE ALARM SECURITY ABBREVIATIONS

GENERAL LIGHTING ARRANGEMENT XX LIGHTING FIXTURE. SUBSCRIPT INDICATES FIXTURE SIMPLEX RECEPTACLE, 20A/120V FACP FIRE ALARM CONTROL PANEL SSCP SECURITY SYSTEM CONTROL PANEL, 120V. A AMPERE
UNLESS SPECIFICALLY INDICATED OTHERWISE, ALL WORK SHOWN ON THE ARRANGE LIGHTING FIXTURES IN ACCORDANCE WITH THE ARCHITECTURAL TYPE (TYP) . REFER TO FIXTURE SCHEDULE FOR ADM ADMINISTRATOR
ELECTRICAL DRAWINGS IS NEW WORK TO BE PROVIDED UNDER THIS CONTRACT. REFLECTED CEILING PLANS. ADDITIONAL TYPES AND INFORMATION. DUPLEX RECEPTACLE, 20A/120V FAA FIRE ALARM ANNUNCIATOR PANEL ADC AUTOMATED DIALER COMMUNICATOR. AFF ABOVE FINISHED FLOOR
THE CONTRACTOR IS RESPONSIBLE FOR THE ENTIRE PROJECT DOCUMENT SET, AFG ABOVE FINISHED GRADE
G
INCLUDING ALL SPECIFICATIONS, CONTRACT DRAWINGS, ADDENDUMS, ETC. PRIOR LIGHTING COORDINATION DUPLEX RECEPTACLE, GFCI TYPE, 20A/120V FATP FIRE ALARM TRANSPONDER PANEL DSA DOOR / SECURITY ANNUNCIATOR PANEL. AIC AMPERE INTERRUPTING CURRENT
TO THEIR BID, THE CONTRACTOR SHALL REVIEW ALL CONTRACT DOCUMENTS. IF COORDINATE LIGHTING FIXTURES WITH GRILLES, DIFFUSERS, SPRINKLER AV AUDIO/VISUAL
WORK ON OTHER TRADE DRAWINGS OR WITHIN OTHER DIVISION SPECIFICATIONS HEADS, AND ACCESS PANELS, ETC. DUPLEX RECEPTACLE ON EMERGENCY POWER ADC AUTOMATED DIALER COMMUNICATOR KEYPAD. PROVIDE DOUBLE GANG BACK BOX 42" BFG BELOW FINISHED GRADE
HAS EQUIPMENT, DEVICES, APPURTENANCES, ETC. INCLUDED WITHIN THEM CIRCUIT, 20A/120V AFF UON WITH 3/4"C WITH PULL STRING STUBBED C CONDUIT
REQUIRING ELECTRICAL EQUIPMENT OR POWER FEEDS IN ORDER TO PROVIDE A MATERIAL COORDINATION KP CATV CABLE ANTENNA TELEVISION
ANSUL SYSTEM, FURNISHED BY KITCHEN EQUIPMENT TO ABOVE ACCESSIBLE CEILING. TERMINATE WITH ARCHITECTS
COMPLETE OPERATIONAL SYSTEM, IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY CEILING AND WALL CONSTRUCTION AND MATERIAL PRIOR TO ORDERING G DUPLEX RECEPTACLE ON EMERGENCY POWER ANS CONTRACTOR. PROVIDE CONNECTION FOR POWER INSULATING BUSHING. CCTV CLOSED CIRCUIT TELEVISION
INCLUDE WITHIN THEIR BID AND PAY FOR ALL ELECTRICAL WORK REQUIRED TO LIGHT FIXTURES OR OTHER DEVICES TO ENSURE PROPER FIXTURE OR DEVICE CIRCUIT, GFCI TYPE, 20A/120V AND FIRE ALARM SYSTEM AS REQUIRED CB CIRCUIT BREAKER
IS FURNISHED TO MATCH CONSTRUCTION. 49 SOUTH CARROLL STREET
COMPLETE THOSE SYSTEMS. THE CONTRACTOR SHALL SUBMIT REQUESTS FOR CARD READER. PROVIDE DOUBLE GANG BOX WITH CF COFFEE MAKER
INFORMATION DURING THE BIDDING PHASE FOR ALL DISCREPANCIES, CONFLICTS, NORMAL/EMERGENCY LIGHTING FIXTURE. SUBSCRIPT IG
ISOLATED GROUND DUPLEX RECEPTACLE, 20A/120V ZAM ZONE ADDRESSABLE MODULE CH CHIME FREDERICK, MARYLAND 21701
3/4"C WITH PULL STRING STUBBED ABOVE
CONSTRUCTABILITY ISSUES, AND CLARIFICATIONS NEEDED IN ORDER FOR THE MOUNTING HEIGHTS "NL", WHERE USED, INDICATES NIGHT LIGHT CR ACCESSIBLE CEILING. TERMINATE WITH CKT CIRCUIT PHONE (301) 662-8532
CONTRACTOR TO PROVIDE COMPLETE OPERATIONAL SYSTEMS FOR THIS PROJECT. MOUNTING HEIGHTS INDICATED ARE FROM THE FINISHED FLOOR TO THE CONNECTED AHEAD OF LIGHTING CONTROLS. EXP DUPLEX RECEPTACLE, EXPLOSION PROOF TYPE, CMR CONTROL MODULE RELAY INSULATING BUSHING. CM CEILING MOUNTED FAX (301) 662-4192
CENTERLINE OF THE WIRING DEVICE UNLESS OTHERWISE NOTED. MOUNTING 20A/120V CO CENTER OFF PROFFITTANDASSOCIATES.COM
COORDINATION HEIGHTS OF LIGHTING FIXTURES ARE TO THE BOTTOM OF THE FIXTURE UNLESS MIM MONITOR INPUT MODULE DO ELECTRICAL DOOR OPERATOR CONNECTION, 120V DM DEMOLISH
COORDINATE AND COOPERATE WITH ALL TRADES ON THE PROJECT. OTHERWISE NOTED. DUPLEX RECEPTACLE, TAMPER RESISTANT TYPE, DO DOOR OPEN
TR
20A/120V. RECEPTACLE SHALL HAVE "TR" STAMPED ON F FIRE ALARM MANUAL PULL STATION REQUEST FOR EXIT MOTION SENSOR. MOUNT E EMERGENCY ENGINEERING
RECORD DRAWINGS DEVICE LOCATIONS FACE OF DEVICE RFE CENTERED ABOVE DOOR. EC ELECTRICAL CONTRACTOR 5285 Westview Drive
SECURE AN EXTRA SET OF ELECTRICAL DRAWINGS TO BE KEPT ON SITE AND MARK, COORDINATE LOCATIONS OF SWITCHES, RECEPTACLES, AND TELE/DATA FIRE ALARM MANUAL PULL STATION, WEATHER EF EXHAUST FAN
Suite 203
Frederick, MD 21703
WR
DAILY, THE DRAWINGS IN RED AS THE PROJECT PROGRESSES IN ORDER TO KEEP OUTLETS WITH OTHER WALL MOUNTED DEVICES SUCH AS THERMOSTATS AND U DUPLEX RECEPTACLE ON UPS POWER CIRCUIT, F RESISTANT. PULL STATION SHALL BE RATED FOR HOLD UP BUTTON. PROVIDE SINGLE GANG BOX EPO EMERGENCY POWER OFF P 301.695.9424
CJL Project # 24-0304
AN ACCURATE RECORD OF ALL DEVIATIONS BETWEEN THE WORK SHOWN ON THE CONTROL STATIONS. DO NOT MOUNT WIRING DEVICES BACK TO BACK. PROVIDE 20A/120V WET LOCATIONS AND COLD TEMPERATURES WITH 3/4"C WITH PULL STRING STUBBED ABOVE EWC ELECTRIC WATER COOLER
DRAWINGS AND THE WORK WHICH IS ACTUALLY INSTALLED. THESE MARKED MINIMUM OF ONE STUD SEPARATION. HUB ACCESSIBLE CEILING. TERMINATE WITH EXP EXPLOSION PROOF
DRAWINGS SHALL REFLECT ANY AND ALL CHANGES AND REVISIONS TO THE DOWNLIGHT FIXTURE ELECTRIC WATER COOLER CONNECTION, PROVIDE FIRE ALARM SYSTEM PHOTO-ELECTRIC SMOKE INSULATING BUSHING. F FIRE ALARM
ORIGINAL DESIGN WHICH EXISTS IN THE COMPLETED WORK. DELIVER THE MARKED EWC RECEPTACLES EWC 20A/120V GFCI TYPE DUPLEX RECEPTACLE. DETECTOR, CEILING MOUNTED. DETECTOR SHALL BE FF FLUSH FLOOR MOUNTED
DRAWINGS TO THE OWNER AT PROJECT CLOSE OUT. RECEPTACLES FOR ELECTRIC WATER COOLERS (EWC) SHALL BE INSTALLED NORML/EMERGENCY DOWNLIGHT FIXTURE. SUBSCRIPT S
COORDINATE WITH EWC MANUFACTURER'S ROUGH-IN MOUNTED NO CLOSER THAN 36" TO NEAREST HOLD UP INDICATOR LIGHT. PROVIDE SINGLE GANG FHP FRACTIONAL HORSE POWER
OUT OF VIEW AND BEHIND THE EWC ENCLOSURE. VERIFY THE MOUNTING "NL", WHERE USED, INDICATES NIGHT LIGHT REQUIREMENTS GRILL/REGISTER/DIFFUSER OR CEILING FAN BOX WITH 3/4"C WITH PULL STRING STUBBED FL FLUORESCENT
TESTS HEIGHT WITH THE EQUIPMENT SUPPLIER PRIOR TO ROUGH-IN. CONNECTED AHEAD OF LIGHTING CONTROLS IND ABOVE ACCESSIBLE CEILING. TERMINATE WITH F
FLA FULL LOAD AMPS
USB
TEST ALL WIRING FOR CONTINUITY AND GROUNDS BEFORE CONNECTING ANY DUPLEX RECEPTACLE, DOUBLE USB PORT, 20A/120V FIRE ALARM SYSTEM PHOTO-ELECTRIC SMOKE INSULATING BUSHING. FO FIBER OPTIC
FIXTURES OR DEVICES. PERFORM INSULATION RESISTANCE TESTS ON ALL WIRING DEVICE COORDINATION: THOROUGHLY REVIEW AND COORDINATE ALL WALL WASH LIGHTING FIXTURE ER DETECTOR, CEILING MOUNTED, WITH ELEVATOR FPC FIRE PROTECTION CONTRACTOR
#8 OR LARGER TO ENSURE THAT ALL PORTIONS ARE FREE FROM SHORT-CIRCUITS CASEWORK, DOOR SWINGS, AND CABINET DRAWINGS AND ARCHITECTURAL S Professional Certification. I hereby
DUPLEX RECEPTACLE, GFCI TYPE, WEATHER RECALL. COORDINATE TIE IN WITH ELEVATOR IS INTERCOM SLAVE STATION. FSS FUSED SAFETY SWITCH
AND GROUNDS. PROVIDE TYPEWRITTEN SIGNED REPORTS TO ENGINEER WITH ELEVATIONS WITH DEVICE LOCATIONS PRIOR TO ROUGH-IN OF OUTLET BOXES. WALL MOUNTED LIGHTING FIXTURE GW
RESISTANT WITH "WHILE-IN-USE" WEATHERPROOF PROVIDER FU FUSE certify that these documents were
RESULTS. COVER, 20A/120V IM INTERCOM MASTER STATION. G GROUND FAULT CIRCUIT INTERRUPTER prepared or approved by me, and
BARRIERS WALL MOUNTED LIGHTING FIXTURE ON EMERGENCY FIRE ALARM SYSTEM DUCT MOUNTED GC that I am a duly licensed
GENERAL CONTRACTOR
INSPECTIONS WHERE A MULTIPLE GANG BOX HAS CIRCUITS OF DIFFERENT VOLTAGES OR CIRCUIT. SUBSCRIPT "NL", WHERE USED, INDICATES QUAD RECEPTACLE, 20A/120V PHOTO-ELECTRIC SMOKE DETECTOR, PROVIDE GLASS BREAK SENSOR. professional engineer under the
GB GND GROUND
SYSTEMS WHICH ARE REQUIRED TO BE SEPARATED, PROVIDE THE NIGHT LIGHT CONNECTED AHEAD OF LIGHTING D laws of the State of Maryland.
ARRANGE ALL NECESSARY INSPECTIONS. DELIVER ALL REQUIRED INSPECTION REMOTE INDICATOR IN NEAREST ACCESSIBLE HOA HAND-OFF INTERRUPTER
CERTIFICATES TO THE OWNER. CODE-REQUIRED SEPARATION USING A FULL HEIGHT AND DEPTH BARRIER CONTROLS License No:45511
QUAD RECEPTACLE ON EMERGENCY POWER CIRCUIT, LOCATION. MS MOTION SENSOR. HP HORSE POWER
PLATE. Expiration Date: 06/03/2026
20A/120V HVAC HEATING VENTILATING, AND AIR CONDITIONING
GROUNDING PENDANT MOUNTED LIGHTING FIXTURE FIRE ALARM SYSTEM ADDRESSABLE HEAT DETECTOR, SM SECURITY MONITOR. IR INFRARED
USB
PROVIDE GROUNDING IN ACCORDANCE WITH THE NEC FOR THE ELECTRICAL FIRE PROOFING QUAD RECEPTACLE, DOUBLE USB PORT, 20A, 120V H FIXED TEMPERATURE/RATE OF RISE TYPE, CEILING IG ISOLATED GROUND
SYSTEM INCLUDING EQUIPMENT FRAMES, CONDUITS, SWITCHES, CONTROLLERS, FOR ANY WALL OR FLOOR PENETRATIONS THROUGH FIRE RATED STRUCTURES, MOUNTED SS SOUND SENSOR. JB JUNCTION BOX
WIRE-WAYS, NEUTRAL CONDUCTORS, AND OTHER EQUIPMENT. PROVIDE A PROVIDE FIRE-PROOFING TO SEAL ALL THE PENETRATIONS AFTER THE TRACK LIGHTING FIXTURE(S) SPECIAL RECEPTACLE, NEMA CONFIGURATION AND K KEY
GROUNDING CONDUCTOR IN ALL POWER CIRCUITS. RACEWAY HAS BEEN INSTALLED. FIRE PROOFING FOR PENETRATIONS SHALL BE AMPERAGE AS NOTED FIRE ALARM SYSTEM CARBON MONOXIDE DETECTOR, PUSH BUTTON. KVA KILO-VOLT AMPERE
UL APPROVED PER THE PENETRATION MADE IN ORDER TO MAINTAIN FIRE C
CEILING MOUNTED KW KILO-WATT
LABELS RATED INTEGRITY OF THE STRUCTURE. POLE MOUNTED SITE LIGHTING FIXTURE SIMPLEX RECEPTACLE, CEILING MOUNTED, 20A/120V DOOR CONTACT (FLUSH IN DOOR). COORDINATE LTG LIGHTING
DC
PROVIDE LABELS FOR ALL PANELBOARDS, CABINETS, SAFETY SWITCHES, FIRE ALARM SYSTEM AUDIBLE (HORN), CEILING WITH ARCHITECTURAL DOOR SCHEDULE. LV LOW VOLTAGE
MOTOR-DISCONNECT SWITCHES, AND MOTOR CONTROLLERS. LABELS SHALL BE CLEAN UP F
DUPLEX RECEPTACLE, CEILING MOUNTED, 20A/120V MOUNTED, RECESSED LVC LOW VOLTAGE CONTRACTOR
MACHINE ENGRAVED, LAMINATED PLASTIC, PERMANENTLY ATTACHED WITH ON PROJECT CLOSE-OUT, CLEAN ALL ELECTRICAL DEVICES, LIGHTING EMERGENCY BATTERY LIGHTING UNIT, CONNECT ELECTRIC STRIKE DOOR LOCK. COORDINATE WITH M MOTOR
ES
SELF-TAPPING SCREWS OR RIVETS. DO NOT USE SELF ADHESIVE LABELS. PROVIDE FIXTURES, LAMPS AND LENSES, AND REMOVE ALL PAINT SPATTERS FROM AHEAD OF LOCAL SWITCH QUAD RECEPTACLE, CEILING MOUNTED, 20A/120V FIRE ALARM SYSTEM AUDIBLE/VISUAL ARCHITECTURAL DOOR SCHEDULE. MCA MINIMUM CIRCUIT AMPS
ADDITIONAL LABELS FOR CLARITY AT THE ENGINEER'S REQUEST. DEVICES, FIXTURES, AND PLATES. REPLACE ALL INOPERATIVE LAMPS. F (HORN/STROBE), CEILING MOUNTED. SUBSCRIPT MC MECHANICAL CONTRACTOR
REMOTE HEAD FOR BATTERY PACK X POKE-THRU, X INDICATES TYPE, REFER TO POKE-THRU INDICATES MINIMUM CANDELA RATING EL ELECTRIC LATCH. COORDINATE WITH MCB MAIN CIRCUIT BREAKER
J-BOX LABELING OWNER FURNISHED EQUIPMENT SCHEDULE FOR ADDITIONAL INFORMATION ARCHITECTURAL DOOR SCHEDULE. ML MULTI-LINE
LABEL ALL JUNCTION BOXES WITH PERMANENT MARKER IDENTIFYING CIRCUIT CONTRACTOR SHALL OBTAIN CUT SHEETS, INSTALLATION DATA, AND ROUGH-IN EXIT LIGHTING FIXTURE WITH DIRECTIONAL ARROWS FIRE ALARM SYSTEM SPEAKER, CEILING MOUNTED, MLO MAIN LUGS ONLY
NUMBER AND PANELBOARD OF CIRCUITS WITHIN. REQUIREMENTS FOR OWNER FURNISHED, CONTRACTOR INSTALLED AS INDICATED ON DRAWINGS. F
DFGI DEAD FRONT GFCI DEVICE RECESSED EH ELECTRIFIED HINGE. COORDINATE WITH MTD MOUNTED
EQUIPMENT AND COORDINATE ROUGH-IN AND POWER REQUIREMENTS WITH SHADED AREA DENOTES LIGHTED FACE ARCHITECTURAL DOOR SCHEDULE. MW MICROWAVE
CONDUCTOR SIZE THE OWNER'S REPRESENTATIVE PRIOR TO STARTING ANY ASSOCIATED WORK. FF FLEXIBLE FURNITURE CONNECTION FIRE ALARM SYSTEM SPEAKER/STROBE, CEILING N NURSE CALL
USE #10 AWG CONDUCTORS (MINIMUM) FOR ALL 20 AMP, 120 VOLT CIRCUIT RUNS SINGLE POLE SWITCH, 20A, 120/277V F MOUNTED, RECESSED. SUBSCRIPT INDICATES ELECTROMAGNETIC DOOR LOCK. COORDINATE NE NORMAL / EMERGENCY
EML
GREATER THAN 50' ONE WAY FROM PANELBOARD TO FIRST DEVICE/FIXTURE. USE CONDUIT ROUTING X FLOOR BOX, X INDICATES TYPE, REFER TO FLOOR BOX MINIMUM CANDELA RATING WITH ARCHITECTURAL DOOR SCHEDULE. NEC NATIONAL ELECTRICAL CODE
3
THREE-WAY SWITCH, 20A, 120/277V FB
#10 AWG CONDUCTORS (MINIMUM) FOR ALL 20 AMP, 277 VOLT CIRCUIT RUNS ALL CONDUIT RUN OVERHEAD SHALL BE RUN AT THE BOTTOM OF THE FLOOR, SCHEDULE FOR ADDITIONAL INFORMATION NF NON-FUSED
GREATER THAN 100' ONE WAY FROM PANELBOARD TO FIRST DEVICE/FIXTURE. ROOF STRUCTURE, OR LOWEST CHORD OF JOIST SPACE (AS APPLICABLE) 4
FIRE ALARM SYSTEM VISUAL (STROBE) APPLIANCE, EMH ELECTROMAGNETIC DOOR HOLDER. COORDINATE NFPA NATIONAL FIRE PROTECTION AGENCY
ABOVE IN ORDER TO AVOID CONFLICTS WITH OTHER TRADES. ALL CONDUITS FOUR-WAY SWITCH, 20A, 120/277V MEDIA BOX, PROVIDE WIREMOLD MODEL EFSB4 BOX F CEILING MOUNTED. SUBSCRIPT INDICATES MINIMUM WITH ARCHITECTURAL DOOR SCHEDULE. NFSS NON-FUSED SAFETY SWITCH
PANEL DIRECTORY SHALL BE RUN PARALLEL OR PERPENDICULAR TO BUILDING LINES AND USE WITH (1) 20A/120V DUPLEX RECEPTACLE AND (2) 1"C CANDELA RATING NIC NOT IN CONTRACT
K
PROVIDE TYPEWRITTEN PANELBOARD DIRECTORY CARD IN EACH PANELBOARD RIGHT ANGLE OFFSETS TO CHANGE DIRECTION. SINGLE POLE KEYED SWITCH, 20A, 120/277V MB WITH PULL STRING STUBBED TO ABOVE ACCESSIBLE FIXED POSITION CCTV CAMERA. NL NIGHT LIGHT
INCLUDING EXISTING PANELBOARDS MODIFIED FOR THIS PROJECT WITH CIRCUIT PL
CEILING FOR A/V CABLING. TERMINATE CONDUITS WITH FIRE ALARM SYSTEM AUDIBLE (HORN), WALL NTS NOT TO SCALE
LOAD INFORMATION AND ROOM NUMBER CLEARLY IDENTIFIED. USE ACTUAL ROOM WIRING DEVICES SINGLE POLE SWITCH WITH PILOT LIGHT, 20A, 120/277V INSULATING BUSHING F MOUNTED OC ON CENTER
NUMBERS IN THE BUILDING, NOT THE ROOM NUMBERS SHOWN ON THE CONTRACT ALL RECEPTACLES AND SWITCHES SHALL BE LABELED WITH PLASTIC PAN-TILT-ZOOM (PTZ) CCTV CAMERA. OFCI OWNER FURNISHED CONTRACTOR INSTALLED
D
DRAWINGS, AS THEY ARE OFTEN DIFFERENT. LAMINATED LABEL WITH THE PANELBOARD DESIGNATION AND CIRCUIT NUMBER DIMMER SWITCH, 20A, 120/277V J JUNCTION BOX FLUSH IN WALL FIRE ALARM SYSTEM AUDIBLE/VISUAL P POLE
FROM WHICH IT IS FED. (HORN/STROBE), WALL MOUNTED. SUBSCRIPT PA PAGING SYSTEM

HILLCREST ELEMENTARY SCHOOL


TIMER SWITCH, 20A, 120/277V, REFER TO LIGHTING F
MOTOR COORDINATION T J JUNCTION BOX ABOVE CEILING INDICATES MINIMUM CANDELA RATING PC PLUMBING CONTRACTOR
MOTORS, MOTOR STARTERS, CONTROLLERS, INTEGRAL DISCONNECT SWITCHES, EQUIPMENT DEMONSTRATION DETAILS FOR ADDITIONAL INFORMATION PF POWER FACTOR
AND CONTACTORS SHALL BE PROVIDED WITH THEIR RESPECTIVE PIECES OF
EQUIPMENT BY THE EQUIPMENT SUPPLIER. COMMUNICATE WITH THE TRADES
PROVIDE A DEMONSTRATION OF THE OPERATION OF ALL ELECTRICAL
COMPONENTS UPON REQUEST OF THE OWNER. REFER TO SPECIFICATION OC WALL SWITCH OCCUPANCY SENSOR, 120/277V, REFER
E EQUIPMENT CONNECTION F FIRE ALARM SYSTEM SPEAKER, WALL MOUNTED COMMUNICATIONS PH
PL
PHASE
PILOT LIGHT
PROVIDING THE EQUIPMENT, VERIFYING ALL REQUIREMENTS. PROVIDE ALL SECTION 260501 FOR ADDITIONAL INFORMATION AND REQUIREMENTS. TO LIGHTING DETAILS FOR ADDITIONAL INFORMATION M MOTOR CONNECTION FIRE ALARM SYSTEM SPEAKER/STROBE, WALL PNL PANEL
ELECTRICAL CONNECTIONS REQUIRED THEREIN, AND INSTALL MOTOR STARTERS. MOUNTED. SUBSCRIPT INDICATES MINIMUM CANDELA VC VOLUME CONTROL FOR PAGING SYSTEM. PROVIDE RED RELOCATED EXISTING DEVICE
LOW VOLTAGE SWITCH, REFER TO LIGHTING CONTROL F BOX PER MANUFACTURER'S RECOMMENDATION REF REFRIGERATOR
CEILING PLENUM LV
CR CORD REEL RATING
MOTOR DISCONNECTS ALL WIRING THAT WILL NOT BE RUN IN CONDUIT SHALL BE PLENUM RATED. DETAILS FOR ADDITIONAL INFORMATION WITH 3/4"C WITH PULL STRING STUBBED ABOVE REL RELOCATE
ALL MOTORS SHALL HAVE DISCONNECTING MEANS. CF CEILING FAN CONNECTION FIRE ALARM SYSTEM VISUAL (STROBE) APPLIANCE, ACCESSIBLE CEILING AND TERMINATED WITH S SOUND SYSTEM

FREDERICK COUNTY PUBLIC SCHOOLS


TEMPORARY ELECTRICAL SERVICE LOW VOLTAGE LIGHTING FIXTURE POWER SUPPLY. F WALL MOUNTED. SUBSCRIPT INDICATES MINIMUM PLASTIC BUSHING SE SERVICE ENTRANCE
PS MOUNT ABOVE ACCESSIBLE CEILING M
SPD SURGE PROTECTIVE DEVICE
MOTOR FUSE PROTECTION PROVIDE TEMPORARY ELECTRICAL SERVICE AS REQUIRED FOR CONSTRUCTION MOTOR STARTING SWITCH CANDELA RATING
WHERE FUSE PROTECTION IS SPECIFICALLY REQUIRED BY THE EQUIPMENT PROJECT. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION AND PS PAGING SYSTEM SPEAKER, RECESSED, CEILING SW SWITCH

NEW MODULAR CLASSROOMS FOR:


MANUFACTURER, PROVIDE FUSED SWITCHES IN LIEU OF NON-FUSED SWITCHES OR REQUIREMENTS. CEILING MOUNTED OCCUPANCY SENSOR. REFER TO SPRINKLER SYSTEM SUPERVISORY VALVE TAMPER T TELEPHONE
OCCUPANCY SENSOR SCHEDULE AND LIGHTING ELECTRICAL DOOR PUSH PAD, MOUNT 46" AFF TS PAGING SYSTEM SPEAKER, WALL MOUNTED. TBB TELEPHONE BACKBOARD
IN LIEU OF ENCLOSED CIRCUIT BREAKERS, OR OTHER DEVICES INDICATED. OC PP SWITCH CONNECTION
DETAILS FOR ADDITIONAL INFORMATION PS COORDINATE MOUNTING HEIGHT WITH A/V TL TWIST LOCK
UNDERGROUND WORK
CONNECTION DETAILS THE CONTRACTOR SHALL VERIFY THE LOCATION OF ALL UNDERGROUND DOOR HARDWARE NOTE SPRINKLER SYSTEM SUPERVISORY VALVE FLOW VENDOR. TR TAMPER RESISTANT
UTILITIES WITHIN THE CONSTRUCTION AREA THREE WORKING DAYS PRIOR TO WALL MOUNTED OCCUPANCY SENSOR. REFER TO ELECTRICAL DOOR OPERATOR AND DOOR FS TYP TYPICAL
SECURE APPROVED SHOP DRAWINGS SHOWING WIRING DIAGRAMS, ROUGH-IN AND SWITCH CONNECTION
HOOK UP DETAILS FROM OTHER INVOLVED CONTRACTORS FOR EQUIPMENT WHICH DIGGING. NOTIFY THE STATE AUTHORITY HAVING JURISDICTION AND AWAIT THE OC OCCUPANCY SENSOR SCHEDULE AND LIGHTING CONTROLLERS SHALL BE PROVIDED BY DOOR SS SOUND SYSTEM SPEAKER, RECESSED, CEILING U ULTRASONIC
MUST BE CONNECTED ELECTRICALLY. REQUIRED TIME BEFORE COMMENCING EXCAVATION. DETAILS FOR ADDITIONAL INFORMATION HARDWARE SUPPLIER. PROVIDE 120V POWER TO PS SPRINKLER SYSTEM PRESSURE SWITCH CONNECTION UGC UNDERGROUND COMMUNICATIONS
DOOR POWER SUPPLY AND OUTLET BOX AND CONDUIT SOUND SYSTEM SPEAKER, WALL MOUNTED. UGE UNDERGROUND ELECTRIC
DAYLIGHT SENSOR, CEILING MOUNTED. REFER TO SS UF UNDERGROUND FIBER
EQUIPMENT DETAILS CONFLICT NOTIFICATION DS FOR CONTROLS. COORDINATE WITH DOOR HARDWARE SPRINKLER SYSTEM LOW/HIGH AIR PRESSURE COORDINATE MOUNTING HEIGHT WITH A/V VENDOR
NOTIFY THE OWNER'S REPRESENTATIVE, ARCHITECT, AND ENGINEER PRIOR TO LIGHTING CONTROLS FOR ADDITIONAL INFORMATION PROVIDER LS UPS UNINTERRUPTED POWER SUPPLY
MECHANICAL EQUIPMENT WILL BE FURNISHED AND INSTALLED BY THE MECHANICAL SWITCH CONNECTION

FREDERICK, MARYLAND 21703


CONTRACTOR. THE LOCATIONS SHOWN ON THE ELECTRICAL DRAWINGS ARE PROCEEDING WITH WORK IF A CONFLICT IS FOUND BETWEEN THE DRAWINGS, F MJ MICROPHONE JACK USB UNIVERSAL SERIAL BUS
APPROXIMATE. COORDINATE WITH THE MECHANICAL CONTRACTOR TO DETERMINE SPECIFICATIONS, AND/OR FIELD CONDITIONS. THE CONTRACTOR WILL BE PHOTOCELL. MOUNT ON ROOF OF BUILDING AND AIM PB PULL BOX FIRE FIGHTER'S TELEPHONE JACK UT UNDERGROUND TELEPHONE
THE EXACT LOCATION OF EACH PIECE OF EQUIPMENT AND DETERMINE THE EXACT RESPONSIBLE FOR ALL COSTS AND CONSEQUENCES IF THE ABOVE LISTED PC NORTH. REFER TO LIGHTING CONTROL DETAILS FOR TV CABLE ANTENNA TELEVISION OUTLET UON UNLESS OTHERWISE NOTED
ROUGH-IN AND CONNECTION REQUIREMENTS. PARTIES ARE NOT CONTACTED FOR A RESOLUTION PRIOR TO PROCEEDING ADDITIONAL INFORMATION GB GROUND BAR, REFER TO DETAIL FIRE ALARM MAGNETIC DOOR HOLD OPEN DEVICE, V VOLTS
WITH THE WORK. POWERED THROUGH FIRE ALARM SYSTEM. VFD VARIABLE FREQUENCY DRIVE

1285 HILLCREST DRIVE


STARTER MOUNTING LIGHTING ZONE CONTROLLER, MOUNT ABOVE VARIABLE FREQUENCY DRIVE, FURNISHED BY COORDINATE MOUNTING HEIGHT WITH ASSOCIATED BULL HORN TYPE SPEAKER W WATTS
WHERE AN INDIVIDUALLY MOUNTED SAFETY SWITCH, STARTER, OR CIRCUIT WIRE SIZE NOTE ACCESSIBLE CEILING. REFER TO LIGHTING CONTROL VFD MECHANICAL EQUIPMENT SUPPLIER, INSTALLED AND DOOR MOUNTED DEVICE S WM WALL MOUNTED
LZC

PROFFITT & ASSOCIATES ARCHITECTS


BREAKER IS SHOWN ADJACENT TO ITS RESPECTIVE LOAD AND NOT MOUNTED ON A ALL 15A AND 20A BRANCH AND LIGHTING CIRCUITS OVER 100 FEET IN LENGTH DETAILS FOR ADDITIONAL INFORMATION POWERED BY EC WG WIRE GUARD
PA PAGING SYSTEM HANDSET WR WEATHER RESISTANT
WALL, PROVIDE ALL SUPPORTS, BRACKETS, ANCHORING, ETC. NECESSARY TO SHALL UTILIZE #10 AWG FOR HOT CONDUCTORS AND #12 FOR GROUND DM DAMPER MOTOR CONNECTION
PROPERLY SUPPORT THE DEVICE. CONDUCTORS UNLESS OTHERWISE NOTED ON DRAWINGS OR SPECIFICATIONS. EMERGENCY TRANSFER DEVICE, MOUNT ABOVE SPD SURGE PROTECTIVE DEVICE WT WATER TIGHT
ACCESSIBLE CEILING. DEVICE SHALL BE UL 924 LISTED. SPRINKLER SYSTEM BELL ALARM APPLIANCE, XFMR TRANSFORMER
ETD PA XR EXISTING TO REMAIN
GENERAL DEMOLITION NOTES REFER TO LIGHTING CONTROL DETAILS FOR
ADDITIONAL INFORMATION
SURFACE RACEWAY. MOUNT 46" AFF, UON B WEATHERPROOF ER
PAGING SYSTEM EQUIPMENT RACK
XRN EXISTING TO BE REPLACED WITH NEW
GENERAL REPAIR DAMAGE EMERGENCY POWER OFF BUTTON ARP AREA OF RESCUE MASTER PANEL
DEMOLITION DRAWINGS ARE BASED ON EXISTING PLANS AND FIELD INVESTIGATION EXERCISE CARE IN REMOVAL OF DEMOLITION ITEMS. REPAIR, AT NO LS
DIMMING PANEL, RECESS MOUNTED IN WALL. REFER LOCAL SOUND SYSTEM EQUIPMENT RACK
PRIOR TO DEMOLITION. VISIT THE EXISTING BUILDING PRIOR TO BID IN ORDER TO
BECOME FAMILIAR WITH THE EXISTING CONDITIONS AND IN ORDER TO AVOID
ADDITIONAL COST TO OWNER, AND DAMAGE CAUSE TO EXISTING
CONSTRUCTION AND/OR EQUIPMENT TO REMAIN.
DP TO LIGHTING CONTROL DETAILS FOR ADDITIONAL
INFORMATION
DISCONNECT SWITCH. FRAME AND FUSE AS NOTED ARS AREA OF RESCUE REMOTE CALL STATION
ER
TELE/DATA

-
AV
CONFLICTS. FUSED DISCONNECT SWITCH. FRAME AND FUSE AS AUDIO/VISUAL SYSTEM EQUIPMENT RACK

© COPYRIGHT
ASSOCIATED APPURTENANCES ER
NOTED. BD PROJECTED BEAM SMOKE DETECTOR TRANSMITTER WALL MOUNTED TELE/DATA OUTLET, 4"X4"X2 1/4"
DEMOLITION (DASHED) ITEMS REMOVE ALL ELECTRICAL APPURTENANCES (DISCONNECTS, STARTERS, BOX WITH SINGLE GANG PLASTER RING, WITH 1"C
ALL ITEMS SHOWN DASHED ON DEMOLITION PLANS, AND/OR TAGGED WITH 'DM', ARE WIRING, CONDUIT, ETC.) ASSOCIATED WITH EQUIPMENT TO BE REMOVED BY ENCLOSED CIRCUIT BREAKER. FRAME AND TRIP AS EPS EMERGENCY CALL SYSTEM POWER SUPPLY, 120V XD STUBBED ABOVE ACCESSIBLE CEILING AND
EXISTING, AND SHALL BE REMOVED COMPLETE INCLUDING: BOXES, CONDUIT, WIRE,
FASTENERS, AND ASSOCIATED APPURTENANCES, UON.
OTHERS.
GENERAL NOTED BD PROJECTED BEAM SMOKE DETECTOR REFLECTOR
ECS EMERGENCY CALL SYSTEM CALL STATION
XV TERMINATED WITH INSULATED BUSHING. XD
INDICATES DATA CABLE COUNT.
KNOCKOUT PLUGS AND COVERS EXISTING PANELBOARD XV INDICATES VOICE CABLE COUNT ISSUE
EXISTING TO REMAIN (SOLID) ITEMS ALL CONDUIT REMOVED SHALL BE REMOVED IN ITS ENTIRETY, INCLUDING # NUMBERED NOTE EMERGENCY CALL SYSTEM MASTER STATION, 46"
ECM REV DATE DESCRIPTION
ALL ITEMS SHOWN SOLID ON DEMOLITION PLANS, AND/OR TAGGED WITH 'XR', ARE FITTINGS, MOUNTING DEVICES, MOUNTING HARDWARE, ETC. PROVIDE PANELBOARD AFF, UON. WALL MOUNTED VOICE OUTLET, 4"X4"X2 1/4" BOX
EXISTING TO REMAIN. CONDUIT PLUGS AND BLANKS FOR ALL OPENINGS CREATED BY THE DET # WITH SINGLE GANG PLASTER RING, WITH 3/4"C 04/30/25 BID SET
REMOVAL OF CONDUIT. PROVIDE BLANK COVER PLATES FOR ALL OPENED DETAIL OR SECTION NOTATION MOTOR STARTER B DOOR BELL PUSH BUTTON. PROVIDE SINGLE GANG STUBBED ABOVE ACCESSIBLE CEILING AND
SHEET XV
CIRCUITING TO REMAIN OUTLET BOXES CREATED BY THE REMOVAL OF THE EQUIPMENT AND/OR BOX WITH 3/4"C STUBBED TO ACCESSIBLE CEILING. TERMINATED WITH INSULATED BUSHING. XV
EXISTING CIRCUITING TO REMAIN SHALL BE REROUTED OR RECONNECTED, AS DEVICES. MOTOR STARTER AND DISCONNECT SWITCH PROVIDE WIRING PER MANUFACTURER'S INDICATES VOICE CABLE COUNT FROM OUTLET TO
REQUIRED, WHERE AFFECTED BY NEW WORK IN ORDER TO MAINTAIN CONTINUITY INDICATES CONTINUATION OF LINE RECOMMENDATION. PATCH PANEL
OF CIRCUIT. DEMOLISHED MATERIALS TRANSFORMER
ALL MATERIALS REMOVED UNDER DEMOLITION, NOT TO BE RELOCATED OR BC DOOR BELL CHIME. PROVIDE SINGLE GANG BOX WALL MOUNTED DATA OUTLET, 4"X4"X2 1/4" BOX
REUSE OF EXISTING CIRCUITRY DESIGNATED TO BE TURNED OVER TO THE OWNER, SHALL BECOME BRANCH CIRCUIT WIRING WITH 3/4"C STUBBED TO ACCESSIBLE CEILING. WITH SINGLE GANG PLASTER RING, WITH 3/4"C
EXISTING CIRCUITRY SERVING LIGHTING FIXTURES AND/OR RECEPTACLES FOR A PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED COMPLETELY PROVIDE WIRING PER MANUFACTURER'S XD STUBBED ABOVE ACCESSIBLE CEILING AND
GIVEN AREA SHALL BE REUSED WHERE CONVENIENT TO SERVE THE NEW LAYOUT. FROM THE SITE. RECOMMENDATION. TERMINATED WITH INSULATED BUSHING. XD
NE NORMAL EMERGENCY CIRCUIT WIRING
PROVIDE CIRCUIT MODIFICATIONS INDICATED OR AS OTHERWISE REQUIRED TO INDICATES DATA CABLE COUNT FROM OUTLET TO
MAINTAIN THE CONTINUITY OF THE EXISTING CIRCUIT THAT REMAIN. SCHEDULE OUTAGES C 12" DIAMETER WALL MOUNTED CLOCK. PATCH PANEL
ALL WORK AND ALL POWER OUTAGES IN THE EXISTING BUILDING SHALL BE
EXTENSION OF EXISTING CIRCUITS SCHEDULED AT TIMES CONVENIENT TO THE OWNER. UPS UNINTURRUPTIBLE POWER SUPPLY CIRCUIT WIRING DATA OUTLET FOR WIRELESS ACCESS POINT,
WHERE AN EXISTING CIRCUIT IS NOTED TO BE SAVED AND REUTILIZED, EXTEND WAP PROVIDE 4"X4"X2 1/4"D BOX SECURED IN CEILING
EXISTING CIRCUIT SAVED DURING DEMOLITION AS REQUIRED TO SERVE EQUIPMENT NOTIFICATION OR WALL FOR CONNECTION OF WAP WITH 1"C
IN NEW LOCATION. NOTIFY THE OWNER PRIOR TO TURNING OFF ANY CIRCUITS. HOMERUN BACK TO PANELBOARD STUBBED ABOVE ACCESSIBLE CEILING AND
TERMINATED WITH INSULATED BUSHING PROJECT NO.: 24-0828.02
EXISTING CONDUIT EXISTING CIRCUITS DATE: 04/30/25
ALL EXISTING CONDUITS AND WIRING THAT WILL NOT BE REUSED SHALL BE IF DURING THE COURSE OF CONSTRUCTION, IT ITS DETERMINED BY THE INDICATES MOUNT DEVICES ABOVE COUNTER TOP XD
TELE/DATA POKE-THRU. XD INDICATES DATA
REMOVED WHERE THEY WILL BE EXPOSED UPON COMPLETION OF NEW WORK. CONTRACTOR THAT AN EXISTING CIRCUIT BECOMES SPARE, THE
XV
CABLE COUNT. XV INDICATES VOICE CABLE COUNT
ELECTRICAL
EXISTING CONDUIT TO REMAIN CONCEALED IN WALLS SHALL BE ABANDONED. CONTRACTOR SHALL UPDATE THE PANELBOARD DIRECTORY TO INDICATE COVER
EXISTING CONDUIT TO REMAIN BELOW FLOOR SLAB SHALL BE CUT OFF ONE INCH SUCH, EVEN IF IT IS NOT EXPLICITLY MARKED ON THE ELECTRICAL PLANS. TD TELEPHONE/DATA SYSTEM DISTRIBUTION SHEET
BELOW ROUGH FLOOR AND GROUTED FLUSH. ALL EXISTING WIRING IN CONDUITS TO ER EQUIPMENT RACK
BE ABANDONED SHALL BE DISCONNECTED FROM POWER SOURCE AND REMOVED.

E0.1
GENERAL NOTES
1. REMOVE ALL LIGHTING FIXTURES AND CONTROLS
WIRING BACK TO SOURCE.

2. RETAIN ALL BRANCH CIRCUITS FOR XRN


MECHANICAL EQUIPMENT FOR REUSE UNDER NEW
WORK.
ARCHITECTS
49 SOUTH CARROLL STREET
FREDERICK, MARYLAND 21701
PHONE (301) 662-8532
FAX (301) 662-4192
PROFFITTANDASSOCIATES.COM

ENGINEERING

MATCHLINE
MATCHLINE
5285 Westview Drive
Suite 203
Frederick, MD 21703
P 301.695.9424
XRN XRN XRN XRN CJL Project # 24-0304
GW GW GW GW
HP-1 M HP-1 M HP-1 M HP-1 M

PANEL A PANEL C PANEL E PANEL G

Professional Certification. I hereby


certify that these documents were
prepared or approved by me, and
that I am a duly licensed
professional engineer under the
DM DM laws of the State of Maryland.
License No:45511
DM DM DM DM DM DM DM DM DM DM DM DM Expiration Date: 06/03/2026
OC
DM

DM DM DM DM DM DM DM DM DM DM DM DM

DM
DM

EF-1
M
XRN

DM DM DM DM DM DM DM DM DM DM DM DM DM

DM
DM G

HILLCREST ELEMENTARY SCHOOL


OC OC OC OC
DM DM DM DM DM
CR
F F

FREDERICK COUNTY PUBLIC SCHOOLS


DM

NEW MODULAR CLASSROOMS FOR:


DM DM DM DM DM DM DM DM DM DM DM DM DM DM

DM
DM
DM

DM DM DM
EWC EWC
OC OC OC

J
G G G G

FREDERICK, MARYLAND 21703


DM

DM

OC

1285 HILLCREST DRIVE


PROFFITT & ASSOCIATES ARCHITECTS
DM DM
G G G G

DM DM DM DM DM DM DM DM DM DM DM DM

EF-2

-
M XRN

© COPYRIGHT
OC G
DM

DM

DM DM DM DM DM DM DM DM DM DM DM DM

ISSUE
DM
OC DM DM REV DATE DESCRIPTION

04/30/25 BID SET

EF-1
M
XRN

G
DM DM DM DM DM DM DM DM DM DM DM DM

DM DM
G
PANEL B PANEL D PANEL F

GW
M HP-1 GW
M HP-1 GW
M HP-1
XRN XRN XRN PROJECT NO.: 24-0828.02

MATCHLINE
MATCHLINE
DATE: 04/30/25

DEMOLITION
FLOOR PLAN
- ELECTRICAL

DEMOLITION FLOOR PLAN - ELECTRICAL


E1.1
1
E1.1 1/4" = 1'-0"
MATCHLINE
MATCHLINE
XRN

HP-1 M
GW
HP-1 M
GW
HP-1 M
GW
GENERAL NOTES
1. REMOVE ALL LIGHTING FIXTURES AND CONTROLS
WIRING BACK TO SOURCE.

PANEL I PANEL K PANEL M 2. RETAIN ALL BRANCH CIRCUITS FOR XRN


MECHANICAL EQUIPMENT FOR REUSE UNDER NEW
WORK.
ARCHITECTS
49 SOUTH CARROLL STREET
FREDERICK, MARYLAND 21701
PHONE (301) 662-8532
DM DM DM DM DM DM DM DM DM DM DM DM FAX (301) 662-4192
PROFFITTANDASSOCIATES.COM

ENGINEERING
5285 Westview Drive
Suite 203
Frederick, MD 21703
P 301.695.9424
CJL Project # 24-0304

DM DM DM DM DM DM DM DM DM DM DM DM

Professional Certification. I hereby


certify that these documents were
prepared or approved by me, and
that I am a duly licensed
professional engineer under the
laws of the State of Maryland.
License No:45511
DM DM DM DM DM DM DM DM DM DM DM DM
Expiration Date: 06/03/2026

OC OC OC
DM DM DM

F F DM

DM DM

DM DM DM DM DM DM DM DM DM DM DM DM

DM DM
DM
DM DM DM CR
OC OC OC
DM

HILLCREST ELEMENTARY SCHOOL


FREDERICK COUNTY PUBLIC SCHOOLS
DM DM DM DM DM DM DM DM DM DM DM DM

NEW MODULAR CLASSROOMS FOR:


DM DM DM DM DM DM DM DM DM DM DM DM

FREDERICK, MARYLAND 21703


1285 HILLCREST DRIVE
PROFFITT & ASSOCIATES ARCHITECTS
DM DM DM DM DM DM DM DM DM DM DM DM

PANEL H PANEL J PANEL L

-
© COPYRIGHT
GW
M HP-1 GW
M HP-1 GW
M HP-1
XRN XRN XRN
MATCHLINE
MATCHLINE

ISSUE
REV DATE DESCRIPTION

04/30/25 BID SET

PROJECT NO.: 24-0828.02


DATE: 04/30/25

DEMOLITION
FLOOR PLAN
- ELECTRICAL

DEMOLITION FLOOR PLAN - ELECTRICAL


E1.2
1
E1.2 1/4" = 1'-0"
GENERAL NOTES
1. FOR ALL EMERGENCY FIXTURES, PROVIDE
UNSWITCHED HOT FROM THE ASSOCIATED
LIGHTING CIRCUIT TO THE FIXTURE BATTERY PACK
AND SENSING CIRCUIT.

2. CONNECT ALL CORRIDOR AND GANG BATHROOM


LIGHTING TO BUILDING TIME CLOCK SYSTEM TO BE
ON DURING OCCUPIED HOURS AND CONTROLLED ARCHITECTS
BY AUTO ON/ AUTO OFF OCCUPANCY SENSOR
DURING UNOCCUPIED HOURS. 49 SOUTH CARROLL STREET
FREDERICK, MARYLAND 21701
PHONE (301) 662-8532
FAX (301) 662-4192

MATCHLINE
MATCHLINE
PROFFITTANDASSOCIATES.COM

NUMBERED NOTES ENGINEERING


5285 Westview Drive
1 MAKE ALL FINAL CONNECTIONS TO DUAL Suite 203
Frederick, MD 21703
LIGHT/EXHAUST FAN COMBINATION UNIT. P 301.695.9424
CJL Project # 24-0304

PANEL A PANEL C PANEL E PANEL G

DS DS DS Professional Certification. I hereby


b b b
certify that these documents were
TS1 TS1 TR1 TR1 TR1 TR1 TR1 TR1 TR1 TR1 TR1 prepared or approved by me, and
b b b b b b b b b that I am a duly licensed
professional engineer under the
OC laws of the State of Maryland.
License No:45511
Expiration Date: 06/03/2026

OC OC OC
a,b a,b a,b
TR1 TR1 TR1 TR1 TR1 TR1 TR1 TR1 TR1
a a a a a a a a a
TS2
C-2 E-2 G-2
TS1
LZC LZC LZC
OC

X2
TR1 TR1 TR1 TR1 TR1 TR1 TR1 TR1 TR1
a a a a a a a a a
TS2

TS1
LZC

D D D
a,b a,b a,b

HILLCREST ELEMENTARY SCHOOL


OC

OC OC
X1
A-6 TR2 TR2 TR2 TR2 TR2 TR2 TR2 TR2
LZC

FREDERICK COUNTY PUBLIC SCHOOLS


X2 X2

NEW MODULAR CLASSROOMS FOR:


a,b
D a,b
D a,b
D

a a a a a a a a a
TR1 TR1 TR1 TR1 TR1 TR1 TR1 TR1 TR1
A-4

FREDERICK, MARYLAND 21703


TS2 OC

TS1

1285 HILLCREST DRIVE


PROFFITT & ASSOCIATES ARCHITECTS
LZC LZC LZC
B-2 D-2 F-2

a a a a a a a a a
TR1 TR1 TR1 TR1 TR1 TR1 TR1 TR1 TR1
1
J a,b OC a,b OC a,b OC
TS2 OC

-
© COPYRIGHT
X2

ISSUE
LZC b b b b b b b b b
TR1 TR1 TR1 TR1 TR1 TR1 TR1 TR1 TR1 REV DATE DESCRIPTION

b b b 04/30/25 BID SET


DS DS DS
OC

TS1 TS1 PANEL B PANEL D PANEL F

MATCHLINE
MATCHLINE
PROJECT NO.: 24-0828.02
DATE: 04/30/25

PART
FLOOR PLAN
- LIGHTING

PART FLOOR PLAN - LIGHTING


E2.1
1
E2.1 1/4" = 1'-0"
MATCHLINE
MATCHLINE
GENERAL NOTES
1. FOR ALL EMERGENCY FIXTURES, PROVIDE
UNSWITCHED HOT FROM THE ASSOCIATED
LIGHTING CIRCUIT TO THE FIXTURE BATTERY PACK
AND SENSING CIRCUIT.
PANEL I PANEL K PANEL M
2. CONNECT ALL CORRIDOR LIGHTING TO BUILDING
TIME CLOCK SYSTEM TO BE ON DURING OCCUPIED
HOURS AND CONTROLLED BY AUTO ON/ AUTO OFF ARCHITECTS
OCCUPANCY SENSOR DURING UNOCCUPIED
HOURS. 49 SOUTH CARROLL STREET
DS DS DS FREDERICK, MARYLAND 21701
b b b
PHONE (301) 662-8532
TR1 TR1 TR1 TR1 TR1 TR1 TR1 TR1 TR1
b b b b b b b b b FAX (301) 662-4192
PROFFITTANDASSOCIATES.COM

ENGINEERING
5285 Westview Drive
Suite 203
Frederick, MD 21703
P 301.695.9424
CJL Project # 24-0304

OC OC OC
a,b a,b a,b
TR1 TR1 TR1 TR1 TR1 TR1 TR1 TR1 TR1
a a a a a a a a a

I-2 K-2 M-2


LZC LZC LZC Professional Certification. I hereby
certify that these documents were
prepared or approved by me, and
that I am a duly licensed
professional engineer under the
laws of the State of Maryland.
License No:45511
Expiration Date: 06/03/2026

TR1 TR1 TR1 TR1 TR1 TR1 TR1 TR1 TR1


a a a a a a a a a

D D D
a,b a,b a,b

X1
OC
CO CO OC
X1 WM1
TR2 TR2 TR2 TR2 TR2 TR2 TR2 TR2 TR2

X2

a,b
D a,b
D a,b
D

M-4
LZC OC

HILLCREST ELEMENTARY SCHOOL


a a a a a a a a a
TR1 TR1 TR1 TR1 TR1 TR1 TR1 TR1 TR1

TR2 TR2

FREDERICK COUNTY PUBLIC SCHOOLS


LZC LZC LZC
H-2 J-2 L-2

NEW MODULAR CLASSROOMS FOR:


a a a a a a a a a
TR1 TR1 TR1 TR1 TR1 TR1 TR1 TR1 TR1
a,b OC a,b OC a,b OC

FREDERICK, MARYLAND 21703


1285 HILLCREST DRIVE
b b b b b b b b b
TR1 TR1 TR1 TR1 TR1 TR1 TR1 TR1 TR1 TR2 TR2

PROFFITT & ASSOCIATES ARCHITECTS


b b b OC
DS DS DS

PANEL H PANEL J PANEL L

-
© COPYRIGHT
MATCHLINE
MATCHLINE

ISSUE
REV DATE DESCRIPTION
TR2 TR2
04/30/25 BID SET

WM1 X1 X1 WM1
OC

PROJECT NO.: 24-0828.02


DATE: 04/30/25
TR2 TR2 PART
FLOOR PLAN
- LIGHTING

PART FLOOR PLAN - LIGHTING


E2.2
1
E2.2 1/4" = 1'-0"
GENERAL NOTES
1. ALL HP-1 UNITS TO BE REPLACED IN KIND AND
RECONNECTED TO MATCH EXISTING.

ARCHITECTS
49 SOUTH CARROLL STREET
FREDERICK, MARYLAND 21701
PHONE (301) 662-8532
FAX (301) 662-4192
NUMBERED NOTES

MATCHLINE
MATCHLINE
PROFFITTANDASSOCIATES.COM

XRN XRN XRN XRN


1 REFER TO DETAIL FOR FCPS DISPLAY BOARD ENGINEERING
GW GW GW GW INSTALLATION. COORDINATE FINAL INSTALLATION
HP-1 M HP-1 M HP-1 M HP-1 M AND REQUIREMENTS WITH OWNER.
5285 Westview Drive
Suite 203
Frederick, MD 21703
P 301.695.9424
2 MAKE ALL FINAL CONNECTIONS TO CEILING CJL Project # 24-0304

MOUNTED EXHAUST FAN REPLACED IN KIND.


RECONNECT TO BRANCH CIRCUIT RETAINED FROM
PANEL A PANEL C PANEL E PANEL G REMOVAL WORK. FAN TO BE PROVIDED WITH
INTEGRAL DISCONNECT SWITCH. EXHAUST FAN TO
BE CONTROLLED BY BAS.

3 MAKE ALL FINAL CONNECTIONS TO CEILING


MOUNTED LIGHT/EXHAUST FAN UNIT. CIRCUIT AND
CONTROLS SHOWN ON LIGHTING DRAWING. Professional Certification. I hereby
certify that these documents were
prepared or approved by me, and
that I am a duly licensed
professional engineer under the
C-8 E-8 G-8 laws of the State of Maryland.
License No:45511
Expiration Date: 06/03/2026
1 1 1
+72" +72" +72"
+72" +72" +72"

F F F
2 EF-1
M
XRN

PS PS PS

WAP WAP WAP

CR
F F

HILLCREST ELEMENTARY SCHOOL


WAP PS PS PS PS PS

FREDERICK COUNTY PUBLIC SCHOOLS


NEW MODULAR CLASSROOMS FOR:
EWC EWC

J J
G G G G

A-5 WH-1
A-11,13 HWCP-1

FREDERICK, MARYLAND 21703


WAP WAP WAP

1285 HILLCREST DRIVE


G G G G

PS PS PS

PROFFITT & ASSOCIATES ARCHITECTS


F
F F

3 EF-2
M
XRN G

-
B-8 D-8 F-8

© COPYRIGHT
1 1 1
+72" +72" +72"
+72" +72" +72"
ISSUE
REV DATE DESCRIPTION

2 EF-1 04/30/25 BID SET


M
XRN

PANEL B PANEL D PANEL F

GW
M HP-1 GW
M HP-1 GW
M HP-1
XRN XRN XRN

MATCHLINE
MATCHLINE
PROJECT NO.: 24-0828.02
DATE: 04/30/25

PART
FLOOR PLAN
- POWER & DATA

PART FLOOR PLAN - POWER & DATA


E3.1
1
E3.1 1/4" = 1'-0"
MATCHLINE
MATCHLINE
HP-1 M
XRN
GW
HP-1 M
XRN
GW
HP-1 M
XRN
GW GENERAL NOTES
1. ALL HP-1 UNITS TO BE REPLACED IN KIND AND
RECONNECTED TO MATCH EXISTING.

PANEL I PANEL K PANEL M

ARCHITECTS
49 SOUTH CARROLL STREET
FREDERICK, MARYLAND 21701
PHONE (301) 662-8532
FAX (301) 662-4192
NUMBERED NOTES PROFFITTANDASSOCIATES.COM
I-8 K-8 M-12
1 REFER TO DETAIL FOR FCPS DISPLAY BOARD ENGINEERING
INSTALLATION. COORDINATE FINAL INSTALLATION
1 1 1 5285 Westview Drive
+72" +72" +72" AND REQUIREMENTS WITH OWNER. Suite 203
Frederick, MD 21703
+72" +72" +72" 2
P 301.695.9424
PROVIDE 30A, 208V, 1PH, NEMA 3R NON-FUSED CJL Project # 24-0304

DISCONNECT. MAKE ALL FINAL CONNECTIONS TO


INDOOR UNITS PER MANUFACTURER'S
RECOMMENDATIONS.

F F F Professional Certification. I hereby


certify that these documents were
prepared or approved by me, and
that I am a duly licensed
PS PS PS professional engineer under the
laws of the State of Maryland.
License No:45511
Expiration Date: 06/03/2026

WAP WAP WAP

CR
F F TR

M-10

PS PS PS PS

F F

HILLCREST ELEMENTARY SCHOOL


PS

WAP WAP WAP

AHU-1

PS PS PS

FREDERICK COUNTY PUBLIC SCHOOLS


F F F

NEW MODULAR CLASSROOMS FOR:


M-5,7
WR

H-8 J-8 L-8 2

FREDERICK, MARYLAND 21703


1 1 1 HP-1
+72" +72" +72"
+72" +72" +72"

1285 HILLCREST DRIVE


PROFFITT & ASSOCIATES ARCHITECTS
PS

PANEL H PANEL J PANEL L

-
© COPYRIGHT
GW
M HP-1 GW
M HP-1 GW
M HP-1
XRN XRN XRN
MATCHLINE
MATCHLINE

AHU-2
ISSUE
REV DATE DESCRIPTION

04/30/25 BID SET

CR

PROJECT NO.: 24-0828.02


DATE: 04/30/25
CR PS F F
PART
FLOOR PLAN
TR - POWER & DATA

PART FLOOR PLAN - POWER & DATA


E3.2
1
E3.2 1/4" = 1'-0" S
ARCHITECTS
49 SOUTH CARROLL STREET
FREDERICK, MARYLAND 21701
PHONE (301) 662-8532
FAX (301) 662-4192
PROFFITTANDASSOCIATES.COM

ENGINEERING
5285 Westview Drive
Suite 203
Frederick, MD 21703
P 301.695.9424
CJL Project # 24-0304

Professional Certification. I hereby


certify that these documents were
prepared or approved by me, and
that I am a duly licensed
professional engineer under the
laws of the State of Maryland.
License No:45511
Expiration Date: 06/03/2026

HILLCREST ELEMENTARY SCHOOL


JUNCTION BOX

CEILING SYSTEM HANGER LIGHTING


WIRES (TYP.) NEW RACEWAY RED VIO
LOAD
(a) GRY
1/2" FLEXIBLE STEEL CONDUIT

FREDERICK COUNTY PUBLIC SCHOOLS


2 #12 THHN WIRE WITH 1 #12
LIGHTING
GREEN GRD. WIRE MAX. 6'-0" YEL LOAD VIO
LONG (b) GRY

NEW MODULAR CLASSROOMS FOR:


NO. 12 GAUGE WIRE HANGER TO CEILING SUSPENSION WATTSTOPPER LMRC-212 (a,b)
BUILDING FRAMING OR STRUCTURAL SYSTEM (TYP.) LIGHTING
LMRC-111
MEMBERS. (4 PER FIXTURE) LOAD DOUBLE RELAY
Dimming Room NEUTRAL WHT
(a) ON/OFF/0-10V DIMMING
Controller ROOM CONTROLLER
UNSWITCHED
NEUTRAL HOT BLK
FIXTURE FASTENED TO CEILING 120/277

FREDERICK, MARYLAND 21703


RED GRN
SUSPENSION SYSTEM
HOT
LAY-IN LIGHT FIXTURE

EARTH

1285 HILLCREST DRIVE


VIO/GRY GROUND

1 LAY-IN LIGHT FIXTURE MOUNTING

PROFFITT & ASSOCIATES ARCHITECTS


E6.1 NO SCALE LMRJ SERIES PRE-TERMINATED

VIO

VIO
CABLE or CAT5e. FREE TOPOLOGY &

GRY

GRY
SPLITTER ACCEPTABLE

Cat 5e/6
C B A,C A
CLASS 2-10 VOLT
F F F F CONTROL WIRING
D D D QUANTITY AS INDICATED ON LIGHTING PLANS
DLM CEILING SENSOR QUANTITY AS INDICATED ON LIGHTING PLANS

-
DLM CEILING SENSOR

© COPYRIGHT
TS FS LMRJ-C8
A,D COUPLER QUANTITY AS INDICATED ON LIGHTING PLANS
A DIGITAL DIMMING
FAA WALL SWITCHES
WATT STOPPER LMDM-101 (a,b) OCCUPANCY SENSOR SWITCH
F F H S AMM AMM
DW-100
ISSUE
SYSTEM BRIDGE
WATT STOPPER LMDC-100
REV DATE DESCRIPTION

FACP
WIRE LEGEND WATT STOPPER LMDC-100 (a,b) 04/30/25 BID SET

A = WPW 60991B AS INDICATED ON LIGHTING PLANS BLACK RED LIGHTING


XR DLM PHOTO SENSOR LINE
B = WPW 60992B LOAD
C = WPW 60993B
GREEN WHITE
D = WPW 60975B RJ45
(TYPICAL)
WATT STOPPER LMLS-400 (b)

NOTES: NEUTRAL
TIME CLOCK
1. REFER TO FLOOR PLANS FOR THE QUANTITIES OF FIRE ALARM DEVICES THAT SHALL BE
CONNECTED TO THE FIRE ALARM SYSTEM. LIGHTING CONTROL WIRING DIAGRAM
2. PROVIDE BATTERY BACKUP FOR THE CONTROL PANEL.
LIGHTING CONTROL WIRING DIAGRAM NO SCALE:
LIGHTING CONTROL WIRING DIAGRAM
NO SCALE:
NO SCALE:
3. DUCT DETECTORS SHALL BE PROVIDED WITH REMOTE LIGHT AND TEST STATION.
LIGHTING CONTROL NOTES: LIGHTING CONTROL SEQUENCE OF OPERATION NOTES:
PROJECT NO.: 24-0828.02
1. QUANTITY OF DEVICES (OCCUPANCY SENSORS, SWITCHES, POWER PACKS) AS SHOWN ON FLOOR PLANS. DATE: 04/30/25
1. QUANTITY OF DEVICES (OCCUPANCY SENSORS, SWITCHES, POWER PACKS) AS SHOWN ON FLOOR PLANS. 2. LIGHT FIXTURES ARE DIMMABLE.
2 FIRE ALARM SYSTEM RISER 2. CONTROL DESCRIPTION:
• LIGHTS CONTROLLED BY TIME CLOCK DURING NORMAL OPERATING HOURS.
3. CONTROL DESCRIPTION: LIGHTING CONTROL NOTES:
E5.1 NO SCALE • LIGHTS MANUAL ON VIA LOCAL LOW VOLTAGE SWITCH. 1. QUANTITY OF DEVICES AS SHOWN ON FLOOR PLANS. ELECTRICAL
• LIGHTS AUTO ON/OFF VIA VACANCY SENSOR WITHIN THE SPACE AFTER NORMAL OPERATING • LIGHTS AUTO OFF VIA VACANCY SENSOR WITHIN THE SPACE (AUTO OFF WITHIN 20 MINUTES) DETAILS
2. CONTROL DESCRIPTION:
HOURS (AUTO OFF WITHIN 20 MINUTES) • LIGHTS MANUAL OFF OVERRRIDE AT LOCAL LOW VOLTAGE SWITCH.
• LIGHTS MANUAL ON/OFF VIA LOCAL SWITCH.
3. THIS DETAIL APPLIES TO ALL CORRIDORS, VESTIBULES, AND PUBLIC BATHROOMS. • LIGHT LEVEL RAISE/LOWER VIA LOCAL LOW VOLTAGE SWITCH.

E5.1
4. THIS DETAIL APPLIES TO CLASSROOMS WITH DAYLIGHT SENSING. • LIGHTS AUTO OFF AUTOMATICALLY WITHIN 20 MINUTES VIA WALL MOUNTED OCCUPANCY SENSOR.
3. THIS DETAIL APPLIES TO ROOMS WITH A SWITCH DESIGNATION S .OC
BRANCH CIRCUIT & FEEDER SCHEDULE - COPPER CONDUCTORS FEEDER TAG KEY
NUMBER OF WIRES
SERVICE OCP TYPE 2 TYPE 3 TYPE 4
RATING (AMPS) (1 PHASE- 3W) (3 PHASE - 3W) (3 PHASE - 4W) WIRE AMPS
20 2 #12, 1 #12 GND - 3/4"C 3 #12, 1 #12 GND - 3/4"C 4 #12, 1 #12 GND - 3/4"C
25 2 #10, 1 #10 GND - 3/4"C 3 #10, 1 #10 GND - 3/4"C 4 #10, 1 #10 GND - 3/4"C 4 0100
30 2 #10, 1 #10 GND - 3/4"C 3 #10, 1 #10 GND - 3/4"C 4 #10, 1 #10 GND - 3/4"C
35 2 #8, 1 #10 GND - 3/4"C 3 #8, 1 #10 GND - 3/4"C 4 #8, 1 #10 GND - 1"C
40 2 #8, 1 #10 GND - 3/4"C 3 #8, 1 #10 GND - 3/4"C 4 #8, 1 #10 GND - 1"C ARCHITECTS
45 2 #6, 1 #10 GND - 3/4"C 3 #6, 1 #10 GND - 1"C 4 #6, 1 #10 GND - 1"C
50 2 #6, 1 #10 GND - 3/4"C 3 #6, 1 #10 GND - 1"C 4 #6, 1 #10 GND - 1"C 49 SOUTH CARROLL STREET
60 2 #4, 1 #10 GND - 3/4"C 4 #4, 1 #10 GND - 1 1/4"C FREDERICK, MARYLAND 21701
3 #4, 1 #10 GND - 1"C
PHONE (301) 662-8532
70 2 #4, 1 #8 GND - 1"C 3 #4, 1 #8 GND - 1"C 4 #4, 1 #8 GND - 1 1/4"C
FAX (301) 662-4192
80 2 #3, 1 #8 GND - 1"C 3 #3, 1 #8 GND - 1 1/4"C 4 #3, 1 #8 GND - 1 1/4"C
PROFFITTANDASSOCIATES.COM
90 2 #2, 1 #8 GND - 1"C 3 #2, 1 #8 GND - 1 1/4"C 4 #2, 1 #8 GND - 1 1/2"C
100 2 #1, 1 #8 GND - 1 1/4"C 3 #1, 1 #8 GND - 1 1/4"C 4 #1, 1 #8 GND - 1 1/2"C
110 2 #1, 1 #6 GND - 1 1/4"C 3 #1, 1 #6 GND - 1 1/4"C 4 #1, 1 #6 GND - 1 1/2"C ENGINEERING
125 2 #1, 1 #6 GND - 1 1/4"C 3 #1, 1 #6 GND - 1 1/4"C 4 #1, 1 #6 GND - 1 1/2"C 5285 Westview Drive
Suite 203
150 2 #1/0, 1 #6 GND - 1 1/4"C 3 #1/0, 1 #6 GND - 1 1/2"C 4 #1/0, 1 #6 GND - 2"C Frederick, MD 21703
P 301.695.9424
175 2 #2/0, 1 #6 GND - 1 1/2"C 3 #2/0, 1 #6 GND - 2"C 4 #2/0, 1 #6 GND - 2"C CJL Project # 24-0304

200 2 #3/0, 1 #6 GND - 1 1/2"C 3 #3/0, 1 #6 GND - 2"C 4 #3/0, 1 #6 GND - 2"C
225 2 #4/0, 1 #4 GND - 2"C 3 #4/0, 1 #4 GND - 2"C 4 #4/0, 1 #4 GND - 2 1/2"C
250 2-250 KCMIL, 1 #4 GND - 2"C 3-250 KCMIL, 1 #4 GND - 2 1/2"C 4-250 KCMIL, 1 #4 GND - 2 1/2"C
300 2-350 KCMIL, 1 #4 GND - 2 1/2"C 3-350 KCMIL, 1 #4 GND - 3"C 4-350 KCMIL, 1 #4 GND - 3"C
350 2-500 KCMIL, 1 #3 GND - 3"C 3-500 KCMIL, 1 #3 GND - 3"C 4-500 KCMIL, 1 #3 GND - 3 1/2"C
400 2-600 KCMIL, 1 #3 GND - 3"C 3-600 KCMIL, 1 #3 GND - 3"C 3-600 KCMIL, 1 #3 GND - 4"C
450 2 SETS EACH: 2 #4/0, 1 #2 GND - 2"C 2 SETS EACH: 3 #4/0, 1 #2 GND - 2"C 2 SETS EACH: 4 #4/0, 1 #2 GND - 2 1/2"C
500 2 SETS EACH: 2-250 KCMIL, 1 #2 GND - 2"C 2 SETS EACH: 3-250 KCMIL, 1 #2 GND - 2 1/2"C 2 SETS EACH: 4-250 KCMIL, 1 #2 GND - 2 1/2"C Professional Certification. I hereby
600 2 SETS EACH: 2-350 KCMIL, 1 #1 GND - 3"C 2 SETS EACH: 3-350 KCMIL, 1 #1 GND - 3"C certify that these documents were
2 SETS EACH: 4-350 KCMIL, 1 #1 GND - 3 1/2"C
prepared or approved by me, and
700 2 SETS EACH: 2-500 KCMIL, 1 #1/0 GND - 3"C 2 SETS EACH: 3-500 KCMIL, 1 #1/0 GND - 3"C 2 SETS EACH: 4-500 KCMIL, 1 #1/0 GND - 3 1/2"C that I am a duly licensed
800 2 SETS EACH: 2-600 KCMIL, 1 #1/0 GND - 3"C 2 SETS EACH: 3-600 KCMIL, 1 #1/0 GND - 3 1/2"C 2 SETS EACH: 4-600 KCMIL, 1 #1/0 GND - 4"C professional engineer under the
1000 3 SETS EACH: 2-500 KCMIL, 1 #2/0 GND - 3"C 3 SETS EACH: 3-500 KCMIL, 1 #2/0 GND - 3"C 3 SETS EACH: 4-500 KCMIL, 1 #2/0 GND - 3 1/2"C laws of the State of Maryland.
1200 3 SETS EACH: 2-600 KCMIL, 1 #3/0 GND - 3"C 3 SETS EACH: 3-600 KCMIL, 1 #3/0 GND - 3 1/2"C 3 SETS EACH: 4-600 KCMIL, 1 #3/0 GND - 4"C License No:45511
Expiration Date: 06/03/2026
1600 4 SETS EACH: 2-600 KCMIL, 1 #4/0 GND - 3"C 4 SETS EACH: 3-600 KCMIL, 1 #4/0 GND - 3 1/2"C 4 SETS EACH: 4-600 KCMIL, 1 #4/0 GND - 4"C
2000 5 SETS EACH: 2-600 KCMIL, 1-250 KCMIL GND - 3"C 5 SETS EACH: 3-600 KCMIL, 1-250 KCMIL GND - 3 1/2"C 5 SETS EACH: 4-600 KCMIL, 1-250 KCMIL GND - 4"C
2500 6 SETS EACH: 2-600 KCMIL, 1-350 KCMIL GND - 3"C 6 SETS EACH: 3-600 KCMIL, 1-350 KCMIL GND - 3 1/2"C 6 SETS EACH: 4-600 KCMIL, 1-350 KCMIL GND - 4"C
3000 8 SETS EACH: 2-500 KCMIL, 1-500 KCMIL GND - 3"C 8 SETS EACH: 3-500 KCMIL, 1-500 KCMIL GND - 3"C 8 SETS EACH: 4-500 KCMIL, 1-500 KCMIL GND - 4"C
3500 9 SETS EACH: 2-600 KCMIL, 1 #3 GND - 3"C 9 SETS EACH: 3-600 KCMIL, 1 #3 GND - 3 1/2"C 9 SETS EACH: 4-600 KCMIL, 1 #3 GND - 4"C
4000 10 SETS EACH: 2-600 KCMIL, 1-500 KCMIL GND - 3"C 10 SETS EACH: 3-600 KCMIL, 1-500 KCMIL GND - 3 1/2"C 10 SETS EACH: 4-600 KCMIL, 1-500 KCMIL GND - 4"C

COORDINATE MOUNTING HEIGHT WITH


ARCHITECTURAL DRAWINGS

HILLCREST ELEMENTARY SCHOOL


HDMI CONNECTOR

USB CONNECTOR

3.5MM AUXILIARY JACK

FREDERICK COUNTY PUBLIC SCHOOLS


NEW MODULAR CLASSROOMS FOR:
CAT 6 DATA JACK TO NEAREST
MDF/IDF CLOSET

CAT6 DATA JACK WITH PATCH


DOUBLE GANG FACEPLATE CORD TO LOW DISPLAY DROP
DUPLEX OUTLET WITH SIX JACKS

FREDERICK, MARYLAND 21703


2" CONDUIT TO ACCESSIBLE
CEILING SPACE FOR
AV CABLING. PROVIDE AUDIO
AND VIDEO CABLING BETWEEN

1285 HILLCREST DRIVE


HIGH AND LOW OUTLETS
FOR REQUIRED JACKS
COORDINATE MOUNTING HEIGHT WITH

PROFFITT & ASSOCIATES ARCHITECTS


ARCHITECTURAL DRAWINGS

-
© COPYRIGHT
HDMI CONNECTOR
ISSUE
USB CONNECTOR REV DATE DESCRIPTION

04/30/25 BID SET


3.5MM AUXILIARY JACK

CAT 6 DATA JACK TO NEAREST


MDF/IDF CLOSET

DOUBLE GANG FACEPLATE


DUPLEX OUTLET SPARE SINGLE GANG WITH SIX JACKS
WITH 2" CONDUIT TO ACCESSIBLE CEILING
SPACE FOR FUTURE OUTLETS

1 CLASSROOM DISPLAY BOARD DETAIL


E7.1 NOT TO SCALE PROJECT NO.: 24-0828.02
DATE: 04/30/25

ELECTRICAL
SCHEDULES

E7.1
ELECTRICAL SPECIFICATIONS

ELECTRICAL GENERAL PROVISIONS TESTS SHALL INCLUDE: ALL CONDUIT FITTINGS SHALL BE GALVANIZED MALLEABLE IRON OR STEEL BOXES OVERCURRENT PROTECTIVE DEVICES
CONNECTORS AND COUPLINGS SHALL BE THREADED, SET SCREW OR
SUMMARY: FURNISH ALL LABOR, MATERIALS, SERVICES AND SKILLED PROPER OPERATION OF LIGHTS AND EQUIPMENT. COMPRESSION TYPE, CONCRETE TIGHT. CONDUIT BODIES SHALL BE OUTLET BOXES: SUMMARY: PROVIDE FUSES IN ACCORDANCE WITH THE CONTRACT
SUPERVISION NECESSARY FOR THE CONSTRUCTION, ERECTION, INSTALLATION, CONTINUITY OF CONDUIT SYSTEM. MALLEABLE IRON, THREADED FOR HEAVY WALL CONDUIT WITH CADMIUM DOCUMENTS.
CONNECTIONS, TESTING AND ADJUSTMENT OF ALL CIRCUITS AND ELECTRICAL INSULATION LEAKAGE AND IMPEDANCES. FINISH AND CADMIUM PLATED SHEET STEEL COVERS. PROVIDE NEOPRENE OUTLET BOXES SHALL BE PROVIDED FOR DEVICES, LIGHTING FIXTURES,
EQUIPMENT SPECIFIED HEREIN OR SHOWN ON THE DRAWINGS AND ITS GROUND SYSTEM RESISTANCE. COVER GASKETS FOR CONDUIT BODY COVERS EXPOSED TO THE WEATHER. MOTORS, EQUIPMENT CONNECTIONS, SYSTEMS EQUIPMENT CONNECTIONS, ALL FUSES SHALL BE LABELED AS UL CLASS 2 OR UL CLASS R, CURRENT
DELIVERY TO THE OWNER COMPLETE IN ALL RESPECTS AND READY FOR USE. ANY SUB-SYSTEM TESTS DESCRIBED IN OTHER SECTIONS OF THESE PROVIDE "EYS" CONDUIT SEALING FITTING AS REQUIRED BY CODE AND AS SPECIAL POWER OUTLETS, AND AS OTHERWISE REQUIRED FOR SPECIAL LIMITING AND RATED FOR UP TO 200,000 AMPERES.
ALL ELECTRICAL WORK SHALL BE NEW EXCEPT WHERE SPECIFICALLY NOTED SPECIFICATIONS. SHOWN ON DRAWINGS (CROUSE-HINDS). SYSTEMS.
OTHERWISE. MANUFACTURER: LITTLEFUSE, BUSSMAN OR GOULD-SHAMUT. ARCHITECTS
SUBMITTALS: OUTLET BOXES SHALL BE GALVANIZED PRESSED STEEL STANDARD 4 INCHES
MANUFACTURERS: REPUBLIC, PITTSBURGH, TRIANGLE, AFC OR ALLIED.
QUALITY: CONTRACTOR SHALL PROVIDE WORK OF HIGHEST QUALITY, SQUARE, MINIMUM 1-1/2-INCHES DEEP. PROVIDE SINGLE GANG PLASTER 49 SOUTH CARROLL STREET
CONFORMING TO THE ACCEPTED PRACTICES AND STANDARDS OF THE MATERIALS AND EQUIPMENT INSTALLED IN THIS WORK SHALL BE NEW AND RINGS. FREDERICK, MARYLAND 21701
MEET ALL THE REQUIREMENTS OF THE CONTRACT DOCUMENTS. NO INSTALLATION:
TRADES INVOLVED, FURTHER DEFINITION OF QUALITY IS GIVEN BY VARIOUS GROUNDING PHONE (301) 662-8532
LAWS, CODES, STANDARDS AND REGULATIONS. MATERIALS OR EQUIPMENT SHALL BE ORDERED UNTIL SUBMITTALS ARE MANUFACTURERS: RACO OR STEEL CITY.
REVIEWED AND APPROVED. MATERIALS AND EQUIPMENT SHALL MEET THE PROVIDE CONDUITS AND SURFACE MOUNTED RACEWAYS AS INDICATED ON FAX (301) 662-4192
THE DRAWINGS. SUMMARY: GROUNDING OF THE ELECTRICAL SYSTEM SHALL BE IN PROFFITTANDASSOCIATES.COM
DEMOLITION: MANUFACTURERS' ASSOCIATION (NEMA) AND THE AMERICAN NATIONAL PULL AND JUNCTION BOXES: ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE ARTICLE 250.
STANDARDS INSTITUTE (ANSI) STANDARDS/REQUIREMENTS. WHERE CONDUITS SHALL BE INSTALLED CONCEALED ABOVE CEILINGS OR IN WALLS
THE CONTRACTOR SHALL VISIT THE SITE TO DETERMINE THE EXACT STANDARDS HAVE BEEN ESTABLISHED, THE MATERIALS AND EQUIPMENT UNLESS INDICATED OTHERWISE ON THE DRAWINGS. PULL OR JUNCTION BOXES SHALL BE PROVIDED IN ALL RACEWAY SYSTEMS METAL ENCLOSURES OR RACEWAYS FOR CONDUCTORS OR EQUIPMENT ENGINEERING
CONDITION, LOCATIONS, SIZES AND QUANTITIES OF EXISTING ELECTRICAL SHALL BEAR THE UL LABEL AND SHALL BE LISTED FOR THE APPLICATION WHERE REQUIRED TO FACILITATE WIRE PULLING, TO ENCLOSE SPECIFIED SHALL BE GROUNDED.
CONDUITS SHALL RUN PARALLEL OR PERPENDICULAR TO BUILDING WALLS EQUIPMENT DEVICES AND APPURTENANCES, OR TO PROVIDE ACCESS TO
5285 Westview Drive
EQUIPMENT, WIRING, CONDUIT AND OTHER ACCESSORIES WHICH MUST BE USED. Suite 203
AND CEILINGS. INSTALL CONDUITS LEVEL AND SQUARE. THESE RACEWAY SYSTEMS. Frederick, MD 21703
REMOVED, REVISED, RELOCATED, DISCONNECTED, CONNECTED TO OR EXPOSED NON-CURRENT-CARRYING METAL PARTS OF FIXED EQUIPMENT P 301.695.9424
RECONNECTED. THE CONTRACTOR WILL BE HELD RESPONSIBLE FOR THE REQUIRED SUBMITTALS INCLUDE: CONDUITS SHALL BE INSTALLED TO AVOID CONFLICTS WITH MECHANICAL LIKELY TO BECOME ENERGIZED SHALL BE GROUNDED. CJL Project # 24-0304

REMOVAL OF ALL EXISTING ELECTRICAL SERVICE EQUIPMENT, PANELBOARDS, DUCTWORK AND PIPING. MANUFACTURERS: HOFFMAN, RACO, OR STEEL CITY
LIGHTING FIXTURES, SWITCHES, RECEPTACLES, BOXES, CONDUITS, WIRING, WIRING DEVICES AND PLATES BONDING SHALL BE PROVIDED AND CONFORM TO ALL REQUIREMENTS OF
ETC., THROUGHOUT THE BUILDING AND AT THE EXTERIOR OF THE BUILDING LIGHTING FIXTURES INSTALL CONDUITS 12-INCHES FROM STEAM AND HOT WATER PIPING. INSTALLATION: NEC ARTICLE 250-G.
NO LONGER REQUIRED AS PART OF THE NEWLY REMODELED BUILDING AND PANELBOARDS, DISCONNECTS
THE INSTALLATION OF NEW FIXTURES, SWITCHES, RECEPTACLES, MOTOR SUPPORT CONDUITS FROM BUILDING STRUCTURE AT A MAXIMUM INTERVALS PROVIDE SUPPORTS FOR ALL PULL, JUNCTION AND OUTLET BOXES. PROVIDE A SEPARATE GROUNDING CONDUCTOR FOR ALL FEEDERS AND
OUTLETS, PANELBOARDS, SWITCHBOARD, EQUIPMENT, CONDUIT, RACEWAYS, OF 8-FEET FOR EMT AND 3-FEET FOR MC. PROVIDE ADDITIONAL SUPPORT BRANCH CIRCUITS.
WIRING, BOXES, ETC., COMPLETE IN EVERY DETAIL, UNLESS NOTED OTHERWISE. THE DRAWINGS AND SPECIFICATIONS ARE BASED ON THE REQUIREMENTS FOR MC CABLE WITHIN 12-INCHES OF EACH TERMINATION. CONDUITS SHALL LABEL JUNCTION BOX COVERS AS INDICATED IN SPECIFICATION SECTION
AND LAYOUTS OF THE EQUIPMENT OF THE DESIGN BASE MANUFACTURER. NOT BE SUPPORTED FROM OR ATTACHED TO THE CEILING, HVAC DUCTWORK 16010.
ALL PRESENT EXPOSED CONDUIT, WIRING AND SIMILAR MISCELLANEOUS DESIGN COORDINATION OF EQUIPMENT WITH THE BUILDING AND WITH OTHER OR CEILING SUPPORT SYSTEM. LIGHTING FIXTURES, LAMPS AND BALLASTS Professional Certification. I hereby
ITEMS THROUGHOUT THE REMODELED AREAS OF THE BUILDING ARE NOT TRADES HAS BEEN MADE FOR THIS SPECIFIC MODEL AND MANUFACTURER INSTALL JUNCTION AND OUTLET BOXES SQUARE TO THE WALLS, FLOORS certify that these documents were
REQUIRED AS PART OF THE REMODELED INSTALLATION, SHALL BE OF EQUIPMENT. WHERE SEVERAL MANUFACTURERS ARE LISTED, THE AND CEILINGS. prepared or approved by me, and
INSTALL A SEPARATE GREEN GROUNDING CONDUCTOR FOR ALL CONDUITS SUMMARY: PROVIDE LED FIXTURES AS INDICATED ON THE DRAWINGS that I am a duly licensed
COMPLETELY REMOVED. ALL PRESENT CONCEALED CONDUIT EMBEDDED FIRST-NAMED IS THE DESIGN BASE MANUFACTURER, UNLESS SPECIFICALLY
AND RACEWAYS. professional engineer under the
IN WALLS OR LOCATED IN INACCESSIBLE SPACES AND NOT REQUIRED NOTED OTHERWISE. PROVIDE COVERS FOR ALL JUNCTION AND PULL BOXES.
laws of the State of Maryland.
AS A PART OF THE REMODELED INSTALLATION, SHALL BE SUITABLY INSTALL POWER CONDUITS WITH A MAXIMUM OF FOUR NINETY-DEGREE PROVIDE ALL REQUIRED INSTALLATION ACCESSORIES FOR THE FIXTURES
COORDINATION DRAWINGS, WHERE NECESSARY, PREPARE NEW LAYOUTS TO PANELBOARDS License No:45511
CAPPED OR PLUGGED BEHIND WALLS, ABOVE CEILINGS, OR BELOW FLOORS BENDS. INSTALL TELE/DATA CONDUITS WITH A MAXIMUM OF TWO AS REQUIRED FOR THE SPECIFIC LOCATION WHETHER OR NOT INCLUDED Expiration Date: 06/03/2026
AND RENDERED COMPLETELY "DEAD." WHEN EXISTING CEILINGS OR BE USED EITHER FOR SUBSTITUTED EQUIPMENT OF OTHER EQUIPMENT LISTED IN THE MANUFACTURER'S CATALOG NUMBER. SUCH ACCESSORIES
NINETY-DEGREE BENDS. SUMMARY: PROVIDE PANELBOARDS AS INDICATED ON THE DRAWINGS.
WALL CONSTRUCTION IS REMOVED, RESULTING EXISTING EXPOSED CONDUIT AS AN APPROVED EQUIVALENT AND WHICH MAY HAVE DIFFERENT INCLUDE PLASTER FRAMES, RINGS, FLANGES, CANOPIES, STEM HANGERS,
NO LONGER REQUIRED AS PART OF THE REMODELED INSTALLATION, SHALL DIMENSIONAL OR SERVICE REQUIREMENTS FROM THE DESIGN BASE PANELBOARDS SHALL CONTAIN COPPER BUSING, BOLT ON TYPE CIRCUIT
INSTALL CONDUITS ABOVE BOTTOM OF BUILDING TRUSSES, JOIST AND AND SUSPENSION STRAPS.
BE COMPLETELY DISCONNECTED AND REMOVED. MANUFACTURER. SUBMIT THESE FOR REVIEW. APPROVAL OF THE BREAKERS AND DOOR-IN-DOOR CONSTRUCTION. CONTRACTOR SHALL
ALTERNATE EQUIPMENT OR MATERIAL DOES NOT RELIEVE THE CONTRACTOR SIMILAR STRUCTURAL MEMBERS. SIZE AND INSTALL CIRCUIT BREAKERS IN ACCORDANCE TO THE PANEL
FIXTURES SHALL BE SECURELY MOUNTED TO ELEMENTS OF THE
EXISTING EXPOSED CONDUIT, RACEWAYS, ETC., NO LONGER REQUIRED OF THE RESPONSIBILITY FOR PROVIDING A WORKING SYSTEM THAT COMPLIES SCHEDULES AS SHOWN ON THE DRAWINGS. PANELBOARDS SHALL BE
BUILDING. PROVIDE MEANS OF SUPPORT AS REQUIRED IN NEC ARTICLE
SHALL NOT BE REUSED AS PART OF THE NEW SYSTEM AND SHALL WITH ALL APPLICABLE CODE REQUIREMENTS. PROVIDE INSULATED BUSHINGS AT ALL CONDUIT ENDS. RATED AS INDICATED ON PANEL SCHEDULES.
410-16 AND LOCAL CODE. PROVIDE SUPPORT FROM THE BUILDING
BE REMOVED FROM THE SITE. PRESENT CONCEALED WIRING SHALL BE MANUFACATURERS: EATON, SQUARE D, SIEMENS OR GENERAL ELECTRIC
STRUCTURE FROM AT LEAST TWO (OPPOSITE) CORNERS OF EACH
DISCONNECTED AND REMOVED WHEREVER POSSIBLE; HOWEVER, WHERE IT PERMITS, FEES, AND NOTICES: REFER TO SPECIFICATION SECTION PROVIDE 200-POUND TENSILE STRENGTH PULL ROPE FOR ALL EMPTY FIXTURE.
IS IMPRACTICABLE TO DO SO, THE WIRING SHALL BE RENDERED DIVISION-0 FOR REQUIREMENTS. CONDUITS. LEAVE 3-FEET SLACK AT EACH END.
COMPLETELY "DEAD." REMOVED WIRING, CONDUITS, AND BOXES SHALL INSTALL LAMPS IN ALL FIXTURES IN ACCORDANCE WITH THE FIXTURE
WIRING DEVICES
NOT BE REUSED AS A PART OF THE NEW INSTALLATION. ELECTRICAL IDENTIFICATION: ALL ELECTRICAL EQUIPMENT MUST BE TAGGED SCHEDULE ON THE DRAWINGS.
BY USING PHENOLIC PLASTIC NAMEPLATES OR OTHER PRE-APPROVED WIRE AND CABLE
SUMMARY: PROVIDE UL LISTED WIRING DEVICES AND COVER PLATES FOR
THE INSTALLATION OF EQUIPMENT SHALL BE METHOD. FASTEN BY STAINLESS STEEL SCREWS TO EQUIPMENT OR DEVICE.
SWITCHES, AND RECEPTACLES. ALL WIRING DEVICES SHALL BE BY THE
COORDINATED WITH WORK BEING PERFORMED UNDER THE OTHER CONTRACTS PANELBOARD CIRCUIT DIRECTORIES SHALL BE TYPE WRITTEN. LOAD SUMMARY: FURNISH AND INSTALL ALL ELECTRICAL AND ELECTRONIC FIXTURE MANUFACTURERS: AS SHOWN ON DRAWING.
SAME MANUFACTURER.
DESCRIPTIONS SHALL INCLUDED FINAL ROOM NUMBERS. PROVIDE ADHESIVE CONDUCTORS FOR BRANCH CIRCUIT WIRING AND SYSTEM WIRING.
ANY OPENINGS THAT ARE EXPOSED DUE TO THE REMOVAL OF THE
VINYL PRINTED LABELS INDICATING THE CIRCUIT NUMBER AND PANELBOARD SWITCHES SHALL BE GENERAL USE AC, QUIET TYPE, 20 AMPERE, 120 VOLT
EXISTING SERVICE SHALL BE PATCHED BY THE CONTRACTOR.
IDENTIFICATION FOR WIRING DEVICE WALL PLATES. LABEL THE JUNCTION BOX WIRE AND CABLE: BACK AND SIDE WIRED, SPECIFICATION GRADE. COLOR SHALL BE BY THE OCCUPANCY SENSORS
COVERS, (INTERIOR FOR NON EXPOSED INSTALLATIONS AND EXTERIOR FOR ARCHITECT.
EXISTING HEATING, VENTILATING, PLUMBING AND MISCELLANEOUS EXPOSED INSTALLATIONS) TO INDICATE PANEL AND CIRCUIT NUMBERS. ALL WIRE SHALL BE UL LISTED COPPER, 600 VOLT RATED, STRANDED FOR SUMMARY: PROVIDE ALL OCCUPANCY SENSORS, LOW VOLTAGE CONTROL WIRING,
EQUIPMENT WILL BE REMOVED UNDER THE HEATING, PLUMBING, AND WIRING SHALL BE COLOR CODED PER SPECIFICATION SECTION 16120. LIGHT NO. 8 AWG AND LARGER, SOLID OR STRANDED FOR NO. 10 AWG AND CONVENIENCE OUTLETS SHALL BE 20 AMPERE, 125 VOLT, 3-WIRE ROOM CONTROLLERS, AND SWITCHES AS INDICATED ON THE DRAWINGS AND DETAILS.
GENERAL CONTRACTS. THE ELECTRICAL CONTRACTOR SHALL FIXTURES ON EMERGENCY CIRCUITS SHALL BE IDENTIFIED WITH A RED DOT SMALLER. TYPE THHN/THWN. GROUNDING TYPE, SPECIFICATION GRADE. COLOR SHALL BE BY THE CONTRACTOR SHALL LOCATE AND INSTALL ALL COMPONENTS OF OCCUPANCY SENSOR
DISCONNECT THE EQUIPMENT FROM THEIR PRESENT ELECTRICAL SERVICES ON THE FRAME. THE MARKING SHALL BE VISIBLE WITHOUT REMOVING ARCHITECT. SYSTEM AS INDICATED ON THE DRAWINGS.
AND REMOVE ALL WIRING, CONDUIT, BOXES, SWITCHES, ETC., NO LONGER CEILING. MC CABLE SHALL BE UL-LISTED TYPE MC METAL CLAD CABLE PER NEMA
REQUIRED. NEW EQUIPMENT WILL BE FURNISHED AND INSTALLED UNDER WC-7, UL-83 AND UL-1569 WITH 90-DEGREE CELSIUS RATED MANUFACTURERS: CRESTNET, WATTSTOPPER, LEVITON, LUTRON.
OTHER CONTRACTS AND SHALL BE CONNECTED BY THE ELECTRICAL CONDUCTORS. PROVIDE INTERLOCKING ALUMINUM OR GALVANIZED STEEL COVER PLATES SHALL BE BY THE ARCHITECT.
WIRING INSTALLATION: NOT MORE THAN THREE 120 VOLT BRANCH CIRCUITS
CONTRACTOR TO THE NEW ELECTRICAL SYSTEM AS SHOWN AND AS MAY BE SERVED WITH A COMMON NEUTRAL BUS, IN NO INSTANCE MAY A STRIP ARMOR CABLE.
REQUIRED FOR A COMPLETE INSTALLATION. MANUFACTURERS: HUBBELL, PASS & SEYMOUR, COOPER OR LEVITON.
COMMON NEUTRAL BE USED WHEN TWO CIRCUITS ARE CONNECTED TO THE
SAME BUS OF THE PANELBOARD. BRANCH CIRCUIT CONDUCTORS MAY BE TYPE THHN WHEN INSTALLED IN INSTALLATION:
CONTRACT DRAWINGS: INTERIOR DRY LOCATIONS. TELE/DATA RACEWAYS AND ACCESSORIES

HILLCREST ELEMENTARY SCHOOL


START UP PROVISIONS FOR ELECTRICAL WORK: INSTALL DEVICES AND ASSEMBLIES PLUMB AND SECURE.
DRAWINGS ARE DIAGRAMMATIC AND SHOW APPROXIMATE LOCATIONS AND MINIMUM WIRE SIZE SHALL BE NO. 12 AWG FOR LIGHTING AND POWER THE CONTRACTOR SHALL PROVIDE RACEWAYS, CABLING AND ACCESSORIES FOR
EXTENT OF WORK. EXACT LOCATIONS MUST BE COORDINATED WITH OTHER CLEANING: UPON COMPLETION OF WORK, ALL MATERIAL AND EQUIPMENT BRANCH CIRCUITS, NO. 14 AWG FOR CONTROL AND AUXILIARY SYSTEMS. PROTECT DEVICES DURING PAINTING. INSTALL WALL PLATES AFTER THE TELE/DATA SYSTEMS IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.
TRADES AND VERIFIED IN THE FIELD. FURNISHED SHALL BE THOROUGHLY CLEANED OF DIRT, GREASE, RUST, AND PROVIDE #10 AWG MINIMUM FOR BRANCH CIRCUITS EXCEEDING 100-FEET IN PAINTING IS COMPLETE.
OIL. PREPARE FOR FINISH PAINTING, WHERE PAINTING IS SPECIFIED. LENGTH. E.M.T. SHALL BE UTILIZED FOR ALL TELE/DATA RACEWAY WITHIN BUILDING
CEILING GRID LAYOUTS, WHERE SHOWN ON THE DRAWINGS, ARE FOR FLUSH MOUNT ALL DEVICES EXCEPT AS NOTED OTHERWISE ON THE EXCEPT AS OTHERWISE NOTED. THE CONTRACTOR SHALL INSTALL RACEWAY RUNS
REFERENCE ONLY. THE EXACT LOCATIONS AND MOUNTING HEIGHTS OF ALL PERSONNEL INSTRUCTION: COLOR CODING SYSTEM ON FEEDERS AND BRANCH CIRCUITS SHALL BE IN DRAWINGS. LESS THAN 100 FEET FROM POINT TO POINT SO THAT THEY CONTAIN NO MORE
LIGHTING FIXTURES SHALL BE COORDINATED WITH ARCHITECTURAL ACCORDANCE WITH THE NEC. THAN 2-90 DEGREE STANDARD FACTORY BENDS OR 3-90 DEGREE 24 IN
REFLECTED CEILING PLANS, ARCHITECTURAL DETAILS, MECHANICAL AND RADIUS BENDS. PROVIDE PULL BOXES IN RACEWAY RUNS EXCEEDING 100 FEET

FREDERICK COUNTY PUBLIC SCHOOLS


AFTER ALL SYSTEM OPERATIONAL TESTS HAVE BEEN COMPLETED, PROVIDE MOUNT DEVICE BOXES WITH THE LONG DIMENSION VERTICAL. MOUNT
PLUMBING PLANS, PRIOR TO INSTALLATION OF FIXTURES. EIGHT HOURS OF INSTRUCTION TO THE DESIGNATED PERSONNEL IN THE PROVIDE CABLE / CONDUCTOR IDENTIFICATION BANDS ON WIRING AT RECEPTACLES WITH THE GROUNDING TERMINAL FACING UP. FROM POINT TO POINT WITH MORE THAN 1-90 DEGREE BEND. RACEWAY RUNS
OPERATION AND MAINTENANCE OF ALL SYSTEMS AND EQUIPMENT. USE PANELBOARDS, JUNCTION BOXES AND OUTLETS BOXES. THE IDENTIFICATION SHALL NOT CONTAIN SQUARE OR OVAL CONDUIT FITTINGS ("CONDULETS"). ENTER
CEILING TYPES SHALL BE AS NOTED ON THE ARCHITECTURAL REFLECTED BANDS SHALL INCLUDE CIRCUIT NUMBER AND PANEL BOARD DESIGNATIONS.

NEW MODULAR CLASSROOMS FOR:


MANUALS TO FAMILIARIZE THE OWNER WITH EQUIPMENT AND PROCEDURES. MOUNT DEVICES AT HEIGHT INDICATED ON THE DRAWINGS. COORDINATE FEEDER RACEWAYS TO TELE/DATA TERMINAL BOARDS TOP OR BOTTOM ON
CEILING PLANS AND ARCHITECTURAL DETAILS. COORDINATE ALL REQUIRED SCHEDULE TIME CONVENIENT FOR THE OWNER AND THE ARCHITECT. WORK WITH COUNTERTOP HEIGHTS PRIOR TO ROUGH IN OF BOXES. THE EXTREME RIGHT OR LEFT SIDE.
LIGHTING FIXTURE ACCESSORIES AND MOUNTING HARDWARE WITH THE MANUFACTURERS: GENERAL CABLE, CABLEC, TRIANGLE, OKONITE, ROME OR
CEILING TYPES AS SHOWN ON THE DRAWINGS PRIOR TO INSTALLATION OF THE INSTRUCTION IS TO INCLUDE THE FOLLOWING: AFC. PROVIDE OUTLET PULLBOXES AS INDICATED ON THE DRAWING AND AS REQUIRED
LIGHTING FIXTURES. THE CONTRACTOR SHALL PROVIDE ALL FIXTURE INSTALL COVERPLATES FOR ALL DEVICES AND BLANK OUTLET BOXES.
FOR THE COMPLETE INSTALLATION OF THE TELE/DATA SYSTEM. PULLBOXES
ACCESSORIES AND MOUNTING HARDWARE AS REQUIRED FOR A COMPLETE LOCATION OF ITEMS OF EQUIPMENT AND EXPLANATION OF THEIR USE. SPLICES AND CONNECTORS: SHALL BE PROVIDED WHERE 3-90 DEGREE BENDS ARE EXCEEDED WITH A
INSTALLATION OF THE FIXTURES. LABEL WIRING DEVICE WALL PLATES WITH ADHESIVE VINYL PRINTED LABEL
REFERENCE TO SERVICE MANUAL FOR RECORD AND CLARITY. SINGLE CONDUIT RUN.
NO. 8 AND SMALLER: SCOTCH LOCK CONNECTORS OR INDENTOR INDICATING THE CIRCUIT NUMBER AND PANELBOARD IDENTIFICATION.
COORDINATION OF WRITTEN AND VERBAL INSTRUCTIONS
ALL DEVICES SHALL BE FLUSH MOUNTED WITH CONCEALED CONDUIT, EXCEPT EXPLANATION OF CONTROL SYSTEM. CRIMP-TYPE CONNECTORS.
PROVIDE A GROUND CONNECTION TO ALL OUTLET BOXES.
AS NOTED ON THE DRAWINGS AND IN ELECTRICAL EQUIPMENT ROOMS. COMPLETE REVIEW OF ITEMS IN THE MANUALS.

FREDERICK, MARYLAND 21703


NO. 10 WIRE AND SMALLER IN AUXILIARY SYSTEMS: PREINSULATED CRIMP
MAINTENANCE PROCEDURES TO BE FOLLOWED. TESTING
RING LUGS. TIGHTEN ELECTRICAL CONNECTORS AND TERMINALS IN ACCORDANCE WITH
EXIT LIGHTS SHALL BE CENTERED IN CEILING TILE OR ABOVE DOOR IF WALL
MOUNTED. INSTALLATION: THE MANUFACTURER'S PUBLISHED TORQUE TIGHTENING VALUES AND UL486 THE OWNER RESERVES THE RIGHT TO INSPECT AND TEST ANY PORTION OF
UPON COMPLETION OF THE WORK, A CERTIFICATION OF INSPECTION AND
A & B. THE EQUIPMENT DURING THE CONSTRUCTION. THE ELECTRICAL CONTRACTOR
APPROVAL SHALL BE SECURED BEFORE FINAL PAYMENT OF CONTRACT WILL
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLETE AND OPERABLE BE ALLOWED. PROVIDE WIRING AND CABLES AS INDICATED ON THE DRAWINGS. SHALL TEST THE ENTIRE SYSTEM IN THE PRESENCE OF THE OWNER OR HIS

1285 HILLCREST DRIVE


TAMPER-RESISTANT CONVENIENCE RECEPTACLES: 125 V, 20 A; COMPLY WITH REPRESENTATIVE WHEN THE WORK IS COMPLETED TO INSURE ALL PORTIONS
SYSTEMS IN ACCORDANCE WITH THE INTENT OF THE CONTRACT DOCUMENTS.
RULES AND REGULATIONS: CABLES SHALL BE INSTALLED IN ACCORDANCE WITH SPECIFICATION NEMA WD 1, NEMA WD 6 CONFIGURATION 5-20R, UL 498, AND FS W-C-596. OF THE WORK ARE FREE FROM DEFECT. ALL EQUIPMENT NECESSARY TO

PROFFITT & ASSOCIATES ARCHITECTS


THE CONTRACTOR SHALL FURNISH AND INSTALL ALL INCIDENTAL ITEMS NOT SECTION-16110. DESCRIPTION: LABELED AND COMPLYING WITH NFPA 70, "HEALTH CARE CONDUCT THE ABOVE TESTS SHALL BE FURNISHED AT THE EXPENSE OF THE
ACTUALLY SHOWN OR SPECIFIED, BUT WHICH ARE REQUIRED BY GOOD RULES AND REGULATIONS SHALL BE COMPLIED WITH AS SET FORTH IN ALL FACILITIES" ARTICLE, "PEDIATRIC LOCATIONS" SECTION. ELECTRICAL CONTRACTOR. THE CONTRACTOR SHALL REPAIR ANY DEFECTS
PRACTICE TO PROVIDE COMPLETE FUNCTIONAL SYSTEMS. APPLICABLE, STATE REGULATIONS, ORDINANCES, AND STATUTES INCLUDING, MAKE ALL CONNECTIONS AND SPLICES NECESSARY TO PROPERLY COMPLETE NOTED AT NO EXTRA COST TO THE OWNER.
BUT NOT LIMITED TO, THE LATEST EDITIONS OF THE FOLLOWING THE ELECTRICAL WIRING. PROVIDE A MINIMUM NUMBER OF SPLICES. SPLICES MOTOR AND CIRCUIT DISCONNECTS
WARRANTY: CONTRACTOR SHALL GUARANTEE HIS WORKMANSHIP AND PUBLICATIONS, AND ALL SUPPLEMENTS THERETO THAT MAY BE IN EFFECT. SHALL BE MADE ONLY IN PULL, JUNCTION OR OUTLET BOXES.
MATERIALS FOR A PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE. SUMMARY: MOTORS, HVAC AND OTHER DRIVEN EQUIPMENT NOT WITHIN FIRE ALARM
BOCA NATIONAL FIRE PREVENTION CODE: CONNECTIONS AND SPLICES SHALL BE MADE WITH APPROVED CONNECTORS SIGHT OF THEIR FEEDER OVER CURRENT PROTECTION DEVICES SHALL
EXAMINATION OF SITE: CONTRACTOR SHALL VISIT THE SITE OF THE ONLY. HAVE NON-FUSIBLE TYPE DISCONNECT SWITCHES LOCATED AT MOTOR PROVIDE AN EXTENSION TO THE EXSITING FIRE ALARM SYSTEM. PROVIDE ALL
PROPOSED PROJECT. CERTAIN EXISTING CONDITIONS MAY AFFECT THE NFPA-70, NATIONAL ELECTRICAL CODE (NEC), 2020, HERE-IN-AFTER OR WHERE SHOWN ON THE DRAWINGS. MODULE, BATTERIES, PANELS, DEVICES, ETC. FOR A COMPLETE AND
TIGHTEN ELECTRICAL CONNECTORS AND TERMINALS IN ACCORDANCE WITH

-
MANNER OR SEQUENCE OF THE PERFORMANCE OF THE WORK. REFERRED TO AS THE "CODE". OPERATIONAL SYSTEM.
THE MANUFACTURER'S PUBLISHED TORQUE TIGHTENING RECOMMENDATIONS

© COPYRIGHT
OR PER UL 486A. SAFETY SWITCHES LOCATED OUTDOORS OR SUBJECT TO MOISTURE TO
RECORD DRAWINGS: CONTRACTOR SHALL MAINTAIN AT THE JOB SITE, ONE LIST OF ELECTRICAL FITTINGS, PUBLISHED BY THE UNDERWRITER'S THE FIRE ALARM SYSTEM SHALL MEET ALL LOCAL AND NATIONAL CODES
BE IN NEMA 3R ENCLOSURES.
COPY OF THE DRAWINGS WHICH SHALL BE USED EXCLUSIVELY FOR LABORATORIES, INC. (UL). INCLUDING BOCA, IBC, NFPA AND MARYLAND UNIFORM STATEWIDE
RECORDING ANY INSTALLATION DEVIATION FROM THE CONTRACT DRAWINGS. TEST ALL CONDUCTORS AND CABLES TO ENSURE NO SHORTS, OPENS OR BUILDING CODE.
ACCIDENTAL GROUNDS EXISTS. NON-FUSIBLE SAFETY SWITCHES TO BE HEAVY DUTY TYPE WITH
SUBMIT DRAWINGS TO ARCHITECT UPON COMPLETION 0F PROJECT. NFPA-72 SINGLE THROW BLADE CONSTRUCTION AND NO FUSE CLIPS.
PROVIDE CABLE/CONDUCTOR IDENTIFICATION BANDS WITH PANEL AND
ALL FIRE ALARM SYSTEM WIRING SHALL BE RUN IN RACEWAY. ISSUE
CUTTING AND PATCHING: CONTRACTOR SHALL PERFORM ALL CUTTING AND IECC 2021
CIRCUIT DESIGNATIONS AT PANELBOARDS AND DEVICE TERMINATIONS, MAIN SWITCH SHALL BE SERVICE ENTRANCE RATED. REV DATE DESCRIPTION
PATCHING REQUIRED. WORK MUST BE ACCOMPLISHED IN A NEAT AND THE MINIMUM FIRE ALARM SYSTEM WIRE SIZE SHALL BE #14 AWG FOR
WORKMANLIKE MANNER, ACCEPTABLE TO THE ARCHITECT. PATCH TO MATCH RACEWAYS AND FITTINGS ENCLOSURES AND ALL PULL, JUNCTION AND OUTLET BOX LOCATIONS. INDICATING CIRCUITS AND #16 AWG FOR INTIATING AND ANNUNCIATION
ALL SWITCHES SHALL BE BY SAME MANUFACTURER. 04/30/25 BID SET
ADJACENT SURFACE CONSTRUCTION. CIRCUITS. THE MINIMUM CONDUIT SIZE SHALL BE 3/4".
ARMORED CABLE - AC - HCF 90 HEALTH CARE HCF 90
CONDUIT AND FITTINGS: TYPE AC CABLE SHALL BE ARMORED, GALVANIZED STEEL, SHEATH CABLE MANUFACTURERS: GENERAL ELECTRIC, SQUARE D COMPANY, OR CUTLER
SLEEVES AND SEALS: FURNISH SLEEVES FOR CONDUIT PENETRATIONS WITH COPPER CONDUCTORS AND THHN 90º C INSULATION. FURNISH WITH NO WIRING OTHER THAN THAT DIRECTLY ASSOCIATED WITH THE FIRE ALARM
THROUGH MASONRY AND CONCRETE CONSTRUCTION. HAMMER.
ALL CONDUCTORS SHALL BE ENCLOSED IN A CONTINUOUS GROUNDED #16 AWG INTEGRAL BOND CONDUCTOR PLUS AN INSULATED GROUNDING SYSTEM AND ITS AUXILARY FUNCTIONS SHALL BE PERMITTED IN FIRE ALARM
RACEWAY SYSTEM. CONDUCTOR. CABLE SHALL BE INSTALLED IN INSTALLATIONS NOTED IN NEC INSTALLATION: RACEWAYS.
THE CONTRACTOR SHALL MAINTAIN THE FIRE RATINGS AS INDICATED ON THE
ARTICLES #517 AND #518.
ARCHITECTURAL DRAWINGS. REFER TO THE APPLICABLE DETAILS ON THE ALL CONDUITS SHALL BE ELECTRICAL METALLIC TUBING (EMT) WITH UL
FIRE PROTECTION AND LIFE SAFETY INFRASTRUCTURE IMPROVEMENTS INSTALL DEVICES AND ASSEMBLIES PLUMB AND SECURE.
LABEL, MINIMUM 3/4-INCH TRADE SIZE. MC CABLE MAY BE USED AS
PROJECT FOR REQUIREMENTS. ALLOWED BY CODE. MC NOT PERMITTED TO BE RUN EXPOSED. PROVIDE IDENTIFICATION PER SPECIFICATION SECTION 16010. LABEL
ELECTRICAL PROCEDURES AND CONTROLS: SHALL INDICATE EQUIPMENT SERVED, AND BRANCH CIRCUIT PANEL AND
FLEXIBLE CONDUIT WITH GREEN GROUNDING CONDUCTOR SHALL BE USED CIRCUIT DESIGNATIONS.
FOR CONNECTIONS TO EQUIPMENT SUBJECT TO VIBRATIONS/MOVEMENT AND
TESTS: THE CONTRACTOR SHALL BEAR ALL COSTS OF SUCH INSPECTIONS,
LIGHT FIXTURES. MAXIMUM LENGTH SHALL BE SIX FEET. SUPPORT ENCLOSURE INDEPENDENT OF THE CONNECTION CONDUIT OR
TESTS OR APPROVALS, AS REQUIRED BY THE AUTHORITY HAVING
JURISDICTION. RACEWAY.
LIQUID-TIGHT FLEXIBLE CONDUIT AND APPROPRIATE LIQUID-TIGHT FITTINGS
SHALL BE USED IN AREAS EXPOSED TO THE WEATHER OR LIKELY TO PROJECT NO.: 24-0828.02
CONTRACTOR SHALL OPERATE THE SYSTEMS FOR A PERIOD OF AT LEAST
BECOME DAMP. DATE: 04/30/25
THREE DAYS, NOT NECESSARILY CONSECUTIVE TO DEMONSTRATE
FULFILLMENT OF THE REQUIREMENTS OF THE CONTRACT. DURING THIS TIME,
ADJUST EQUIPMENT SO THAT IT WILL PERFORM AS THE MANUFACTURER
INTENDED, AND SO THAT SYSTEMS WILL FUNCTION AS DESIGNED. EXECUTE
ELECTRICAL
TESTS AND ADJUSTMENTS OF EQUIPMENT AS REQUIRED TO VERIFY SPECIFICATIONS
PERFORMANCE REQUIREMENTS. SUBMIT DATA TAKEN DURING SUCH TESTS
TO THE ARCHITECT.

E8.1