RELAY COORDINATION BETWEEN INCOMER & OUTGOING FEEDERS OF MV SWITCHGEAR
CTR 2500/1
I/C
CTR 700/1
CTR 250/1
CTR 2500/1
CTR 1250/1
4500KW
2500KVA
2500 A
1250 A
I]
Between Incomer and Motor Feeder FAULT TYPE: SHORT CIRCUIT Motor Rating Motor rated voltage Motor full load current CT Ratio (CTR) CT Secondary current
4500 KW 6.6 KV 454.2 700/1 0.65
Calculation of Operating time of over current protection of Motor Feeder Current Setting in % (PS) Current Setting (I>) (CTR X PS) Fault Current considered (Amps) (I) Operating time calculated as follows
2.0 1400.00 25000
1 >
+ K
IEC Very inverse (A) (B) 13.5 0
1 >
Selected Characteristic Time/current curve group Very inverse C K (TMS)
1 0.7
Operating time of Over current protection,t (sec)
II Calculation of required TMS for Incomer Feeder Fault current considered (A) Current Setting in % (PS) Current Setting (I>)
0.5606
25000 100% 2500
Operating time calculated as follows
1 >
+ K
IEC Very inverse (A) (B) 13.5 0
1 >
#REF!
Selected Characteristic Time/current curve group Very inverse C K (TMS)
1 0.92
Operating time of Over current protection,t (sec)
1.38
0.529 0.92
Minimum TMS for discrimination Selected TMS considering that TIE between unit boards are closed
I]
Between Incomer and Transformer Feeder FAULT TYPE: SHORT CIRCUIT Transformer Rating Transformer rated voltage Transformer full load current CT Ratio (CTR) CT Secondary current
2500KVA 6.6 KV / 433V 218.69 250/1 0.87
Calculation of Operating time of over current protection of Transformer Feeder Current Setting in % (PS) Current Setting (I>) (CTR X PS) Fault Current considered (Amps) (I) Operating time calculated as follows
0.9 225.00 25000
1 >
+ K
IEC Very inverse (A) (B) 13.5 0
1 >
Selected Characteristic Time/current curve group Very inverse C K (TMS)
1 1
Operating time of Over current protection,t (sec)
II Calculation of required TMS for Incomer Feeder Fault current considered (A) Current Setting in % (PS) Current Setting (I>) Operating time calculated as follows
0.1226
25000 100% 2500
1 >
+ K
IEC Very inverse (A) (B) 13.5 0
1 >
Selected Characteristic Time/current curve group Very inverse C K (TMS)
1 1
Operating time of Over current protection,t (sec)
1.5
0.529 0.92
Minimum TMS for discrimination Selected TMS considering that TIE between unit boards are closed
CHGEAR
RELAY COORDINATION BETWEEN INCOMER & OUTGOING FEEDERS OF LV SWICHGEAR
CTR 4000/1
I/C-1 CTR 4000/1
I/C-2
CTR 4000/1
B/C
A CTR 400/1 CTR 400/1
180/200 KW
180/200 KW