D.G Size Calculation (22.8.12)

This document contains technical specifications for equipment and calculations related to sizing an emergency diesel generator set. It lists the voltage ratings, connected loads including motor loads, and load factors. Calculations determine the starting and running load requirements, recommended generator size, and estimates of fuel consumption and operating costs. The generator is sized to 237kVA to meet the starting load of 237kVA and running load of 81kVA while maintaining an efficiency of 63% at full load operation.
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
5K views1 page

D.G Size Calculation (22.8.12)

This document contains technical specifications for equipment and calculations related to sizing an emergency diesel generator set. It lists the voltage ratings, connected loads including motor loads, and load factors. Calculations determine the starting and running load requirements, recommended generator size, and estimates of fuel consumption and operating costs. The generator is sized to 237kVA to meet the starting load of 237kVA and running load of 81kVA while maintaining an efficiency of 63% at full load operation.
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 1

System Voltage ( P-P ) System Voltage ( P-N ) Future Load Expansion Average Intermittent Use of Equipment Sr.

N o

415

Volt

Linear Load:

General Equipments, Heater

Jignesh.N.Parmar www.electricalnotes.wordpress.com jiguparmar@yahoo.com

Equipment Tower Crain-E Tower Crain-C Tower Crain-C

UPS,Invertor,Ballast,VFD Non-Linear Load: 230 Volt 0% % 1 (0.7 To 1.0) 0.8 0.8 Total Connected Load on Diesel Generator Set Load Starting Running Diversity Load Type Supply Qty P.F P.F Factor Load Kw/Hp Motor Motor Motor 3Ph 3Ph 3Ph 1 1 1 43 43 43 Kw Kw Kw 0.8 0.8 0.8 0.8 0.8 0.8 0.5 0.5 0.5

Starting Condition Motor Starter Y-D Y-D Auto.Tra. Starting Amp 150 150 112 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Starting Kva 108 108 81 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Starting Kw 86 86 65 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Running Condition Full Full Full Load Load Load Kva Kw Amp 27 27 27 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 22 22 22 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 37 37 37 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

RESULTS
Starting Kva Starting Kw Starting Amp Running Kva Running Kw Running Amp Alternator Details Voltage (P-N) Efficiency Engine Overload Capacity 296 237 411 81 65 112 230 80% 130%

(Appro 130% To 150%)

Required Generator Rating

Generator KVA Engine KW

237 67

(Select D.G near This Value)

Calculate D.G Set Efficiency & Unit Rate of Power D.G Size ( Kva ) D.G P.F D.G Running Hours Diesel Consumption (Liter) KWH Reading of Meter M.F of KWH Meter Diesel Rate /Liter (Rs) Efficiency of D.G KWH/Liter (Unit Per Liter) Unit Rate of Power (Rs) 1000 1 20 1000 10000 1 40 63% 10 4.0

Calculate Approximate Fuel Consumption D.G Size (Kva) D.G P.F D.G Operation 115 0.8 Full Load

Required Diesel Liter/Hour 23.11