Product Information
Hilti, Inc. (U.S.) 1-800-879-8000  www.us.hilti.com  en espaol 1-800-879-5000  Hilti Firestop Systems Guide 
Hilti. Outperform. Outlast.
Hilti Firestop
Saving lives
through innovation
and education
Firestop Block 
CFS-BL
Product description
   Ready-to-use, intumescent fexible block designed to seal medium 
to large size openings
Product features
   Integrated Grid-Tech increases Annular Space up to 12 
   Suitable for re-penetration or new penetrations
   Economical to use with short installation times
   Easy installation  no special tools required
   Ideal for use in foors  no forming required
   One sided wall systems available
   Halogen, asbestos and solvent free
   Operational immediately after installation
   Smoke resistant
Areas of application
   Sealing single or multiple penetrations in small to large openings
   Temporary or permanent sealing of cables and cable tray 
penetrations
   Temporary or permanent sealing of insulated and non-insulated 
metallic pipes and combustible pipe penetrations
For use with
   Walls (UL tested up to max. opening 72" x 36")
   Floors (UL tested up to max. opening 72" x 36")
   Concrete, porous concrete, masonry and gypsum wall assemblies
   Wall assemblies rated up to 4 hours
   Floor assemblies rated up to 3 hours
Examples
   Completely dust and fber free rooms and places where electrical 
installations are frequently used (ie: computer centers, hospitals, 
laboratories, etc.)
   New buildings in the construction phase and during renovation
   Large openings containing multiple penetrations as found in 
production bays, warehouses, hospitals etc.
Installation instructions for Firestop Block CFS-BL
FILL, VOID OR CAVITY MATERIALFOR USE IN THROUGH-
PENETRATION FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY  
66Y7
FM
For Penetration Fire Stops.
Consult the Factory Mutual Research Corporation Approval Guide.
R  
FILL, VOID OR CAVITY MATERIALS
 CLASSIFIED BY
UNDERWRITERS LABORATORIES, INC.
FOR USE IN TROUGH-PENETRATION
FIRESTOP SYSTEMS 
SEE UL FIRE RESISTANCE DIRECTORY
66Y7
Notice 
  Before handling, read Material Safety Data Sheet and 
product label for safe usage and health information. 
  Instructions below are general guidelines  always 
refer to the applicable drawing in the UL Fire 
Resistance Directory or Hilti Firestop Systems Guide 
for complete installation information
Opening
1.  Clean the opening. Penetration and penetration 
supporting structures must be installed in 
compliance with local building and electrical 
standards.
Application of Firestop Blocks
2a.If no penetrations are located, build up Firestop 
Block CFS-BL, firmly seated, within opening.
2b.If penetrations are located, build up Firestop Block 
CFS-BL, firmly seated, while cutting blocks with a 
knife to suit the placed penetrations.
3.  Finish building up Firestop Blocks until entire 
opening is filled.
4.  Completely fill cable spaces, gaps between blocks 
and pipes, and joints with FS-ONE Firestop Sealant 
(as required).
5.  For maintenance reasons, a penetration seal could 
be permanently marked with an identification plate.  
In such a case, mark the identification plate and 
fasten it in a visible position next to the seal.
Re-installing cables or other penetrations
  Remove or cut the block from the seal.
   Install the penetrant and re-lay the block in 
compliance with the approval. Fill gaps and spaces 
with FS-ONE Firestop Sealant (as required).
  Single cables can be run through joints between 
blocks or a hole can be drilled through a block using 
a sharpened piece of metal pipe or tubing.
Not for use
  In wet rooms, outdoors or exposed to the weather 
or UV radiation (can be done only after applying an 
additional silicone coating, i.e. CP 601S). 
Storage
  Store only in the original packaging in a location 
protected from moisture and direct sunlight
1. Clean opening. 2a. Build up blocks  2b. Cut blocks to 
size for penetrations 
in place
3. Build up blocks 4. Fill gaps with
FS-ONE, CP 617 
or CP 618 putty (as 
required).
5. Fasten identifcation 
plate in place (If 
required)
Technical Data*  CFS-BL
Color Red
Application temperature 40 F to 104 F (5 C to 40 C)
Temperature resistance 5 F to 140 F (-15 C to 60 C)
Intumescent activation Approx. 392 F (200 C)
Expansion ratio (unrestricted) Up to 1:3
Surface burning characteristics 
(ASTM E84-10b)
Flame Spread Index: 10
Smoke Development Index: 15
Sound transmission classifcation 
(ASTM E84-10b)
In Progress
Approvals
 California State Fire Marshal - In Progress
Tested in accordance with
 UL 1479      ASTM E 814      ASTM E 84
*At 73F (23C) and 50% relative humidity