<<Contents>> <<Index>>
General Specications
GS 33K50F20-50E
Models ANB10S, ANB10D ESB Bus Node Units (for FIO)
GENERAL
The ESB Bus Node Unit has an interface function that communicates the analog I/O signals and contact I/O signals of a eld with a Field Control Unit (FCU) via an ESB bus, as well as a function that supplies power to the I/O Modules. This node units are connected to FCU via an ESB bus.
HARDWARE SPECIFICATIONS
For the installation specications and environmental conditions that are common to the systems, refer to FIO System Overview (for Vnet/IP) (GS 33K50F1050E).
No. of Node Units Connectable
Vnet/IP
Field Control Unit Database
F01.ai
Total Number of ESB Bus Node Units (ANB10) and Optical ESB Bus Node Units (ANB11) Connected per FCU Max. 3 Max. 9 Max. 13
Control Function for Field Control Station (LFS1700) AFV30 Control Function for Field Control Station (LFS1700) AFV40 plus Node Expansion Package (LFS1750-V1) (*1) Control Function for Field Control Station (LFS1700) plus Node Expansion Package (LFS1750-V2) *1: Up to 11 node units per 1 cabinet can be installed in AFV40.
Field Control Unit
Database
ESB Bus Node Units (ANB10) Connected per FCU Max. 3 Max. 9
ER Bus Node Units (ANR10) Connected per FCU Max. 3 Max. 14
Control Function for Field Control Station (LFS1500) AFV10 Control Function for Field Control Station (LFS1500) plus Application Capacity Expansion Package (LFS1550)
Total Number of ESB Bus Node Units (ANB10) and ER Bus Node Units (ANR10) Connected per FCU Max. 3 Max. 14
Vnet
Field Control Unit AFF50 ESB Bus Node Units (ANB10) Connected per FCU Max. 3 Max. 10 Max. 10 (*1) ER Bus Node Units (ANR10) Connected per FCU Max. 3 Max. 14 Max. 9 (*1) Total Number of ESB Bus Node Units (ANB10) and ER Bus Node Units (ANR10) Connected per FCU Max. 3 Max. 15 Max. 10 (*1)
Database
Control Function for Compact Field Control Station (LFS1350) AFG30 Control Function for Enhanced Field Control Station AFG40 (LFS1330) with Node expanded databases Others *1:
In Case of AFG81 and AFG82, there are total number with SIO Nest (for CENTUM V or CENTUM-XL). Total number of SIO: Max 5/FCU
Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan Tel.: 81-422-52-5634 Fax.: 81-422-52-9802
GS 33K50F20-50E Copyright Aug. 2011 (YK) 6th Edition June 12, 2013 (YK)
<<Contents>> <<Index>>
ESB Bus Node Connection
When connecting an ESB Bus Node Unit to FCU, install ESB Bus Coupler Module (EC401 or EC402) to FCU (*1). EC401 or EC402 must be installed in slot 7 and slot 8. To make single conguration, EC401 or EC402 must be installed in slot 7, and Slot 8 must be empty. EC402 can be installed in AFV30 or AFV40.
*1: AFV30, AFV40, AFV10, or AFF55.
Power Supply
Specify with Sufx Codes Voltage: 100-120 V AC, Frequency: 50/60 Hz Voltage: 220-240 V AC, Frequency: 50/60 Hz Voltage: 24 V DC
Electric Power Consumption
100-120 V AC: 200 VA, 120 W 220-240 V AC: 230 VA, 120 W 24 V DC: 5.5 A
Weight
10 kg (incl. 8 I/O Modules)
Mounting
19-inch Rack Mounting Rack mount (M5 x 4 screws) Insulation bash (accessory)
Regulatory Compliance
For the detailed information of following standards, see System Overview (GS 33K01A10-50E). Safety Standards [CSA] (for 100-120 V AC and 24 V DC power supply) [CE Marking] (for 100-120 V AC, 220-240 V AC and 24 V DC power supply) EMC Conformity Standards [CE Marking] (for 100-120 V AC, 220-240 V AC and 24 V DC power supply) [C-Tick Marking] (for 220-240 V AC and 24 V DC power supply) [KC Marking] (for 100-120 V AC, 220-240 V AC and 24 V DC power supply) Standards for Hazardous Location Equipment [CSA Non-Incendive] (for 100-120 V AC and 24 V DC power supply) [FM Non-Incendive] (for 100-120 V AC, 220-240 V AC and 24 V DC power supply) [Type n] (for 24 V DC power supply)
CONFIGURATION
Module conguration
Power Supply Module (PW481 or PW482 or PW484): Two modules in case of a dual-redundant conguration. Power supply to the I/O Modules, and supply power to the transmitters. The power supply terminals use M4 screws. ESB Bus Interface Slave Module (SB401): Two modules in case of a dual-redundant conguration. I/O Modules (*1): Max. 8
*1: Non-standard components.
LIMITATIONS OF INSTALLATION AND NOTICES FOR INSTALLATION
For installing I/O modules in node unit, the quantity and allocation are limited. Also, when installing a node unit to the dedicated cabinet, there are limitations of installation under the ambient operating temperature conditions. When modules with built-in barriers are installed in any node unit, an insulating partition (Part No. T9083NA) must be installed. For details, please refer to FIO System Overview (for Vnet/IP) (GS 33K50F10-50E) and Installation Guidance (TI 33K01J10-50E).
All Rights Reserved. Copyright 2011, Yokogawa Electric Corporation
GS 33K50F20-50E Sep. 1, 2012-00
<<Contents>> <<Index>>
EXTERNAL DIMENSIONS
ANB10D, ANB10S ESB Bus Node Unit (Figure of ANB10D)
Unit: mm
8.75 21.3
482.6 465.1 440
205 150.6 18.4
146 221.5
37.75
Hole for mounting on a 19-inch rack (4 holes for M5 screws)
F03E.ai
All Rights Reserved. Copyright 2011, Yokogawa Electric Corporation
GS 33K50F20-50E Dec. 7, 2011-00
<<Contents>> <<Index>>
MODELS AND SUFFIX CODES
Node Unit for Single ESB Bus
Model ANB10S -3 -4 1 2 4 5 Sufx Codes 6 7 E F G /CU1N Option Codes /CU1T /ATDOC /NDEL Description Node Unit for Single ESB Bus Single power supply Dual-redundant power supply 100 - 120 V AC power supply 220 - 240 V AC power supply 24 V DC power supply Basic type with no explosion protection With ISA Standard G3 option, temperature (-20 C to 70 C) option, and no explosion protection (*1) With ISA Standard G3 option and no explosion protection Basic type with explosion protection With ISA Standard G3 option, temperature (-20 C to 70 C) option, and explosion protection (*1) With ISA Standard G3 option and explosion protection Connector Unit for ESB Bus [part No.: S9562FA] Connector Unit with Terminator for ESB Bus [part No.: S9564FA] Explosion Protection Manual (*2) Software License for Node Expansion (*3) *1: If ANB10 is connected to the Optical ESB Bus Node Unit (ANB11), ISA Standard G3 option and temperature (-20 to 70 C) option may be specied. Select the option code /ATDOC to follow the ATEX Directive for use in potentially explosive atmospheres. It must be sure to specify the Option Code /NDEL to connect Node Unit with AFV10, AFV30, AFV40 and AFF50. Description Dummy Cover (for I/O Module) Dummy Cover (for Power Supply Module)
*2: *3:
Dummy Cover
ADCV01 ADCV02
Model
Insulating Partition
Part No. T9083NA Description Insulating Partition
Note: When mounting an FIO module with built-in barrier to a node unit, place this part to the 8th slot.
ACCESSORIES AND SPARE PARTS
Parts Names Insulating bush Parts Numbers S9049PM Description Quantity 4 Remarks Accessory
Node Unit for Dual-Redundant ESB Bus
Model ANB10D -4 1 2 4 5 Sufx Codes 6 7 E F G /CU2N Option Codes /CU2T /ATDOC /NDEL Description Node Unit for Dual-Redundant ESB Bus Dual-redundant power supply 100 - 120 V AC power supply 220 - 240 V AC power supply 24 V DC power supply Basic type with no explosion protection With ISA Standard G3 option, temperature (-20 C to 70 C) option, and no explosion protection (*1) With ISA Standard G3 option and no explosion protection Basic type with explosion protection With ISA Standard G3 option, temperature (-20 C to 70 C) option, and explosion protection (*1) With ISA Standard G3 option and explosion protection Connector Unit for ESB Bus [part No.: S9562FA (2 pieces)] Connector Unit with Terminator for ESB Bus [part No.: S9564FA (2 pieces)] Explosion Protection Manual (*2) Software License for Node Expansion (*3)
ORDERING INFORMATION
Specify the model and sufx codes. For selecting the right products for explosion protection, please refer to TI 33Q01J30-01E without fail.
TRADEMARKS
CENTUM and Vnet/IP are registered trademarks of Yokogawa Electric Corporation. Other product and company names appearing in this document are trademarks or registered trademarks of their respective holders.
All Rights Reserved. Copyright 2011, Yokogawa Electric Corporation Subject to change without notice.
GS 33K50F20-50E June 12, 2013-00