Power distribution in control
panels
Presentation
Pre-assembled panel busbar system AK5
The assembly of automated control and distribution panels requires the use of
products that are not only safe but also simple and quick to mount and cable.
The AK5 pre-assembled busbar system meets all these criteria by incorporating
prefabricated components which cater for 3 principal functions:
Carrying of electric current
By the pre-assembled 4-pole busbar system 1, 160 A at 35 C.
4-pole busbar systems can be used for 3-phase + Neutral or 3-phase + Common.
The busbar systems are available in 6 lengths: 344, 452, 560, 668, 992, 1100 mm.
An incoming supply terminal block 2 is located at the extreme left of the busbar
system.
"Knock-out" partitions allow connection of the power supply from above or below to
connectors 3 which are protected by a removable cover 4.
Upstream protection of the busbar system is shown on page 1/206.
Current distribution
Tap-off units 5 (factory assembled) are available in 4 versions:
b 2-pole,
b 3-pole,
b 4-pole (3-phase + Neutral),
b 4-pole (3-phase + Common).
The tap-offs clip onto the busbar system with instantaneous mechanical and
electrical connection to the busbars.
2 ratings are available: 16 and 32 A.
The tap-off units ensure not only rapid mounting, but also a neat appearance for the
power distribution system and complete safety when accessing under live circuit
conditions.
Component mounting
Component mounting plates with incorporated tap-off allow mounting of and supply
of power to components.
They are available in 25 A or 50 A ratings.
These mounting plates clip onto the mounting rail 11, which also supports the busbar
system, and at the same time make electrical connection via the incorporated
tap-off.
2 types of mounting plate are available:
b single plates 6 (height 105 mm), with bolt-on 35 mm wide 7 rail 7, which may be
bolted on in one of two positions, allowing height adjustment of 10 mm.
b double plates 8 and 14 (height 190 mm), with two bolt-on, 35 mm wide 7 rails 9
mounted on 100 mm fixing centres; each rail may be bolted on in one of 4 positions,
allowing height adjustment in 10 mm steps. These plates are supplied with
connectors 12 to allow wiring between control and protection devices.
Single mounting plates enable the following types of distribution:
b 2-pole (Ph + N) and (Ph + Ph)
b 3-pole,
b 4-pole (3 Ph + N or 3 Ph + common).
Double mounting plates enable the following types of distribution: 2-pole (Ph + N,
Ph + Ph), 3-pole or 4-pole (3Ph+N and 3Ph + common).
Extension plates 10 can be bolted onto single and double mounting plates to enable
mounting of wider components. Using a side stop 15 in conjunction with these
extension plates also supports the AK5 JB busbar system when used vertically.
A control terminal block 13 comprising a support plate bolted onto the single or
double mounting plates and a 10-pole plug-in block, enables connection of the
control circuit wires (c.s.a. 1.5 mm2 max).
Characteristics:
pages 1/206 and 1/207
13230-EN
References:
pages 1/210 and 1/211
Dimensions:
pages 1/212 and 1/213
Version : 8.0
Schemes:
pages 1/210 and 1/211
08/11/2011
Mounting possibilities:
pages 1/208
1/205
Power distribution in control
panels
Characteristics
Pre-assembled panel busbar system AK5
Busbar system characteristics
Conforming to standards
IEC 60439
Product certifications
UL, CSA, DNV, LROS
Degree of protection
Against access to live parts
Flame resistance
Conforming to IEC 60695
Number of conductors
IP XXB conforming to IEC 60529
Conforming to standard UL 94
V0
AK5JB14p
4
a
Supply current
Rated operational frequency
Rated operational current
Rated insulation voltage
Hz
50 or 60
Ambient temperature 35 C
160
Coefficient K to be applied
according to the
ambient temperature
35
40
45
50
55
60
0.96
0.92
0.88
0.83
0.78
Conforming to IEC 60439-1
690
Conforming to UL and CSA
600
Off-load plugging-in and unplugging, with supply switched on
Conforming to IEC 60439-1
400
Conforming to UL, CSA
480
Plugging-in and unplugging, with supply switched off
Conforming to IEC 60439-1
690
Conforming to UL, CSA
V
kA
600
25
A 2s
1 x 10 7
Operational voltage
Maximum permissible
peak current
Maximum let-through energy
Upstream short-circuit (1)
and overload protection
Type of protection
Prsentation :
pages 1/204 and 1/205
1/206
Schneider Electric circuit-breaker
Fuses
NSX 160 N
NSX 160 H
aM
gF
Rating
160
160
160
160
Prospective
short-circuit current
kA
36
70
100
100
Operational current
160
160
160
160
Cabling
Mounting position
850 (incandescent wire)
Maximum c.s.a.
Minimum c.s.a.
Flexible cable with cable end
mm2
70
2.5
Solid cable
mm2
70
2.5
Tightening torque
Nm
10
Horizontal or vertical (2)
References :
pages 1/210 and 1/211
Fixing with screws provided
(1) For conditions where conditional short-circuit current exceeds 25 kA.
(2) Using side stop AK5BT01 on mounting plates AK5PA.
Schemes:
pages 1/210 and 1/211
Version : 8.0
Mounting possibilities :
page 1/208
08/11/2011
13230-EN
Power distribution in control
panels
Characteristics (continued)
Pre-assembled panel busbar system AK5
Tap-off characteristics
Type
AK5
AK5
AK5
AK5
AK5
AK5
AK5
PC12
PC12PH
PC13
PC14
PC131
PC32L
PC32LPH PC33
AK5
PC33L
Conforming to standards
IEC 60439
Product certifications
UL, LROS, CSA, DNV
Degree of protection
Against access to live parts: IP XXB conforming to IEC 529
Polarity
Conductor c.s.a.
mm2
3-phase
PC34L
Phase
Phase
3-phase
3-phase
Phase
Phase
3-phase
3-phase
Neutral
Phase
Neutral
Common
Neutral
Phase
Neutral
Common
2 x 2.5
2 x 2.5
3 x 2.5
2x4
2x4
4x4
3x4
3 x 2.5
4 x 2.5
3x4
1 x 1.5
Conductor colours
Permissible current
AK5
PC331
(UL cables)
3-phase
AK5
PC34
Black
Black
Black
Black
Black
Black
Blue
Blue
White
Blue
Blue
White
(Neutral)
(Neutral)
(Neutral)
(Neutral)
(Common)
32
32
16
Black
Black
16
16
16
Rated insulation voltage
690 conforming to IEC 60439-1
Rated peak current
kA
Maximum let-through energy
A 2s
100 000
Type of conductor insulation
1 x 1.5
16
32
Black
32
Black
32
10
10
(Common)
(Common)
200000
PVC 105 C
Tap-off characteristics
Type
AK5
PA211N1
PA211N2
PA211N3
PA212N1
PA212N2
PA212N3
Conforming to standards
IEC 60439
Product certifications
UL, LROS, CSA, DNV
Degree of protection
Against access to live parts: IP XXB conforming to IEC 60529
Polarity
Phase +
Neutral
Phase +
Phase
3-phase
3-phase
+ Neutral
AK5
PA211PH12
PA211PH13
PA211PH23
PA212PH12
PA212PH13
PA212PH23
AK5
PA231
PA232
PA232S
AK5
PA241
PA242
AK5
PA2311
PA2312
PA2312S
AK5
PA532
AK5
PA542
AK5
PA5312
3-phase
+ Common
3-phase
3-phase
+ Neutral
3-phase
+ Common
Conductor c.s.a.
(UL cables)
mm2
2x4
2x4
3x4
4x4
3x4
1 x 1.5
2 x (3 x 4)
2 x (4 x 4)
2 x (3 x 4)
1 x 1.5
Permissible current
25
25
25
25
25
10
(Common)
50
50
50
10
(Common)
Rated insulation voltage
Rated peak current
Maximum let-through energy
V
kA
A 2s
690 conforming to IEC 60439-1
6
200 000
Type of conductor insulation
PVC 105 C
Characteristics of mounting rails AM1DL201 and AM1DL2017
Omega 7 (width 75 mm, depth 15 mm)
Type
Material
2 mm sheet steel
Surface treatment
Galvanized
13230-EN
Version : 8.0
08/11/2011
1/207
Power distribution in control
panels
Mounting
(equipment possibilities)
Pre-assembled panel busbar system AK5
Component mounting plates incorporating tap-off mounted on AK5 JB busbar system
AK5
PA211N1
PA211N2
PA211N3
AK5
AK5
AK5
PA231 PA241 PA212N1
PA2311
PA212N2
(1)
PA212N3
AK5
AK5
AK5
AK5
PA212PH12 PA232 PA242 PA232S
PA213PH13 PA2312
PA2312S
(1)
PA212PH23 (1)
AK5
AK5
PA532 PA542
PA5312
54
54
54
54
54
54
54
108
108
108
105
105
105
190
190
190
190
190
190
190
No. of 18 mm pitches
Thermal current
25 A
25 A
25 A
25 A
25 A
25 A
25 A
25 A
50 A
50 A
Application
Ph + N
3-pole
3-pole
+N
Ph + N
Ph + Ph
3-pole
3-pole
+N
3-pole
3-pole
3-pole
+N
Mounting
Width in mm
plate
incorporating
Height in mm
tap-off
(1) 3-pole + common.
(1)
Note:
b if the equipment is wider than the mounting plate, an extension plate can be used to increase the width of the support plate.
b for upstream protection, see page 1/206
1/208
Version : 8.0
08/11/2011