DATE: 30-01-15
PROJECT: ASPIRE INTERNATIONAL SHOOL
SERVICES: ELECTRICAL SYSTEMS
PRICE SUMMARY
SR. NO.
DESCRIPTION
AMOUNT
HT WORK
A)
RING MAIN UNIT
B)
SUBSTATION
C)
HT ABLE
D)
SUBSTATION AUXILARIES
E)
APFC PANEL
F)
DG SYSTEM
G)
LV SWITCHBOARDS
H)
LT CABLING
I)
POINT WIRING
J)
DISTRIBUTION BOARD
K)
ELV SYSTEM
L)
UPS
M)
LIFT
N)
EARTHING
O)
LIGHT FITTINGS
P)
LIGHTNING ARRESTOR
In words:
2,510,722.00
TOTAL
AMOUNT IN WORDS
SR. NO.
DESCRIPTION
11KV RING MAIN GEAR PANEL
Supply.Installation,Testing,Commissioning of
11KV,630Amps,25KA outdoor type(IP54) ring main gear panel as
per below specification.
INCOMING2Nos. 11KV ,630A, 25kA Triple Pole load break switch with
3position (ON ,OFF,and Earth),and fully rated earth switch with
provision for earth and test of the cable
Power frequency & Impulse voltage: 28KV
Bottom side Cable Entry.
Mechanical ON/OFF/EARTH indication.
Anti reflex operating handle.
2 NO + 2 NC auxiliary contacts.
Shunt Trip coil (230V AC) for external trip signal.
Self powered O/C+E/F relay type VIP35.
Live Cable indicating LEDs energized thru capacitive voltage
dividers.
Cable testing facility without opening cable compartment &
without
disconnecting the cable termination.
Cable Box for termination of cable upto 1No. 3C X 95 sqmm.
XLPE cable.
Right angle boots (Push-On Type)
OUTGOING1 Nos VCB of 11KV, 25 KA , 3 sec,630 A, 50 Hz, Circuit Breaker
with Earth Switch & Motorized Spring Charged 240V AC supply,
Mechanical tripping & Closing arrangement
Type of Main Busbars: Copper
Rating of Main Busbars: 11KV, 630A, 25 KA/3sec
Shunt Tripping coil shall be at 30 V DC. With single & double
core CT Epoxy Cast resin Insulation.
Mechanical ON , OFF, Earth Indications. Mechanical Spring
Charging.
Cable Testing Facility without Opening the Compartment &
Without Disconnecting the cable Terminations.
Live Cable Indications, Indicating LED's Energized through
capacitive voltage divider
Cable Box Suitable For Cable Termination of 3C X 95 sq.mm
XLPE Cable
One Control Switch for TOD Operation. 1.No.
1 No. Breaker Control Switch
Emergency Trip Push Button
Remote & Local switch for Circuit Breaker, Master Trip Relay
METERING:
Analog Voltmeter ( 0 - 12KV ) with selector switch - 1 No.
Analog Ammeter ( 0 - 25 A ) with selector switch. - 1 No.
CT:
UNIT QUANTITY
25/5A Core 1-15VA burden class 1.0 for metering.
25/5A Core 2-15VA burden class 5P 10 for protection
PT Ratio:
11000/22000/ 3 / 110 / 3 Volt. With class 0.5 , 100VA.
PROTECTIONS:
Numerical Self Powered Relay with following protections
a) Over Current (Instantaneous) 50
b) Earth Fault (Instantaneous) 50N
c) Over Current ( IDMT) 51
d) Earth Fault (IDMT) 51N
INDICATIONS :
1 Set of fuses, ferrules, wiring etc. as required.
1 set of following indicating lamps
- Red, Yellow and Blue for phase Indication
- Amber for trip indication
- Red `ON & Green `OFF
- Earth & SF6 Gas Pressure Indication
- Spring charge indication
- 'Blue'Trip Circuit, Healthy Indication
Adequate no. of NO/NC contacts of Circuit Breaker shall
be wired up to the terminal block for connection to control
and relay panel.
No
TOTAL CARRIED OVER TO SUMMARY
SUPPLY
INSTALLATION
AMOUNT
SR. NO. DESCRIPTION
B
TRANSFORMER
Supply, Installation, Testing and Commissioning of 315 kVA,
11 / 0.433 KV, 50 Hz., 5.0% impedance, vector symbol Dyn11,
Indoor duty, oil cooled, copper wound, ONAN type transformers
with tappings of +7.5% to 7.5% on primary side with Off load
tap changing mechanism and all the standard accessories as
required by the local electricity boards.
Termination arrangementsHV Side - 3 Core, 95 Sq.mm XLPE Cable
LV Side - Provision for 2 runs of 240 Sq.mm XLPE Cable.
Note: Scope shall also include testing and inspection at works
by the Electricity Board officials / Client / PMC / Consultants
TOTAL CARRIED OVER TO SUMMARY
UNIT
QUANTITY
SUPPLY
INSTALLATION
AMOUNT
SR. NO. DESCRIPTION
UNIT
QUANTITY
HT CABLING
Supplying, laying, testing and commissioning of 11 kV earthed grade, 3
Core, 95 Sq.mm Cross Linked Polyethylene (XLPE) insulated, Aluminium
Cable.The cables shall be laid in 150mm RCC hume pipe.The cost
include all fixing accessories, excavation, back filling, sand & brick
bedding etc. shall be included in the scope. (From MSEDCL to
Substation)
Rm
200
Supplying, laying, testing and commissioning of 11 kV earthed grade, 3
Core, 95 Sq.mm Cross Linked Polyethylene (XLPE) insulated, Aluminium
Cable.The cables shall be laid in existing cable trays,concrete trenches
or buried hume pipe. (From HT Panel to Transformer )
Rm
50
Supplying and termination of 3 Core, 95 Sq.mm Cross Linked
Polyethylene (XLPE) insulated, Aluminium Cable with cable gland,
indoor type sealing kit, epoxy compound, heat shrinkable slews etc.
complete as required for termination.
Nos.
Supply and laying, installation of following RCC (NP-2 class) Hume pipe
however all fixing accessories, excavation, back filling, sand & brick
bedding etc. shall be included in the scope. This shall also include cost of
required size chambers.
150 mm dia ID
Rm
250
ii
300 mm dia ID
Rm
350
TOTAL CARRIED OVER TO SUMMARY
SUPPLY
INSTALLATION
AMOUNT
SR. NO. DESCRIPTION
D
UNIT
QUANTITY
SUBSTATION AUXILLARIES
Supply and fixing in position the best quality danger boards of approved
shape and size as specified by the local electrical authorities written in
English, Hindi and local language.
No
ii
Providing and fixing in position approved shock treatment chart written in
English and local language. The chart shall be framed in Teakwood and
covered with glass.
No
iii
Supply and fixing in position the fire extinguishers carbon-di-odide type 2.5
Kgs capacity..
No
iv
Supply of fire buckets 5 nos. in each set duly filled with fine sand and fixed
on an angle iron frame as per requirement of local authorities. Fire buckets
shall be painted red from outside and white from inside with additional
handle at the bottom
Sets
Supply and fixing in position 1000 mm wide rubber matting of 11 KV grade
as per electricity rules.
Sq.m
vi
Supply and fixing in position the approved single line diagram framed in
1000 x 800 mm size glass frame in the sub station.
Nos.
vii
Supply of first aid box of approved make as per specification.
Nos.
viii
Supply of tool kit with 1 pair 11 KV rubber hand gloves of approved make.
Nos.
RM
30
Nos.
ix
xi
Supplying, laying, testing and commissioning of 1100V grade PVC insulated
PVC sheathed steel wire/ tape armoured aluminium / copper conductor
control cables . The cables shall be laid in cable trays, clamped on walls
and in concrete trenches, with suitable clamps and saddles fixing bolts etc.
The cost of the cable trays or ladders, excavation and back filling of
trenches not to be included in this scope.
10 Core 2.5 sq mm PVC insulated copper conductor armoured control
cables
Supplying and Installation of cable terminations for the above cables
including double compression type chrome plated brass glands and
bimetallic lugs (crimping type), PVC taping as required and all accessories
complete.
10 Core 2.5 sq.mm Control cable
The professional charges for liason work and departmental procedures
required for the above said work .
The work shall include the following:
* Obtaining the feasibility report and spot inspection, etc.
* Obtaining saction of H.T. connection of 2 nos.630 kVA Transformers.
* Preparation and submission of all statutory drawings to MSEDCL and
electrical inspectorate.
* Obtaining necessary approvals and submitting to the clients.
* Any other works related to MSEDCL and Electrical inspectorate.
Lumpsum
TOTAL CARRIED OVER TO SUMMARY
RATE
AMOUNT
SR.NO
DESCRIPTION
CONTACTOR BASED APFC PANELSWITH
UNIT
Design, Assembling, Supply, Installation, Testing and Commissioning of following 125 KVAR Contactor
based Auto Power Factor Correction Panels and Swithgears suitable for 415 Volts, 3 phase 4 wire, 50 Hz
power distribution system. In conjunction with general specifications following points should also be
considered and adhered to.
1) All the Switchboards shall be Indoor type, dust and vermin proof type compartmentalised design
maintaining IP 54 degree of protection.
2) Panels shall be free standing floor mounted.
3) All hinged door shall be earthed through 2.5 sq mm tinned copper wire. Doors shall be pad locking type
whereas for MCCB compartments they should be openable only in switch OFF mode.
4) All the busbars and links shall be of copper with color coded heat shrinkable insulating sleeves.
Separate earth busbars shall be provided along the length of the switchboards.
5) All measuring instruments (Meters) shall be of digital electronic with LED display of approved make and
compatible with IBMS / BAS.
6) Adequate additional sets of C.T.s, potential free contacts, connectors, contactors with wiring etc are to
be provided for IBMS including space required for various transducers.
7) Adequate space for cable enteries and terminations shall be provided refering SLDs. Cable entries can
be either from the top or bottom as required.
8) All panel switches with locking arrangement.
9) All types of switches,db mcb's require lockout mechanism
1
125 KVAR CONTACTOR BASED APFC PANELS as per schematic
Incomer
One(1) No 250 Amps, 415 Volts, 50 KA, TP ,MCCB releases for Short
Circuit, Earth fault and Over Current protection along with adjustable setting.
Each breaker shall be fitted vertical with following accessories, complete as
required.
1 Nos. 96 x 96 sq.mm 0-250/ 1 amps CTR digital ammeter with 1 Nos. 250 /
5 amps, 15 VA Class I CTs.
ii
0-500 Volts, size 96 mm x 96 mm digital voltmeter with selector switch and
protected by 2 amp TP MCBs
a.
b.
c.
d.
e.
f.
g.
h.
i.
Electronic energy meter of accuracy class-I, with 3 Nos. 250/1 amps 15VA
CTs to measure and display the following electrical quantities :
Current
Voltage
Frequency / Harmonics
Instantaneous power factor
Total active energy (KWH/MWH)
Maximum demand (KVA/MVA) (KW/MW)
Maximum demand reset count.
Eight time of a day energy.
RS 485 Port as required for IBMS/BAS.
iv.
R, Y & B Phase indicating lamps protected by 2 Amps MCBs.
iii
v.
Breaker indicating lamps for CB open, CB close, CB auto trip, Trip circuit
healthy etc.
vi.
Under voltage relay with timer
vii.
Over voltage relay with timer
viii.
Breaker control switch
Relay
Microprocessor based APFC controller along with continuously monitor all
three phases and displays various Electrical Parameters like voltage, input
current, capacitive current, KVA demand,KW, Power Factor, self diagnostic
error code indication with printout facility of the above with RS 232C / 485
port as required. Controller should mounted on the front side of the panel.
Capacitors
Combination of Banks forming a 125 KVAr with mixed dielectric or MPP type
dielectric medium.Capacitor banks shall be connected through appropriate
sized MCCBs. Banks should be selected such that power factor should be
close to unity.
Switching System
Switching System shall be through high speed response Contactor with a
response time less than 60 mill seconds. This should be complete with
required firing cards.
No
TOTAL CARRIED OVER TO SUMMARY
QUANTITY
SUPPLY
INSTALLATION
AMOUNT
SR. NO.
DESCRIPTION
UNIT
QUANTITY
Sets
Rm
50
Rm
Set
DG SYSTEM
Diesel Generator set
ii
Supply, Installation, testing and commissioning of 160 KVA Prime power
rated Diesel Generator Set complete with Diesel Engine suitable for
Generator application, developing 1500RPM with an overloading capacity
of 10% for one hour in any 12 continuous hours operation coupled to 160
KVA at 0.8 Power factor, 415V, 3 Phase , 4 wires, 50 Hz. self excited, self
regulated and brushless excitation complete with acoustic enclosure as per
CPCB norms. DG set shall be radiator type with residential silencer,
electronic governor, termination box, MS mounting frame, fuel piping,
24VDC Battery Charger & batteries, Battery mounting frame, oil level
indicator with gauge board, The DG Set shall be suitable for auto-mains
failure start.The cost shall include fuel piping & Exhaust pipeing with
standard accessories and fuel oil required for testing DG Set at full load.
Total for DG Sets
2.1
2.2
Cabling System
Supply, laying, testing and commissioning of 1100V grade PVC insulated
PVC sheathed steel wire/ tape armoured aluminium / copper conductor
cables. The cables shall be laid in cable trays, clamped on walls and in
concrete trenches, with suitable clamps and saddles fixing bolts etc. The
cost of the cable trays or ladders, excavation and back filling of trenches
not to be included in this scope.
6 core 2.5 sq.mm Cu. Shielded & Armoured Control Cable
Supply,Installation of cable terminations for the above cables including
double compression type chrome plated brass glands and bimetallic lugs
(crimping type), PVC taping as required and all accessories complete.
6 core 2.5 sq.mm Cu. Shielded & Armoured Control Cable
AMF PANEL/DG PANEL
3.1
DG Incomer
Two(2) No 250Amps, 415 Volts, 50 KA, TPN, MCCB with Thermomagnetic
releases for Short Circuit, Earth fault and Over Current protection along
with adjustable setting. Each breaker shall be fitted vertical with following
accessories, complete as required.
1 Nos. 96 x 96 sq.mm 250/ 5 amps CTR digital ammeter with 1 Nos. 250 /
5 amps, 15 VA Class I CTs.
ii
0-500 Volts, size 96 mm x 96 mm digital voltmeter with selector switch and
protected by 2 amp TP MCBs
Set
Set
a.
b.
c.
d.
e.
f.
g.
h.
i
Electronic energy meter of accuracy class-I, with 3 Nos. 250/5 amps 15VA
CTs to measure and display the following electrical quantities :
Current
Voltage
Frequency / Harmonics
Instantaneous power factor
Total active energy (KWH/MWH)
Maximum demand (KVA/MVA) (KW/MW)
Maximum demand reset count.
Eight time of a day energy.
RS 485 Port as required for IBMS/BAS.
iv.
R, Y & B Phase indicating lamps protected by 2 Amps MCBs.
Set
v.
Breaker indicating lamps for CB open, CB close, CB auto trip, Trip circuit
healthy etc.
Set
vi.
Under voltage relay with timer
Set
vii.
Over voltage relay with timer
Set
viii.
Breaker control switch
Set
ix.
Auto-manual selector switch
Set
3.2
Bus Bar
630 Amps, 415 Volts TPN, 50KA uniform Aluminium busbars with color
coded heat shrinkable insulating sleeves.
3.3
Outgoing Feeders
630 Amps, 415 Volts, 50 KA, TPN, ACB with Thermomagnetic releases for
Short Circuit, Earth fault and Over Current protection along with adjustable
setting. Each breaker shall be fitted vertical with following accessories,
complete as required.
Nos
iii
The professional charges for liason work and departmental procedures
Lumpsum
required for the above said work .
TOTAL CARRIED OVER TO SUMMARY
SUPPLY
INSTALLATION
AMOUNT
DESCRIPTION
UNIT
G
L.V
SWITCHBOARDS
Design,
Assembling, Supply, Installation, Testing and Commissioning of following LV Switchboards and
Swithgears suitable for 415 Volts, 3 phase 4 wire, 50 Hz power distribution system. In conjunction with general
1)
All the Switchboards
shall be
Indoor
type,
and vermin
proof type
specifications
following points
should
also
be dust
considered
and adhered
to. compartmentalised design maintaining
IP 52 degree of protection.
2) Switchboards shall be free standing floor mounted or wall mounted as required.
3) All the Switchboards shall be of compartmenttalised with entire fabrication in 14 Guage Sheet Steel and
Powder
Coated
with
Siemens
gray through
paint shade
no.mm
RAL-7032
of IS-5.wire. Doors shall be pad locking type
4) All hinged
door
shall
be earthed
2.5 sq
tinned copper
whereas
MCCBand
compartments
they
openable
in switch
OFF mode.
5)
All thefor
busbars
links shall be
ofshould
copperbewith
colour only
coded
heat shrinkable
insulating sleeves. Separate
earth busbars shall be provided along the length of the switchboards.
6) All measuring instruments (Meters) shall be of digital electronic with LED display of approved make.
7) Adequate space for cable entries and terminations shall be provided refering SLDs. Cable entries can be
either from the top or bottom as required.
1
MAIN LT PANEL as per Schematis
Nos.
GROUND FLOOR PANEL as per Schematics
Nos.
FIRST FLOOR PANEL as per Schematics
COMMON SERVIE PANEL as per schematics
PLUMBING PANEL as per Schematics
FIRE FIGHTING PANEL as per Schematics
TOTAL CARRIED OVER TO SUMMARY
QUANTITY
1
1
SUPPLY
INSTALLATION
AMOUNT
SR. NO.
DESCRIPTION
UNIT
LT CABLING SYSTEM
Supplying, laying, testing and commissioning of 1100V grade XLPE type
steel wire/ tape armoured aluminium / copper conductor cables. The cables
shall be laid in cable trays, clamped on walls and in concrete trenches, with
suitable clamps and saddles fixing bolts etc. The cost of the cable trays or
ladders, excavation and back filling of trenches not to be included in this
scope.
3.5C x 240 sqmm A2XFY
Rm
3.5Cx 150 sqmm A2XFY
Rm
3.5Cx 50 sqmm A2XFY
Rm
for copper cables
a
4 C 16 sqmm 2XFY
Rm
4 C 6 sqmm 2XFY
Rm
4 C
4 sqmm 2XFY
Rm
3 C
2.5 sqmm 2XFY
Rm
3 C 4 sqmm 2XFY
Rm
3 C 6 sqmm 2XFY
Rm
Supplying and Installation of cable terminations for the above cables
including double compression type chrome plated brass glands and
bimetallic lugs (crimping type), PVC taping as required and all accessories
complete.
3.5C x 240 sqmm A2XFY
Nos.
3.5Cx 150 sqmm A2XFY
Nos.
3.5Cx 50 sqmm A2XFY
Nos.
4 C 16 sqmm 2XFY
Nos.
4 C 6 sqmm 2XFY
Nos.
4 C
4 sqmm 2XFY
Nos.
3 C
2.5 sqmm 2XFY
Nos.
3 C 4 sqmm 2XFY
Nos.
3 C 6 sqmm 2XFY
Supplying and Installation of Pregalvanised factory fabricated Perforated
type cable trays with 50mm height & 1.5 mm thick. The tray shall be
suspended from ceiling using anchor bolt and angle iron supports or
mounted from wall. The rate shall include all accessories like radial bends,
elbows, tees, coupler plates, etc., which will be measured as linear
measurement and fixing accessories.
150 mm wide single horizontal/vertical tier.
TOTAL CARRIED OVER TO SUMMARY
Nos.
Rm
QUANTITY
340
250
1450
300
250
75
20
60
20
8
2
10
4
12
8
4
12
SUPPLY
INSTALLATION
AMOUNT
250
SR. NO.
DESCRIPTION
POINT WIRING
Note: 1) Client reserves the right to supply the lighting fixtures, where
contractor shall be paid only for the installation.
UNIT
Supply of following Cu PVC FRLS Wires for point
wiring with Rmt(Quote for Wire Only)
Point wiring for all Light points using 2x2.5 + 1x1.5PE Cu PVC FRLS Wires
in 25 mm PVC conduits contactor shall be consider three to four circuits in
single conduits wherever possible from GF.LDB-1,GF LDB-2,FF LDB-1,FF
LDB-2 including of submains wiring.(Wire rates only)
Rm
Point wiring for all Light points using 2x2.5 + 1x1.5PE Cu PVC FRLS Wires
in 25 mm PVC conduits contactor shall be consider three to four circuits in
single conduits wherever possible from COMMON AREA DB including of
submains wiring.(Wire rates only)
Rm
Point wiring for all Light points using 2x2.5 + 1x1.5PE Cu PVC FRLS Wires
in 25 mm PVC conduits contactor shall be consider three to four circuits in
single conduits wherever possible from TERRAE LTG. DB including of
submains wiring.(Wire rates only)
Rm
Point wiring for all Light points using 2x2.5 + 1x1.5PE Cu PVC FRLS Wires
in 25 mm PVC conduits contactor shall be consider three to four circuits in
single conduits wherever possible from EXTERNAL AREA DB including of
submains wiring.(Wire rates only)
Rm
Supply,Installation,Testing of following power points
One 6 A Socket controlled by one 6 A Switch.(Half Point)
No
One 6 A Socket controlled by one 6 A Switch.(Individual Points)
No
One 16 A Socket controlled by one 16 A Switch.
No
POINTWIRING-WING-A(Quote for Wire Only)
Supply, Installation,Testing of One light point wiring from switchboard(1
switch controlled) to light point with 3x 1.5 insulated copper conductor 1100
volts grade stranded flexible FRLS wires in 25 mm PVC conduit concealed /
embeded in walls. This shall include installation of 6 A single way modular
switch, 2 mm thick GI concealed box and other accessories such as bends,
junction boxses, saddles, spacers, switch plates, angle holders, ceiling roses
etc. as required to complete the wiring.(Avg. point wiring length 6 mtr.)
No
ii
Supply, Installation,Testing of Two light point wiring from switchboard (1
switch controlled) to light point with 3x 1.5 insulated copper conductor 1100
volts grade stranded flexible FRLS wires in 25 mm PVC conduit concealed /
embeded in walls. This shall include installation of 6 A single way modular
switch, 2 mm thick GI concealed box and other accessories such as bends,
junction boxses, saddles, spacers, switch plates, angle holders, ceiling roses
etc. as required to complete the wiring.
No
iii
Supply, Installation,Testing of Three light point wiring from switchboard (1
switch controlled) to light point with 3x 1.5 insulated copper conductor 1100
volts grade stranded flexible FRLS wires in 25 mm PVC conduit concealed /
embeded in walls. This shall include installation of 6 A single way modular
switch, 2 mm thick GI concealed box and other accessories such as bends,
junction boxses, saddles, spacers, switch plates, angle holders, ceiling roses
etc. as required to complete the wiring.
No
iv
Supply, Installation,Testing of Four light point wiring from switchboard (1
switch controlled) to light point with 3x 1.5 insulated copper conductor 1100
volts grade stranded flexible FRLS wires in 25 mm PVC conduit concealed /
embeded in walls. This shall include installation of 6 A single way modular
switch, 2 mm thick GI concealed box and other accessories such as bends,
junction boxses, saddles, spacers, switch plates, angle holders, ceiling roses
etc. as required to complete the wiring.
No
Supply, Installation & Testing of Ceiling Fan point wiring from switch boards
to fan points with 3 x 1.5 sq.mm PVC insulated copper conductor 1100
volts grade stranded flexible FRLS wires in 25 mm heavy duty concealed
PVC conduits.These points shall be controlled by 6 amps single pole
modular flush mounted switch from local switch board and an electronic
type regulator. This shall include 2 mm thick GI concealed box, fan box with
hook and other accessories such as socket type 5 step electronic regulator,
modular switches & switch boards, holders, ceiling rose, etc. as required to
complete the wiring. (Avg. Point Length 6 mtrs.)
No
vi
Supply, Installation & Testing of Exhaust fan point wiring with 3 x 1.5 sq.mm
PVC insulated copper conductor 1100 volts grade stranded flexible
FRLS wires in 25 mm heavy duty concealed PVC conduits. These 6 A
sockets points shall be controlled by 6 amps single pole modular flush
mounted switch on the switchboard. This shall include 2 mm thick GI
concealed box and other accessories such as modular switches, sockets &
switch boards, holders, ceiling rose, etc. as required to complete the wiring.
(Avg. Point length 6 mtrs.)
No
vii
Supply, Installation and testing of Light point wiring from common lighting
DBs &External Ltg. DB. to light point with 2 x 2.5 + 1x 1.5 sq.mm PVC
insulated copper conductor 1100 volts grade stranded flexible FRLS
wires in concealed or on surface 25mm PVC conduits.These points shall be
controlled by MCB in distribution board. This shall include holders, holder
box, connectors etc. as required to complete the wiring. (for Staircase, ,
Ground ,Common area,External area ltg.)
1 LP controlled by 1 MCB
No.
2 LP controlled by 1 MCB
Nos.
3 LP controlled by 1 MCB
Nos.
4 LP controlled by 1 MCB
Nos.
5 LP controlled by 1 MCB
Nos.
6 LP controlled by 1 MCB
Nos.
7 LP controlled by 1 MCB
Nos.
8 LP controlled by 1 MCB
Nos.
9 LP controlled by 1 MCB
Nos.
10 LP controlled by 1 MCB
Nos.
viii
Supply, laying and fixing of following Precision make (HMS) PVC conduits
embedded in the RCC slab at the time of slab casting. This shall include all
the accessories such as sockets, bends, binding wire, etc. and every thing
as required to complete the conduiting.
20 mm PVC Conduits
Rm
25 mm PVC Conduits
Rm
32 mm PVC Conduits
Rm
TOTAL CARRIED OVER TO SUMMARY
QUANTITY
SUPPLY
INSTALLATION
AMOUNT
3,000
86.00
40.00
378,000.00
3,600
86.00
40.00
453,600.00
1,300
86.00
40.00
163,800.00
2,000
86.00
40.00
252,000.00
168
290.00
80.00
62,160.00
36
620.00
200.00
29,520.00
360.00
100.00
2,300.00
172
470.00
150.00
106,640.00
17
700.00
230.00
15,810.00
84
940.00
300.00
104,160.00
RO
1,175.00
375.00
1,550.00
238
1,050.00
180.00
292,740.00
45
470.00
150.00
620.00
RO
705.00
235.00
940.00
1,055.00
353.00
1,408.00
1,410.00
470.00
7,520.00
1,760.00
588.00
7,044.00
2,115.00
705.00
25,380.00
12
2,465.00
823.00
39,456.00
11
2,820.00
940.00
41,360.00
19
3,170.00
1,058.00
80,332.00
3,525.00
1,175.00
23,500.00
3,878.00
1,293.00
20,684.00
RO
49.00
16.00
65.00
5000
62.00
18.00
400,000.00
RO
111.00
22.00
133.00
2,510,722.00
SR. NO.
DESCRIPTION
DISTRIBUTION BOARDS
Supply, Installation, Testing and Commissioning of the following Distribution Boards
fabricated in sheet steel with phase copper bus bars, neutral and earth bar with
tapped holes, cutouts for operating the MCB knobs in the inner cover, bakelite
phase barriers, double door construction, powder coated with approved shade and
partitions to segregate phases etc. DB's shall be suitable for single phase/3 phase
operation. DB's shall be flush mounted to brick wall or surface mounted as
required.(IP-43)
UNIT
Distribution Board -(with separate neutral links) (For External Ltg.)
12 Way TPN DB
Incomer 63A, 10 KA, TPN ,MCB+ELCB(30mA) - 1 no.
Outgoing 10 Amps, 10 KA, SP MCBs - 25 nos.
16 Amps, 10 KA, SP MCBs - 2 nos.
Nos.
ii
Distribution Board - (with separate neutral links) (For Common Area Ltg)
12 Way TPN DB
Incomer 63A, 10 KA, TPN ,MCB+ELCB(30mA) - 1 no.
Outgoing 10 Amps, 10 KA, SP MCBs - 36 nos.
Nos.
iii
Distribution Board -(with separate neutral links) (For Terrace Ltg.)
4 WAY TPN DB
Incomer 20 Amps, TPN MCB+ELCB(30mA) - 1 nos.
No.s
Outgoing 10 Amps, 10 KA, SP MCBs - 12 nos.
iv
Distribution Board -(with separate neutral links) (For Ground floor DB-1.)
6 WAY TPN DB
Incomer 63 Amps, TPN MCB+ELCB, (30mA )- 1 nos.
No.s
Outgoing 10 Amps, 10 KA, SP MCBs - 3 nos.
16 Amps, 10 KA, SP MCBs - 15 nos.
v
Distribution Board -(with separate neutral links) (For Ground floor DB-2.)
8 WAY TPN DB
Incomer 63 Amps, TPN MCB+ELCB, (30mA )- 1 nos.
No.s
Outgoing 10 Amps, 10 KA, SP MCBs - 8 nos.
16 Amps, 10 KA, SP MCBs - 14 nos.
vi
Distribution Board -(with separate neutral links) (For First floor DB-1.)
6 WAY TPN DB
Incomer 63 Amps, TPN MCB+ELCB, (30mA )- 1 nos.
No.s
Outgoing 10 Amps, 10 KA, SP MCBs - 2 nos.
16 Amps, 10 KA, SP MCBs - 16 nos.
vii
Distribution Board -(with separate neutral links) (For First floor DB-2.)
8 WAY TPN DB
Incomer 63 Amps, TPN MCB+ELCB, (30mA )- 1 nos.
Outgoing 10 Amps, 10 KA, SP MCBs - 4 nos.
16 Amps, 10 KA, SP MCBs - 16 nos.
TOTAL CARRIED OVER TO SUMMARY
No.s
QUANTITY
SUPPLY
INSTALLATION
AMOUNT
SR. NO.
K
A
DESCRIPTION
UNIT
QUANTITY
Nos.
Nos.
Nos.
1
1
ELV SYSTEM
TELEPHONE SYSTEM
Supply, Installation, Testing and Commissioning of
following Krone make Main Distribution Frame (MDF)
protector panel for the service providers incoming
lines.The panel shall have provision for both top and
bottom cable entry.
30 Pair MDF
Supply, installation, testing and commissioning of Krone
make Cable termination block prepackaged with wiring
block with legs, insert labels, label holders, jumper
troughs, metal back panel, duct assembly, wire
managers for distribution, screws, washers and an
instruction sheet for termination of incoming pairs.
a
b
20 Pair krone Cable termination block
5 Pair krone Cable termination block
Supply, installation, testing and commissioning of Jelly
filled Arm Telephone Riser cable consisting of multiple
core solid copper conductors of 24 AWG size insulated
with expanded polyethylene covered with a PVC skin
and inner shielding for grounding. The core shall be
covered by a layer of plastic tape and overlaid with a
corrugated PVC plastic. The cable shall be as per
specifications laid down in the tender.
a
b
20 pair Riser Cable
5 Pair Riser Cable
Rm
Rm
30
35
Supply, installation, testing and commissioning of 4 pair
Category 6 cable consisting of 24 AWG solid copper
conductors through 25mm rigid pvc conduit and as per
the specification. The cable shall have flexible jacket
and ripcord for easy stripability
Rm
200
Single outlet faceplate with RJ-11 jack
Nos.
10
Nos.
DATA NETWORKING SYSTEM
Supply, installation, testing and commissioning of 12 port
Ethernet central switch(JACK PANEL) as per schematic
Supply, installation, testing and commissioning of
following Ethernet work station switch as per
specification.
SUPPLY
a
b
16 Port Switch
8 Port Switch
Nos.
Nos.
1
RO
Supply and installation of following sizes Racks with all
accessories & wire managers
a
b
c
12 U Rack
9 U Rack
6 U Rack
Nos.
Nos.
Nos.
RO
RO
RO
Supply, installation, testing and commissioning of
Category 6 LAN cable consisting of 24 AWG solid copper
conductors and as per the specification. The cable shall
have flexible jacket and ripcord for easy
Stripability(Laying of cable through tray)
Rm
250
Supply,Installaton,Testing and Commissioning of Single
outlet faceplate with RJ-45 UTP information Outlets.The
price shall include 2 mm thick GI boxes, inner plates,
outer plates etc.
Nos.
11
TOTAL CARRIED OVER TO SUMMARY
INSTALLATION
AMOUNT
SR. NO.
DESCRIPTION
UPS SYSTEM
Supply, Installation, testing and commissioning of 7.5KVA UPS System
complete with the required accessories as specified in the drawings & the
specifications called for.
15 Minutes Battery Back-up for the 7.5KVA UPS system complete with the
required accessories
TOTAL CARRIED TO SUMMARY
UNIT
QUANTITY
No
SUPPLY
INSTALLATION
AMOUNT
SR. NO.
DESCRIPTION
UNIT
LIFT SYSTEM
Hoist way maintenance Lighting and Power for LIFT-1 including supply &
intallation of I) 1# 5/15A Switch Socket per Floor ii)1# 60w Bulkhead Light
Fixture iii)1# 5A switch to control Bulkhead Light Fixture iv) Conduit Wiring for
above using 3# 2.5 Sq.mm Cu wires in PVC Conduit with termination of
cables & junction box.
No
TOTAL CARRIED TO SUMMARY
QUANTITY SUPPLY
INSTALLATION
AMOUNT
SR. NO. DESCRIPTION
UNIT
QUANTITY
CHEMICAL EARTHING
Supply, Installing, Testing and Commissioning of CU earthing
with 32 x 6 mm CU strips from earth electrode to inspection
chamber, 50 mm dia CU pipe with 3 mtr long and surrounding
area will be filled by BACKFILL COMPOUND. Prices should
include 6'' dia bore, back filling, masonry chamber 500 x 500
mm with concrete base, cast Iron cover, test links, disconnecting
link etc.
Nos.
Supply, Installing, Testing and Commissioning of GI earthing
station with 32 x 6 mm GI strips from earth electrode to
inspection chamber, 50 mm dia GI pipe with 3 mtr long and
surrounding area will be filled by BACKFILL COMPOUND.
Prices should include 6'' dia bore, back filling, masonry chamber
500 x 500 mm with concrete base, cast Iron cover, test links,
disconnecting link etc.
Nos.
Supply, Installing, Testing and Commissioning of GI earthing
station with 25 x 3 mm GI strips from earth electrode to
inspection chamber, 50 mm dia GI pipe with 3 mtr long and
surrounding area will be filled by BACKFILL COMPOUND.
Prices should include 6'' dia bore, back filling, masonry chamber
500 x 500 mm with concrete base, cast Iron cover, test links,
disconnecting link etc.
Nos.
17
Supply, Installing, Testing and Commissioning of CU earthing
with 25x 3 mm CU strips from earth electrode to inspection
chamber, 50 mm dia CU pipe with 3 mtr long and surrounding
area will be filled by BACKFILL COMPOUND. Prices should
include 6'' dia bore, back filling, masonry chamber 500 x 500
mm with concrete base, cast Iron cover, test links, disconnecting
link etc.
Nos.
Supplying and laying earthing conductors of Copper / GI strips
including necessary accessories, clamping to walls, cables
etc.as required and interconnection between lengths as per
specifications and as per good installation practice. Prices
should include all supports, accessories and hardware
necessary for proper installation.
32 x 6 mm thick CU Strip
Rm
120
ii
32 x 6 mm thick GI Strip
Rm
120
iii
25 x 3 mm thick CU Strip
Rm
85
iv
25 x 3 mm thick GI Strip
Rm
400
8 SWG CU Wire
Rm
320
TOTAL CARRIED OVER TO SUMMARY
CHEMICAL EARTHING
SUPPLY
INSTALLATION
AMOUNT
SR. NO.
DESCRIPTION
Note: 1) Client reserves the right to supply the lighting fixtures, where
contractor shall be paid only for the installation.
LIGHTING FIXTURES
UNIT QUANTITY
Installation, testing and commissioning of following type of light fixtures as per
drawings and specifications with all other accessories such as supporting rods /
frames, anchor fasteners, necessary hardware etc. The rate shall include for
fittings along with transformers where required, diffuser, chokes, starter, power
factor improvement capacitors, wires, downrods etc., complete with all
accessories to complete the installation as required.
a
2X36 W TUBE LIGHT/CFL
Nos.
804
1X 28W WALL LIGHT
Nos.
139
DOWN LIGHT
Nos.
1x36 W WALL MOUNTED LIGHT
Nos.
134
70 W POLE LIGHT
Nos.
48
FOOT LIGHT
Nos.
72
TOTAL CARRIED OVER TO SUMMARY
SUPPLY INSTALLATION
AMOUNT
SR. NO.
DESCRIPTION
UNIT
QUANTITY
LIGHTNING PROTECTION
Supply and Installation of Early strimer lightning arrestor for protection of
building-Radius 79Mtr. This shall include the cost of mast of 5mtr height,
lightning event counter, fixing hardware etc.
Nos.
TOTAL CARRIED OVER TO SUMMARY
SUPPLY
INSTALLATION
AMOUNT