TM1600
Circuit Breaker Analyzer
TM1600
Circuit Breaker Analyzer
Stand-alone functionality one toolbox
for all breaker testing
Expandable modular concept
Low-weight
Rugged and reliable for field use
Description
The TM1600 circuit breaker analyzer measures a circuit breakers timing cycle. The timing channels record closings and openings
of main contacts, resistor contacts and auxiliary contacts.
Since the timing channels are not interconnected, you can take
measurements of resistor contacts and series-connected breaker
chambers without having to disconnect them.
A built-in program unit permits easy selection of different sequences of breaker control pulses. The delay time between pulses
is set on a thumbwheel. The breaker operation unit can be used to
control coil currents of up to 25A. The time values obtained refer
to the exact instant at which voltage was applied to the coil, and a
built-in printer provides you with a hardcopy printout immediately
after measurement.
The TM1600 can be equipped with up to 24 time-measuring
channels as required by the user. When more than 24channels are
needed, one or several units can be connected together to get an
unlimited number of measurement channels. Modular design also
makes it easy to combine the system with the MA61 Motion
Analyzer for up to 6 analog channels.
The TM1600 supports communication with the CABA Win
Breaker Analysis Software. Fully equipped, it weighs only 12 kg
(26.5 lbs).
TM1600
Circuit Breaker Analyzer
Application example
1. Setup
A
typical breaker test hookup is shown in the figure below.
2. Preparation
Set
the desired breaker operating sequence on the TM1600.
In this case, CLOSE-OPEN (C-O).
3. Recording
Enable
recording with the READY button. Start the breaker
sequence and measurement simultaneously by turning the
START switch.
4. Test report
The
result is printed automatically. This example shows
a CLOSEOPEN (C-O) sequence presented in the report 1
format (85 % of actual size). Only the initial contact closing
time (for CLOSE) and final contact separation time (for
OPEN) are presented in the report 1 format. Short bounces
are not shown.
Timing with motion recording
1. Setup
Connect
the transducers to the circuit breaker.
2. Preparation of the MA61
The following additional settings are needed when you include
motion recording in circuit breaker analysis. These settings are
menudriven via the built-in display on the MA61.
Select
test interval (50 ms to 1 s).
Calibrate
the input(s) connected to the position
transducer(s) as follows:
a) Close the circuit breaker.
b) Record the closed position via a menu option.
c) Open the circuit breaker.
d) Record the open position.
e) Estimate or measure breaker stroke. Enter the value via
the menu.
f) Enter speed calculation parameters.
Enter
the current range and the scale factor for the current
shunt if current is to be measured.
Space for userentered header
info
Space for user-entered comments
Digital printout
Diagram printout
Closing circuit
Trip circuit
Ready
Start
TM1600
Circuit Breaker Analyzer
Enter
range and scale factor for other transducers (if used).
3. Recording
Press
the READY button to prepare the TM1600 for
measurement.
Turn
the START knob. Travel measurement, time
measurement and the breaker sequence all start
simultaneously. The inputs now record the input voltages
obtained from the connected transducers.
4. Test report
The
motion recording report includes both curves and a
table. The table presents calculated breaker parameters
such as closing speed, opening speed, overtravel and
penetration.
User-entered
header info
The
diagram shows one or more time/amplitude curves
and the calculated breaker parameters. The time axis scale
factor can be changed to provide you with a quick overview
or an enlarged view of part of the diagram.
The
position of the curve in the diagram and the amplitude
scale factor can also be changed to make best use of the
available space.
The
damping and speed variations at closing and opening
times can be studied on the speed curve obtained from each
of the motion-monitoring channels.
Date and time of
measurement start
Session number incremented
automatically for each recording
Digital printout
Settings for the
speed calculations
Calculated circuit
breaker
parameters
Settings for this
recording
Settings for this
printout
Close pulse
Main contacts
Trip pulse
Auxiliary contact
trip circuit
Auxiliary contact
close circuit
Printout provided
by built-in printer.
TM1600
Circuit Breaker Analyzer
1. PARKING TERMINALS. Safety terminals for breaker
control wires. Not connected to internal circuits.
2. OPEN DELAY. Trip pulse delay setting. Pulse delay is measured from the start of the previous pulse. 10 ms resolution.
3. CLOSE DELAY. Closing pulse delay setting.
Pulse delay is measured from the start of the previous pulse.
10ms resolution.
4. Breaker control outputs. Two separate contact functions.
5. Fuses for breaker control outputs.
6. Power ON/OFF Power-ON lamp. Flashing = Low battery
7. Earth (ground) connection
8. TRIG OUT. Output for synchronous start of other equipment. Short-circuits the terminals at instant of triggering. Used
when several TM1600s are used together.
9. REMOTE START input. External short-circuit provides same
result as turning the start switch (item 16).
10. PRINT MODE. Report format selector switch.
11. Printer START/STOP and PAPER FEED button. Paper feed
if pressed longer than 1 s.
12. Timing channel input terminals.
13. Timing channel mode switch.
Contact mode: 0-250
Resistor contact mode: 0-3 k
Voltage mode: 12-250 V unpolarized
14. Motion Analyzer MA61.
15. Breaker operation SEQUENCE selector switch.
C = Close, O = Open
16. START of breaker operation and recording switch.
Recording starts only if the Ready lamp is on.
17. READY for measuring button. Enables the timing channels.
1st touch: Prepares for normal recording. Enables the timing
channels throughout 90 s.
2nd touch: Provides long-term monitoring (optional).
18. TRIG. Input for external start of recording. Recording starts if
the READY lamp is on.
Contact mode: 0-250
Voltage mode: 12-250 V unpolarized
19. READY lamp.
Steady light: Ready for normal recording.
Slow flash: Ready for long term monitoring (optional).
Fast flash: Measurement in progress.
10 11
4
12 13
14
5 6
15 16 17 18 19
TM1600
Circuit Breaker Analyzer
MA61 Motion Analyzer
The MA61 Motion Analyzer is an excellent supplement to the
TM1600. It combines the easy readability of an oscillograph with
the extra accuracy ensured by computerized measurement and
computer-processed readings. Menu-driven button selection via
the built-in display makes operation simple and easy.
The MA61 can be equipped with up to 6 analog channels, and
it can be easily adapted to the different measurement requirements for high-voltage circuit breaker testing. It can measure and
calculate contact paths and the speeds at which breaker contacts
operate as well as the current in operating coils. It can also measure
dynamic resistance (DRM), voltage, pressure, vibration signals and
other analog entities.
After measurement, the MA61 performs the necessary calculations
and prints results in both diagram and table form via the TM1600s
built-in printer. Moreover, parts of curves can be easily enlarged
for closer study.
TM1600 Basic Unit with four time-measuring channels, BL39091
MA61 Basic Unit with two analog channels, BL-12092
The MA61 incorporates a battery-backed memory that can store
up to ten measurements for subsequent processing.
CABA Win
CABA Win is a circuit breaker analysis software designed to be
used with the TM1600/MA61. CABA Win organizes all the test
tasks and ensures that measurements are conducted in the same
way for each object being tested.
CABA Win saves the results and generates the report. In the analysis section, you can work with a number of graphic windows, compare different measurements by overlaying one graph on another
in the same display, and use cursors and powerful zoom functions
for detailed analysis. CABA Win simplifies testing and ensures the
quality of the test procedure.
Fully equipped TM1600 with 16 time-measuring channels
and MA61 with six analog channels, BL-39098
Movement starts
Motion curve
Lenght of arcing contact
Current
Main contact opens
Arcing contact opens, current drops
and resistance infinite
Resistance curve
DRM is a reliable method to estimate the length/wear of the arcing contact. The SDRM202 provides high current and the
TM1600 gives an accurate measurement with very good resolution.
TM1600
Circuit Breaker Analyzer
Specifications TM1600
Specifications are valid at nominal input voltage and an ambient
temperature of +25C, (77F). Specifications are subject to change
without notice.
Environment
Application field
Operating temperature
TM1600
MA61
Storage temperature
TM1600
MA61
Humidity
The instrument is intended for use in
medium and high-voltage substations
and industrial environments.
-20 to +50C (-4 to +122F)
-10 to +50C (+15 to +122F)
-30 to +70C (-22 to +158F)
-30 to +85C (-22 to +185F)
5% 95% RH, non-condensing
Contact functions
Contact properties
Two independent contact functions
Bounceless closing. Closing time < 0.1
ms
Sequences
C, O, C-O, O-C, O-C-O
Make / break capacity
25 A, 250 V (AC or DC) per contact
function
Start breaker operation Locally via rotary switch or remotely by
closing contacts at the opto-isolated
start input.
Time difference
< 0.1 ms
between control pulse
and timer start
Pulse delay
Adjustable in steps of 10 ms
Printout
Types of printout
CE-marking
EMC
LVD
2004/108/EC
2006/95/EC
General
Mains voltage
Power consumption
Battery operation
Dimensions
TM1600 Basic Unit
Transport case
Weight
TM1600 Basic Unit
Time-measuring
module
MA61
Transport case
Complete TM1600/
MA61
85-270 V AC or 100-270 V DC (set automatically), 47-63 Hz
150 W (max)
Built-in battery with automatic charger
400 x 250 x 153 mm
(15.7 x 9.8 x 6.0)
520 x 485 x 210 mm
(20.5 x 19.1 x 8.3)
Printer
Graphic resolution
Paper width
Time-measuring module
No. of channels
Time-measuring channels
6.5 kg (14.3 lbs)
0.6 kg (1.3 lbs)
Time-measurement at
main contacts
1.1 kg (2.4 lbs)
5.1 kg (11.2 lbs)
12 kg (26.5 lbs). 20 kg (44.1 lbs) with
accessories and transport case.
Time-measurement at
resistor contacts
Voltage detection
Time measurement
Maximum configuration: 24 time-measuring channels (6 time
measuring modules) or 16 time-measuring channels and six analog channels (4 time-measuring modules and one MA61).
Range
0 to 6.5 s (up to 1000 s with CABA)
Resolution
0.1 ms
Inaccuracy
0.01% of printed value 0.1 ms
Start time
Automatic a) when breaker is operated
measurement
from the TM1600, b) when an external
event actuates the trigger input or c)
optionally when the status of any timemeasuring channel is changed.
Trigger input
Independent input with its own voltage
source. Measurement starts when voltage is detected or when contacts close.
Same data as for time-measuring channel when it is in the contact-measuring
state or voltage detection state.
Trigger output
Closing capacity, up to 1 A
Breaker operation
Protection of inputs
against transients
Induction protection
4
Each channel is independent of the
others and has its own limited-current
DC voltage source. Each channel can be
set to measure main contacts, resistor
contacts or to detect voltage. The input
circuits are provided with 2.5 kV optoisolators.
0 to 250 . Test voltage is about 25 V.
Measurement current is limited to about
150 mA.
250 to 3 k. Test voltage is about 50
V. Measurement current is limited to
about 30 mA.
12 to 250 V. Detection indicates that voltage is present. Independent of polarity.
Provides a load of at least 3 W.
All inputs have protective diodes. 18 kW,
8/20 s between sockets and 4.8 kW,
8/20 s between socket and ground.
Capacitive discharge to ground.
Max 15mA per input.
Specifications MA61
No. of channels
Measurement ranges
Transducer resistance
Voltage
Measurement resolution
Basic inaccuracy
Dynamic errors
Motion
Speed
Time-base inaccuracy
Measurement interval
Sampling
frequency
Display
A number of different printout formats
are available, both graphic and numeric.
Printout can be obtained in English, German, French, Spanish, Italian, Swedish
or Finnish.
Thermal printer with fixed print head
8 dots/mm (203 dpi)
114 mm (4.5)
2, 4, 6
100 to 10 k
-4 to +4 V
0.03% (0.006% optional)
0.5%
1%
3%
0.02%
50, 100, 200, 400 or 1000 ms, user
selectable (up to 200 s with CABA)
1-20 kHz (40 kHz optional)
Back-lit LCD, two 16-character lines
TM1600
Circuit Breaker Analyzer
Accessories
Vibration kit, BL-13090
Includes: SCA606, CABA Win Vibration software and one
Vibration transducer kit
Vibration transducer kit, XB-32010
Includes: Cable SCA606/COAX, Transducer DYTRAN 3200B5,
Cable DYTRAN, Cable XLRF/XLRM 1m and Transducer kit VIB.
SDRM202
SDRM Cable
TM1600
Circuit Breaker Analyzer
Rotary transducer, Novotechnic IP6501 (analog)
Rotary transducer mounting kit, XB-51010
Linear transducer, LWG 150
Voltage divider, VD401
Switch magnetic base
Universal support
Cable XLR, GA-00760
Extension cable XLR, GA-01005
Linear transducer, TLH 225
Linear transducer, TS 25
Cable reels, 20 m (65.5 ft), 4 mm stackable safety plugs
TM1600
Circuit Breaker Analyzer
Ordering information
Item
Art.No.
Item
Description
TM1600
Optional Accessories
The TM1600/MA61 Breaker Analyzer System can be
equipped with time-measuring and analog channels
as desired. The TM1600 Basic Unit includes two
rolls of thermal printer paper, 2.5 m (8.2 ft) power
cord, transport case and ground cable.
Software and application kits
TM1600/4
Basic Unit with 4 timing channels
CABA Win Circuit Breaker analysis software
CABA Win
BL-39091
CABA Win upgrade
BL-39092
TM1600/12
Basic Unit with 12 timing channels
BL-39093
TM1600/16
Basic Unit with 16 timing channels
BL-39094
TM1600/20
Basic Unit with 20 timing channels
BL-39095
TM1600/24
Basic Unit with 24 timing channels
BL-39096
Separate module
With four time-measuring channels
BL-19010
MA61
Each of the MA61/2-6 includes:
One shielded cable/channel, 1 m (3.3 ft) (with
female XLR connectors and bare-wire ends)
One shielded cable/channel 7.5 m (24.6 ft), (with
male and female XLR connectors)
One shielded cable, 1 m (3.3 ft) with female XLR
connectors an 4 mm safety plugs
BL-12092
MA61/4
MA61 Basic Unit with 4 analog channels
BL-12094
MA61/6
MA61 Basic Unit with 6 analog channels
BL-12096
Separate module
With two analog channels
BL-12010
Upgrade to latest version
CG-8010X
Vibration kit
The Vibration kit extends
TM1600 and CABA Win with
the equipment and software
required for recording and
analyzing vibration signals at a
circuit breaker. The kit includes
the signal conditioning unit
SCA606, the software CABA
Win Vibration and one Vibration
transducer kit. The vibration
solution can be extended up to
BL-13090
6 channels.
Vibration transducer kit
Additional Vibration transducer
kit to be used together with the
Vibration kit. Each Vibration
transducer kit includes accelerometer, accelerometer adapter,
cables to SCA606 and cables to
XB-32010
TM1600.
SSR kit incl.
accessories, software and cables
SSR kit for TM1600 (incl. VD401)
BL-91200
(delivered in transport case)
Static and Dynamic Resistance Measurement
SDRM202
MA61S
High speed (40 kHz/14 bit) measurement module for
BL-12020
vibration measurements with 2 analog channels.
TM1600/MA61
Basic unit includes two rolls of thermal printer
paper, 2.5 m (8.2 ft) power cord, transport case and
ground cable.
Basic unit with 16 time-measuring channels,
6analog channels and CABA Win
Incl. accessories (see MA61)
BL-8203X
Synchronized Switching Relay test kit
MA61/2
MA61 Basic Unit with 2 analog channels
Basic unit with 16 time-measuring channels,
4analog channels and CABA Win
Incl. accessories (see MA61)
incl. fiberoptics and USB interface
Vibration analysis
TM1600/8
Basic Unit with 8 timing channels
Basic unit with 16 time-measuring channels,
2analog channels and CABA Win
Incl. accessories (see MA61)
Art. No.
The SDRM202 uses new technology, patent pending, with
ultra capacitors. The current
output is up to 220 A from a
box that weighs only 1.8 kg
(4lbs). The weight of the current
cables is also low because the
SDRM202 is placed very close to
the circuit breaker. Timing M/R
measurement can be done with
CG-90200
the same hook-up
SDRM202 Pack of Pack for CB with 2 Breaks /
3 units
Phase
Extension cable
SDRM202
BL-39192
BL-39098
GA-12815
10 m (33 ft)
GA-12810
Transducers Linear
TLH 500
BL-39194
CG-90230
7.5 m (24.6 ft)
500 mm (20) travel Incl. cable
0.5 m (20)
XB-30020
LWG 225
225 mm (9) travel Incl. cable
0.5m (20)
XB-30117
TS 150
150 mm (5.9) travel Incl. cable
1.0 m (39)
XB-30030
TS 25
25 mm (1) travel Incl. cable
1.0m (39)
XB-30033
TM1600
Circuit Breaker Analyzer
Ordering information
Item
Description
Art. No.
Item
The above transducers are also available in other
lengths, please contact Megger for more information.
XLR to 4 mm
safety plugs
Transducers Rotary
VD401
Incl. cable 1 m (39), 6 mm Flex
coupling, Hexagon wrench
XB-31010
Flex coupling for
IP6501
For shaft diam. 6 mm
XB-39030
PIR adapter
Transducer mounting kits
Universal kits
Universal transducer mounting
kit
XB-51010
HPL/BLG Kit
(ABB)
Incl. mounting kit XB-51010,
Software conversion table
BL-8720X
GA-00040
Voltage divider, ratio 400/1 (for
TM1600 with analog channel)
BL-90070
XB-61010
XB-61020
Used to test circuit breakers with
pre-insertion resistors when
resistance is lower than 250
or higher than 3000 . There
are two versions:
BL-90080
PIR, 15 250
BL-90082
Current sensor kit 1 channel
(Fluke 80i-110s incl. cable
GA-00140)
BL-90600
Current sensor kit 3 channels
(Fluke 80i-110s incl. cables
GA-00140)
BL-90610
Thermopaper
114 mm, 30 m
GC-00030
Cable organizer
Velcro straps, 10 pcs.
AA-00100
For linear and rotary transducers XB-51020
Incl. mounting kit XB-51010,
Software conversion table
BL-8730X
For customized analog transducer connection
PIR2, 90 4500
Current sensor
Circuit breaker specific kits
LTB Kit (ABB)
Art. No.
Other
Novotechnic
IP6501
Rotary transducer For transducers XB-31010 and
mounting kit
XB-39130
Description
For more information about optional accessories please contact
Megger Sweden AB.
Ready-to-use kits Rotary
1-phase kit
Incl. transducer XB-31010,
mounting kit XB-51010
XB-71010
3-phase kit
Incl. 3 x 1-pase kits XB-71010
XB-71013
Transducer mounting accessories
Universal support
XB-39029
Switch magnetic
base
XB-39013
Cables
Cable reel
20 m (65.5 ft),
4 mm stackable
safety plugs
Black
GA-00840
Red
GA-00842
Yellow
GA-00844
Green
GA-00845
Blue
GA-00846
Extension cables,
XLR female to
male
For analog input, 10 m (32.8 ft)
GA-01005
Open analog
cable
For customized analog transducer connection
GA-01000
SWEDEN
Megger Sweden AB
Eldarvgen 4, Box 2970
SE-187 29 TBY
T +46 8 510 195 00
F +46 8 510 195 95
E seinfo@megger.com
UK
Archcliffe Road Dover
CT17 9EN England
T +44 (0) 1304 502101
F +44 (0) 1304 207342
Other Technical Sales Offices
Dallas USA, Norristown USA,
Toronto CANADA, Trappes FRANCE,
Oberursel GERMANY, Johannesburg
SOUTH AFRICA, Kingdom of BAHRAIN
Mumbai INDIA, Chonburi THAILAND
Sydney AUSTRALIA
Registered to ISO 9001 and 14001
Subject to change without notice.
Art.No. ZI-BL13E Doc. BL1053AE 2010
TM1600_DS_en_V03
www.megger.com
Megger is a registered trademark