Universal Consultancy Services
CTG BUILDING HVAC CALCULATION
R0 08-02-2010
01 27-01-2010
00 13-01-2010
Rev.
Released for Construction
Incorporating with FTI comments
Date
Description
UCS
UCS
UCS
UCS
UCS
UCS
DSGN
CHKD
APPD
Project Title:
Al Qatrana Power Project
The Hashemite Kingdom of Jordan
The Ministry of Energy and Mineral Resources
Owner :
Owners Technical advisor :
EPC Contractor :
Engineering Company:
Sub-Vendors Name:
Project No.
3480870001
Document No.
Job No.
-
Scale
-
Sheet No.
-
KP-170-28-001
Sub-Contractor Document No.:
Sub-Supplier:
Tel. + 962.6. 55 29 476
Fax. + 962.6. 55 22 476
P:\U00-238-03\calcs\mech\CTG\CTG HVAC CALCULATION (17-04-2010).rtf
Email: info@ucs-jo.com
Page 1 of 18
Universal Consultancy Services
CONTENTS
Section 1
i.
ii.
iii.
Section 2
i.
ii.
Section 3
i.
Section 4
i.
ii.
Section 5
i.
Section 6
i.
ii.
iii.
Section 7
i.
ii.
iii.
iv.
v.
vi.
General Information
General Project Information
Applicable Codes, Standards and References
Calculation Method
Design Parameters
Weather Data
Indoor Criteria
HVAC Systems Designation
System Definition
Overall Heat Transfer Coefficients (U Factors)
U Value Summary
U Value Detailed Calculations
Outdoor Air Sizing
Outdoor Air Sizing
Calculation Input Data
Space Input Data
Schedule Input Data
System Input Data
Calculation Results
Results Summary
Air System Sizing Summary
Zone Sizing Summary
System Design Load Summary
Space Load Summary
Results Calculation
Tel. + 962.6. 55 29 476
Fax. + 962.6. 55 22 476
P:\U00-238-03\calcs\mech\CTG\CTG HVAC CALCULATION (23-01-2010).rtf
Email: info@ucs-jo.com
Page 2 of 20
Universal Consultancy Services
SECTION 1
GENERAL INFORMATION
Tel. + 962.6. 55 29 476
Fax. + 962.6. 55 22 476
P:\U00-238-03\calcs\mech\CTG\CTG HVAC CALCULATION (23-01-2010).rtf
Email: info@ucs-jo.com
Page 3 of 20
Universal Consultancy Services
i.
GENERAL PROJECT INFORMATION
ii.
: Al Qatrana Power Project
: Jordan - Qatrana
: Steam Turbine Generator
APPLICABLE CODES, STANDARDS & REFERENCES
iii.
Project
Location
Building
ASHRAE ( American Society of Heating, Refrigerating and Air Conditioning Engineers).
Jordanian National Code.
HVAC CALCULATION METHOD
Supplied air flow rate for a space is determined by the zone load requirements, any possible makeup
air needs due to direct exhaust and pressurization requirements. Outdoor air quantity of spaces
is determined as per applicable standard to maintain acceptable indoor air quality in the space.
The software programs used for load calculation are Carrier E20-II / HAP V.4.40 & Carrier E20-II / Block Load V.3.05.
Tel. + 962.6. 55 29 476
Fax. + 962.6. 55 22 476
P:\U00-238-03\calcs\mech\CTG\CTG HVAC CALCULATION (23-01-2010).rtf
Email: info@ucs-jo.com
Page 4 of 20
Universal Consultancy Services
SECTION 2
DESIGN PARAMETERS
Tel. + 962.6. 55 29 476
Fax. + 962.6. 55 22 476
P:\U00-238-03\calcs\mech\CTG\CTG HVAC CALCULATION (23-01-2010).rtf
Email: info@ucs-jo.com
Page 5 of 20
Universal Consultancy Services
i.
WEATHER DATA
As per 2006 ASHRAE Fundamentals Handbook design condition for Amman
Latitude
: 31.98 N
Daily Range
: 11.3 C
 Outdoor Design Conditions ( Ventilation system ):
The maximum outdoor temperature considered for design of ventilation system shall be 38.9 
 Indoor Design Conditions ( Ventilation system ):
The temperature rise of air above the design ambient temperature : + 5 C .
Positive pressure to be maintained insides CTG building
Tel. + 962.6. 55 29 476
Fax. + 962.6. 55 22 476
P:\U00-238-03\calcs\mech\CTG\CTG HVAC CALCULATION (23-01-2010).rtf
: 25 Pa
Email: info@ucs-jo.com
Page 6 of 20
DESIGN TEMPERATURE REPORT
Block Load 3.05
Location: Amman, Jordan
Prepared by: UCs
January 12, 2010
Page: 1
TABLE 1. DESIGN PARAMETERS
Latitude
Elevation
Summer Design Dry Bulb Temp
Summer Coincident Wet Bulb Temp
Daily Temperature Range
Winter Design Dry Bulb Temp
Atmospheric Clearness Number
Data Source
32.0
766.9
38.9
21.1
13.9
0.6
1.00
User Defined
Degree
m
C
C
K
C
January
TABLE 2. COOLING DESIGN TEMPERATURE PROFILES (DB/WB in C)
DB
15.8
15.1
14.4
13.8
13.4
13.3
13.5
14.2
15.5
17.3
19.4
21.7
24.0
25.6
26.7
27.2
26.7
25.8
24.2
22.4
20.6
19.1
17.7
16.6
WB
10.0
9.8
9.5
9.2
9.0
9.0
9.1
9.4
9.9
10.7
11.5
12.4
13.3
13.9
14.3
14.4
14.3
14.0
13.4
12.7
12.0
11.4
10.8
10.4
30
25
DB
Temperature
Hour
000
100
200
300
400
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300
20
15
10
WB
5
0
0 2 4 6 8 10 12 14 16 18 20 22 24
Hour of the day
DESIGN SOLAR REPORT
Block Load 3.05
Location: Amman, Jordan
Prepared by: UCs
January 12, 2010
Page: 1
TABLE 1. DESIGN PARAMETERS
Latitude
Elevation
Summer Design Dry Bulb Temp
Summer Coincident Wet Bulb Temp
Daily Temperature Range
Winter Design Dry Bulb Temp
Atmospheric Clearness Number
Data Source
32.0
766.9
38.9
21.1
13.9
0.6
1.00
User Defined
Degree
m
C
C
K
C
TABLE 2. MAXIMUM SOLAR HEAT GAINS (W/sqm)
Month
January
February
March
April
May
June
July
August
September
October
November
December
NE
92.7
203.6
338.6
462.1
535.2
556.0
526.2
446.0
324.4
200.1
93.0
68.8
E
553.0
646.0
716.8
715.3
693.9
676.6
679.6
690.2
678.6
616.4
544.6
512.4
SE
784.1
782.8
716.3
590.6
487.6
439.9
474.6
569.8
688.5
755.1
772.3
777.3
S
777.3
695.8
553.9
362.7
232.7
190.6
226.1
350.1
540.0
676.7
766.2
794.2
SW
784.1
782.8
716.3
590.6
487.6
439.9
474.6
569.8
688.5
755.1
772.3
777.3
W
553.0
646.0
716.8
715.3
693.9
676.6
679.6
690.2
678.6
616.4
544.6
512.4
NW
92.7
203.6
338.6
462.1
535.2
556.0
526.2
446.0
324.4
200.1
93.0
68.8
N
74.3
86.4
99.4
112.1
120.8
147.6
126.0
117.3
102.9
88.9
75.3
68.8
HOR
556.1
684.3
795.3
854.2
872.7
871.1
860.7
836.7
769.1
671.5
552.7
499.6
Universal Consultancy Services
ii.
INDOOR CRITERIA
OUTDOOR
AIR
INDOOR CONDITIONS
ITEM
SPACE
SUMMER
WINTER
TEMP
DB
(C)
RH
(%)
TEMP
DB
(C)
RH
(%)
INDOOR
PRESS.
(Pa)
INTERNAL HEAT GAINS
EQUIP DISSIP
REQ.
PEOPLE
(No.)
LIGHTS
2
(W/m )
SENS.
(W)
LAT.
(W)
GAS
TURBINE
AREA
43.9
NA
NA
NA
+25
12 ACH
21.5
514000
GENERATOR
AREAS
43.9
NA
NA
NA
+25
12 ACH
21.5
130000
Tel. + 962.6. 55 29 476
Fax. + 962.6. 55 22 476
P:\U00-238-03\calcs\mech\CTG\CTG HVAC CALCULATION (23-01-2010).rtf
Email: info@ucs-jo.com
Page 7 of 20
Universal Consultancy Services
SECTION 3
HVAC SYSTEMS DESIGNATION
Tel. + 962.6. 55 29 476
Fax. + 962.6. 55 22 476
P:\U00-238-03\calcs\mech\CTG\CTG HVAC CALCULATION (23-01-2010).rtf
Email: info@ucs-jo.com
Page 8 of 20
Universal Consultancy Services
i.
SYSTEM DEFINITION:
SYSTEM-1
EQUIPMENT
NO.
DESCRIPTION
TYPE
UNIT TAG
VENTILATION SYSTEM
AIR HANDLING UNIT
CTG-AHU-1
VENTILATION SYSTEM
AIR HANDLING UNIT
CTG-AHU-2
VENTILATION SYSTEM
AIR HANDLING UNIT
CTG-AHU-3
VENTILATION SYSTEM
AIR HANDLING UNIT
CTG-AHU-4
VENTILATION SYSTEM
AIR HANDLING UNIT
CTG-AHU-5
VENTILATION SYSTEM
AIR HANDLING UNIT
CTG-AHU-6
VENTILATION SYSTEM
AIR HANDLING UNIT
CTG-AHU-7
VENTILATION SYSTEM
AIR HANDLING UNIT
CTG-AHU-8
Tel. + 962.6. 55 29 476
Fax. + 962.6. 55 22 476
P:\U00-238-03\calcs\mech\CTG\CTG HVAC CALCULATION (23-01-2010).rtf
SERVED AREA
GAS TURBINE
AREA
GAS TURBINE
AREA
GAS TURBINE
AREA
GAS TURBINE
AREA
GAS TURBINE
AREA
GAS TURBINE
AREA
GENERATOR
AREAS
GENERATOR
AREAS
NOTES
DUTY- 13.3%
DUTY- 13.3%
DUTY- 13.3%
DUTY- 13.3%
DUTY- 13.3%
DUTY- 13.3%
DUTY- 10.0%
DUTY- 10.0%
Email: info@ucs-jo.com
Page 9 of 20
Universal Consultancy Services
SECTION 4
OVERALL HEAT TRANSFER COEFFICIENTS
Tel. + 962.6. 55 29 476
Fax. + 962.6. 55 22 476
P:\U00-238-03\calcs\mech\CTG\CTG HVAC CALCULATION (23-01-2010).rtf
Email: info@ucs-jo.com
Page 10 of 20
Universal Consultancy Services
i.
U VALUE SUMMARY:
ITEM
DESCRIPTION
HEAT TRASNFER
COEFFICIENT
U
(W/m2.K)
1
2
3
4
5
EXTERIOR WALL
ROOF
FLOOR
EXTERIOR DOORS
WINDOWS
0.25
0.25
1.30
5.80
3.50
ii.
NOTES
U VALUE DETAILED CALCULATION:
 EXTERIOR WALL
ITEM
DESCRIPTION
THICKNESS
(mm)
HEAT
TRANSFER
FILM COEFF.
(h)
(W/m2.K)
THERMAL
CONDUCTIVITY
(k)
(W/m.K)
THERMAL
RESISTANCE
(R)
(m2.K/W)
REFERENCES/NOTES
0.12
JORDANIAN NATIONAL
CODES
EXTERIOR WALL
1
1.1
INDOOR AIR FILM
HEAT FLOW
1.2
SHEET METAL
NEGLIGIBLE
1.3
POLYSTYRENE
130
1.4
SHEET METAL
NEGLIGIBLE
1.5
OUTDOOR AIR FILM
HEAT FLOW,
18 km/h WIND
8.33
JORDANIAN NATIONAL
CODES
0.034
3.82
JORDANIAN NATIONAL
CODES
16.6
0.06
OVERALL THERMAL
RESISTANCE
(R)
(m2.K/W)
JORDANIAN NATIONAL
CODES
4.00
OVERALL HEAT
TRANSFER COEFF.
(U)
(W/ m2.K)
Tel. + 962.6. 55 29 476
JORDANIAN NATIONAL
CODES
0.25
Fax. + 962.6. 55 22 476
P:\U00-238-03\calcs\mech\CTG\CTG HVAC CALCULATION (23-01-2010).rtf
Email: info@ucs-jo.com
Page 11 of 20
Universal Consultancy Services
 ROOF
ITEM
DESCRIPTION
THICKNESS
(mm)
HEAT
TRANSFER
FILM COEFF.
(h)
(W/m2.K)
THERMAL
CONDUCTIVITY
(k)
(W/m.K)
THERMAL
RESISTANCE
(R)
(m2.K/W)
REFERENCES/NOTES
ROOF
2.1
INDOOR AIR FILM
HEAT FLOW
2.2
SHEET METAL
NEGLIGIBLE
2.3
POLYSTYRENE
130
2.4
SHEET METAL
NEGLIGIBLE
2.5
OUTDOOR AIR FILM
HEAT FLOW,
18 km/h WIND
8.33
JORDANIAN NATIONAL
CODES
JORDANIAN NATIONAL
CODES
JORDANIAN NATIONAL
CODES
JORDANIAN NATIONAL
CODES
0.12
0.034
3.82
16.6
JORDANIAN NATIONAL
CODES
0.06
OVERALL THERMAL
RESISTANCE
(R)
(m2.K/W)
4.00
OVERALL HEAT
TRANSFER COEFF.
(U)
(W/ m2.K)
0.25
 FLOOR
ITEM
DESCRIPTION
THICKNESS
(mm)
HEAT
TRANSFER
FILM COEFF.
(h)
(W/m2.K)
THERMAL
CONDUCTIVITY
(k)
(W/m.K)
THERMAL
RESISTANCE
(R)
(m2.K/W)
REFERENCES/NOTES
0.12
JORDANIAN NATIONAL
CODES
0.25
JORDANIAN NATIONAL
CODES
FLOOR
3.1
INDOOR AIR FILM
HEAT FLOW
3.2
RCC
8.83
300
1.2
OVERALL THERMAL
RESISTANCE
(R)
(m2.K/W)
0.77
OVERALL HEAT
TRANSFER COEFF.
(U)
(W/ m2.K)
Tel. + 962.6. 55 29 476
1.30
Fax. + 962.6. 55 22 476
P:\U00-238-03\calcs\mech\CTG\CTG HVAC CALCULATION (23-01-2010).rtf
Email: info@ucs-jo.com
Page 12 of 20
Universal Consultancy Services
 EXTERIOR DOORS
ITEM
DESCRIPTION
EXTERIOR DOORS
THICKNESS
(mm)
HEAT
TRANSFER
FILM COEFF.
(h)
(W/m2.K)
THERMAL
CONDUCTIVITY
(k)
(W/m.K)
THERMAL
RESISTANCE
(R)
(m2.K/W)
REFERENCES/NOTES
0.17
JORDANIAN NATIONAL
CODES
THERMAL
RESISTANCE
(R)
(m2.K/W)
REFERENCES/NOTES
0.29
JORDANIAN NATIONAL
CODES
DOUBLE SKINNED PRESSED
STEEL DOOR
OVERALL THERMAL
RESISTANCE
(R)
(m2.K/W)
OVERALL HEAT
TRANSFER COEFF.
(U)
(W/ m2.K)
5.8
 WINDOWS
ITEM
DESCRIPTION
WINDOWS
THICKNESS
(mm)
HEAT
TRANSFER
FILM COEFF.
(h)
(W/m2.K)
THERMAL
CONDUCTIVITY
(k)
(W/m.K)
Double glazing, 6mm air
space, vertically installed,
operable, aluminum frame
OVERALL THERMAL
RESISTANCE
(R)
(m2.K/W)
OVERALL HEAT
TRANSFER COEFF.
(U)
(W/ m2.K)
Tel. + 962.6. 55 29 476
3.5
Fax. + 962.6. 55 22 476
P:\U00-238-03\calcs\mech\CTG\CTG HVAC CALCULATION (23-01-2010).rtf
Email: info@ucs-jo.com
Page 13 of 20
Universal Consultancy Services
SECTION 5
OUTDOOR AIR SIZING
Tel. + 962.6. 55 29 476
Fax. + 962.6. 55 22 476
P:\U00-238-03\calcs\mech\CTG\CTG HVAC CALCULATION (23-01-2010).rtf
Email: info@ucs-jo.com
Page 14 of 20
Universal Consultancy Services
i.
10.1
PEOPLE
(no.)
Tel. + 962.6. 55 29 476
580
22
PRESSUR
(Pa)
GENERATOR
AREAS
1295
SPACE
VOLUME
3
(m )
CEILING
HEIGHT
(m)
GAS
TURBINE
AREA
FLOOR AREA
2
(m )
CTGAHU1
CTGAHU2
CTGAHU3
CTGAHU4
CTGAHU5
CTGAHU6
CTGAHU7
CTGAHU8
SPACE
EQUIPMENT
SYSTEM
1
OUTDOOR AIR SIZING:
+25
MINIMUM OUTDOOR AIR
REQUIREMENTS
RATE
ACH
L/S.per
L/s.m
12
MINIMUM EXHAUST AIR
REQUIREMENTS
RATE
AIR
FLOW
3
(m /h)
REF.
468300
AS PER
DESIGN
REQ.
ACH
L/S.
per
L/S.
2
m
AIR
FLOW
3
(m /h)
REF.
HIGHEST
OUTDOOR
AIR
3
(m /h)
468300
HIGHEST
EXHAUST
AIR
3
(m /h)
OUTDOOR
AIR
ADOPTED
IN CALC'S
3
(m /h)
468300
28490
5860
Fax. + 962.6. 55 22 476
P:\U00-238-03\calcs\mech\CTG\CTG HVAC CALCULATION (23-01-2010).rtf
Email: info@ucs-jo.com
Page 15 of 20
Universal Consultancy Services
SECTION 6
CALCULATION INPUT DATA
Tel. + 962.6. 55 29 476
Fax. + 962.6. 55 22 476
P:\U00-238-03\calcs\mech\CTG\CTG HVAC CALCULATION (23-01-2010).rtf
Email: info@ucs-jo.com
Page 16
ZONE INPUT REPORT
ZoneName: CTG HALL
Location: Amman, Jordan
Prepared by: UCs
Block Load 3.05
February 02, 2010
Page: 1
TABLE 1. GENERAL ZONE DATA
GENERAL ZONE DATA
Zone Name
Floor Area
Building Weight
LIGHTING DATA
Lighting Usage
Unoccupied Diversity
Wattage Multiplier
Fixture Type
OTHER ELECTRIC
Usage
Unoccupied Diversity
PEOPLE
Occupancy
Unoccupied Diversity
Activity Level
Sensible Gain
Latent Gain
CTG HALL
1,875.0 sqm
Medium
21.53 W/sqm
0 %
1.10
Recessed, Not Vented
644,000 Watts
0 %
1.0
0
Seated At Rest
67.4
35.2
MISCELLANEOUS LOADS
Sensible
Latent
Unoccupied Diversity
0.0 W
0.0 W
0 %
INFILTRATION
Cooling
Heating
.00 L/s/sqm
.00 L/s/sqm
SLAB
Area
Perimeter
Depth
1,659.0 sqm
288.0 m
0.30 m
People
%
W /person
W /person
TABLE 2. BUILDING MATERIAL
TYPE 1
TYPE 2
TYPE 3
WALL DETAIL
U-Value (W/sqm/K )
Weight (kg/sqm)
Color
0.250
361
Medium
0.570
361
Light
0.570
361
Light
ROOF DETAIL
U-Value (W/sqm/K )
Weight (kg/sqm)
Color
0.250
Medium
Medium
0.740
Medium
Light
0.740
Medium
Light
GLASS INFORMATION
U-Value (W/sqm/K )
Glass Factor
Interior Shades
3.500
0.50
No
3.010
0.51
No
3.010
0.51
No
SHADE INFORMATION
Window Height (m)
Window Width (m)
Reveal Depth (mm)
Overhang Height (mm)
Overhang Ext (mm)
Fin Separation (mm)
Fin Extension (mm)
1.0
1.0
0.0
0.0
0.0
0.0
0.0
2.4
1.2
0.0
0.0
0.0
0.0
0.0
2.4
1.2
0.0
0.0
0.0
0.0
0.0
ZONE INPUT REPORT
ZoneName: CTG HALL
Location: Amman, Jordan
Prepared by: UCs
Block Load 3.05
February 02, 2010
Page: 2
TABLE 3. EXPOSURE AREA
Exposure
East
West
South
North
Roof
Wall
Type
1
1
1
1
1
Gross
Area
(sqm)
1,967.3
1,967.3
495.0
495.0
1,659.0
Glass
Type
1
1
1
1
0
Glass
Area
(sqm)
74.0
74.0
12.0
18.0
0.0
Shade
Type
Glass
Type
0
0
0
0
0
0
0
0
0
0
Glass
Area
(sqm)
0.0
0.0
0.0
0.0
0.0
TABLE 4. PARTITION DATA
Net Area (sqm)
U-Value (W/sqm/K )
Adjacent Region Temp
Cooling
Heating
Partition 1
0.00
.568
Partition 2
0.00
.568
Partition 3
0.00
.568
32.2 C
32.2 C
32.2 C
32.2 C
32.2 C
32.2 C
Shade
Type
0
0
0
0
0
SYSTEM INPUT REPORT
System: Ventilation
Location: Amman, Jordan
Prepared by: UCs
Block Load 3.05
February 02, 2010
Page: 1
TABLE 1. HVAC SYSTEM DESCRIPTION
System Type
Clg and Warm Air Ht
System Start
:00
Duration
24
SIZING SPECIFICATIONS
Supply
38.0
Ventilation
15.00
Exhaust
0.00
FACTORS
Coil Bypass
0.050
Safety (Sens)
0
Safety (Latent)
0
Heating Safety
0
hrs
C
L/s/Per
L/s
THERMOSTAT SETPOINTS
Cooling (Occ.)
Cooling (Unocc.)
Heating
RETURN AIR PLENUM
FAN
Configuration
Static Pressure
%
%
%
TABLE 2. SYSTEM ZONING INFORMATION
System Arrangement:
Total Zones Selected:
Selected Zones:
All zones served by a common air handler
1
1) CTG HALL
43.0 C
43.0 C
21.0 C
No
Blow Thru
250.00 Pa.
Universal Consultancy Services
SECTION 7
CALCULATION RESULTS
Tel. + 962.6. 55 29 476
Fax. + 962.6. 55 22 476
P:\U00-238-03\calcs\mech\CTG\CTG HVAC CALCULATION (23-01-2010).rtf
Email: info@ucs-jo.com
Page 17
Universal Consultancy Services
i.
RESULTS SUMMARY:
SUMMER
CTG
1659
23
38157
+25
43
NA
TOTAL
CTGAHU1
CTGAHU2
CTGAHU3
CTGAHU4
CTGAHU5
CTGAHU6
CTGAHU7
CTGAHU8
Tel. + 962.6. 55 29 476
SUPPLY
AIIRFLOW
(m3/h)
RETURN
AIIRFLOW
(m3/h)
EXHAUST
AIIRFLOW
(m3/h)
OUTDOOR
AIR
(m3/h)
476000
476000
476000
476000
63500
63500
63500
63500
63500
63500
63500
63500
63500
63500
63500
63500
47500
47500
47500
47500
Fax. + 962.6. 55 22 476
P:\U00-238-03\calcs\mech\CTG\CTG HVAC CALCULATION (23-01-2010).rtf
Email: info@ucs-jo.com
Page 18
RH
(%)
1.1
EQUIPMENT
INDOOR
COND.
DB
(C)
SPACE
VLOUME
(m3)
LAT.
(kW)
CEILING
HEIGHT
(m)
SEN.
(kW)
FLOOR
AREA
2
(m )
COOLING
LOAD
RH
(%)
SPACE
INDOOR
COND.
DB
(C)
ITEM
PRESS.
REL. TO
ADJ.
SPACE
(Pa)
WINTER
HEATING
LOAD
(W)
COOLING
CAPACITY
(W)
HEATING
CAPACITY
(W)
TERMINAL
UNIT REF.
DETAILED SYSTEM LOAD REPORT
System: Ventilation
Location: Amman, Jordan
Prepared by: UCs
Block Load 3.05
February 02, 2010
Page: 1
TABLE 1. CALCULATION INFORMATION
Design Load:
Db/Wb Temp
Winter Design Temp
July 17:00
37.5/ 20.7 C
0.6 C
TABLE 2. LOAD COMPONENT SUMMARY
Load Component
Solar Loads
Wall Transmission
Roof Transmission
Glass Transmission
Skylight Transmission
Partitions
Lighting
Other Electric
People
Infiltration
Miscellaneous
Slab
Pulldown/Warm-Up
Safety Factor
Total Zone Loads
Ventilation Load
Supply Fan Load
Plenum Load thru Wall
Plenum Load thru Roof
Plenum Load - Lights
Reheat Load
Total Coil Loads
Walls:
Glass:
Component
NE
E
SE
S
SW
W
NW
N
NE
E
SE
S
SW
W
NW
N
Hor
Details
178
4,747
1,659
178
0
0
21.53
343.47
1
Design Cooling
Sensible
(W )
18,024
-3,874
1,700
-4,492
0
0
44,323
643,620
67
0
0
0
0
699,368
-73
58,792
0
0
0
0
758,087
sqm
sqm
sqm
sqm
sqm
sqm
W/sqm
W/sqm
People
1,659 sqm
0/0/0 %
12
126,997
0
0
0
L/s
L/s
%
%
%
TABLE 3. WALL AND GLASS BREAKDOWN
Total
Net Area
(sqm)
0
1,893
0
483
0
1,893
0
477
0
74
0
12
0
74
0
18
0
Cooling
Transmission
(W )
0
-546
0
-674
0
-1,727
0
-928
0
-1,867
0
-303
0
-1,867
0
-454
0
Cooling
Solar Load
(W )
0
5,976
0
524
0
10,747
0
778
0
Loads
Latent
(W )
35
0
0
0
35
-35
0
Heating
Transmission
(W )
0
9,651
0
2,462
0
9,651
0
2,431
0
5,281
0
856
0
5,281
0
1,285
0
Design
Heating
(W )
24,194
8,456
12,702
0
0
0
6,403
0
51,756
269
52,025
DETAILED ZONE LOAD REPORT
System: Ventilation
Location: Amman, Jordan
Prepared by: UCs
Block Load 3.05
February 02, 2010
Page: 1
TABLE 1. GENERAL INFORMATION
Zone Name:
System Name:
Design Load:
Db/Wb Temp:
CTG HALL
Ventilation
July 17:00
37.5/ 20.7 C
TABLE 2. LOAD COMPONENT SUMMARY
Load Component
Solar Loads
Wall Transmission
Roof Transmission
Glass Transmission
Skylight Transmission
Partitions
Lighting
Other Electric
People
Infiltration
Miscellaneous
Slab
Pulldown/Warm-Up
Safety Factor
Total Zone Loads
Details
178
4,747
1,659
178
0
0
21.53
343.47
1
sqm
sqm
sqm
sqm
sqm
sqm
W/sqm
W/sqm
People
1,659 sqm
0/ 0 %
Design Cooling Loads
Sensible
(W )
18,024
-3,874
1,700
-4,492
0
0
44,323
643,620
67
0
0
0
0
699,368
Design
Heating
(W )
24,194
8,456
12,702
0
0
0
6,403
0
51,756
TABLE 3. WALL AND GLASS BREAKDOWN
Walls:
Glass:
Component
NE
E
SE
S
SW
W
NW
N
NE
E
SE
S
SW
W
NW
N
Hor
Total
Net Area
(sqm)
0
1,893
0
483
0
1,893
0
477
0
74
0
12
0
74
0
18
0
Cooling
Transmission
(W )
0
-546
0
-674
0
-1,727
0
-928
0
-1,867
0
-303
0
-1,867
0
-454
0
Cooling
Solar Load
(W )
0
5,976
0
524
0
10,747
0
778
0
Heating
Transmission
(W )
0
9,651
0
2,462
0
9,651
0
2,431
0
5,281
0
856
0
5,281
0
1,285
0
Universal Consultancy Services
vi.
RESULTS CALCULATION:
 Solar Loads = 18,024 W (From E20 II-Block Load)
 Wall Transmission = -3,874 W (From E20 II-Block Load)
 Roof Transmission = 1,700 W (From E20 II-Block Load)
 Glass Transmission = -4,492 W (From E20 II-Block Load)
 Lighting = 44,323 W (From E20 II-Block Load)
 Heat dissipation in generator building = 130,000 W
 Heat dissipation from GT building = 514,000 W
Total Load = 699,681 W
Temperature difference = 5 C
Specific heat at constant pressure (Cp) = 1.007 kJ/kg.C
Density of air @ 38.9 C ambient condition ( )= 1.1 kg/m
To find the Air Flow required for ventilation:
Heat Load
= Q X Cp X
X T
699,681
= Q X 1.007 X 1.1 X 5
Q1
= 126,330 l/s (Based on waste heat removal basis)
3
= 454788 m /hr
Q2
= ACH X Volume (Based on air change method)
= 12 X ((1295 X 22)+(2 X 290 X10.1))
= 412176 m3/hr
3
To maintain ( P = 25 Pa) inside CTG building we need air flow = 13415 m /hr
Total air flow required for ventilation
= 457884 + 13415
3
= 468,292 m /hr
3
476,000 m /hr
Distribution of fans shall be as follows:
-
Heat dissipation in generator building = 130,000 W
Heat dissipation from GT building = 514,000 W
Percentage of heat in generator building = 130 / (514 +130) = 20%
Therefore, 20% of the required air will be supplied to generator areas and 80% to turbine area.
Tel. + 962.6. 55 29 476
Fax. + 962.6. 55 22 476
P:\U00-238-03\calcs\mech\CTG\CTG HVAC CALCULATION (23-01-2010).rtf
Email: info@ucs-jo.com
Page 19
Universal Consultancy Services
Exhaust air quantity
= 476000 -13415
3
= 462,585 m /hr
3
= 128.5 m /s
Exhaust air velocity
= 1.75 m/s
Required area for roof vent
= 128.5 / 1.75
= 73.4 m
= 74 m
Required area (A)
= Available area  area blocked by rafters.
= AAV - AR
Available area (AAV)
=LxW
where, L = Available span length for roof vent (84.0m)
W = Throat width (m)
Area blocked by rafters (AR) = LR x W R x N
where, LR = Length of the rafter blocking exhaust air flow i.e nothing but throat width (W)
W R = Rafter width (0.229 m)
N = No. of rafters (17 nos.)
A
= AAV - AR
= (L x W - LR x W R x N)
74.0
= (84.0 x W  W x 0.229 x 17)
= 74.0 / 80.11
= 0.924 m
Throat size for roof vent = 950 mm
Tel. + 962.6. 55 29 476
Fax. + 962.6. 55 22 476
P:\U00-238-03\calcs\mech\CTG\CTG HVAC CALCULATION (23-01-2010).rtf
Email: info@ucs-jo.com
Page 20