Tata CGL-2 SJ-700 commissioning
Parameter list
1. Motor nameplate data:
H003H004A003A004A082C041C111-
Motor capacity(KW)
Motor pole
Base frequency
Maximum frequency
Motor Voltage
Motor current
Motor current
2. Other parameters:
F002Ramp up time
F003Ramp down time
A001- * Frequency Source setting
01: from remote
02: from display
A002- * Run command setting
01: from remote
02: from display
A044V/f characteristics
A061Maximum frequency
A062Minimum frequency
A081B006B021- *
B022B023- *
B024- *
B025B027B082B100B101B102B103B104B105B106B107B108B109B110B111B112B113P001-*
P002-*
AVR select
Phase loss detection
Overload restriction mode
Overload restriction
Dec rate at overload restr.
Overload restriction mode
Overload restriction
Overcurrent suppression
Starting frequency
V/f frequency(1)
V/f voltage(1)
V/f frequency(2)
V/f voltage(2)
V/f frequency(3)
V/f voltage(3)
V/f frequency(4)
V/f voltage(4)
V/f frequency(5)
V/f voltage(5)
V/f frequency(6)
V/f voltage(6)
V/f frequency(7)
V/f voltage(7)
Oper mode on com 1 error
Oper mode on com 2 error
220kw
220kw
4
50 Hz
50 Hz
415V
416A
416A
132kw
132kw
2
50 Hz
50 Hz
415V
217A
217A
90kw
90kw
4
50 Hz
50 Hz
415V
156A
156A
75kw
90kw
4
50 Hz
50 Hz
415V
130A
130A
200s
200s
200s
200s
150s
150s
100s
100s
2
50 Hz
0.0 Hz
2
50 Hz
0.0 Hz
2
50 Hz
0.0 Hz
2
50 Hz
0.0 Hz
00: always on 00: always on 00: always on 00: always on
01: On
01: On
01: On
01: On
3
3
3
3
624A
325A
234A
195A
5s
5s
5s
5s
3
3
3
3
624A
325A
234A
195A
01: enable
01: enable
01: enable
01: enable
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
5 Hz
5 Hz
5 Hz
5 Hz
25V
25V
25V
25V
10 Hz
10 Hz
10 Hz
10 Hz
53V
53V
53V
53V
15 Hz
15 Hz
15 Hz
15 Hz
73V
73V
73V
73V
20 Hz
20 Hz
20 Hz
20 Hz
88V
88V
88V
88V
30 Hz
30 Hz
30 Hz
30 Hz
187V
187V
187V
187V
40 Hz
40 Hz
40 Hz
40 Hz
291V
291V
291V
291V
50 Hz
50 Hz
50 Hz
50 Hz
415V
415V
415V
415V
1
1
1
1
1
1
1
1
C001C002-
DI 1 function
DI 2 function
C021-
DO 1 function
C022-
DO 2 function
C026-
Alarm relay
C036- * Alarm relay active state
C102- * Reset mode selection
C103- * Restart mode after reset
C029-
Analog o/p function
For VC and VD only:
A062Minimum frequency
B082Starting frequency
A051- * DC braking enable
A052DC braking freq setting
A053DC braking wait time
A054DC braking force during dec
A055DC braking time for dec
A056- * DC braking edge/level
A057DC braking force for starting
A058DC braking time for starting
C102- * Reset mode selection
C103- * Restart mode after reset
220kw:
132KW:
90KW:
75KW:
7.5KW:
11KW:
18: Reset
16: AI1-V/I
selection
21: 0 Hz
detection
00: Running
18: Reset
16: AI1-V/I
selection
21: 0 Hz
detection
00: Running
18: Reset
16: AI1-V/I
selection
21: 0 Hz
detection
00: Running
50: inverter
ready
00: NO
0
0
01: o/p
current
50: inverter
ready
00: NO
0
0
01: o/p
current
50: inverter
ready
00: NO
0
0
01: o/p
current
50: inverter
ready
00: NO
0
0
01: o/p
current
0.1 Hz
0.1 Hz
1
0.0Hz
0s
35%
5s
01: level
35%
10s
2
1
0.1 Hz
0.1 Hz
1
0.0Hz
0s
35%
5s
01: level
35%
10s
2
1
0.1 Hz
0.1 Hz
1
0.0Hz
0s
35%
5s
01: level
35%
10s
2
1
0.1 Hz
0.1 Hz
1
0.0Hz
0s
35%
5s
01: level
35%
10s
2
1
VC, VD, VK, VL, VM, VN, VP, VQ
VJ, VH
VE, VF, VG
VA, VB
GE, GF
FA
Note: (*) indicates to read the manual for details of the parameter.
Parameters of FA, GE, GF:
Motor details:
H003- Motor capacity(KW)
H004- Motor pole
A003Base frequency
A004Maximum frequency
A082Motor Voltage
C041Motor current
C111Motor current
18: Reset
16: AI1-V/I
selection
21: 0 Hz
detection
00: Running
11KW
11kw
4
50 Hz
50 Hz
415V
19A
19A
7.5KW
7.5kw
4
50 Hz
50 Hz
415V
14A
14A
2. Other parameters:
F001Frequency reference
F002Ramp up time
F003Ramp down time
A001- * Frequency Source setting
01: from remote
02: from display
A002- * Run command setting
01: from remote
02: from display
A044V/f characteristics
A061Maximum frequency
A062Minimum frequency
A081-
AVR select
B006B021- *
B022B024- *
B025B027-
Phase loss detection
Overload restriction mode
Overload restriction
Overload restriction mode
Overload restriction
Overcurrent suppression
C021-
DO 1 function
C022-
DO 2 function
10.00Hz
30s
30s
10.00Hz
30s
30s
0
50 Hz
0.0 Hz
0
50 Hz
0.0 Hz
00: always on 00: always on
01: On
01: On
3
3
28.5A
21A
3
3
28.5A
21A
01: enable
01: enable
50: Inverter 50: Inverter
ready
ready
00: Running 00: Running