Pvmaster: Operation Manual
Pvmaster: Operation Manual
PV
                           ma
                                ste
Operation manual r
Large-scale inverters
                   The safety instructions and symbols in this operation manual are defined as
                   follows:
                   Note
                   Useful information.
                   •   Handling instructions
                   Terms written in italics are those which appear on the display.
No.: 181-10017
                   Date: 11/2009
                   Revision: 1
2 Description of system 9
                    2.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
                    2.2 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
                        2.2.1 Order code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
                    2.3 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3 Prerequisites 13
                    4.1 Transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
                    4.2 Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5 Installation 19
6 Operation 41
7 Description of operation 59
8 Inspection 63
9 Troubleshooting 65
A Appendix 69
                       Your qualification:
                       – In order to avoid personal injury and prevent damage to equipment, only
                         qualified and trained electrical engineers are permitted to work on the
                         equipment.
                       – The qualified person must familiarise himself/herself with the operating
                         instructions.
                       – The national accident prevention regulations (e. g. BGV A3 in Germany)
                         must be complied with.
2 Description of system
2.1 Overview
                                                                                    PV
                                                                                      ma
                                                                                           ste
                                                                                                 r
                                          PV
                                            ma
                                                   ste
     PV                                                  r
       ma
               ste
                     r
                                                             1
       1
                                                                 0
           0
                                  PV
                                    ma
                                         ste
                                               r
2.2 Description
                            PV
                               m   as
                                        ter
                                                                        1
                                                                        2
                                                                        3
                                                      1
                                                                        4
                                                          0
                                                                        8
                                                                        9
                                                                        10
                  Legend
                  1   Exhaust air opening                        6    DC main switch
                  2   Touchscreen display / LED display with     7    AC main switch
                     RJ45 socket for PC (optional)               8    Air inlet opening with filter
                  3   Inverter enable switch                     9    Base trim panel
                  4   Enclosure door                             10   Base feet
                  5   Door handle with lock
                  The PVmaster series covers a power range from 33 to 100 kilowatts. Each size
                  is optimised for its power class and therefore achieves a high level of efficiency.
                  The modular design provides for a variety of equipment options. The operating
                  state and parameters of the PVmaster can be displayed and adjusted on site via
                  a touchscreen display or via the integrated "WebVisualization" user interface. The
                  operating state can also be indicated via an LED display. All the relevant
                  PVmaster data in the online monitoring system can be viewed at
                  www.pvmaster.de via the optional GPRS communication module.
                  The PVmaster is available in the following topology configurations:
                  – PVM 450 TT with an internal isolation transformer
                  – PVM 450 ET with an external isolation transformer
                  – PVM 450 CM with an internal transformer without electrical isolation between
                    AC and DC sides
                  The PVmaster series is prepared for immediate use. It is only necessary to install
                  the AC and DC conductors coming from outside. Start of operation is therefore a
                  quick and uncomplicated process.
3 Prerequisites
                                                                                                           B                                     B
                                               B                           B                                            PV
                                                                                                                             ma
                                                                                                                               ste
                                                                                   PV                                             r
                                                                                     ma
                                                                                       ste
                                                                                          r
                                                        PV
                                                          ma
                                                            ste
                              PV                               r
                                ma
                                        ste
                                           r
A 1
                                    0
                                                                   1
                                                                                                    0
                                                                                                                                         1
C H H H H
F E D
T T T T
PVM 450-033 TT,CM PVM 450-047 TT,CM PVM 450-068 TT,CM PVM 450-100 TT,CM
Legend
PVmaster                                               Prerequisites                                                                                     13
                                      3.1 Conditions at the site of placement
PVM 450 ET
                                                                                 B                            B
                                                                                          PV
                                                                                            ma
                                                                                              ste
                                                               PV                                r
                                                                 ma
                                                                         ste
                                                                            r
A 1
                                                                     0
                                                                                                     1
C H H
F E D
T T
Legend
14                                                    Prerequisites                                                        PVmaster
                                      3.2 Exhaust air heat
                                          PV
                                            ma
                                              ste
                                                 r
                       4
                                                          1
                       Legend
                       1   Air supply opening for the room
                       2   Opening for the exhaust air system
                       3   Exhaust air system
                       4   Air supply opening for PVmaster
PVmaster                                    Prerequisites                                               15
     3.2 Exhaust air heat
16      Prerequisites       PVmaster
                                                        4.1 Transport
4.1 Transport
                                    The PVmaster must be transported upright. Care must be taken during transport
                                    to avoid vibrations and to avoid tipping the enclosure. The weight must also be
                                    taken into account.
                                    The centre of gravity of the enclosure is off-centre.
                                    It is important to provide a wide area to set the PVmaster down in order to avoid
           Danger!
                                    tipping the enclosure. The enclosure should be picked up from the front or from
                                    the back only.
4.2 Placement
                                    The PVmaster 450-033 to 450-068 is delivered on a pallet.
                                    • When preparing to lift down the enclosure, pick it up so that it is on the base
                                      feet.
                                    The PVmaster 450-100 is fitted with a special transport base (1).
                                    • Unscrew the base trim panels (3).
                                    • Pick up the enclosure from the front or from the back.
           PV                                                        PV
             ma                                                        ma
                  ste                                                       ste
                        r                                                         r
1 1
0 0
      1
      2
                                    Legend
                                    1   Transport base
                                    2   Base feet
                                    3   Base trim panels
                     The PVmaster series is prepared for immediate use. It is only necessary to install
                     the AC and DC conductors coming from outside.
                     Note
                     The installation process is identical for the PVmaster PVM 450 TT and CM. The
                     isolation transformer is also connected in the case of the PVmaster PVM 450 ET.
PVmaster                                Installation                                                   19
                          5.1 Installing PVM 450-033 and PVM 450-047
10
                      9
                                                                                                                                     11
                                                                                                                                          12
PWR
                                                                                             LOCK
                                                                                             CF
                                                                                                                                                  13
                                                                                                                                                  14
                                                                                                                                                  15
                                                                                                                   Pow
                                                                                                                   COMer
                                                                                                                   Data
                                                                                                                   Statu
                                                                                                                        s
Rese
                                                                                                                                                  16
                                                                                                                     t
RJ-45/Line
                                                                                                                            RS 232
                                                                                                                                                  17
                                                                                                                                                  18
                                                                                                                                                  19
                      8
                      7
                      6
                      5                     0
                                            OFF
                                                  1
                                                  ON
                                            +
                      4                                –           0
                                                                   OF
                                                                     F
                                                                          1
                                                                          ON
                                                                     L1
                                                                               L2
                                                                                        L3
                      2
                      1
                           Legend
                           1   Cable opening                                                                                         11   Data acquisition
                           2   PE busbar                                                                                             12   Controller
                           3   Transformer                                                                                           13   Communication module (optional)
                           4   Cable clamping rail                                                                                   14   Power supply unit
                           5   AC main switch (2Q5)                                                                                  15   Insulation monitor (PVM 450 TT only,
                           6   Connection for auxiliary voltage (X5.1)                                                                    optional)
                           7   DC main switch (1Q1)                                                                                  16   Key-operated control voltage switch
                           8   PV generator earthing (PVM 450 TT only, optional)                                                     17   Auxiliary voltage bridge (X5)
                           9   Inverter                                                                                              18   DC overvoltage protector
                           10 Automatic circuit breakers (2F7, 3F1, 3F4)                                                             19   Circuit breakers (1F5)
20                                                             Installation                                                                                      PVmaster
                                                                                       5.1 Installing PVM 450-033 and PVM 450-047
10
                                                                                                          9
                                                                                                                                                                                                                                                                            11
                                                                                                                                                                                                                                                                                 12
PWR
                                                                                                                                                                                                                                    LOCK
                                                                                                                                                                                                                                    CF
                                                                                                                                                                                                                                                                                      13
                                                                                                                                                                                                                                                                                      14
                                                                                                                                                                                                                                                                                      15
                                                                                                                                                                                                                                                          Pow
                                                                                                                                                                                                                                                          COMer
                                                                                                                                                                                                                                                          Data
                                                                                                                                                                                                                                                          Statu
                                                                                                                                                                                                                                                               s
Rese
                                                                                                                                                                                                                                                                                      16
                                                                                                                                                                                                                                                               t
RJ-45/Line
                                                                                                                                                                                                                                                                   RS 232
                                                                                                                                                                                                                                                                                      17
                                                                                                                                                                                                                                                                                      18
                                                                                                          8                                                                                                                                                                           19
                                                                                                          7          1
                                                                                                                         2
                                                                                                                             3
                                                                                                                                 PE
                                                                                                                                      4
                                                                                                          6                               5
                                                                                                                                              6
                                                                                                                                                  PE
                                                                                                          5
             0
             OFF
                   1
                   ON                                                                                     4                                            0
                                                                                                                                                       OFF
                                                                                                                                                             1
                                                                                                                                                             ON
                            0                                                                                                                                         0
                                     12                                                                                                                                        12
                                          5                                                                                                                                         5
                                                     1N                                                                                                                                        1N
             +                                                                                                                                         +
                                                                                                          3
                                X2
X2
                        –                                                                                                                                         –
                                              X5.1
X5.1
                                                          0         1                                                                                                                               0      1
                                                          OF        ON                                                                                                                              OF     ON
                                                            F                                                                                                                                         F
0 0
     8                                                         L1                                                                                                                                     L1
                                                                         L2                                                                                                                                     L2
                                                                                  L3                                                                                                                                     L3
                   PMV 450-033
                                                                                                          2
                                                                                                          1
PMV 450-047
                                                                                        Legend
                                                                                        1   Cable opening                                                                                                                     11   Data acquisition
                                                                                        2   PE busbar                                                                                                                         12   Controller
                                                                                        3   Cable clamping rail                                                                                                               13   Communication module (optional)
                                                                                        4   AC main switch (2Q5)                                                                                                              14   Power supply unit
                                                                                        5   Connection for auxiliary voltage (X5.1)                                                                                           15   Insulation monitor
                                                                                        6   DC main switch (1Q1)                                                                                                              16   Key-operated control voltage switch
                                                                                        7   PV generator earthing (optional)                                                                                                  17   Auxiliary voltage bridge (X5)
                                                                                        8   Terminal clamps for external isolation transformer                                                                                18   DC overvoltage protector
                                                                                        9   Inverter                                                                                                                          19   Circuit breakers (1F5)
                                                                                        10 Automatic circuit breakers (2F7, 3F1, 3F4)
PVmaster                                                                                                       Installation                                                                                                                                                                21
                                      5.1 Installing PVM 450-033 and PVM 450-047
                                                                                    Connection           Temperature
                             Primary/secondary winding             Output [kVA]
                                                                                     symbol                sensor
PVM 450-033                             290 V / 400 V                    36              Yy                    KTY
PVM 450-047                             290 V / 400 V                    52              Yy                    KTY
Table 5.1 Technical data for external isolation transformer
                                         The external isolation transformer is connected to the supply via the terminal
                                         clamps (Fig. 5.2, 8):
                                        Danger of electric shock from live subassemblies!
                                        Up to three separately fused voltage supplies can be connected to the
                    Danger!
                                        PVmaster.
                                        • Before starting work, make sure that the plant is not live.
                                         •   Please refer to the table for information on the primary and secondary winding
                                             cable cross-sections in the external isolation transformer:
                                                   Cable cross-section
                             Primary winding (290 V)            Secondary winding (400 V)      Tightening torque [Nm]
                               Terminals 1, 2, 3, PE               Terminals 4, 5, 6, PE
                                     [mm2]                               [mm2]
PVM 450-033                                  16                               10                        2.5 ... 3
PVM 450-047                                  25                               16                        4 ... 4.5
Table 5.2 Terminal clamps for external isolation transformer
                                         •   Feed the cables through the cable opening (Fig. 5.2, 1) in the base of the
                                             enclosure.
                                         •   Connect the primary end of the transformer to the terminals
                                             (Fig. 5.2, 8) 1/L1, 2/L2, 3/L3 and PE.
                                         •   Connect the secondary end of the transformer to the terminals (Fig. 5.2, 8)
                                             4/L1, 5/L2, 6/L3 and PE.
                                         •   Connect the KTY sensor to terminal X3.
                                         •   Fasten the cables to the clamping rail (Fig. 5.2, 3) to take the strain.
22                                                             Installation                                     PVmaster
                         5.1 Installing PVM 450-033 and PVM 450-047
                                                                                                                           LOCK
                                                                                                                           CF
                                                                                                                                                 Pow
                                                                                                                                                 COMer
                                                                                                                                                 Data
                                                                                                                                                 Statu
                                                                                                                                                      s
                                                                                                                                               Rese
                                                                                                                                                   t
RJ-45/Line
                                                                                                                                                          RS 232
                         0         1
                         OF        ON
                           F
                  2     +
                                                                          0     1
                                                                          OFF   ON
                                         –
                                                                                         0
                                                                          +
                                                                         0
                                                                                     –       0
                                                                         OF
                                                                                                    1
                            6
                                                                                             OF     ON
                                                                                               F
F 0
                                                                                               L1
                                     9                                                                   L2
                                                                                                                  L3
                            Legend
                            2   Terminal clamp, DC (L+) from PV generator
                            6   Terminal clamp, DC (L-) from PV generator
                            9   Terminal clamp, protective earth conductor (PE)
                            The photovoltaic generator is connected to the supply via the DC main switch
                            (Fig. 5.1, 7).
                            Danger of electric shock from live subassemblies!
                            Up to three separately fused voltage supplies can be connected to the
             Danger!
                            PVmaster.
                            • Before starting work, make sure that the plant is not live.
PVmaster                                           Installation                                                                                                    23
                             5.1 Installing PVM 450-033 and PVM 450-047
                                                                                                                                       Rese
                                                                                                                                              t
RJ-45/Line
                                                                                                                                                  RS 232
                 0      1
                 OF     ON
                   F
                                      0                                0
                                                                       OFF
                                                                             1
                                                                             ON
                                                                       +
                                                                                  –        0
                                                                                           OF
                                                                                                   1
                                                                                                   ON
                                                                                              F
           2T1     L1                                                                         L1
                                                                                                        L2
                                                                                                                 L3
                 4T2         L2
                         6T3
                                  7
                                          L3
                                          8
                              Legend
                              2T1 Terminal clamp L1 for the supply network 7              Terminal clamp for neutral conductor (N)
                              4T2 Terminal clamp L2 for the supply network 8              Terminal clamp, protective earth conductor (PE)
                              6T3 Terminal clamp L3 for the supply network
24                                                   Installation                                                                                          PVmaster
                               5.1 Installing PVM 450-033 and PVM 450-047
                                                                                                              LOCK
                                                                                                              CF
                               PE
                                                                                                                                    Pow
                                                                                                                                    COMer
                                                                                                                                    Data
                                                                                                                                    Statu
                                                                                                                                         s
                                                                                                                                  Rese
                                                                                                                                      t
RJ-45/Line
                                                                                                                                             RS 232
                   X5.1
                                    0           1
                                    OF          ON
                                      F
           1
               N
                   PE
                                                                 0
                                                                 OFF
                                                                       1
                                                                       ON
                                                                            0
                                                                                                                                             1
                                                                                0
                                                                +
                                                                                                                                                      4
                                                                            –                                                                             7
                                                                                    0
                                                                                    OF
                                                                                      F
                                                                                           1
                                                                                           ON
                                                                                                                                                              2
                                                                                                     0
                                                                                                                                                                  5
                                                                                                                                                                      8
                                                                                                                                                                          3
                                                                                      L1
                                                                                                L2                                                                            6
                                                                                                         L3                                                                       9
                                                                                                                                                                                      N
                                                                                                                                                                                          N
                                                                                                                                                                                              N
10
                                Legend
                                1   Terminal clamp L1 (X5.1/1)
                                N Terminal clamp for neutral conductor (X5.1/N)
                                PE Terminal clamp for protective earth conductor (X5.1/PE)
                                10 Bridges, change of voltage supply (X5)
                                Note
                                The auxiliary voltage supply can only be connected to a TN S network (five-wire
                                system).
PVmaster                                              Installation                                                                                                                                25
                                 5.1 Installing PVM 450-033 and PVM 450-047
                                         •        Change over the bridge (Fig. 5.5, 10) on terminals 1 and 4 to terminals 4 and 7.
                                         •        Change over the bridge (Fig. 5.5, 10) on the N terminals accordingly.
                                         •        Identify the cable cross-section as dictated by local conditions. This depends
                                                  on cable protection, ambient temperature and installation method.
                                         •        Feed the AC cables through the cable opening (Fig. 5.1, 1) in the base of the
                                                  enclosure.
Z1 G1 L1 C1 T1 Z2 2Q2 VN
                                                                                                                                  L1
                =
                                                                                                                                  L2
                     ~                                                                                                            L3
                                                                                                                                  N
                                                                                                                                  PE
                                                                                         1   2   3    N
                                                                                                                 X5
                                                                                         4   5   6    N                     HS (X5.1)
                                                                                                             4        7                  16 A
                                                                                                                                  1
                         1
                             4
                                 7
                                     2
1Q1                                      5
                                              8
                                                  3
                                                      6                                                     N         N
                                                          9                                                                       N
                                                              N
                                                                  N
                                                                      N                                                           PE
      PV
                                                                                                 PP
                                     X5
                                         Legend
                                         PV Photovoltaic generator                  Z2 EMC filter
                                         1Q1 DC main switch                         2Q5 AC main switch
                                         Z1 EMC filter                              VN Supply network
                                         G1 Inverter                                HS Connection for auxiliary voltage (X5.1)
                                         L1 Inductor                                X5 Bridges, change of voltage supply (X5)
                                         C1 Capacitor                               PP Peripheral devices for PVmaster
                                         T1 Transformer
                                         •        Screw the protective earth cable (PE) to the terminal clamp (Fig. 5.5, PE).
                                         •        Screw the L1 cable to the terminal clamp (Fig. 5.5, 1).
                                         •        Screw the neutral conductor (N) to the terminal clamp (Fig. 5.5, N).
                                         •        Fasten the cables to the clamping rail (Fig. 5.1, 4) to take the strain.
26                                                                        Installation                                                PVmaster
                       5.2 Installing PVM 450-068 and PVM 450-100
                                                                                                                                              3
                                                                                                                                                  4
                                                                                                                                                      5
PWR
                                                                                          LOCK
                                                                                          CF
                                                                                                                                                          6
                                                                                                                                                          7
                                                                                                                                                          8
                                                                                                                                                          9
                                                                                                                                                          10
                                                                                                                      Powe
                                                                                                                      COM r
                                                                                                                      Data
                                                                                                                      Statu
                                                                                                                           s
                                                                                                                    Rese
                                                                                                                        t
RJ-45/Line
                                                                                                                               RS 232
                                                                                                                                                          11
                                                                                                                                                          12
                                                                                                                                                          13
                                                                                                                                                          14
             1
                                                                                                                                                          15
                                                                0     1
                                                                                                                                                          16
                                                                OF    ON
                                                                  F
                                                                               0     1
                                                                               OFF   ON
0 17
                                                                                                                                                          18
                                                                                                                                                          19
                         Legend
                         1   Transformer                                                                                                11   Auxiliary voltage bridge (X5)
                         2   Inverter                                                                                                   12   DC main switch (1Q1)
                         3   Automatic circuit breakers (2F7, 3F1, 3F4)                                                                 13   DC overvoltage protector
                         4   Data acquisition                                                                                           14   Circuit breakers (1F5)
                         5   Controller                                                                                                 15   AC main switch (2Q5)
                         6   Communication module (optional)                                                                            16   Connection for auxiliary voltage (X5.1)
                         7   Power supply unit                                                                                          17   Cable clamping rail
                         8   Insulation monitor (PVM 450 TT only, optional)                                                             18   Cable opening
                         9   PV generator earthing (PVM 450 TT only, optional)                                                          19   PE busbar
                         10 Key-operated control voltage switch
PVmaster                                        Installation                                                                                                                    27
                         5.2 Installing PVM 450-068 and PVM 450-100
                     9
                                                                                                                                                                                11
                                                                                                                                                                                          12
PWR
                                                                                                                                        LOCK
                                                                                                                                        CF
                                                                                                                                                                                                13
                                                                                                                                                                                                14
                                                                                                                                                                                                15
                                                                                                                                                              Pow
                                                                                                                                                              COMer
                                                                                                                                                              Data
                                                                                                                                                              Statu
                                                                                                                                                                   s
Rese
                                                                                                                                                                                                16
                                                                                                                                                                t
RJ-45/Line
                                                                                                                                                                       RS 232
                                                                                                                                                                                                17
                                                                                                                                                                                                18
                     8                                                                                                                                                                          19
                     7         1
                                   2
                                       3
                                           PE
                                                4
                     6                              5
                                                        6
                                                            PE
                     5
                     4                                           0
                                                                 OFF
                                                                       1
                                                                       ON
                                                                                0
                                                                                         12
                                                                                              5
                                                                                                         1N
                                                                 +
                     3
                                                                                    X2
                                                                            –
                                                                                                  X5.1
                                                                                                              0      1
                                                                                                              OF     ON
                                                                                                                F
                                                                                                                L1
                                                                                                                          L2
                                                                                                                                   L3
                     2
                     1
                          Legend
                          1   Cable opening                                                                                                                                          11   Data acquisition
                          2   PE busbar                                                                                                                                              12   Controller
                          3   Cable clamping rail                                                                                                                                    13   Communication module (optional)
                          4   AC main switch (2Q5)                                                                                                                                   14   Power supply unit
                          5   Connection for auxiliary voltage (X5.1)                                                                                                                15   Insulation monitor
                          6   DC main switch (1Q1)                                                                                                                                   16   Key-operated control voltage switch
                          7   PV generator earthing (optional)                                                                                                                       17   Auxiliary voltage bridge (X5)
                          8   Terminal clamps for external isolation transformer                                                                                                     18   DC overvoltage protector
                          9   Inverter                                                                                                                                               19   Circuit breakers (1F5)
                          10 Automatic circuit breakers (2F7, 3F1, 3F4)
28                                                                                   Installation                                                                                                                 PVmaster
                                      5.2 Installing PVM 450-068 and PVM 450-100
                                                                                    Connection           Temperature
                             Primary/secondary winding             Output [kVA]
                                                                                     symbol                sensor
PVM 450-068                             290 V / 400 V                    75              Yy                    KTY
PVM 450-100                             290 V / 400 V                   110              Yy                    KTY
Table 5.3 Technical data for external isolation transformer
                                         The external isolation transformer is connected to the supply via the terminal
                                         clamps (Fig. 5.8, 8):
                                        Danger of electric shock from live subassemblies!
                                        Up to three separately fused voltage supplies can be connected to the
                    Danger!
                                        PVmaster.
                                        • Before starting work, make sure that the plant is not live.
                                         •   Please refer to the table for information on the primary and secondary winding
                                             cable cross-sections in the external isolation transformer:
                                                   Cable cross-section
                             Primary winding (290 V)            Secondary winding (400 V)      Tightening torque [Nm]
                               Terminals 1, 2, 3, PE               Terminals 4, 5, 6, PE
                                     [mm2]                               [mm2]
PVM 450-068                                  50                               35                         6 ... 8
PVM 450-100                                  95                               70                        15 ... 20
Table 5.4 Terminal clamps for external isolation transformer
                                         •   Feed the cables through the cable opening (Fig. 5.8, 1) in the base of the
                                             enclosure.
                                         •   Connect the primary end of the transformer to the terminals
                                             (Fig. 5.8, 8) 1/L1, 2/L2, 3/L3 and PE.
                                         •   Connect the secondary end of the transformer to the terminals (Fig. 5.8, 8)
                                             4/L1, 5/L2, 6/L3 and PE.
                                         •   Connect the KTY sensor to terminal X3.
                                         •   Fasten the cables to the clamping rail (Fig. 5.8, 3) to take the strain.
PVmaster                                                       Installation                                               29
                         5.2 Installing PVM 450-068 and PVM 450-100
                                                                                                          LOCK
                                                                                                          CF
                                                                                                                                    Powe
                                                                                                                                    COM r
                                                                                                                                    Data
                                                                                                                                    Statu
                                                                                                                                         s
                                                                                                                                  Rese
                                                                                                                                         t
RJ-45/Line
                                                                                                                                             RS 232
                            0       1
                            OF      ON
                              F
                                                          0     1
                                                          OF    ON
                                                            F
                  2
                                                                     0
                        6
                                                                                0     1
                                                                                OF    ON
                                                                                  F
9 0
                                                                                               0     1
                                                                                               OFF   ON
                                Legend
                                2   Terminal clamp, DC (L+) from PV generator
                                6   Terminal clamp, DC (L-) from PV generator
                                9   Terminal clamp, protective earth conductor (PE)
                                The photovoltaic generator is connected to the supply via the DC main switch
                                (Fig. 5.7, 12).
                             Danger of electric shock from live subassemblies!
                             Up to three separately fused voltage supplies can be connected to the
             Danger!
                             PVmaster.
                             • Before starting work, make sure that the plant is not live.
30                                                      Installation                                                                                       PVmaster
                                   5.2 Installing PVM 450-068 and PVM 450-100
           1
           ON                                                                          0
                                                                                       OF
                                                                                             1
                                                                                             ON
                                                                                         F
                                                                                                          0     1
                                                                                                          OFF   ON
                   0
                                                                                                                     0
                                   0         1
                                   OF        ON
                                     F
                                                          NP
                                                      0     E
                       2T1
                             4T2
                                    6T3
                                                  7
                                                      8
                                                          9
                                         Legend
                                         2T1 Terminal clamp L1 for the supply network 7               Terminal clamp for neutral conductor (N)
                                         4T2 Terminal clamp L2 for the supply network 8               Bridge (TN C)
                                         6T3 Terminal clamp L3 for the supply network 9               Terminal clamp, protective earth conductor (PE)
                                         The public supply network is connected to the supply via the AC main switch
                                         (Fig. 5.7, 15):
                                         Danger of electric shock from live subassemblies!
                                         Up to three separately fused voltage supplies can be connected to the
                Danger!
                                         PVmaster.
                                         • Before starting work, make sure that the plant is not live.
PVmaster                                                         Installation                                                                    31
     5.2 Installing PVM 450-068 and PVM 450-100
32                       Installation                                       PVmaster
                         5.2 Installing PVM 450-068 and PVM 450-100
                                                                                                         Powe
                                                                                                         COM r
                                                                                                         Data
                                                                                                         Statu
                                                                                                              s
                                                                                                       Rese
                                                                                                           t
RJ-45/Line
                                                                                                                  RS 232
                    1                                       0
                                                            OF
                                                                  1
                                                                  ON
                                                              F
N 0
                                                                                                                           1
                   PE
                                                                           0
                                                                           OFF
                                                                                 1
                                                                                 ON
                                                                                                                               4
                                                                                                                                   7
                                                                                      0
                                                                                                                                       2
                                                                                                                                           5
                                                                                                                                               8
                                                                                                                                                   3
                                                                                                                                                       6
                                                                                                                                                           9
                                                                                                                                                               N
                                                                                                                                                                   N
                                                                                                                                                                       N
10
                           Legend
                           1   Terminal clamp L1 (X5.1/1)
                           N Terminal clamp for neutral conductor (X5.1/N)
                           PE Terminal clamp for protective earth conductor (X5.1/PE)
                           10 Bridges, change of voltage supply (X5)
                           Note
                           The auxiliary voltage supply can only be connected to a TN S network (five-wire
                           system).
PVmaster                                         Installation                                                                                                              33
                                 5.2 Installing PVM 450-068 and PVM 450-100
                                         •        Change over the bridge (Fig. 5.11, 10) on terminals 1 and 4 to terminals 4 and
                                                  7.
                                         •        Change over the bridge (Fig. 5.11, 10) on the N terminals accordingly.
                                         •        Identify the cable cross-section as dictated by local conditions. This depends
                                                  on cable protection, ambient temperature and installation method.
                                         •        Feed the AC cables through the cable opening (Fig. 5.7, 18) in the base of the
                                                  enclosure.
Z1 G1 L1 C1 T1 Z2 2Q2 VN
                                                                                                                                  L1
                =
                                                                                                                                  L2
                     ~                                                                                                            L3
                                                                                                                                  N
                                                                                                                                  PE
                                                                                         1   2   3    N
                                                                                                                 X5
                                                                                         4   5   6    N                     HS (X5.1)
                                                                                                             4        7                  16 A
                                                                                                                                  1
                         1
                             4
                                 7
                                     2
1Q1                                      5
                                              8
                                                  3
                                                      6                                                     N         N
                                                          9                                                                       N
                                                              N
                                                                  N
                                                                      N                                                           PE
      PV
                                                                                                 PP
                                     X5
                                         Legend
                                         PV Photovoltaic generator                  Z2 EMC filter
                                         1Q1 DC main switch                         2Q5 AC main switch
                                         Z1 EMC filter                              VN Supply network
                                         G1 Inverter                                HS Connection for auxiliary voltage (X5.1)
                                         L1 Inductor                                X5 Bridges, change of voltage supply (X5)
                                         C1 Capacitor                               PP Peripheral devices for PVmaster
                                         T1 Transformer
                                         •        Screw the protective earth cable (PE) to the terminal clamp (Fig. 5.11, PE).
                                         •        Screw the L1 cable to the terminal clamp (Fig. 5.11, 1).
                                         •        In the case of a TN S network, screw the neutral conductor (N) to the terminal
                                                  clamp (Fig. 5.11, N) and remove the bridge.
                                         •        Fasten the cables to the clamping rail (Fig. 5.7, 17) to take the strain.
34                                                                        Installation                                                PVmaster
                     5.3 Installing external automatic disconnection device
                           •   Disconnect the PVmaster (Section 6.2, p. 42) and verify safe isolation from the
                               supply.
                           •   Install the external disconnection device.
                           •   Switch on the key-operated control voltage switch, e. g. PVM 450-033
                               (Fig. 5.1, 16).
                           •   Switch on the AC main switch if using an internal power supply.
                           •   Switch off the internal mains monitoring device:
                               • WebVisualization: Navigate to the menu: Mains monitoring and set the
                                  Monitoring switch to Off.
                               • Touchscreen display: Navigate to the menu: Configuration > AC limit
                                  values and set the Monitoring switch to Off.
                           Note
                           • Switch off the key-operated control voltage switch.
                           •   Disconnect the PVmaster (Section 6.2, p. 42) and verify safe isolation from the
                               supply.
                           •   Using an Ethernet cable, connect a PC to the communication module, e. g.
                               PVM 450-033 (Fig. 5.1, 13). Feed the cable through the
                               opening (Fig. 5.1, 1) in the base of the enclosure as the PVmaster must be
                               enclosed if using an internal control voltage supply.
                           •   Switch on the key-operated control voltage switch (Fig. 5.1, 16).
                           •   Switch on the AC main switch if using an internal power supply.
                           The communication module is configured at the factory with IP address
                           192.168.31.200. The IP address of the PC must be in the same range, e.g.
                           192.168.1.10. Deactivate any proxy server which may be configured in the
                           browser settings.
                           • Call up the following address in a browser: http://192.168.31.200.
PVmaster                                      Installation                                                  35
         5.4 Start the communication module
36                    Installation                                   PVmaster
             5.4 Start the communication module
           Note
           • Switch off the key-operated control voltage switch again.
PVmaster                     Installation                                                37
            5.5 Connecting power reduction and S0 interface of electricity meter
                            7A3        1
                                                                                           PWR
                                                                                           LOCK
                                                                                           CF
                                           I1
                                           I2                                                                    Powe
                                                                                                                 COM r
                                                                                                                 Data
                                                                                                                 Statu
                                                                                                                      s
                       I1         I2
                                                                                                               Rese
                                                                                                                      t
RJ-45/Line
                                                                                                                          RS 232
                    +24 V         +24 V
+24 V +24 V
                       I3         I4       I4
                                           I3
                                                         0     1
                                                         OF    ON
                                                           F
                                                         +
                                                                    –       0
                                                                            OF
                                                                                  1
                                                                                  ON
                                                                              F
                             Legend
                             1   Ripple control receiver (e.g. with 4 relays)
                             I1 Relay 1
                             I2 Relay 2
                             I3 Relay 3
                             I4 Relay 4
38                                                  Installation                                                                   PVmaster
              5.5 Connecting power reduction and S0 interface of electricity meter
7A2 PWR
                                                                                         LOCK
                                                                                         CF
                                                                                                               Powe
                                                                                                               COM r
                                                                                                               Data
                                                                                                               Statu
                                                                                                                    s
                                                                                                             Rese
                                                                                                                    t
RJ-45/Line
                                                                                                                        RS 232
                                   S0+   +24 V
                                   S0–
I3
                                                       0     1
                                                       OF    ON
                                                         F
                                                       +
                                                                  –       0
                                                                          OF
                                                                                1
                                                                                ON
                                                                            F
                           Legend
                           1   Meter of system operator
                           •   Switch the S0 interface on and set the weighting of the electricity meter.
                               – WebVisualization: Yield > S0 interface > Enable S0/S0 gain
                               – Touchscreen display: Status & values > AC values > Yield > Yield
                                 calculator (lock symbol) > S0 interface/gain
PVmaster                                         Installation                                                                    39
     5.5 Connecting power reduction and S0 interface of electricity meter
40                               Installation                               PVmaster
                            6.1 Switching on the PVmaster
6 Operation
                     Legend
                     1   AC main switch
                     2   DC main switch
                     3   Enable inverter
PVmaster                                   Operation                            41
                            6.2 Switching off the PVmaster
                     Note
                     Always follow this procedure when switching off the equipment in order to prevent
                     unnecessary fault messages appearing on the PVmaster.
42                                      Operation                                            PVmaster
                                    6.3 Operation indicator lamps
                            Legend
                            1   Red LED
                            2   Blue LED
                            3   Yellow LED
                            4   Green LED
PVmaster                                             Operation                                           43
                     6.3 Operation indicator lamps
               The operating state of the PVmaster is indicated via red, blue, yellow and green
               LEDs. A detailed description of operation can be found in Section 7.
                              Off
                              – The PVmaster is switched off but not deenergised!
                              Quiescent state
                              – The photovoltaic inverter only is switched on.
                              – The intermediate circuit of the inverter is supplied by the PV
                                generator.
                              – When the generator voltage on the intermediate circuit
                                exceeds a threshold value, the controller cuts in and the power
                                is measured.
                              Power measurement
                              – The controller measures the photovoltaic generator output (at
                                140-second intervals according to the factory setting)
                              – If the PV generator output exceeds the internal power
                                consumption of the PVmaster, the controller switches to
                                MPPT-regulated mode.
                              MPPT-regulated mode
                              – In MPPT-regulated mode, the maximum possible power is
                                taken from the PV generator and fed into the supply network.
                              Shut-down procedure
                              – The PV generator output drops below the internal power
                                consumption of the PVmaster and nothing is fed into the
                                supply network.
                              – The controller measures the PV generator output (three times
                                at 140-second intervals according to the factory setting).
                              – If the PV generator output power stays below the internal
                                power consumption of the PVmaster, the PVmaster switches
                                to quiescent state.
                              – If the PV generator output power exceeds the internal power
                                consumption of the PVmaster, the PVmaster switches to
                                MPPT-regulated mode.
                              Fault notification
                              – The PVmaster reports a fault.
                              – The fault can be acknowledged automatically or manually.
                              A detailed description of the fault messages can be found in
                              Section 9.
44                               Operation                                         PVmaster
                                 6.3 Operation indicator lamps
6.3.2 WebVisualization
                         The RJ45 socket allows operating states and PVmaster readouts to be displayed
                         locally on the PC.
                         Note
                         This is only possible if Java Runtime Environment 1.6.0.x (or higher) is installed.
                                                                                  1
                                                          1
                         Legend
                         1   RJ45 socket
                         Note
                         The parameters of the PVmaster are set at the factory for optimum operation in
                         standard conditions. Arbitrary changes to the parameters can result in lower
                         efficiency or automatic shutdown. The settings should only be changed by trained
                         and skilled personnel. The factory settings can be loaded by carrying out a reset
                         process (Section 9).
                         The menu is subdivided into three user levels:
                         0 Administrator, parameter adjustment by manufacturer, password required
                         1 Expert, parameter adjustment by operator, password required
                         2 Observer, parameter display
PVmaster                                      Operation                                                  45
              6.3 Operation indicator lamps
                                         Designation                          Description
     Status
                   Global status
                                   Status word                              Tab. A.1
                                   Error word                               Tab. A.2
                   Local status
                                   Status word                              Tab. A.3
                                   Error word                               Tab. A.4
     Yield
                   Prognosis counter                                        Tab. A.5
                                   Daily yield
                                   Monthly yield
                                   Annual yield
                                   User yield
                                   Reset
                                   System yield
                                   CO2 saving
                   S0 interface                                             Tab. A.6
                                   Enable S0
                                   S0 pulse
                                   S0 gain
     AC values
                   AC phase values                                          Tab. A.7
                                   Phase L1 ... L3
                                                   Veff
                                                   Ieff
                                                   f
                                                   Pac
                                                   cosPhi
                   AC total/average values                                  Tab. A.8
                                   Veff
                                   Ieff
                                   f
                                   Pac
                                   cosPhi
                                   Daily max. power
     DC values
                   DC values                                                Tab. A.9
                                   Vg0
                                   Vdc_act
                                   Idc_act
                                   Pdc_act
                                   Pdc limit active
                                   Vdc_ref
                                   Pdc_max
                                   Active limit
     Temperature
                   Temperatures                                             Tab. A.10
                                   Filter choke
                                   PSU interior
                                   PSU heatsink
                                   Transformer
                                   Cabinet fan (user level 1)
                   DC power derating                                        Tab. A.11
                                   Derating active
                                   Level 1, 2
                   Temp. Configuration (user level 1)
                                   Cabinet fan                              Tab. A.12
                                                   Switch-on threshold
                                                   Hysteresis
                                   Derating parameters                      Tab. A.13
                                                   Level 1, 2,
                                                   Overtemperature values
                                                   Derating factors
     Table 6.1 TWebVisualization menu structure
46                             Operation                                          PVmaster
                    6.3 Operation indicator lamps
                                               Designation                                 Description
           Grid monitoring
                         Test OP                                                         Tab. A.14
                         Enable                                                          Tab. A.14
                         AC limit values                                                 Tab. A.15
                                         System voltage Veff
                                         System frequency fN
                         Power Reducer                                                   Tab. A.16
                                         Enable
                                         reducer active
                                         Active limit
                                         Analogue input
                                                          Analogue input
                                                          Pdc limit
           Data logger
                         FTP client status                                               Tab. A.17
                                         Run
                                         Busy
                                         Load OK
                                         Error
                         Data logger for online portal                                   Tab. A.18
                                         Data cycle time
                                         File creation/upload
                                                          Daily
                                                          or after X min
                                         „Meter“ file
                                         FTP client                                      Tab. A.19
                                                          FTP client status
                                                                           RUN
                                                                           Busy
                                                                           Load OK
                                                                           Error
                                                          Err.-Message
                                                          Target server
                                                                           Server name
                                                                           Server path
                                                          Upload requests (data files)
                                                          Upload requests (info files)
                                                          Test upload (user level 1)
                                                          Reset (user level 1)
           Errors
                         Active errors                                                   Tab. A.20
                                         Error PSU: ID/Loc
                                         BUS Watchdog
                                         Insulation fault
                                         Overvoltage
                                         System frequency error
                                         External error
                                         Overtemp.: Transformer
                                         Overtemp.: Filter choke
                                         Overtemp.: PSU interior
                                         Overtemp.: PSU heatsink
                         Unacknowledged error state                                      Tab. A.20
                         Manual reset
                         Automatic reset                                                 Tab. A.22
                                         Num. of attempts
                                         Automatic reset not possible
                         Active errors                                                   Tab. A.23
                                         System voltage error: L1, L2, L3
                         Parameters                                                      Tab. A.24
                                         Auto reset delay
                                         Reset timer „attempts“
                                         Acknowledgement attempts
           Table 6.1 TWebVisualization menu structure
PVmaster                            Operation                                                        47
             6.3 Operation indicator lamps
                                     Designation                        Description
     Parameters
                  Modell                                              Tab. A.25
                  Serial number (PVmaster unit)
                  Serial number                                       Tab. A.26
                  Software Rev.
                  UTC-Offset
                  Language
                  User level
     Table 6.1 TWebVisualization menu structure
48                          Operation                                       PVmaster
                  6.3 Operation indicator lamps
           Changing parameters
           Example: Switching on the enclosure fan manually
           • Click on Parameters.
           The parameters will be displayed.
           Note
           Please note that the password is case-sensitive.
PVmaster                     Operation                                                49
            6.3 Operation indicator lamps
50                      Operation                                          PVmaster
                                    6.3 Operation indicator lamps
                            Legend
                            1   Touchscreen
                            2   Buttons
                            3   Operating state coloured boxes (red, blue, yellow, green)
                            Note
                            The parameters of the PVmaster are set at the factory for optimum operation in
                            standard conditions. Arbitrary changes to the parameters can result in lower
                            efficiency or automatic shutdown. The settings should only be changed by trained
                            and skilled personnel. The factory settings can be loaded by carrying out a reset
                            process (Section 9).
PVmaster                                          Operation                                                   51
              6.3 Operation indicator lamps
                                             Designation                                  Description
     Status & Values (user level 0)
                   DC values                                                            Tab. A.27
                                     Generator voltage Vdc > graph
                                     Generator current Idc > graph
                                     Generator power Pdc > graph
                                     Daily curve > graph
                                     Limitation                                         Tab. A.28
                                                    Actual „power reducer“ limit
                                                    Temperature depend. derating
                                                    Active limit
                                                    Power reducer                       Tab. A.29
                                                                    Enable
                                                                    Dig. input 1 to 4
                                                                    Reducer active
                                                    Temp. dep. derating                 Tab. A.33
                   AC values                                                            Tab. A.30
                                     Phase voltage Vac > graph
                                     Phase current Iac > graph
                                     Active power Pac > graph
                                     System frequency f
                                     Power factor cos ϕ
                                     Yield                                              Tab. A.31
                                                    Daily yield
                                                    Monthly yield
                                                    Annual yield
                                                    System yield
                                                    Configuration (user level 1)        Tab. A.31
                                                                    (user level 2)
                                                                    New value
                                                                    Correction factor
                                                                    Daily yield
                                                                    Monthly yield
                                                                    Annual yield
                                                                    System yield
                                                    S0 interface (user level 1)         Tab. A.31
                                                                    S0 interface
                                                                    S0 pulse
                                                                    Gain
                                                    CO2 savings                         Tab. A.31
                                                    Daily maximum
                                                    User yield
                                                    Reset
                   Temperature                                                          Tab. A.32
                                     Control cabinet Transformer > graph
                                     Control cabinet Filter choke > graph
                                     Inverter Interior > graph
                                     Inverter Heatsink > graph
                                     Derating, temperature-dependent                    Tab. A.33
                                                    „Derating“ active
                                                    Level 1
                                                    Level 2
                                                    Actual „Derating“
                                                    Configuration (user level 2)        Tab. A.33
                   Status inverter                                                      Tab. A.34
                                     Status word
                                     Control word
     Table 6.2 Touchscreen display menu structure
52                             Operation                                                      PVmaster
                    6.3 Operation indicator lamps
                                                 Designation                        Description
           Configuration (user level 0)
                          Panel                                                   Tab. A.35
                                           System language
                                           Time zone
                          AC limit values                                         Tab. A.36
                                           Voltage Veff
                                           Frequency f
                                           Monitoring
                                           E.ON-Check
                          Automatic acknowledgement                               Tab. A.37
                                           Acknowledgement attempts
                                           Acknowledgement not possible
                                           ErrResetDelay
                                           NoErrTime
                                           No. of trials
                          Pdc limitation                                          Tab. A.38
                                           Max. DC power
                                           Limit active
                          Data logger
                                           Configuration                          Tab. A.39
                                                           Logger cycle time
                                                           File upload
                                           FTP client                             Tab. A.40
                                                           Client ready
                                                           Client active
                                                           Upload okay
                                                           Error
                                                           Reset
                                                           Test upload
                                           Server (user level 2)                  Tab. A.41
                                           Login (user level 2)                   Tab. A.41
                          Factory settings                                        Tab. A.42
                                           Set parameter values to default
                                           Set energy values to default
                                           Delete trend data
                          AC measurement (user level 2)                           Tab. A.43
                          DC measurement (user level 2)                           Tab. A.43
                          Start-up procedure (user level 2)                       Tab. A.43
                          MPP-Tracking (user level 2)                             Tab. A.43
                          Shut-down procedure (user level 2)                      Tab. A.43
                          Fan control (user level 1)                              Tab. A.44
                                           Start-up threshold inverter interior
                                           Start-up threshold inverter heatsink
                                           Start-up threshold transformer
                                           Start-up threshold filter choke
                                           Hysteresis inverter interior
                                           Hysterese inverter heatsink
                                           Hysterese transformer
                                           Hysterese filter choke
                                           Operation
                                           Auto/On
                          Temperature cut-out (user level 2)                      Tab. A.45
                          Manual control (user level 2)                           Tab. A.45
           Diagnosis                                                              Tab. A.46
           Info
                          Serial number
                          Modell/type
                          Software rev.
           Table 6.2 Touchscreen display menu structure
PVmaster                              Operation                                               53
           6.3 Operation indicator lamps
                                        •   Touch the
                                            Graph      button to the right of the
                                            generator output (Pg).
                                        The generator output graph will appear.
     Changing parameters
     Example: Setting the time zone
                                        •   Navigate to the menu: Configuration >
                                            Terminal > Terminal [2] (next).
54                     Operation                                           PVmaster
                 6.3 Operation indicator lamps
                                             Note
                                             Please note that the password is case-
                                             sensitive. You can change this using the
                                             and     buttons.
                                             If no operations are carried out for one
                                             minute, the display will revert to the lowest
                                             user level.
                                             •   Touch the Auto/On button.
                                             The On indicator lamp will light up if the fans
                                             are on.
PVmaster                    Operation                                                    55
                6.4 Testing the internal automatic disconnection device
56                                        Operation                                         PVmaster
                    6.5 Copying files from the compact flash card
                                                            PW
                                                              R
                                                            LO
                                                               CK
                                                            CF
                      Note
                      The compact flash card folder structure must be retained.
                      Note
                      The online monitoring portal can only be accessed with the memory card plugged
                      in.
PVmaster                                    Operation                                            57
     6.5 Copying files from the compact flash card
58                    Operation                      PVmaster
                                               7.1 Block schematic diagram
7 Description of operation
G1 L1 C1 T1 Z2 K1 2Q5 VN
                                     S1
    Z1
                                              P4   C°
                P1                                              P3   C°
I DC
                       H2
                       Ω
                                                                                P2    iL1 iL2 iL3
                            H1                                                                      uL1
                                                                                                    uL2
                                                                                                    uL3
    1Q1
                                                    GE
PV
                                      Legend
                                      PV Photovoltaic generator             T1 Transformer
                                      1Q1 DC main switch                    Z2 EMC filter
                                      H1 Overvoltage protection device      K1 Load contactor
                                      H2 Insulation monitor (optional)      2Q5 AC main switch
                                      P1 Current transformer                VN Supply network
                                      Z1 EMC filter                         P2 Measurement device
                                      S1 Controller                         P3 Temperature sensor
                                      G1 Inverter                           P4 Temperature sensor
                                      L1 Inductor                           GE Communication module
                                      C1 Capacitor
                                      The photovoltaic generator is connected to the supply via the DC main switch
                                      (1Q1). The insulation monitor (H2), overvoltage protection device (H1), current
                                      transformer (P1) and EMC filter (Z1) are arranged between the DC main switch
                                      and the inverter (G1).
                                      Earthing is required with certain PV generator module types:
                                      – Negative grounding: thin-film modules
                                      – Positive grounding: modules with rear contact cells
                                      The earthing is done internally on PVmasters using isolation transformers.
                                      The insulation monitor (H2) monitors the DC-side IT system. If the insulation
                                      resistance falls below the set value, the controller (S1) interrupts the operation of
                                      the PVmaster and sends an alarm signal. The overvoltage protection device (H1)
                                      limits high induced overvoltages which can arise from lightning, switching
                                      operations and atmospheric disturbances. If a unit is defective, this is signalled to
                                      the controller via an internal contactor in the overvoltage protection device. This
                                      does not affect the operation of the PVmaster. The EMC filter (Z1) prevents any
                                      interference from the inverter on the DC side.
                                      All the operations of the PVmaster are regulated and controlled via the internal
                                      controller (S1). The parameters of the controller, as explained in Section A, are
                                      freely configurable. Logbook data from the controller can be transmitted via the
                                                   PVmaster
                                                     OFF
                                         V DC            V DC
                                       > 400V          < 250V
                                                   Controller
                                                      ON
                                                                              Power measurement
                                                                              3 x unsuccessful
           Parameter: Vdc_start   Parameter: Vdc_min                          Parameter: Cycles
                                                   Power
                                                 measurement
Parameter: Vdc_start
                                                                           Output power
                                                      MPPT                 measurement again /
                                                      mode                 Line contactor
                                                                           remains closed
                          PAC ≤ 0W
                          Parameter: Tab_delay
                                                   Shut-down
                                                   procedure
           The PVmaster comes out of its quiescent state when the voltage of the
           photovoltaic generator exceeds 400 V. The internal power supply unit starts
           oscillating and the controller powers up. If the generator voltage exceeds
           Vdc_min, the performance test is carried out. If the performance test is
           unsuccessful, it is repeated after 140 seconds. If the measurement is successful,
           the regulator is activated and MPPT-regulated mode is started. If the generator
           power falls to zero watts or if power is absorbed by the PVmaster, the latter starts
           the shut-down procedure. The shut-down procedure contains three power
           measurements, 140 seconds apart. During this time, the line contactor remains
           closed. If these three measurements are unsuccessful, the line contactor isolates
           the PVmaster from the supply network and the regulator is deactivated. If the
           generator voltage falls below 250 V, the internal power supply unit cuts out and
           the PVmaster switches off.
                      The inspection may only be carried out by the operator or by a person authorised
           Caution!
                      by the operator.
                      If there is a defect, the plant must not be put into operation again. Arrangements
           Caution!
                      should be made to have the PVmaster checked by a specialist company.
PVmaster                                 Inspection                                                     63
     Carry out a visual and mechanical inspection every month in order to prevent
     interruptions caused by faults:
     • Check the operation of the fan by starting it manually (Table A.44, 9).
     • Switch off the PVmaster (Section 6).
     • Check the enclosure, the components and the fuses for any signs of
         discolouring or damage. Discolouration of components indicates damage due
         to overheating or corrosion and means that the components must be replaced.
     • Check the filter in the air supply opening (Fig. 2.2, 8).
         Clean or change the filter if it is heavily soiled (accessories, Rittal GmbH & Co.
         KG).
     Carry out a mechanical inspection every six months in order to prevent
     interruptions caused by faults.
     • Switch off the PVmaster (Section 6).
     • Disconnect the DC line from the photovoltaic generator.
     • Disconnect the AC line from the supply network.
     • Disconnect the AC line from the auxiliary supply.
     • Make sure that the plant is not live.
     • Check the threaded cable connections to make sure that they are firmly
         seated. Thermal stresses can cause screwed connections to work loose over
         time. Retighten the threaded connections where necessary.
64                      Inspection                                            PVmaster
                                                 9.1 Description of fault
9 Troubleshooting
                                                                                                                  Acknow-
                    Fault                        Possible cause                           Remedy
                                                                                                                 ledgement
 Inverter fault                         -                                      Please contact the                Automatic
                                                                               LTi helpline.
 Bus Watchdog fault                     Fault in internal bus system           Please contact the                Automatic
                                                                               LTi helpline.
 Overvoltage (lightning protection)     Overvoltage protection is defective.   Replace the defective protection Automatic
                                                                               module (DEHNguard T440).
 Insulation fault                       Insulation resistance has dropped      Check the insulation resistance   Manual
                                        below the critical value. The          of the PV generator.
                                        PVmaster shuts down.
 Overheating                            The transformer has overheated.        Provide sufficient heat           Manual
 Transformer                                                                   discharge facilities.
 Overheating                            The filter inductor has overheated.    Provide sufficient heat           Manual
 Filter inductor                                                               discharge facilities.
 Inverter interior overheating          The inverter has overheated.           Provide sufficient heat           Manual
                                                                               discharge facilities.
 Inverter heat sink overheating         The heat sink has overheated.          Provide sufficient heat           Manual
                                                                               discharge facilities.
 Unacceptable voltage L1 ... L3         The supply voltage is outside the      If the fault persists please      Automatic
                                        limits.                                contact your network provider.
 Unacceptable frequency                 The line frequency is outside the      If the fault persists please      Automatic
                                        limits.                                contact your network provider.
Table 9.1 Fault messages
PVmaster                                              Troubleshooting                                                        65
                                         9.2 Resetting faults
9.2.1 WebVisualization
                            The faults can be reset manually on the touchscreen display as follows:
                            • Go to Diagnosis in the menu.
                            • Remedy the fault indicated.
                            • Acknowledge the fault message by touching Manual acknowledgement.
                            The faults can be acknowledged and the list deleted by touching Delete      (user
                            level 2).
You can hide or show the time stamps for the faults using the Clock button.
Caution! Do not carry out a reset without consulting your project engineer.
66                                         Troubleshooting                                          PVmaster
                                  9.4 LTi helpline
                   Germany                            France
                   LTi DRiVES GmbH                    LTi DRiVES GmbH
                   Heinrich-Hertz-Str. 18             260 Rue Denis Papin
                   59423 Unna                         54710 Ludres
                   Tel.: +49-23-03 7 79 - 0           Tel.: +33-383 26 40 99
                   Fax: +49-23-03 7 79 - 3 97         Fax: +33-383-26 79 23
                   pvmaster@lt-i.com                  Info-fr@lust-tec.com
                   www.lt-i.com                       www.lt-i.com
                   Italy                              Spain
                   LTi ITALiA srl                     SAIN AUTOMATIZACIÓN SOLUTIONS, S. L.
                   via F. lli Rosselli 3/29           Carretera N-151, de Girona-Anglès, km 106
                   20019 Settimo Milanese (MI)        17163 Vilana-Bescanó (Girona)
                   Tel.: +39-0-2-33 51 48 96          Tel.: +34-972 100 619
                   Fax: +39-0-2-33 54 98 76           Fax: +34-972 442 317
                   info.italia@lt-i.com               info@sainsl.com
                   www.lt-i.it                        www.sainsl.com
                   Switzerland
                   LTi DRiVES GmbH
                   Rte. des Arsenaux 41
                   1705 Fribourg
                   Tel.: +41-(0)-44 440 66 60
                   Fax: +41-(0)-26 422 14 88
                   Technoparkstraße 1
                   8005 Zürich
                   Tel.: +41-(0)-44 440 66 60
                   Fax: +41-(0)-26 422 14 88
                   info@lt-i.ch
                   www.lt-i.ch
PVmaster                          Troubleshooting                                                67
     9.4 LTi helpline
68   Troubleshooting    PVmaster
                   A.1 Description of WebVisualization parameters
A Appendix
                      Note
                      The parameters of the PVmaster are set at the factory for optimum operation in
                      standard conditions. Arbitrary changes to the parameters can result in lower
                      efficiency or automatic shutdown. The settings should only be changed by trained
                      and skilled personnel. The factory settings can be loaded by carrying out a reset
                      process (Section 9, p. 65).
                      The following paramaters can be viewed via the menu (user level 2):
                        No.                    Designation                                   Description
                              Status word                             -
                         0    PLC ready                               -
                         1    Parameter changed                       -
                         2    Default values                          -
                         3    Error list deleted                      -
                         4    Energy values cleared                   -
                         5    Trend data deleted                      -
                         6    Power reduction relay 1                 -
                         7    Power reduction relay 2                 -
                         8    Power reduction relay 3                 -
                         9    Power reduction relay 4                 -
                         10   - Reserve -                             -
                         11   - Reserve -                             -
                         12   - Reserve -                             -
                         13   - Reserve -                             -
                         14   - Reserve -                             -
                         15   - Reserve -                             -
                      Table A.1 Status > global status, status word
PVmaster                                           Appendix                                                       69
     A.1 Description of WebVisualization parameters
70                                  Appendix                                                              PVmaster
           A.1 Description of WebVisualization parameters
PVmaster                                 Appendix                                                                    71
     A.1 Description of WebVisualization parameters
72                                  Appendix                                                                    PVmaster
           A.1 Description of WebVisualization parameters
PVmaster                                 Appendix                                                                               73
     A.1 Description of WebVisualization parameters
74                               Appendix                                                 PVmaster
                  A.2 Description of touchscreen display parameters
                      Note
                      The parameters of the PVmaster are set at the factory for optimum operation in
                      standard conditions. Arbitrary changes to the parameters can result in lower
                      efficiency or automatic shutdown. The settings should only be changed by trained
                      and skilled personnel. The factory settings can be loaded by carrying out a reset
                      process (Section 9, p. 65).
                      The following paramaters can be viewed via the menu (user level 0):
                        No.         Designation                Unit                                 Description
                         1    Vdc                      V                Present generator voltage
                         2    Idc                      A                Present generator current
                         3    Pdc                      kW               Present generator output
                         4    Daily curve                               Generator output as daily trend graph
                      Table A.27 Status & values > DC values
PVmaster                                          Appendix                                                                            75
     A.2 Description of touchscreen display parameters
76                                   Appendix                                                                PVmaster
                                   A.2 Description of touchscreen display parameters
PVmaster                                                           Appendix                                                                              77
                                          A.2 Description of touchscreen display parameters
78                                                                        Appendix                                                                      PVmaster
           A.2 Description of touchscreen display parameters
PVmaster                              Appendix                                                                        79
     A.2 Description of touchscreen display parameters
80                       Appendix                        PVmaster
LTi DRIVES GmbH
Heinrich-Hertz-Str. 18
59423 Unna
GERMANY
Tel. +49 (0) 23 03 / 7 79 -0
Fax +49 (0) 23 03 / 7 79 -3 97
www.lt-i.com
pvmaster@lt-i.com