Genesis Range
Auto Reclose Relay  Single Shot
Cut-Out Details
Ordering Information
Description
1. Auxiliary supply rating in DC
The relay is suitable for single and three phase auto reclosing
2. Optically isolated (status) inputs rating in DC
The relay consists of five modules viz. Front fascia, power supply,
two relay & status module and microcontroller module. All the
modules are housed in a compact 3N Non draw-out case
3. Timer range  Standard or Optional
Qualification
Microcontroller does the sequence control and timing function.
Different operating functions and time setting are selected by
the DIP-Switches on the relay front fascia.
ISO 9001-2000
Case
There is a watch-dog timer in the relay which continuously
monitors the program, put off POWER ON indication and closes
annunciation contact in case the watch dog timer elapses.
3N-Non draw out with 27 terminals
PART
01
CASE
SIZE
3N
CUT OUT
A
B
104
140
BEZEL
C
D
128
170
Inputs
Two optically isolated inputs are provided to take the single
phase or three phase protection operated contact inputs to
initiate the auto reclose relay.
Note:
1. All dimensions are in mm
2. All dimensions are measured equidistant from centre line
3. Maximum depth of equipment inside panel : 200mm
MART113
When the external blocking input is initiated, the reclose function
is blocked and it energise external blocking LED, Lockout LED
and Lockout relay.
As the relay is suitable for single shot auto reclose, at the time
of first reclosing if the fault persists or further fault develops
within the reclaim time it will energises the lockout relay and its
LED indication.
Before the reclaim time elapses if the second fault occurs the
relay goes to lockout
Applications
 Transmission lines
 Distribution circuits
 Single phase and three phase breaker reclosing schemes
In addition, one permit input is given which when energized
from check synchronizing or dead line charging function
interlocked with the breaker status permits the auto reclose
The reclose function is get blocked when the external blocking
input is initiated.
Reclose Timer
The policy of Easun Reyrolle is one of continuous improvement and development. The company therefore reserves the right to supply equipment, which may
differ slightly from that described and illustrated in this publication.
#98, Sipcot Industrial Complex,
Hosur 635 126, India.
Tel: +91 4344 401600/01/02
Fax: +91 4344 276397
SWITCHGEAR WORKS
Ernavur,
Chennai-600 057, India.
Tel: +91 44 25733715/358
Fax: +91 44 25733468
Email: switchgear@easunreyrolle.net
FACT/MART 113/12-05/REV 0
HOSUR WORKS
BANGALORE WORKS
#17/3 Arakere,
Bannerghatta Road,
Bangalore-560 076, India.
Tel: +91 80 26581023 / 3268
Fax: +91 80 26580642
Email: blrworks@easunreyrolle.net
AUTOMATION DIVISION
Ashirwad, #25, 29th Main,
4th B Cross, BTM Layout 2nd Stage,
Bangalore-560 076, India.
Tel: +91 80 26685496/51311405
Fax: +91 80 26685446
Email: smabp@easunreyrolle.net
EXPORTS DIVISION
#17/3 Arakere,
Bannerghatta Road,
Bangalore-560 076, India.
Tel: +91 80 26581023 / 3268
Fax: +91 80 26580642
Email: exports@easunreyrolle.net
Delhi
Kolkata
Bangalore
Chennai
Secunderabad
Tel: +91 22 22022270/22855415
Fax: +91 22 22825703
Email: mumbai@easunreyrolle.net
Tel: +91 80 26685496/51311405
Fax: +91 22 26685446
Email: blroffice@easunreyrolle.net
Bhopal
Telefax: +91 755 2684221
Email: bhopal@easunreyrolle.net
Tel: +91 11 25747321/25747322
Fax: +91 11 25747320
Email: delhi@easunreyrolle.net
Tel: +91 44 24346425/24347608
Fax: +91 44 24346435
Email: chennai@easunreyrolle.net
There is the common reclaim timer. It operates in series with
the reclose timers. The over all reclaim time delay from relay
energisation to relay reset is therefore reclaim timer setting
plus reclose time.
When the reclose selector switch is in OFF mode any one of the
protection operated contact input initiation condition it will
energise the lockout relay and its LED indication and it blocks
the reclose function.
Tel: +91 33 22848320
Fax: +91 33 22848326
Email: kolkata@easunreyrolle.net
Telefax: +91 40 27817847
Email: hyderabad@easunreyrolle.net
Reclaim Timer
Lockout Function
Sales Offices
Mumbai
The relay having two reclose timers one for single phase reclose
another for three phase reclose. The both timers are selected
automatically depending upon the reclose selection
Corporate Office
Easun Reyrolle Limited. 98 Sipcot Industrial Complex
Hosur 635 126 India. Tel: +91 4344 401600/01/02
Fax: +91 4344 276397
www.easunreyrolle.com
Auto Reclose Relay  Single Shot  MART 113
Features
Protection
 Automatic tripped breaker reclosure
 Suitable for single phase and three phase reclosing
 Micro-controller based relay
Wiring Diagram
Switch setting = 20 to 27
Output Contacts
Single Phase Reclose Time  T2 secs.
The relay has 8 output contacts and 4 status inputs
 Reclose pulse relay
1 N/O
 Reclose pulse alarm relay
1 N/O
 Lockout relay
2 N/O
 Power on relay
1 N/C
 Three phase trip mode relay
2 N/C
 Auto reclose initiation relay
1 C/O
Range:0.1 to 25.5secs in steps of 0.1 sec
Three Phase Reclose Time  T1 secs.
Range: 0.1 to 25.5 secs in steps of 0.1 sec
Reclaim Time  T0 secs.
Control
Range: 1 to 255 secs in steps of 1 sec
The relay has 8 output contacts and 4 status inputs
 Reclose pulse relay
1 N/O
 Reclose pulse alarm relay
1 N/O
 Lockout relay
2 N/O
 Power on relay
1 N/C
 Three phase trip mode relay
2 N/C
 Auto reclose initiation relay
1 C/O
Reclose pulse time 1 Second fixed.
Monitoring
Seven LED on the relay front fascia Indicate
Optional Setting
 Green
For any Reclose and Reclaim
 Yellow
Single phase reclose is initiated
Timer Setting Range in Seconds
 Yellow
Three phase reclose is initiated
1. 0.25 to 63.75 in steps of 0.25
 Green
Single phase reclose is completed
2. 0.5 to 127.5 in steps of 0.5
 Green
Three phase reclose is completed
3. 1 to 255 in steps of 1
 Red
External Blocking signal is IN
Self-monitoring facility
4. 2 to 510 in steps of 2 and
 Red
Relay is in Lockout mode
User Interface
5. 4 to 1020 in steps of 4
 Dip switches for parameter setting
 LED indications
 Sealable front cover to prevent unauthorised access
Contact Rating
Reclose Pulse Contacts
Other Features
Make a Carry for 200msec
 Both DC and AC auxiliary supply available
 Compact design
 Non-drawout case
Technical Information
Rating
Power Supply Input Rating in DC (AUX.)
18 to 135V DC or 43 to 280 V DC
Optically Isolated Input Rating in DC (STATUS)
24V, 30V, 50V, 110V or 220V
Above 110V use external resistor
Reclose Selection
Reclose in OFF
Reclose in single phase
Reclose in three phase
Reclose in single and three phase
Time Settings
Standard Setting
Time setting (In seconds)=s x Multiples of setting
s= Sum of switch settings
Power supply is ON
Environmental
Temperature
IEC 60068-2-1/2
30A AC or DC with L/R >5msec
Operating Range
Humidity
Vibration (Sinusoidal)
Shock and Bump
Insulation
-100C to +550C
IEC 60068-2-3
IEC 60255-21-1 Class I
IEC 60255-21-2 Class I
IEC 60255-5
All Other Contacts
2.0KV rms for 1 min between all terminals and earth
Carry continuously 5A AC or DC
Make and carry  3A continuously / 250V DC Break
24V DC Resistive at 0.75Amps
48V DC Resistive at 0.5Amps
125V DC Resistive at 0.3Amps
250V DC Resistive at 0.2Amps
Burden
Power Supply Burden (AUX.)
Quotient Drain
Maximum Energised Drain
2W
8W
Optically Isolated Input Burden (STATUS)
Maximum Energised Drain
3W
Input, Outputs and Indications
Four Optically Isolated (STATUS) Inputs
Initiating signal input (From single phase protective relay
contact)
External blocking signal input
Initiating signal input (From three phase protective relay
contact)
Reclose permit input (From breaker contacts etc.)
2.0KV rms for 1 min between independent circuits
1.0KV rms for 1 min across normally open contacts
Transient Over Voltage
IEC 60255-5
5 KV, 1.2/50 S, 0.5J between all terminals and earth or between
any two terminals without damage or flashover.
High Frequency Disturbance IEC 60255-22-1 Class III
2.0 KV Common (Longitudinal) mode
1.0 KV Series (Transverse) mode
Fast Transient
IEC 60255-22-4 Class IV
4 KV, 5/50 ns, 2.5 kHz repetitive
Features
Protection
 Automatic tripped breaker reclosure
 Suitable for single phase and three phase reclosing
 Micro-controller based relay
Wiring Diagram
Switch setting = 20 to 27
Output Contacts
Single Phase Reclose Time  T2 secs.
The relay has 8 output contacts and 4 status inputs
 Reclose pulse relay
1 N/O
 Reclose pulse alarm relay
1 N/O
 Lockout relay
2 N/O
 Power on relay
1 N/C
 Three phase trip mode relay
2 N/C
 Auto reclose initiation relay
1 C/O
Range:0.1 to 25.5secs in steps of 0.1 sec
Three Phase Reclose Time  T1 secs.
Range: 0.1 to 25.5 secs in steps of 0.1 sec
Reclaim Time  T0 secs.
Control
Range: 1 to 255 secs in steps of 1 sec
The relay has 8 output contacts and 4 status inputs
 Reclose pulse relay
1 N/O
 Reclose pulse alarm relay
1 N/O
 Lockout relay
2 N/O
 Power on relay
1 N/C
 Three phase trip mode relay
2 N/C
 Auto reclose initiation relay
1 C/O
Reclose pulse time 1 Second fixed.
Monitoring
Seven LED on the relay front fascia Indicate
Optional Setting
 Green
For any Reclose and Reclaim
 Yellow
Single phase reclose is initiated
Timer Setting Range in Seconds
 Yellow
Three phase reclose is initiated
1. 0.25 to 63.75 in steps of 0.25
 Green
Single phase reclose is completed
2. 0.5 to 127.5 in steps of 0.5
 Green
Three phase reclose is completed
3. 1 to 255 in steps of 1
 Red
External Blocking signal is IN
Self-monitoring facility
4. 2 to 510 in steps of 2 and
 Red
Relay is in Lockout mode
User Interface
5. 4 to 1020 in steps of 4
 Dip switches for parameter setting
 LED indications
 Sealable front cover to prevent unauthorised access
Contact Rating
Reclose Pulse Contacts
Other Features
Make a Carry for 200msec
 Both DC and AC auxiliary supply available
 Compact design
 Non-drawout case
Technical Information
Rating
Power Supply Input Rating in DC (AUX.)
18 to 135V DC or 43 to 280 V DC
Optically Isolated Input Rating in DC (STATUS)
24V, 30V, 50V, 110V or 220V
Above 110V use external resistor
Reclose Selection
Reclose in OFF
Reclose in single phase
Reclose in three phase
Reclose in single and three phase
Time Settings
Standard Setting
Time setting (In seconds)=s x Multiples of setting
s= Sum of switch settings
Power supply is ON
Environmental
Temperature
IEC 60068-2-1/2
30A AC or DC with L/R >5msec
Operating Range
Humidity
Vibration (Sinusoidal)
Shock and Bump
Insulation
-100C to +550C
IEC 60068-2-3
IEC 60255-21-1 Class I
IEC 60255-21-2 Class I
IEC 60255-5
All Other Contacts
2.0KV rms for 1 min between all terminals and earth
Carry continuously 5A AC or DC
Make and carry  3A continuously / 250V DC Break
24V DC Resistive at 0.75Amps
48V DC Resistive at 0.5Amps
125V DC Resistive at 0.3Amps
250V DC Resistive at 0.2Amps
Burden
Power Supply Burden (AUX.)
Quotient Drain
Maximum Energised Drain
2W
8W
Optically Isolated Input Burden (STATUS)
Maximum Energised Drain
3W
Input, Outputs and Indications
Four Optically Isolated (STATUS) Inputs
Initiating signal input (From single phase protective relay
contact)
External blocking signal input
Initiating signal input (From three phase protective relay
contact)
Reclose permit input (From breaker contacts etc.)
2.0KV rms for 1 min between independent circuits
1.0KV rms for 1 min across normally open contacts
Transient Over Voltage
IEC 60255-5
5 KV, 1.2/50 S, 0.5J between all terminals and earth or between
any two terminals without damage or flashover.
High Frequency Disturbance IEC 60255-22-1 Class III
2.0 KV Common (Longitudinal) mode
1.0 KV Series (Transverse) mode
Fast Transient
IEC 60255-22-4 Class IV
4 KV, 5/50 ns, 2.5 kHz repetitive
Genesis Range
Auto Reclose Relay  Single Shot
Cut-Out Details
Ordering Information
Description
1. Auxiliary supply rating in DC
The relay is suitable for single and three phase auto reclosing
2. Optically isolated (status) inputs rating in DC
The relay consists of five modules viz. Front fascia, power supply,
two relay & status module and microcontroller module. All the
modules are housed in a compact 3N Non draw-out case
3. Timer range  Standard or Optional
Qualification
Microcontroller does the sequence control and timing function.
Different operating functions and time setting are selected by
the DIP-Switches on the relay front fascia.
ISO 9001-2000
Case
There is a watch-dog timer in the relay which continuously
monitors the program, put off POWER ON indication and closes
annunciation contact in case the watch dog timer elapses.
3N-Non draw out with 27 terminals
PART
01
CASE
SIZE
3N
CUT OUT
A
B
104
140
BEZEL
C
D
128
170
Inputs
Two optically isolated inputs are provided to take the single
phase or three phase protection operated contact inputs to
initiate the auto reclose relay.
Note:
1. All dimensions are in mm
2. All dimensions are measured equidistant from centre line
3. Maximum depth of equipment inside panel : 200mm
MART113
When the external blocking input is initiated, the reclose function
is blocked and it energise external blocking LED, Lockout LED
and Lockout relay.
As the relay is suitable for single shot auto reclose, at the time
of first reclosing if the fault persists or further fault develops
within the reclaim time it will energises the lockout relay and its
LED indication.
Before the reclaim time elapses if the second fault occurs the
relay goes to lockout
Applications
 Transmission lines
 Distribution circuits
 Single phase and three phase breaker reclosing schemes
In addition, one permit input is given which when energized
from check synchronizing or dead line charging function
interlocked with the breaker status permits the auto reclose
The reclose function is get blocked when the external blocking
input is initiated.
Reclose Timer
The policy of Easun Reyrolle is one of continuous improvement and development. The company therefore reserves the right to supply equipment, which may
differ slightly from that described and illustrated in this publication.
#98, Sipcot Industrial Complex,
Hosur 635 126, India.
Tel: +91 4344 401600/01/02
Fax: +91 4344 276397
SWITCHGEAR WORKS
Ernavur,
Chennai-600 057, India.
Tel: +91 44 25733715/358
Fax: +91 44 25733468
Email: switchgear@easunreyrolle.net
FACT/MART 113/12-05/REV 0
HOSUR WORKS
BANGALORE WORKS
#17/3 Arakere,
Bannerghatta Road,
Bangalore-560 076, India.
Tel: +91 80 26581023 / 3268
Fax: +91 80 26580642
Email: blrworks@easunreyrolle.net
AUTOMATION DIVISION
Ashirwad, #25, 29th Main,
4th B Cross, BTM Layout 2nd Stage,
Bangalore-560 076, India.
Tel: +91 80 26685496/51311405
Fax: +91 80 26685446
Email: smabp@easunreyrolle.net
EXPORTS DIVISION
#17/3 Arakere,
Bannerghatta Road,
Bangalore-560 076, India.
Tel: +91 80 26581023 / 3268
Fax: +91 80 26580642
Email: exports@easunreyrolle.net
Delhi
Kolkata
Bangalore
Chennai
Secunderabad
Tel: +91 22 22022270/22855415
Fax: +91 22 22825703
Email: mumbai@easunreyrolle.net
Tel: +91 80 26685496/51311405
Fax: +91 22 26685446
Email: blroffice@easunreyrolle.net
Bhopal
Telefax: +91 755 2684221
Email: bhopal@easunreyrolle.net
Tel: +91 11 25747321/25747322
Fax: +91 11 25747320
Email: delhi@easunreyrolle.net
Tel: +91 44 24346425/24347608
Fax: +91 44 24346435
Email: chennai@easunreyrolle.net
There is the common reclaim timer. It operates in series with
the reclose timers. The over all reclaim time delay from relay
energisation to relay reset is therefore reclaim timer setting
plus reclose time.
When the reclose selector switch is in OFF mode any one of the
protection operated contact input initiation condition it will
energise the lockout relay and its LED indication and it blocks
the reclose function.
Tel: +91 33 22848320
Fax: +91 33 22848326
Email: kolkata@easunreyrolle.net
Telefax: +91 40 27817847
Email: hyderabad@easunreyrolle.net
Reclaim Timer
Lockout Function
Sales Offices
Mumbai
The relay having two reclose timers one for single phase reclose
another for three phase reclose. The both timers are selected
automatically depending upon the reclose selection
Corporate Office
Easun Reyrolle Limited. 98 Sipcot Industrial Complex
Hosur 635 126 India. Tel: +91 4344 401600/01/02
Fax: +91 4344 276397
www.easunreyrolle.com
Auto Reclose Relay  Single Shot  MART 113