Fluke 1555 and
1550C Insulation
Resistance Testers
Technical Data
Digital insulation testing up to 10 kV, ideal
for wide range of high voltage applications
Evaluate the trends, eliminate the doubt
The Fluke 1555 and Fluke 1550C insulation resistance testers, offer
digital insulation testing up to 10kV, making them ideal for testing a
wide range of high voltage equipment including switchgear, motors,
generators and cables.
Fluke insulation testers can now conduct the entire range of test
voltages specified in IEEE 43-2000 with a best in class, 3 year
warranty and CAT IV 600 V safety rating. With measurement
storage and PC interface, the 1555 and 1550C are perfect tools for
preventative or predictive maintenance programs designed to identify
potential equipment failures before they occur.
Features include:
Test voltages to up 10 kV provides solutions for all applications
CAT III 1000 V, CAT IV 600 V safety rating
Warning function alerts the user that line voltage is present and
gives the voltage reading up to 600 V ac or dc for increased user
safety
Selectable test voltages in 50 V steps from 250 V to 1000 V, and
100 V steps above 1000 V
Measurements can be stored in up to 99 memory locations, with
each location assigned a unique, user defined, label for easy recall
Long battery life gives the user over 750 tests between charges
Automatic calculation of Dielectric Absorption (DAR) and
Polarization Index (PI) with no additional setup
Guard system eliminates the effect of surface leakage current
on high-resistance measurements
Large digital/analog LCD for easy viewing
Capacitance and leakage current measurement
Ramp function for breakdown testing
Resistance measurements up to 2 T
Timer settings up to 99 minutes for timed tests
3-year warranty
Electrical specifications
The testers accuracy is specified for one year after calibration at operating
temperatures of 0 C to 35 C. For operating temperatures outside the range
(-20 C to 0 C and 35C to 50 C), add .25 % per C, except on the 20 % bands
add 1 % per C.
Insulation resistance measurement
Test voltage (dc)
Range
Accuracy ( reading)
250 V
< 250 k
250 k to 5 G
5 G to 50 G
> 50 G
< 500 k
500 k to 10 G
10 G to 100 G
> 100 G
< 1 M
1 M to 20 G
20 G to 200 G
> 200 G
< 2.5 M
2.5 M to 50 G
50 G to 500 G
> 500 G
< 5 M
5 M to 100 G
100 G to 1 T
> 1 T
< 10 M
10 M to 200 G
200 G to 2 T
> 2 T
unspecified
5%
20 %
unspecified
unspecified
5%
20 %
unspecified
unspecified
5%
20 %
unspecified
unspecified
5%
20 %
unspecified
unspecified
5%
20 %
unspecified
unspecified
5%
20 %
unspecified
500 V
1000 V
2500 V
5000 V
10000 V (1555 Only)
Bar graph range
Insulation test voltage accuracy
Induced ac mains current rejection
Charging rate for capacitive load
Discharge rate for capacitive load
Leakage current
measurement
Capacitance measurement
0 to 1 T (1550C) - 0 to 2 T (1555)
-0 %, +10 % at 1 mA load current
2 mA maximum
5 seconds per F
1.5 s/F
Range
1 nA to 2 mA
0.01 uF to 15.00 F
Accuracy
(5 % + 2 nA)
(15 % rdg + 0.03 F)
Timer
Range
0 to 99 minutes
Resolution
Setting: 1 minute
Indication: 1 second
Live circuit warning
Warning range
30 V to 660 V ac/dc, 50/60 Hz
Voltage accuracy
(15 % + 2 V)
General specifications
Display
Power
Charger Input (AC)
(RF connection time (binding
time) can take up to 1 minute.)
75 mm x 105 mm
12 V lead-acid rechargeable battery, Yuasa NP2.8-12
85 V to 250 V ac 50/60 Hz 20 VA
This Class II (double insulated) instrument is supplied with a Class 1 (grounded) power cord. The protective earth terminal
(ground pin) is not connected internally. The extra pin is for added plug retention only.
Dimensions
Weight
Temperature (operating)
Temperature (storage)
Humidity
Altitude
Enclosure sealing
Input overload protection
Electromagnetic compatibility
Certifications
269 mm x 277 mm x 160 mm (10.6 in x 10.9 in x 6.3 in)
3.7 kg (8.2 lb)
-20 C to 50 C (-4 F to 122 F)
-20 C to 65 C (-4 F to 149 F)
80 % to 31 C decreasing linearly to 50% at 50 C
2000 m
IP40
1000 V ac
EN 61326
Safety compliance
IEC 61010-1: Overvoltage categroy II, pollution degree 2.
IEC 61010-2-030: Measurement 600V CAT IIV / 1000V CAT III
IEC 61557-1, IEC 61557-2
2 Fluke Corporation
Fluke 1555 and 1550C Insulation Resistance Testers
Software specifications
Fluke ViewForms basic software
requires a PC running Windows XP,
Windows Vista , Windows 7 and
Windows 8.
Ordering
1550C
5 kV information
Insulation Tester
1555 10 kV Insulation Tester
1550C/Kit 5 kV Insulation Tester Kit
1555/Kit 10 kV Insulation Tester Kit
Optional accessories
TL1550EXT 2
5 foot extended
test lead set
TLK1550-RTLCT Heavy Duty Alligator
Clip leads
Included accessories
Test Cables with Alligator Clips
(red, black, green)
Infrared adapter with interface cable
FlukeView Forms Basic CD-ROM
AC Power Cord
Soft Carrying Case (base models only)
English Manual
Users Manual on CD-ROM
Quick Reference Card
Software License Agreement
Registration Card
FlukeView Forms Installation Guide
USB-IR Cable Installation Guide
IP67 Hard Case (kit only)
Certificate of Calibration (kit only)
Heavy Duty Alligator Clip Leads
(kit and 1555 only)
Fluke. Keeping your world
up and running.
Fluke Corporation
PO Box 9090, Everett, WA 98206 U.S.A.
Fluke Europe B.V.
PO Box 1186, 5602 BD
Eindhoven, The Netherlands
For more information call:
In the U.S.A. (800) 443-5853 or
Fax (425) 446-5116
In Europe/M-East/Africa +31 (0) 40 2675 200 or
Fax +31 (0) 40 2675 222
In Canada (800)-36-FLUKE or
Fax (905) 890-6866
From other countries +1 (425) 446-5500 or
Fax +1 (425) 446-5116
Web access: http://www.fluke.com
2005-2014 Fluke Corporation.
Specifications subject to change without notice.
Printed in U.S.A. 10/2014 6002295B_EN
Modification of this document is not permitted
without written permission from Fluke Corporation.