Relpol-Relee de Timp PDF

This document provides information about Relpol S.A., a manufacturer of electromagnetic relays located in Europe. It discusses Relpol's long history as a supplier of automation components worldwide. It also highlights Relpol's focus on quality improvement, certifications, research and development capabilities, technical support services, and environmental protection initiatives. The document contains specifications, diagrams and ordering information for several of Relpol's time relay products.

Uploaded by

ChioibasNicolae
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
206 views64 pages

Relpol-Relee de Timp PDF

This document provides information about Relpol S.A., a manufacturer of electromagnetic relays located in Europe. It discusses Relpol's long history as a supplier of automation components worldwide. It also highlights Relpol's focus on quality improvement, certifications, research and development capabilities, technical support services, and environmental protection initiatives. The document contains specifications, diagrams and ordering information for several of Relpol's time relay products.

Uploaded by

ChioibasNicolae
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 64

61

20
07
/2
00
Time relays
8
Monitoring relays

www.relpol.com.pl
Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
Automation is our passion
62

For dozens of years now, Relpol S.A.


has been a worldwide known supplier of components

used in industrial and power automation, power electronics,


industrial and applied electronics, telecommunication, etc.

Apart from complete delivery Taking into account


of components, Relpol S.A. the significant role
provides its partners with of the products of Relpol S.A.,
technical consultancy based upon we have made their quality
extensive knowledge of the improvement our priority
application of the components. strategic goal.

You are welcome to review Due to the wide line


our catalogs which present of products, orders
a very wide line of products of non-standard products
for industrial automation. should be consulted with
the manufacturer or distributor.

www.relpol.com.pl
www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
1

The leading position


of the manufacturer of electromagnetic relays in Europe
provides for Relpol's presence
in markets worldwide.

Commercial Partnerships of Relpol S.A.

RELPOL M Minsk / Belarus

RELPOL BG Varna / Bulgaria

RELPOL HUNGARY Budapest / Hungary

RELPOL BALTIJA Vilnius / Lithuania

RELPOL ELTIM Sankt-Petersburg / Russia

RELPOL ALTERA Kiev / Ukraine

RELPOL FRANCE Paris / France

RELPOL LTD. London / England

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
In automation for you
2

The standards quality guaranteed


Taking into account the high requirements of the market
and our customers' full satisfaction, Relpol S.A. constantly
ISO 9001 : 2001
strives for improvement of the quality of the products
and services we offer. Our own technological, designing
ISO 14001 : 2005
and research facilities remarkably help us to achieve our goals.
The modern production profile and high quality of the products
that comply with the requirements of the European Union
are confirmed by the ISO 9001 : 2001, ISO 14001 : 2005
CERTIFICATES.
The Gold Statuette of the Business Centre Club 1995
/ EUROPRODUCT 2002 / EUROPRODUCT 2003 /
the Statuette of the Minister of Economic Affairs,
Labor and Social Policy 2003 / GOLD EUROPRODUCT
2003 / ELECTROPRODUCT 2003 / GOLD MEDAL
Automaticon 2004 / the Statuette for the Pillar of the
Polish Economy 2004 / Product of the Year 2005

The innovative features


of our technological solutions
and the reliability of our products
are confirmed by numerous
recognitions and certifications
BBJ, VDE, UL, CSA, GOST, LR,
RoHS and by prizes and awards.

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
3

Relations and trust


Our co-operation with numerous renowned The permanent development
suppliers of materials and components of our staff along with human
necessary for the production process resources stabilization provide our
allows us to realize even complex deliveries customers with professional service.
quickly and smoothly. We build long-term Relpol S.A. Technical Support
partnership relations with our customers. Department advises the Client
Owing to regular and helps to solve the problems
Relpol S.A. runs of electrical applications and, thus,
consultations and its own Research
steady contribution enhances their satisfaction
and Development
of our Partners Department which at cooperation with ourselves.
to our activities, designs new products The long years of experience, the know-
to follow the worldwide
we gain the knowledge ledge of the electrotechnical industry
trends and solutions
necessary for reliable in the electrotechnical and the market activities of Relpol S.A.
and professional industry. have been proved by co-operation
services. with the largest corporations worldwide.

Environment protection
With the development of technology we shall not forget

about the issues of the environment protection.


Reduction of the natural environment pollution with regard to the production
process and the products of Relpol S.A. is a constant process aimed
at minimizing of the environmental impact.
Our products meet the requirements of the RoHS Directive.

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
Contents
4

Time relays
TR4N 4 C/O PIR15...T
Technical data ......................... 5
with time module T (COM3)

Dimensions, diagrams .............. 6 Technical data ...................... 13


Ordering codes ........................ 6 Dimensions, diagrams ........... 15
Ordering codes ..................... 16
Time functions ...................... 20
Time functions ...................... 20
TR4N 1 C/O, 2 C/O
Technical data ......................... 7
PIR6WT-1Z

Dimensions, diagrams .............. 8 Technical data ...................... 17


Ordering codes ........................ 8 Dimensions, diagrams ........... 18
Ordering codes ..................... 19
Time functions ...................... 20
Time functions ...................... 20
T-R4
Technical data ......................... 9 Series TR-E...

Dimensions, diagrams ........... 10 TR-EM1P-UNI ...................... 22


TR-EM2P-UNI ...................... 24
Ordering codes ..................... 12
TR-EI1P-UNI ........................ 26
Time functions ...................... 20
TR-EI2P-UNI ........................ 28

TR-ES2P-UNI ....................... 30

Monitoring relays
Series MR-E... Series MR-G...
MR-EU3M1P ...................... 32 MR-GI1M2P-TR2 ................ 42
MR-EU31UW1P .................. 34 MR-GI3M2P-TR2 ................ 44

MR-EU1W1P ...................... 36 MR-GU1M2P-TR2 ............... 46


MR-EI1W1P ....................... 38 MR-GU32P-TR2 .................. 48
MR-ET1P ............................ 40 MR-GU3M2P-TR2 ............... 50
MR-GU3M2P ...................... 52
MR-GT2P-TR2 ..................... 54

MR-GP2P ........................... 56
TR2 supply transformers ....... 58

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
TR4N 4 C/O
time relays 5

10-functions electronic time relays in compact cover Cadmium - free


contacts AC and AC/DC input voltages Direct mounting on 35 mm
DIN rail mount, EN 50022 (wiring: 1 x 2,5 mm2, 2 x 1,5 mm2) The main
advantages of application: simple selection of the performed function,
possibility to control a few circuits (4 changeover contacts), esthetic
design in the control cabinet The switching capacity of contacts as
in R4 electromagnetic relay Compliance with standard PN-EN 61812-1
Recognitions, certifications, directives:

Type of relay TR4N 4 C/O


Output circuits - contact data
Number and type of contacts 4 C/O - changeover
Contact material AgNi
Max. switching voltage AC/DC 250 V / 250 V
Min. switching voltage 5V
Rated load AC1 6 A / 250 V AC
DC1 6 A / 24 V DC
Min. switching current 5 mA
Rated current 6A
Max. breaking capacity AC1 1 500 VA
Min. breaking capacity 0,3 W
Contact resistance 100 m
Max. operating frequency
at rated load AC1 1 200 cycles/hour
no load 18 000 cycles/hour
Input control circuit
Rated voltage 50/60 Hz AC 115-230 V
AC: 50/60 Hz AC/DC 12-24 V
Operating range of supply voltage 0,9 < Un < 1,1 12 V AC/DC
0,85 < Un < 1,1 24 V AC/DC, 115 V AC, 230 V AC
Rated power consumption 1,0 VA / 1,0 W 12 V AC/DC, 24 V AC/DC
2,2 VA 115 V AC, 230 V AC
Range of supply frequency AC: 48...63 Hz
AC/DC: 48...100 Hz

Insulation
Insulation category B250
Overvoltage category II PN-EN 60664-1
Insulation pollution degree 2
Flammability degree V-1 UL94
Dielectric strength
input - outputs 2 500 V AC
Input - outputs distance
clearance 1,6 mm
creepage 3,2 mm
General data
Electrical life
resistive AC1 105 6 A, 250 V AC
Mechanical life (cycles) 2 x 107
Dimensions (L x W x H) 90 x 36 x 55 mm
Weight 115 g
Ambient temperature
storage -40...+70 oC
operating -20...+55 oC
Cover protection category IP 20
Environmental protection RTI PN-EN 116000-3
Shock resistance (NO/NC) 10 g / 5 g
Vibration resistance 0,35 mm DA 10...55 Hz
The data in bold type pertain to the standard versions of the relays.

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
TR4N 4 C/O
6 time relays

Time module data


Functions E, Wu, Bp, Bi, PWM, R, Ws, Wa, Esa, B
permanent switching ON and OFF
Time intervals 1 s ; 10 s; 1 min.; 10 min.; 1 h; 10 h; 1 d; 10 d
Timing adjustment smooth - (0,1...1) x time interval
Setting accuracy 5% (calculate from final range value)
Repeatability 0,5%
Temperature influence 0,01% / C
Recovery time 90 ms
Min. pulse of the control contact AC: 25 ms DC: 15 ms
LED indicator green LED - indication of supply voltage U
yellow LED - indication of time period T
and the status of outputs after the time T has been measured
Descriptions of time functions - see pages 22-21. For first range setpoint (1 s) setting accuracy and repeatability are smaller than the given
ones in technical parameters (significant influence of the operational relay operating time). Recommend to set measuring time by experimental method.
The yellow LED - T time measurement (flashing); excited operational relay, time not measured (steady light); de-excited operational relay, time not
measured (no light).

Dimensions Connections diagram

4 C/O

Control contact S is activated by connecting it to A1 terminal.

Mounting

Relays TR4N 4 C/O are designed for direct


mounting on 35 mm DIN rail mount, EN 50022.

Ordering codes

Type Rated supply voltage Number and type of Perform of time


contacts functions

Rated supply voltage


012AC/DC - 12 V AC/DC AC: 50/60 Hz
024AC/DC - 24 V AC/DC AC: 50/60 Hz
115AC - 115 V AC 50/60 Hz
230AC - 230 V AC 50/60 Hz

Number and type of contacts


14 - 4 C/O

Perform of time functions


M - multifunction

Example of ordering code:


TR4N-230AC-14-M time relay TR4N 4 C/O, rated input voltage 230 V AC 50/60 Hz, with four changeover contacts,
multifunction (relay perform 10 functions), contact material AgNi

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
TR4N 1 C/O, 2 C/O
time relays 7

10-functions electronic time relays in compact cover Cadmium - free


contacts AC and AC/DC input voltages Direct mounting on 35 mm
DIN rail mount, EN 50022 (wiring: 1 x 2,5 mm2, 2 x 1,5 mm2) The main
advantages of application: simple selection of the performed function,
possibility to control one or two circuits (1 or 2 changeover contacts), esthetic
design in the control cabinet The switching capacity of contacts as
in RM85 (1 C/O) or RM84 (2 C/O) electromagnetic relay Compliance with
standard PN-EN 61812-1 Recognitions, certifications, directives:

Type of relay TR4N 1 C/O TR4N 2 C/O


Output circuits - contact data
Number and type of contacts 1 C/O - changeover 2 C/O - changeover
Contact material AgNi AgNi
Max. switching voltage AC/DC 250 V / 250 V 250 V / 250 V
Min. switching voltage 5V 5V
Rated load AC1 16 A / 250 V AC 8 A / 250 V AC
DC1 16 A / 24 V DC 8 A / 24 V DC
Min. switching current 5 mA 5 mA
Rated current 16 A 8A
Max. breaking capacity AC1 4 000 VA 2 000 VA
Min. breaking capacity 0,3 W
Contact resistance 100 m
Max. operating frequency
at rated load AC1 1 200 cycles/hour
no load 18 000 cycles/hour
Input control circuit
Rated voltage 50/60 Hz AC 115-230 V
AC: 50/60 Hz AC/DC 12-24 V
Operating range of supply voltage 0,9 < Un < 1,2 12 V AC/DC
0,85 < Un < 1,2 24 V AC/DC, 115 V AC, 230 V AC
Rated power consumption 0,5 VA / 0,5 W 12 V AC/DC 0,7 VA / 0,7 W 24 V AC/DC
1,3 VA 115 V AC 1,7 VA 230 V AC
Range of supply frequency AC: 48...63 Hz
AC/DC: 48...100 Hz

Insulation
Insulation category B250
Overvoltage category III PN-EN 60664-1
Insulation pollution degree 2
Flammability degree V-1 UL94
Dielectric strength
input - outputs 2 500 V AC
Input - outputs distance
clearance 10 mm
creepage 10 mm
General data
Electrical life
resistive AC1 0,7 x 105 16 A, 250 V AC 105 8 A, 250 V AC
Mechanical life (cycles) 3x 107
Dimensions (L x W x H) 90 x 17,6 x 55 mm
Weight 67 g
Ambient temperature
storage -40...+70 oC
operating -20...+55 oC
Cover protection category IP 20
Environmental protection RTI PN-EN 116000-3
Shock resistance 15 g
Vibration resistance 0,35 mm DA 10...55 Hz
The data in bold type pertain to the standard versions of the relays.

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
TR4N 1 C/O, 2 C/O
8 time relays

Time module data


Functions E, Wu, Bp, Bi, PWM, R, Ws, Wa, Esa, B
permanent switching ON and OFF
Time intervals 1 s ; 10 s; 1 min.; 10 min.; 1 h; 10 h; 1 d; 10 d
Timing adjustment smooth - (0,1...1) x time interval
Setting accuracy 5% (calculate from final range value)
Repeatability 0,5%
Temperature influence 0,01% / C
Recovery time 80 ms
Min. pulse of the control contact AC: 25 ms DC: 15 ms
LED indicator green LED - indication of supply voltage U
yellow LED - indication of time period T
and the status of outputs after the time T has been measured
Descriptions of time functions - see pages 20-21. For first range setpoint (1 s) setting accuracy and repeatability are smaller than the given
ones in technical parameters (significant influence of the operational relay operating time). Recommend to set measuring time by experimental method.
The yellow LED - T time measurement (flashing); excited operational relay, time not measured (steady light); de-excited operational relay, time not
measured (no light).

Dimensions Connections diagrams

1 C/O 2 C/O

Control contact S is activated by connecting it to A1 terminal.

Mounting

1 C/O 2 C/O
Relays TR4N 1 C/O, 2 C/O are designed for direct
mounting on 35 mm DIN rail mount, EN 50022.

Ordering codes

Type Rated supply voltage Number and type of Perform of time


contacts functions

Rated supply voltage


012AC/DC - 12 V AC/DC AC: 50/60 Hz
024AC/DC - 24 V AC/DC AC: 50/60 Hz
115AC - 115 V AC 50/60 Hz
230AC - 230 V AC 50/60 Hz

Number and type of contacts


11 - 1 C/O
12 - 2 C/O

Perform of time functions


M - multifunction

Examples of ordering codes:


TR4N-230AC-11-M time relay TR4N 1 C/O, rated input voltage 230 V AC 50/60 Hz, with one changeover contact,
multifunction (relay perform 10 functions), contact material AgNi
TR4N-024AC/DC-12-M time relay TR4N 2 C/O, rated input voltage 24 V AC/DC 50/60 Hz, with two changeover contacts,
multifunction (relay perform 10 functions), contact material AgNi

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
T-R4
time relays 9

Single-function, single-voltage time relays offered in the following


versions: T-R4E - relay with time function E, T-R4Wu - relay with time
function Wu, T-R4Bp - relay with time function Bp, T-R4Bi - relay with
time function Bi Cadmium - free contacts AC and DC input voltages
For plug-in sockets, 35 mm DIN rail mount, EN 50022 or on panel
mounting Applications: as time systems in electric circuits of machines,
technological lines, in automation systems, etc.
Recognitions, certifications, directives: recognitions R4,

Type of relay T-R4


Output circuits - contact data
Number and type of contacts 4 C/O - changeover
Contact material AgNi
Max. switching voltage AC/DC 250 V / 250 V
Min. switching voltage 5V
Rated load AC1 6 A / 230 V AC
Min. switching current 5 mA
Max. inrush current 12 A
Rated current 6A
Max. breaking capacity AC1 1 500 VA
Min. breaking capacity 0,3 W
Contact resistance 100 m
Max. operating frequency
at rated load AC1 1 200 cycles/hour
no load 18 000 cycles/hour
Input control circuit
Rated voltage 50/60 Hz AC 24-115-230 V
DC 12-24 V
Must release voltage AC: 0,2 Un DC: 0,1 Un
Operating range of supply voltage 0,8 < Un < 1,1 see Tables 1, 2
Rated power consumption AC 2,2 VA
DC 1,2 W
Range of supply frequency 48...63 Hz
Insulation
Insulation category B250
Insulation rated voltage 250 V AC
Overvoltage category III PN-EN 60664-1
Dielectric strength
input - outputs 2 500 V AC
contact clearance 1 500 V AC
pole - pole 2 000 V AC
Input - outputs distance
clearance 1,6 mm
creepage 3,2 mm
General data
Operating time (typical value) 10 ms
Release time (typical value) 8 ms
Electrical life
resistive AC1 105 6 A, 250 V AC
cos see Fig. 2
Mechanical life (cycles) 2 x 107
Dimensions (L x W x H) 21,2 x 29,5 x 62,5 mm
Weight 49 g
Ambient temperature
storage -20...+85 oC
operating -20...+55 oC
Cover protection category IP 20 (with socket)
Environmental protection T-R4: RTI GZM4: RT0 PN-EN 116000-3
Shock resistance (NO/NC) 10 g / 5 g
Vibration resistance 5 g 10...150 Hz
The data in bold type pertain to the standard versions of the relays.

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
T-R4
10 time relays

Time module data


Functions E, Wu, Bp, Bi
Time intervals 0,1 s ; 10 s; 1 min.; 10 min.; 1 h; 10 h; 100 h
Timing adjustment range - with the range-adjusting knob / switch
within the range - with the time-adjusting knob / potentiometer
Setting accuracy 5% (calculate from final range value)
Repeatability 1%
Temperature influence 0,01% / C
Recovery time 100 ms
LED indicator green LED - indication of supply voltage U
yellow LED - indication of time period T
and the status of outputs after the time T has been measured
Descriptions of time functions - see pages 20-21. For first range setpoint (1 s) setting accuracy and repeatability are smaller than the given
ones in technical parameters (significant influence of the operational relay operating time). Recommend to set measuring time by experimental method.
The yellow LED - T time measurement (flashing); excited operational relay, time not measured (steady light); de-excited operational relay, time
not measured (no light).

The data in bold type pertain to the standard versions of the relays.

The data in bold type pertain to the standard versions of the relays.

GZM4

GZM4 GZT4

GZT4

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
T-R4
time relays 11

4 C/O

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
T-R4
12 przekaniki czasowe

Mounting

Relays T-R4E, T-R4Wu, T-R4Bp, T-R4Bi are designed for screw Separate T-R4 control circuits GZM4: yes
from load circuits GZT4: no
terminals plug-in sockets GZM4 or GZT4, 35 mm DIN rail mount, (T-R4 contacts)
EN 50022 or on panel mounting with two M3 screws. For sockets Increased dielectric strength GZM..: min. 5 kV
are offered description plates GZT4-0035 and clips TR4-2000. spacing between coil GZT.. : min. 4 kV
and contacs clamps
Double A2(14) terminal GZM2/3/4: yes
is introduced for easy wiring GZT2/3/4: no
in electrical devices

T-R4 GZM4 GZM4 GZT4 TR4-2000 GZT4-0035

Note: sockets GZM4 are available in black and gray colours.

Ordering codes

Cover protection
category

Type Time function Contact Number and type of Connection Input voltage
material contacts mode code

Time function
E - function E
Wu - function Wu
Bp - function Bp
Bi - function Bi
see Tables 1, 2 page 10
Contact material
20 - AgNi

Number and type of contacts


14 - 4 C/O

Cover protection category


2 - in cover, IP 40 version

Connection mode
3 - for plug-in sockets

Example of ordering code:


T-R4E-2014-23-1012 time relay T-R4, performing the time function E - ON Delay
Voltage Controlled, contact material AgNi, with four
changeover contacts, in cover IP 40, for plug-in sockets,
rated input voltage 12 V DC

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
PIR15...T with time module T(COM3)
interface - time relays 13

35 mm DIN rail mount, EN 50022 or on panel mounting with two M3 screws.


Interface relay PIR15 2 C/O consists of:
- electromagnetic relay R15 2 C/O, plug-in socket ES 9 black,
- time module T(COM3), spring wire clip PZ11 0031.
Interface relay PIR15 3 C/O (standard) consists of:
- electromagnetic relay R15 3 C/O, plug-in socket ES 12 black,
- time module T(COM3), spring wire clip PZ11 0031.
Recognitions, certifications, directives: recognitions R15, RoHS,

Type of relay PIR15 2 C/O PIR15 32 C/O


Output circuits - contact data
Number and type of contacts 2 C/O - changeover 3 C/O - changeover
Contact material AgNi
Max. switching voltage AC/DC 250 V / 300 V
Min. switching voltage 5V
Rated load AC1 10 A / 250 V AC
DC1 10 A / 24 V DC
Min. switching current 5 mA
Max. inrush current 20 A
Rated current 10 A
Max. breaking capacity AC1 2 500 VA
Min. breaking capacity 0,3 W
Contact resistance 100 m
Max. operating frequency
at rated load AC1 1 200 cycles/hour
no load 12 000 cycles/hour
Input control circuit
Rated voltage of output relay R15 50/60 Hz AC 24-48-60-110-120-230-240 V
DC 24-48-60-110-120-220 V
Supply voltage of time module T(COM3) 24...240 V AC/DC (uniwersal module)
Operating range of supply voltage 0,85 < Un < 1,1 see Tables 1, 2
Must operate voltage 0,85 Un
Rated power consumption AC 3,0 VA
DC 2,0 W
Range of supply frequency 48...63 Hz
Insulation
Insulation category C250
Insulation rated voltage 250 V AC
Overvoltage category III PN-EN 60664-1
Dielectric strength
input - outputs 2 500 V AC
contact clearance 1 500 V AC
pole - pole 2 000 V AC
Input - outputs distance
clearance 3 mm
creepage 4,2 mm
General data
Operating time (typical value) AC: 12 ms DC: 18 ms
Release time (typical value) AC: 10 ms DC: 7 ms
Electrical life
resistive AC1 2 x 105 10 A, 250 V AC
cos see Fig. 2
Mechanical life (cycles) > 2 x 107
Dimensions (L x W x H) 75 x 38 x 83,1 mm
Weight 168 g
Ambient temperature
storage -40...+70 oC
operating -40...+55 oC
Cover protection category IP20
Environmental protection R15: RTI ES 9, ES 12: RT0 PN-EN 116000-3
Shock resistance 10 g
Vibration resistance 5 g 10...500 Hz
The data in bold type pertain to the standard versions of the relays.

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
PIR15...T with time module T(COM3)
14 interface - time relays

Time module data


Functions E, E(S), Wu, Wu(S), Bi, Bi(S), Bp, Bp(S), R, Ws, Wa, Es
Function adjustment selection with microswitches
Time intervals 1 s; 10 s; 1 min.; 10 min.; 1 h; 10 h; 1 d; 10 d
Timing adjustment range - with microswitches
within the range - with a potentiometer
Setting accuracy \ Repeatability 1% \ 0,2%
Temperature influence 0,01% / C
Recovery time 150 ms
LED indicator green LED - indication of time period T
and the status of outputs after the time T has been measured
Descriptions of time functions - see pages 20-21. Settings of switches - see page 216. The green LED - T time measurement (flashing);
excited operational relay, time not measured (steady light); de-excited operational relay, time not measured (no light).

Settings of switches

The data in bold type pertain to the standard versions of the relays.

The data in bold type pertain to the standard versions of the relays.

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
PIR15...T with time module T(COM3)
interface - time relays 15

PIR15 2 C/O

PIR15 3 C/O

PIR15 2 C/O PIR15 3 C/O

Control contact (B1) S is activated by connecting it to A1 terminal.

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
PIR15...T with time module T(COM3)
16 interface - time relays

Mounting

Relays PIR15...T are designed for 35 mm DIN rail mount, EN 50022 or on panel mounting with two M3 screws.
Interface relay PIR15 2 C/O consists of: electromagnetic relay R15 2 C/O, plug-in socket ES 9 black, time module
T(COM3) and spring wire clip PZ11 0031.
Interface relay PIR15 3 C/O consists of: electromagnetic relay R15 3 C/O, plug-in socket ES 12 black, time module
T(COM3) and spring wire clip PZ11 0031.

R15 2 C/O ES 9 R15 3 C/O ES 12 T(COM3) PZ11 0031

Ordering codes

Contact
material
Type Number and type of Input voltage Connection Options
contacts code mode

Number and type of contacts


2 - 2 C/O
3 - 3 C/O see Tables 1, 2 page 14
Connection mode
0 - with socket (35 mm DIN rail mount, EN 50022)

Contact material
0 - AgNi

Options
T - time module T(COM3)

Examples of ordering codes:


PIR152-012DC-00T interface relay PIR15 2 C/O, which consists of: relay R15 2 C/O, contact material AgNi,
rated input voltage 12 V DC, plug-in socket ES 9 black (screw terminals), time module
T(COM3), spring wire clip PZ11 0031
PIR153-230AC-00T interface relay PIR15 3 C/O, which consists of: relay R15 3 C/O, contact material AgNi,
rated input voltage 230 V AC 50/60 Hz, plug-in socket ES 12 black (screw terminals),
time module T(COM3), spring wire clip PZ11 0031

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
PIR6WT-1Z
interface - time relays 17

9-functions electronic time relays


Time relay PIR6WT-1Z consists of:
- universal socket with electronic PI6WT-1Z with screw terminals,
- changeover relay RM699V, rated load 6 A / 230 V (AC1)
or solid state relay RSR30
35 mm DIN rail mount, EN 50022 Adapted for the co-operation
with interconnection strip type ZG20 Equipped in LED green
Recognitions, certifications, directives:

Type of relay PIR6WT-1Z


Output circuit (RM699V) - contact data
Number and type of contacts (code of output) 1 NO - normally open (R)
Contact material AgSnO2
Max. switching voltage AC/DC 250 V / 300 V
Min. switching voltage AC/DC 12 V
Rated load AC1 6 A / 230 V AC
DC1 6 A / 24 V DC
Min. switching current 100 mA
Max. inrush current 15 A 20 ms
Rated current 6A
Max. breaking capacity AC1 1 500 VA
Min. breaking capacity 1W
Contact resistance 100 m 100 mA, 24 V
Max. operating frequency
at rated load AC1 360 cycles/hour
no load 72 000 cycles/hour
Output circuit (RSR30) - output data
Type of output (code of output) Triac (T) Transistor (C) Transistor (O)
240 V / 2 A 48 V / 1 A 24 V / 2 A
Number and type of outputs 1 NO - normally open 1 NO - normally open 1 NO - normally open
Rated voltage 240 V AC 48 V DC 24 V DC
Max. output voltage 280 V AC 60 V DC 32 V DC
Min. output voltage 12 V AC 1,5 V DC 1,5 V DC
Rated continuous output current AC1 1 A / 240 V AC
DC1 1 A / 60 V DC 2 A / 60 V DC
Min. making capacity current 50 mA 1 mA 1 mA
Max. off-state leakage current (rest condition) 1,5 mA 1 mA 1 mA
Output rated current 1A 1A 2A
Max. on-state voltage drop on the connection (operating state) 1,2 V 0,4 V 0,24 V
Operating switching frequency 10 Hz 10 Hz
Input control circuit
Rated voltage AC: 50/60 Hz AC/DC 12-24 V
Operating range of supply voltage 0,9...1,2 Un 12 V AC/DC 0,85...1,2 Un 24 V AC/DC
Rated power consumption AC/DC 0,5 VA / 0,5 W 12 V AC/DC 1,0 VA / 1,0 W 24 V AC/DC
Range of supply frequency AC: 48...100 Hz
Control contact (A3) S
control voltage between terminals (A3) S and A1
min. voltage 8V
min. time of pulse duration 15 ms
Insulation
Insulation category B250
Insulation rated voltage 250 V AC
Rated surge voltage 2 500 V AC
Overvoltage category II PN-EN 60664-1
Insulation pollution degree 2
Flammability degree contact plate: V-0 cover: V-1 UL94
Dielectric strength input - output 2 500 V AC 50/60 Hz, 1 min.
contact clearance 1 000 V AC 50/60 Hz, 1 min., output R
The data in bold type pertain to the standard versions of the relays. Characteristics of the contact capacity of relays PIR6WT-1Z with RM699V
- see catalogue Relpol S.A. Electromagnetic relays , pages 49-51; PIR6WT-1Z with RSR30 - see catalogue Relpol S.A. Solid state relays, pages 10-14.
Control contact (A3) S is activated by connecting it to A1 terminal. Where the control signal is recognizable.

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
PIR6WT-1Z
18 interface - time relays

General data
Dimensions (L x W x H) \ Weight 98,5 x 6,2 x 85,5 mm \ 50 g
Ambient temperature storage \ operating -40...+70 oC \ -20...+55 oC
Protection category IP 20
Environmental protection RTI PN-EN 116000-3
Shock resistance 10 g
Vibration resistance 5 g 10...55 Hz
Relative humidity up to 85%
Time module data
Functions E, Wu, Bp, Bi, R, Ws, Wa, Esa, B OFF - OFF mode
Function adjustment selection with microswitches
Time intervals 1 s ; 10 s; 1 min.; 10 min.; 1 h; 10 h; 1 d; 10 d
Timing adjustment smooth - (0,1...1) x time interval
Repeatability 0,5%
Temperature influence 0,01% / C
Humidity influence 0,05% / %HR
Recovery time max. 80 ms
LED indicator green LED - indication of time period T
and the status of outputs after the time T has been measured
Descriptions of time functions - see pages 20-21. Settings of switches - see page 218. For the first range (1 s) repeatability is smaller
than the given one in technical parameters (significant influence of the operational relay operating time, processor start-time, and the moment of supply
switching as referred to the AC supply course). The green LED - T time measurement (flashing); excited operational relay, time not measured
(steady light); de-excited operational relay, time not measured (no light).

Settings of switches

Connections diagrams Dimensions

Control contact (A3) S is activated by connecting it to A1 terminal.

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
PIR6WT-1Z
interface - time relays 19

Ordering codes

Ordering codes PIR6WT-1Z are specified in Table 1, "Time relay code" column.

Mounting

Relays PIR6WT-1Z are designed for 35 mm DIN rail mount, EN 50022. Maximum size of wires 1 x 2,5 mm2 (1 x 14
AWG). Rated contactability 2 x 1,5 mm2 (2 x 16 AWG). Maximum screw torgue: 0,3 Nm. Time relay PIR6WT-1Z
consists of: universal socket with electronic PI6WT-1Z and electromagnetic relay RM699V or solid state relay RSR30.
PIR6WT-1Z are adapted for the co-operation with interconnection strip type ZG20. Strip ZG20 bridges common input
or output signals, maximum permissible current is 36 A / 250 V AC. Colours of strips: ZG20-1 red, ZG20-2 black,
ZG20-3 blue.

PIR6WT-1Z RM699V RSR30 ZG20

Potentiometer P (t): Interconnection strip ZG20: Transparent, movable ejector:


smooth regulation of time bridging of common protection and easy replacement
within the range. input or output signals. of the operational relay,
It is recommended to use it plays the role of light indicator
a screwdriver of max. 2,5 mm. (optical wave-guide of LED diode).

Table of codes Table 1

Rated
Rated Power
Operational relay voltage of
Time relay code input of input Socket code
code operational
voltage control circuit
relay
Un
Us
PIR6WT-1Z-12VAC/DC-R 12 V AC/DC 0,5 VA / 0,5 W PI6WT-1Z-12/24VAC/DC RM699V-3011-85-1012 12 V DC
PIR6WT-1Z-24VAC/DC-R 24 V AC/DC 1,0 VA / 1,0 W PI6WT-1Z-12/24VAC/DC RM699V-3011-85-1024 24 V DC

PIR6WT-1Z-12VAC/DC-T 12 VAC/DC 0,5 VA / 0,5 W PI6WT-1Z-12/24VAC/DC RSR30-D12-A1-24-020-1 12 V DC


PIR6WT-1Z-24VAC/DC-T 24 VAC/DC 1,0 VA / 1,0 W PI6WT-1Z-12/24VAC/DC RSR30-D24-A1-24-020-1 24 V DC

PIR6WT-1Z-12VAC/DC-C 12 VAC/DC 0,5 VA / 0,5 W PI6WT-1Z-12/24VAC/DC RSR30-D12-D1-04-025-1 12 V DC


PIR6WT-1Z-24VAC/DC-C 24 V AC/DC 1,0 VA / 1,0 W PI6WT-1Z-12/24VAC/DC RSR30-D24-D1-04-025-1 24 V DC

PIR6WT-1Z-12VAC/DC-O 12 VAC/DC 0,5 VA / 0,5 W PI6WT-1Z-12/24VAC/DC RSR30-D12-D1-02-040-1 12 V DC


PIR6WT-1Z-24VAC/DC-O 24 V AC/DC 1,0 VA / 1,0 W PI6WT-1Z-12/24VAC/DC RSR30-D24-D1-02-040-1 24 V DC

The data in bold type pertain to the standard versions of the relays. It shall be remarked that rated input voltage of the operational relay Us not always complies
with the rated input voltage Un (which is important on ordering operational relays for sockets).

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
Time functions
20 of relays TR4N, T-R4, PIR15...T, PIR6WT-1Z

E - ON Delay Voltage Controlled Bp(S) - Flasher Pause Firstwith Control Contact

After the supply voltage [U] has been applied, the preset time [T]
measurement starts. After the time [T] has been measured, the output
relay [R] switches to ON position and remains in such until the supply After the control contact [S] has been switched on and then off at the
voltage [U] is removed. supply voltage [U] being applied, the measurement of the preset time
[T] starts. After the time has been measured, the output relay [R]
E(S) - ON Delay Voltage Controlled with Control Contact switches, and the time [T] is measured again. After the time has been
measured, the output relay returns to the initial position, and the next
cycle of the relay operation starts. The relay operates until the supply
voltage is removed.

Bi - Flasher Impulse First

After the supply voltage [U] has been applied, the time [T] measurement
starts. If the control contact [S] is switched on, the measurement
of time [T] is interrputed for the time of switching the control contact [S].
After the control contact [S] has been switched of, the time [T] (T=T1+T2) After the supply voltage [U] has been applied, the preset time [T]
is continued to be measured. After the time [T] has been measured, measurement starts simultaneously with switching of the output
the output relay [R] will switch, and it will be in operating postion until relay [R]. After the preset time [T] has been measured, the output relay
the supply voltage [U] is removed. [R] returns to the initial state, and the next operating cycle of the relay
starts. The relay operates until the supply voltage is removed.
Wu - Single Shot Leading Edge Voltage Controlled
Bi(S) - Flasher Impulse First with Control Contact

After the supply voltage [U] has been applied, the output relay [R]
switches immediately, and the preset time [T] is measured. After the
preset time [T] has been measured, the output relay [R] returns to the
initial state.
After the control contact [S] has been switched on and then off at the
supply voltage [U] being applied, the measurement of the preset time
Wu(S) - Single Shot Leading Edge Voltage Controlled with Control [T] starts with the simultaneous switching of the output relay [R]. After
Contact the time[T] has been measured, the output relay [R] returns to the initial
position and the time [T] measurement starts again. After the time [T]
has been measured, the next cycle of the relay operation starts.
The relay operates until the supply voltage is removed.

R - OFF Delay with Control Contact

After the supply voltage [U] has been applied, the output relay [R]
switches immediately and the preset time [T] measurement starts. If the
control contact [S] is switched on, the time [T] measurement will be
interrupted for the time for which the control contact [S] is switched.
After the control contact [S] has been released, the time [T] (T=T1+T2) is
continued to be measured. After the preset time [T] has been measured,
the output relay [R] returns to the initial position. The supply voltage [U] must be applied to the time relay continuously.
After the control contact [S] has been closed, the output relay [R] switches
immediately. After opening of the control contact [S] measurement
Bp - Flasher Pause First of the preset time [T] starts. After the preset time [T] has lapsed,
the output relay [R] returns to the initial position. If the control contact
[S] is closed again, even before the preset time [T] has lapsed, the
previously measured time is cancelled, and after the control contact [S]
has been opened, the preset time [T] is measured again.

After the supply voltage [U] has been applied, the preset time [T]
measurement starts. After the time [T] has been measured, the output
relay [R] switches to ON position and the preset time [T] is being measured
once more. After the preset time [T] has been measured, the output
relay [R] returns to the initial state, and the next operating cycle of the
relay starts. The relay operates until the supply voltage is removed.

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
Time functions
of relays TR4N, T-R4, PIR15...T, PIR6WT-1Z 21

Ws - Single Shot Leading Edge with Control Contact Esa - Delayed Switching ON and OFF Controlled with Control Contact

The supply voltage [U] must be applied to the time relay continuously. The supply voltage [U] must be applied to the time relay continuously.
After the control contact [S] has been closed, the output relay [R] switches After the control contact [S] has been closed, the preset time [T]
immediately. After opening of the control contact [S] measurement measurement starts, and after it has lapsed, the output relay [R]
of the preset time [T] starts. After the preset time [T] has lapsed, the is switched on. If closing time of control contact [S] is shorter than seting
output relay [R] returns to the initial position. In course of the time [T] time delay [T] output relay [R] will switch on after time delay [T] and
measurement the control contact [S] may be repeatedly closed and will be on during time [T]. Closing of control contact [S] during time
opened with no influence upon the output relay [R]. It is only after the of switch on output relay [R] will not influence for realize function.
time [T] has lapsed that closing of the control contact [S] causes switching
the output relay [R] on again and measurement of the time [T].
B - Flasher with Control Contact

Wa - Single Shot Trailing Edge with Control Contact

Each closing of the control contact [S] results in the change of the
The supply voltage [U] must be applied to the time relay continuously. output relay position to the opposite one (a feature of bistable relay).
Closing of the control contact [S] does not result in measurement of the
time delay or switching of the output relay [R]. It is only when the control
contact [S] is opened that the output relay [R] switches immediately and
the preset time [T] measurement starts. After the preset time [T] has Permanent switching ON and OFF
lapsed, the output relay [R] returns to the initial position. In course of the The functions available in TR4N relays. The functions ON and OFF are
time [T] measurement the control contact [S] may be repeatedly closed selected with TIME potentiometer. In the ON function, the normally
and opened with no influence upon the output relay [R]. It is only after open contacts are closed all the time whereas in the OFF function they
the time [T] has lapsed that closing and opening of the control contact are open. The position of the FUNC potentiometer is of no significance
[S] causes switching the output relay [R] on again and measurement in these functions as is the preset measurement time. The ON or OFF
of the time [T]. functions are used for the time relay operation control in electric systems.

Es - ON Delay with Control Contact


OFF - OFF mode
The mode available in PIR6WT-1Z relays. The OFF mode is selected
with the switches of TIME range settings. In the OFF mode the normally
open contact is permanently open. The position of MODE setting
switches is of no significance with this mode. The OFF mode appears
useful in operation control of the the time relay in electrical system.

The supply voltage [U] shall be applied to the time relay continuously.
After the control contact [S] has been closed, the preset time [T]
is measured after which the output relay [R] is switched on and remains
in this position until the control contact [S] is opened. If the closing time
of [S] is shorter than the preset time [T], the relay [R] will not operate.

PWM - Pulse with Modulation

After the supply voltage has been applied, the output relay switches on
for the preset time [T], and then switches off for the remaining time
interval to complete the full value of the preset interval [Tz].

U - supply voltage; R - output state of the relay; S - control contact state; T, T1, T2 - measured times; Tz - value of the set interval; t - time axis

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
TR-EM1P-UNI
22 time relays

Multifunction time relay


7 time functions: E, Wu, Bp, R, Ws, Wa, Es
7 time ranges: 1 s; 10 s; 1 min.; 10 min.; 1 h; 10 h; 100 h
Wide input voltage range: 12...240 V AC/DC
1 changeover contact: 1 C/O
Rated load: 8 A / 250 V AC at cat. AC1
Installation design: width 17,5 mm
Recognitions, certifications, directives:

Type of relay TR-EM1P-UNI


Output circuit
Number and type of contacts 1 C/O - changeover
Rated load AC1 8 A / 250 V AC
Max. breaking capacity AC1 2 000 VA
Max. operating frequency
at 100 VA resistive load 3 600 cycles/hour
PN-EN 60947-5-1
at 1 000 VA resistive load 360 cycles/hour
Input circuit
Supply voltage U 12...240 V AC/DC, AC: 50/60 Hz; terminals A1(+)-A2
Drop-out voltage AC: 0,3 Un
Operating range of supply voltage 0,9 < Un < 1,1
Rated power consumption 4,0 VA / 1,5 W
Rated frequency AC: 48...63 Hz
Duty cycle 100%
Residual ripple to DC 10%
Control contact input terminals A1-B1
loadable yes
max. line length 10 m
trigger level (sensitivity) automatic adaption to supply voltage
Insulation
Rated surge voltage 4 000 V AC
Overvoltage category III PN-EN 60664-1
Insulation pollution degree 2, if built-in 3 PN-EN 60664-1
General data
Electrical life resistive AC1 2 x 105 1 000 VA
Mechanical life (cycles) 2 x 107
Dimensions (L x W x H) 87 x 17,5 x 60 mm
Weight 63 g
Ambient temperature storage, transport -25...+70 oC
operating -25...+55 oC PN-EN 60068-1
Housing protection category IP 40
Relative humidity 15...85% PN-EN 60721-3-3 class 3K3
Shock resistance 15 g 11 ms PN-EN 60068-2-27
Vibration resistance 0,35 mm DA 10...55 Hz PN-EN 60068-2-6
Time module data
Functions E, Wu, Bp, R, Ws, Wa, Es
Time intervals (timing adjustment) 1 s (50 ms...1 s); 10 s (0,5...10 s); 1 min. (3 s...1 min.); 10 min. (30 s...10 min.);
1 h (3 min. ...1 h); 10 h (30 min. ...10 h); 100 h (5...100 h)
Base accuracy 1% (calculate from final range value)
Setting accuracy 5% (calculate from final range value)
Repeatability 0,5% or 5 ms
Temperature influence 0,01% / C
Recovery time 100 ms
Min. pulse of the control contact AC: 100 ms DC: 50 ms
LED indicator green LED U/T ON - indication of supply voltage
green LED U/T flashing - indication of time period T
yellow LED R ON/OFF - indication of output relay
The function has to be set before connecting the relay to the supply voltage.

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
TR-EM1P-UNI
time relays 23

Dimensions Connections diagrams

Without control contact S With control contact S

Mounting, mechanical design

Relays TR-EM1P-UNI are designed for direct mounting on 35 mm DIN rail mount, EN 50022. Mounting position: any.
Self-extinguishing plastic housing, IP 40. Shockproof terminal connection according to VBG 4 (PZ1 required), IP 20.
Maximum screw torgue: 1,0 Nm. Terminal capacity: 1 x 0,5 do 2,5 mm2 with/without multicore cable end, 1 x 4 mm2 without
multicore cable end, 2 x 0,5 do 1,5 mm2 with/without multicore cable end, 2 x 2,5 mm2 flexible without multicore cable end.

Functions

E - ON delay again. After the interval T has expired, the Wa - single shot trailling edge with control
output relay switches into off-position (yellow input S
LED not illuminated). The output relay is
triggered at a ratio of 1:1 until the supply
When the supply voltage U is applied, the set voltage is interrupted.
interval T begins (green LED U/T flashes).
After the interval T has expired (green LED R - OFF delay The supply voltage U must be constantly
U/T illuminated) the output relay R switches applied to the device (green LED U/T
into on-position (yellow LED illuminated). illuminated). Closing the control contact S
This status remains until the supply voltage is has no influence on the condition of the
interrupted. If the supply voltage is interrupted output R. When the control contact is
before the expiry of the interval T, the interval The supply voltage U must be constantly opened, the output relay switches into
already expired is erased and is restarted when applied to the device (green LED U/T on-position (yellow LED illuminated) and the
the supply voltage is next applied. illuminated). When the control contact S set interval T begins (green LED U/T flashes).
is closed, the output relay R switches into After the interval T has expired (green LED
Wu - single shot leading edge voltage on-position (yellow LED illuminated). If the U/T illuminated), the ouput relay switches
controlled control contact is opened, the set interval T into off-position (yellow LED not illuminated).
begins (green LED flashes). After the interval During the interval, the control contact can
T has expired (green LED U/T illuminated) be operated any number of times. A further
the output relay switches into off-position cycle can only be started when the cycle run
When the supply voltage U is applied, the (yellow LED not illuminated). If the control has been completed.
output relay R switches into on-position contact is closed again before the interval T
(yellow LED illuminated) and the set interval has expired, the interval already expired is Es - ON delay with control input S
T begins (green LED U/T flashes). After the erased and is restarted.
interval T has expired (green LED U/T
illuminated) the output relay switches into Ws - single shot leading edge with control
off-position (yellow LED not illuminated). input S
This status remains until the supply voltage is The supply voltage U must be constantly
interrupted. If the supply voltage is interrupted applied to the device (green LED U/T
before the interval T has expired, the output illuminated). When the control contact S
relay switches into off-position. The interval is closed, the set interval T begins (green LED
The supply voltage U must be constantly U/T flashes). After the interval T has expired
already is erased and is restarted when the
applied to the device (green LED U/T illumi- (green LED U/T illuminated) the output relay
supply voltage is next applied.
nated). When the control contact S is closed, R switches into on-position (yellow LED
the output relay R switches into on-position illuminated). This status remains until the
Bp - flasher pause first
(green LED U/T illuminated) and the set control contact is opened again. If the control
interval T begins (green LED U/T flashes). contact is opened before the interval T has
After the interval T has expired (green LED expired, the interval already expired is erased
U/T illuminated) the output relay switches and is restarted with the next cycle.
When the supply voltage U is applied, the set into off-position (yellow LED not illuminated).
interval T begins (green LED U/T flashes). During the interval, the control contact can
After the interval T has expired, the output be operated any number of times. A further
relay R switches into on-position (yellow LED cycle can only be started when the cycle run U - supply voltage; R - output relay;
illuminated) and the set interval T begins has been completed. S - control contact; T - timing adjustment

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
TR-EM2P-UNI
24 time relays

Multifunction time relay


7 time functions: E, Wu, Bp, R, Ws, Wa, Es
7 time ranges: 1 s; 10 s; 1 min.; 10 min.; 1 h; 10 h; 100 h
Wide input voltage range: 12...240 V AC/DC
2 changeover contacts: 2 C/O
Rated load: 8 A / 250 V AC at cat. AC1
Installation design: width 35 mm
Recognitions, certifications, directives:

Type of relay TR-EM2P-UNI


Output circuit
Number and type of contacts 2 C/O - changeover
Rated load AC1 8 A / 250 V AC
Max. breaking capacity AC1 2 000 VA
Max. operating frequency
at 100 VA resistive load 3 600 cycles/hour
PN-EN 60947-5-1
at 1 000 VA resistive load 360 cycles/hour
Input circuit
Supply voltage U 12...240 V AC/DC, AC: 50/60 Hz; terminals A1(+)-A2
Drop-out voltage AC: 0,3 Un
Operating range of supply voltage 0,9 < Un < 1,1
Rated power consumption 6,0 VA / 2,0 W
Rated frequency AC: 48...63 Hz
Duty cycle 100%
Residual ripple to DC 10%
Control contact input terminals A1-B1
loadable yes
max. line length 10 m
trigger level (sensitivity) automatic adaption to supply voltage
Insulation
Rated surge voltage 4 000 V AC
Overvoltage category III PN-EN 60664-1
Insulation pollution degree 2, if built-in 3 PN-EN 60664-1
General data
Electrical life resistive AC1 2 x 105 1 000 VA
Mechanical life (cycles) 2 x 107
Dimensions (L x W x H) 87 x 35 x 60 mm
Weight 120 g
Ambient temperature storage, transport -25...+70 oC
operating -25...+55 oC PN-EN 60068-1
Housing protection category IP 40
Relative humidity 15...85% PN-EN 60721-3-3 class 3K3
Shock resistance 15 g 11 ms PN-EN 60068-2-27
Vibration resistance 0,35 mm DA 10...55 Hz PN-EN 60068-2-6
Time module data
Functions E, Wu, Bp, R, Ws, Wa, Es
Time intervals (timing adjustment) 1 s (50 ms...1 s); 10 s (0,5...10 s); 1 min. (3 s...1 min.); 10 min. (30 s...10 min.);
1 h (3 min. ...1 h); 10 h (30 min. ...10 h); 100 h (5...100 h)
Base accuracy 1% (calculate from final range value)
Setting accuracy 5% (calculate from final range value)
Repeatability 0,5% or 5 ms
Temperature influence 0,01% / C
Recovery time 100 ms
Min. pulse of the control contact AC: 100 ms DC: 50 ms
LED indicator green LED U/T ON - indication of supply voltage
green LED U/T flashing - indication of time period T
yellow LED R ON/OFF - indication of output relay
The function has to be set before connecting the relay to the supply voltage.

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
TR-EM2P-UNI
time relays 25

Dimensions Connections diagrams

Without control contact S With control contact S

Mounting, mechanical design

Relays TR-EM2P-UNI are designed for direct mounting on 35 mm DIN rail mount, EN 50022. Mounting position: any.
Self-extinguishing plastic housing, IP 40. Shockproof terminal connection according to VBG 4 (PZ1 required), IP 20.
Maximum screw torgue: 1,0 Nm. Terminal capacity: 1 x 0,5 do 2,5 mm2 with/without multicore cable end, 1 x 4 mm2 without
multicore cable end, 2 x 0,5 do 1,5 mm2 with/without multicore cable end, 2 x 2,5 mm2 flexible without multicore cable end.

Functions

E - ON delay again. After the interval T has expired, the Wa - single shot trailling edge with control
output relay switches into off-position (yellow input S
LED not illuminated). The output relay is
triggered at a ratio of 1:1 until the supply
When the supply voltage U is applied, the set voltage is interrupted.
interval T begins (green LED U/T flashes).
After the interval T has expired (green LED R - OFF delay The supply voltage U must be constantly
U/T illuminated) the output relay R switches applied to the device (green LED U/T
into on-position (yellow LED illuminated). illuminated). Closing the control contact S
This status remains until the supply voltage is has no influence on the condition of the
interrupted. If the supply voltage is interrupted output R. When the control contact is
before the expiry of the interval T, the interval The supply voltage U must be constantly opened, the output relay switches into
already expired is erased and is restarted when applied to the device (green LED U/T on-position (yellow LED illuminated) and the
the supply voltage is next applied. illuminated). When the control contact S set interval T begins (green LED U/T flashes).
is closed, the output relay R switches into After the interval T has expired (green LED
Wu - single shot leading edge voltage on-position (yellow LED illuminated). If the U/T illuminated), the ouput relay switches
controlled control contact is opened, the set interval T into off-position (yellow LED not illuminated).
begins (green LED flashes). After the interval During the interval, the control contact can
T has expired (green LED U/T illuminated) be operated any number of times. A further
the output relay switches into off-position cycle can only be started when the cycle run
When the supply voltage U is applied, the (yellow LED not illuminated). If the control has been completed.
output relay R switches into on-position contact is closed again before the interval T
(yellow LED illuminated) and the set interval has expired, the interval already expired is Es - ON delay with control input S
T begins (green LED U/T flashes). After the erased and is restarted.
interval T has expired (green LED U/T
illuminated) the output relay switches into Ws - single shot leading edge with control
off-position (yellow LED not illuminated). input S
This status remains until the supply voltage is The supply voltage U must be constantly
interrupted. If the supply voltage is interrupted applied to the device (green LED U/T
before the interval T has expired, the output illuminated). When the control contact S
relay switches into off-position. The interval is closed, the set interval T begins (green LED
The supply voltage U must be constantly U/T flashes). After the interval T has expired
already is erased and is restarted when the
applied to the device (green LED U/T illumi- (green LED U/T illuminated) the output relay
supply voltage is next applied.
nated). When the control contact S is closed, R switches into on-position (yellow LED
the output relay R switches into on-position illuminated). This status remains until the
Bp - flasher pause first
(green LED U/T illuminated) and the set control contact is opened again. If the control
interval T begins (green LED U/T flashes). contact is opened before the interval T has
After the interval T has expired (green LED expired, the interval already expired is erased
U/T illuminated) the output relay switches and is restarted with the next cycle.
When the supply voltage U is applied, the set into off-position (yellow LED not illuminated).
interval T begins (green LED U/T flashes). During the interval, the control contact can
After the interval T has expired, the output be operated any number of times. A further
relay R switches into on-position (yellow LED cycle can only be started when the cycle run U - supply voltage; R - output relay;
illuminated) and the set interval T begins has been completed. S - control contact; T - timing adjustment

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
TR-EI1P-UNI
26 time relays

Asymmetric flasher with controled times T1 and T2


2 time functions: li, lp
7 time ranges: 1 s; 10 s; 1 min.; 10 min.; 1 h; 10 h; 100 h
Wide input voltage range: 12...240 V AC/DC
1 changeover contact: 1 C/O
Rated load: 8 A / 250 V AC at cat. AC1
Installation design: width 17,5 mm
Recognitions, certifications, directives:

Type of relay TR-EI1P-UNI


Output circuit
Number and type of contacts 1 C/O - changeover
Rated load AC1 8 A / 250 V AC
Max. breaking capacity AC1 2 000 VA
Max. operating frequency
at 100 VA resistive load 3 600 cycles/hour
PN-EN 60947-5-1
at 1 000 VA resistive load 360 cycles/hour
Input circuit
Supply voltage U 12...240 V AC/DC, AC: 50/60 Hz; terminals A1(+)-A2
Drop-out voltage AC: 0,3 Un
Operating range of supply voltage 0,9 < Un < 1,1
Rated power consumption 4,0 VA / 1,5 W
Rated frequency AC: 48...63 Hz
Duty cycle 100%
Residual ripple to DC 10%
Control contact input terminals A1-B1
loadable yes
max. line length 10 m
trigger level (sensitivity) automatic adaption to supply voltage
Insulation
Rated surge voltage 4 000 V AC
Overvoltage category III PN-EN 60664-1
Insulation pollution degree 2, if built-in 3 PN-EN 60664-1
General data
Electrical life resistive AC1 2 x 105 1 000 VA
Mechanical life (cycles) 2 x 107
Dimensions (L x W x H) 87 x 17,5 x 60 mm
Weight 63 g
Ambient temperature storage, transport -25...+70 oC
operating -25...+55 oC PN-EN 60068-1
Housing protection category IP 40
Relative humidity 15...85% PN-EN 60721-3-3 class 3K3
Shock resistance 15 g 11 ms PN-EN 60068-2-27
Vibration resistance 0,35 mm DA 10...55 Hz PN-EN 60068-2-6
Time module data
Functions Ii - A1-B1 terminals bridged Ip - terminals not bridged
Time intervals (timing adjustment) 1 s (50 ms...1 s); 10 s (0,5...10 s); 1 min. (3 s...1 min.); 10 min. (30 s...10 min.);
1 h (3 min. ...1 h); 10 h (30 min. ...10 h); 100 h (5...100 h)
Base accuracy 1% (calculate from final range value)
Setting accuracy 5% (calculate from final range value)
Repeatability 0,5% or 5 ms
Temperature influence 0,01% / C
Recovery time 100 ms
LED indicator green LED U/T ON - indication of supply voltage
green LED U/T slow flashing - indication of time period T1
green LED U/T fast flashing - indication of time period T2
yellow LED R ON/OFF - indication of output relay

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
TR-EI1P-UNI
time relays 27

Dimensions Connections diagram

Mounting, mechanical design

Relays TR-EI1P-UNI are designed for direct mounting on 35 mm DIN rail mount, EN 50022. Mounting position: any.
Self-extinguishing plastic housing, IP 40. Shockproof terminal connection according to VBG 4 (PZ1 required), IP 20.
Maximum screw torgue: 1,0 Nm. Terminal capacity: 1 x 0,5 do 2,5 mm2 with/without multicore cable end, 1 x 4 mm2 without
multicore cable end, 2 x 0,5 do 1,5 mm2 with/without multicore cable end, 2 x 2,5 mm2 flexible without multicore cable end.

Functions

Ii - asymmetric flasher pulse first Ip - asymmetric flasher pause first

When the supply voltage U is applied, When the supply voltage U is applied, the set
the output relay R switches into on-position interval T1 begins (green LED U/T flashes
(yellow LED illuminated) and the set interval slowly). After the interval T1 has expired,
T1 begins (green LED U/T flashes slowly). After the output relay R switches into on-position
the interval T1 has expired, the output relay (yellow LED illuminated) and the set interval
switches into off-position (yellow LED not T2 begins (green LED U/T flashes fast). After
illuminated) and the set interval T2 begins the interval T2 has expired, the output relay
(green LED U/T flashes fast). After the interval switches into off-position (yellow LED not
T2 has expired, the output relay switches illumninated). The output relay is triggered
into on-position (yellow LED illuminated). at the ratio of T1:T2 until the supply voltage
The output relay is triggered at the ratio of is interrupted.
T1:T2 until the supply voltage is interrupted.
Ip - terminals not bridged
Ii - A1-B1 terminals bridged

U - supply voltage; R - output relay; T1-T2 - timing adjustment

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
TR-EI2P-UNI
28 time relays

Multifunction time relays with controled times T1 and T2


7 time functions: li, lp, EWu, ER, EWs, WsWa, Wt
7 time ranges: 1 s; 10 s; 1 min.; 10 min.; 1 h; 10 h; 100 h
Wide input voltage range: 12...240 V AC/DC
2 changeover contacts: 2 C/O
Rated load: 8 A / 250 V AC at cat. AC1
Installation design: width 35 mm
Recognitions, certifications, directives:

Type of relay TR-EI2P-UNI


Output circuit
Number and type of contacts 2 C/O - changeover
Rated load AC1 8 A / 250 V AC
Max. breaking capacity AC1 2 000 VA
Max. operating frequency
at 100 VA resistive load 3 600 cycles/hour
PN-EN 60947-5-1
at 1 000 VA resistive load 360 cycles/hour
Input circuit
Supply voltage U 12...240 V AC/DC, AC: 50/60 Hz; terminals A1(+)-A2
Drop-out voltage AC: 0,3 Un
Operating range of supply voltage 0,9 < Un < 1,1
Rated power consumption 6,0 VA / 2,0 W
Rated frequency AC: 48...63 Hz
Duty cycle 100%
Residual ripple to DC 10%
Control contact input terminals A1-B1
loadable yes
max. line length 10 m
trigger level (sensitivity) automatic adaption to supply voltage
Insulation
Rated surge voltage 4 000 V AC
Overvoltage category III PN-EN 60664-1
Insulation pollution degree 2, if built-in 3 PN-EN 60664-1
General data
Electrical life resistive AC1 2 x 105 1 000 VA
Mechanical life (cycles) 2 x 107
Dimensions (L x W x H) 87 x 35 x 60 mm
Weight 120 g
Ambient temperature storage, transport -25...+70 oC
operating -25...+55 oC PN-EN 60068-1
Housing protection category IP 40
Relative humidity 15...85% PN-EN 60721-3-3 class 3K3
Shock resistance 15 g 11 ms PN-EN 60068-2-27
Vibration resistance 0,35 mm DA 10...55 Hz PN-EN 60068-2-6
Time module data
Functions EWu, ER, EWs, WsWa, Wt
Ii - A1-B1 terminals bridged Ip - terminals not bridged
Time intervals (timing adjustment) 1 s (50 ms...1 s); 10 s (0,5...10 s); 1 min. (3 s...1 min.); 10 min. (30 s...10 min.);
1 h (3 min. ...1 h); 10 h (30 min. ...10 h); 100 h (5...100 h)
Base accuracy 1% (calculate from final range value)
Setting accuracy 5% (calculate from final range value)
Repeatability 0,5% or 5 ms
Temperature influence 0,01% / C
Recovery time 100 ms
Min. pulse of the control contact AC: 100 ms DC: 50 ms
LED indicator green LED U/T ON - indication of supply voltage
green LED U/T slow flashing - indication of time period T1
green LED U/T fast flashing - indication of time period T2
yellow LED R ON/OFF - indication of output relay
The function has to be set before connecting the relay to the supply voltage.

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
TR-EI2P-UNI
time relays 29

Dimensions Connections diagram

Mounting, mechanical design

Relays TR-EI2P-UNI are designed for direct mounting on 35 mm DIN rail mount, EN 50022. Mounting position: any.
Self-extinguishing plastic housing, IP 40. Shockproof terminal connection according to VBG 4 (PZ1 required), IP 20.
Maximum screw torgue: 1,0 Nm. Terminal capacity: 1 x 0,5 do 2,5 mm2 with/without multicore cable end, 1 x 4 mm2 without
multicore cable end, 2 x 0,5 do 1,5 mm2 with/without multicore cable end, 2 x 2,5 mm2 flexible without multicore cable end.

Functions

Ii - asymmetric flasher pulse first not illuminated). If the supply voltage is interrupted WsWa - single shot leading and single shot
before the interval T1+T2 has expired, the interval trailing edge with control contact
already expired is erased and is restarted when the
supply voltage is next applied.
When the supply voltage U is applied, the output
relay R switches into on-position (yellow LED
ER - ON delay and OFF delay with control
illuminated) and the set interval T1 begins (green contact The supply voltage U must be constantly applied
LED U/T flashes slowly). After the interval T1 has to the device (green LED U/T illuminated). When
expired, the output relay switches into off-position the control contact S is closed, the output relay R
switches into on-position (yellow LED illuminated)
(yellow LED not illuminated) and the set interval T2
and the set interval T1 begins (green LED U/T
begins (green LED U/T flashes fast). After the flashes slowly). After the interval T1 has expired,
interval T2 has expired, the output relay switches The supply voltage U must be constantly applied the output relay R switches into off-position
into on-position (yellow LED illuminated). The to the device (green LED U/T illuminated). When (yellow LED not illuminated). If the control contact
output relay is triggered at the ratio of T1:T2 until the control contact S is closed, the set interval T1 is opened, the output relay again switches into
the supply voltage is interrupted. begins (green LED U/T flashes slowly). After the on-position (yellow LED illuminated) and the set
interval T1 has expired, the output relay R switches interval T2 begins (green LED U/T flashes fast).
Ip - asymmetric flasher pause first into on-position (yellow LED illuminated). If the After the interval T2 has expired the output relay
control contact is opened, the set interval T2 switches into off-position (yellow LED not illumi-
nated). During the interval, the control contact can
begins (green LED U/T flashes fast). After the
be operated any number of times.
interval T2 has expired, the output relay switches
into off-position (yellow LED not illuminated). If the
When the supply voltage U is applied, the set Wt - pulse sequence monitoring
interval T1 begins (green LED U/T flashes slowly). control contact is opened before the interval T1
After the interval T1 has expired, the output relay has expired, the interval already expired is erased
R switches into on-position (yellow LED illuminated) and is restarted with the next cycle.
and the set interval T2 begins (green LED U/T
flashes fast). After the interval T2 has expired, EWs - ON delay and single shot leading edge
When the supply voltage U is applied, the set
the output 2 changeover contacts switches into with control contact
interval T1 begins (green LED U/T flashes slowly)
off-position (yellow LED not illumninated). The output and the output relay R switches into on-position
2 changeover contacts is triggered at the ratio (yellow LED illuminated). After the interval T1 has
of T1:T2 until the supply voltage is interrupted. expired, the set interval T2 begins (green LED U/T
flashes fast). So that the output relay R remains
EWu - ON delay and single shot leading edge The supply voltage U must be constantly applied
in on-position, the control contact S must be closed
voltage controlled to the device (green LED U/T illuminated). When
and opened again within the set interval T2. If this
the control contact S is closed, the set interval T1
does not happen, the output relay R switches into
begins (green LED U/T flashes slowly). After the
off-position (yellow LED not illuminated) and
interval T1 has expired, the output relay R switches
all further pulses at the control contact are ignored.
into on-position (yellow LED illuminated) and the
To restart the function the supply voltage must be
When the supply voltage U is applied, the set set interval T2 begins (green LED U/T flashes fast).
interrupted and reapplied.
interval T1 begins (green LED U/t flashes slowly). After the interval T2 has expired, the output relay
After the interval T1 has expired, the output relay switches into off-position (yellow LED not illumi-
R switches into on-position (yellow LED illuminated) nated). During the interval, the control contact can
and the set interval T2 begins (green LED U/T be operated any number of times. A further cycle U - supply voltage; R - output relay;
flashes fast). After the interval T2 has expired, the can only be started when the cycle run has been S - control contact; T1-T2 - timing adjustment
output relay switches into off-position (yellow LED completed.

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
TR-ES2P-UNI
30 time relays

Star-delta start up with controled times T1 and T2


4 time ranges: 10 s; 30 s; 1 min.; 3 min.
4 transit times (fixed): 40 ms; 60 ms; 80 ms; 100 ms
Wide input voltage range: 12...240 V AC/DC
2 changeover contacts: 2 C/O
Rated load: 8 A / 250 V AC at cat. AC1
Installation design: width 35 mm
Recognitions, certifications, directives:

Type of relay TR-ES2P-UNI


Output circuit
Number and type of contacts 2 C/O - changeover
Rated load AC1 8 A / 250 V AC
Max. breaking capacity AC1 2 000 VA
Max. operating frequency
at 100 VA resistive load 3 600 cycles/hour
PN-EN 60947-5-1
at 1 000 VA resistive load 360 cycles/hour
Input circuit
Supply voltage U 12...240 V AC/DC, AC: 50/60 Hz; terminals A1(+)-A2
Drop-out voltage AC: 0,3 Un
Operating range of supply voltage 0,9 < Un < 1,1
Rated power consumption 4,0 VA / 1,5 W
Rated frequency AC: 48...63 Hz
Duty cycle 100%
Residual ripple to DC 10%
Control contact input terminals A1-B1
loadable yes
max. line length 10 m
trigger level (sensitivity) automatic adaption to supply voltage
Insulation
Rated surge voltage 4 000 V AC
Overvoltage category III PN-EN 60664-1
Insulation pollution degree 2, if built-in 3 PN-EN 60664-1
General data
Electrical life resistive AC1 2 x 105 1 000 VA
Mechanical life (cycles) 2 x 107
Dimensions (L x W x H) 87 x 35 x 60 mm
Weight 120 g
Ambient temperature storage, transport -25...+70 oC
operating -25...+55 oC PN-EN 60068-1
Housing protection category IP 40
Relative humidity 15...85% PN-EN 60721-3-3 class 3K3
Shock resistance 15 g 11 ms PN-EN 60068-2-27
Vibration resistance 0,35 mm DA 10...55 Hz PN-EN 60068-2-6
Time module data
Functions S
Time intervals (timing adjustment) 10 s (0,5...10 s); 30 s (1,5..30 s); 1 min. (3 s...1 min.); 3 min. (9 s...3 min.)
transit times (fixed) 40 ms; 60 ms; 80 ms; 100 ms
Base accuracy 1% (calculate from final range value)
Setting accuracy 5% (calculate from final range value)
Repeatability 0,5% or 5 ms
Temperature influence 0,01% / C
Recovery time 100 ms
LED indicator green LED U/T ON - indication of supply voltage delta-contactor
in on-position (terminals 25-28)
green LED U/T flashing - indication of time period star time
yellow LED R ON/OFF - indication of star-contactor (terminals 15-18)

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
TR-ES2P-UNI
time relays 31

Dimensions Connections diagram

Mounting, mechanical design

Relays TR-ES2P-UNI are designed for direct mounting on 35 mm DIN rail mount, EN 50022. Mounting position: any.
Self-extinguishing plastic housing, IP 40. Shockproof terminal connection according to VBG 4 (PZ1 required), IP 20.
Maximum screw torgue: 1,0 Nm. Terminal capacity: 1 x 0,5 do 2,5 mm2 with/without multicore cable end, 1 x 4 mm2 without
multicore cable end, 2 x 0,5 do 1,5 mm2 with/without multicore cable end, 2 x 2,5 mm2 flexible without multicore cable end.

Functions

S - Star-delta start up

When the supply voltage U is applied, the star-


contact switches into on-position (yellow LED
illuminated) and the set star-time T1 begins
(green LED U/T flashes). After the interval T1
has expired (green LED U/T illuminated) the
star-contact switches into off-position (yellow
LED not illuminated) and the set transit-time
T2 begins. After the interval T2 has expired
the contact for the delta-contactor switches into
on-position. To restart the function the supply
voltage must be interrupted and re-applied.

U - supply voltage; T1-T2 - timing adjustment

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
MR-EU3M1P
32 monitoring relays

Voltage monitoring in 3-phase mains


Monitoring of phase sequence and phase failure
Monitoring of asymmetry
Connection of neutral wire optional
Supply voltage = measuring voltage
1 changeover contact: 1 C/O
Rated load: 5 A / 250 V AC at cat. AC1
Installation design: width 17,5 mm
Recognitions, certifications, directives:

Type of relay MR-EU3M1P


Output circuit
Number and type of contacts 1 C/O - changeover
Rated load AC1 5 A / 250 V AC
Max. breaking capacity AC1 1 250 VA
Max. operating frequency
at 100 VA resistive load 3 600 cycles/hour
PN-EN 60947-5-1
at 1 000 VA resistive load 360 cycles/hour
Input circuit
Supply voltage U = measuring voltage; terminals (N)-L1-L2-L3
Rated voltage Un 3(N)~400/230 V
Drop-out voltage AC: 0,2 Un
Operating range of supply voltage 0,7 < Un < 1,3
Rated power consumption 8,0 VA / 0,8 W
Rated frequency AC: 48...63 Hz
Duty cycle 100%
Measuring circuit terminals (N)-L1-L2-L3
measuring variable 3(N)~, sinus, 48...63 Hz
measuring input = supply voltage
overload capacity determined by tolerance specified for supply voltage
asymmetry 5...25%
Insulation
Rated surge voltage 4 000 V AC
Overvoltage category III PN-EN 60664-1
Insulation pollution degree 2, if built-in 3 PN-EN 60664-1
General data
Electrical life resistive AC1 2 x 105 1 000 VA
Mechanical life (cycles) 2 x 107
Dimensions (L x W x H) 87 x 17,5 x 60 mm
Weight 63 g
Ambient temperature storage, transport -25...+70 oC
operating -25...+55 oC PN-EN 60068-1
Housing protection category IP 40
Relative humidity 15...85% PN-EN 60721-3-3 class 3K3
Shock resistance 15 g 11 ms PN-EN 60068-2-27
Vibration resistance 0,35 mm DA 10...55 Hz PN-EN 60068-2-6
Meassuring circuit data
Functions monitoring of phase sequence, phase failure and asymmetry
with adjustable asymmetrie , connection of neutral wire optional
Time intervals tripping delay (fixed, approx. 0,1 s)
Base accuracy 5% (calculate from final range value)
Setting accuracy 5% (calculate from final range value)
Repeatability 2%
Temperature influence 0,05% / C
Recovery time 500 ms
LED indicator green LED U/T ON - indication of supply voltage
yellow LED R ON/OFF - indication of output relay
By means of evaluating the asymmetry.

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
MR-EU3M1P
monitoring relays 33

Dimensions Connections diagram

Mounting, mechanical design

Relays MR-EU3M1P are designed for direct mounting on 35 mm DIN rail mount, EN 50022. Mounting position: any.
Self-extinguishing plastic housing, IP 40. Shockproof terminal connection according to VBG 4 (PZ1 required), IP 20.
Maximum screw torgue: 1,0 Nm. Terminal capacity: 1 x 0,5 do 2,5 mm2 with/without multicore cable end, 1 x 4 mm2 without
multicore cable end, 2 x 0,5 do 1,5 mm2 with/without multicore cable end, 2 x 2,5 mm2 flexible without multicore cable end.

Functions

Phase sequence monitoring Phase failure monitoring Asymmetry monitoring

When all the phases are connected in The output relay R switches into off-position The output relay R switches into off-position
the correct sequence and the measured (yellow LED not illuminated), when one (yellow LED not illuminated) when the asym-
asymmetry is less than the fixed value, of the three phases fails. metrie exceeds the value set at the ASYM-
the output relay R switches into on-position regulator. Reverse voltages of a consumer
(yellow LED illuminated). When the phase (e.g. a motor which continues to run on two
sequence changes, the output relay R phases only) do not effect the disconnection.
switches into off-position (yellow LED not
illuminated).

U - supply voltage; R - output relay

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
MR-EU31UW1P
34 monitoring relays

Voltage monitoring in 3-phase and 1-phase mains


Multifunctions monitoring relays
Monitoring of phase sequence and phase failure
Connection of neutral wire optional
Supply voltage = measuring voltage
1 changeover contact: 1 C/O
Rated load: 5 A / 250 V AC at cat. AC1
Installation design: width 17,5 mm
Recognitions, certifications, directives:
Type of relay MR-EU31UW1P
Output circuit
Number and type of contacts 1 C/O - changeover
Rated load AC1 5 A / 250 V AC
Max. breaking capacity AC1 1 250 VA
Max. operating frequency
at 100 VA resistive load 3 600 cycles/hour
PN-EN 60947-5-1
at 1 000 VA resistive load 360 cycles/hour
Input circuit
Supply voltage U = measuring voltage; terminals (N)-L1-L2-L3
Rated voltage Un 3(N)~400/230 V
Drop-out voltage AC: 0,2 Un
Operating range of supply voltage 0,7 < Un < 1,3
Rated power consumption 8,0 VA / 1,0 W
Rated frequency AC: 48...63 Hz
Duty cycle 100%
Measuring circuit terminals (N)-L1-L2-L3
measuring variable 3(N)~, sinus, 48...63 Hz
measuring input = supply voltage
overload capacity determined by tolerance specified for supply voltage
swiching threshold Us max.: 0,8 < Un < 1,3 min.: 0,7 < Un < 1,2

Insulation
Rated surge voltage 4 000 V AC
Overvoltage category III PN-EN 60664-1
Insulation pollution degree 2, if built-in 3 PN-EN 60664-1
General data
Electrical life resistive AC1 2 x 105 1 000 VA
Mechanical life (cycles) 2 x 107
Dimensions (L x W x H) 87 x 17,5 x 60 mm
Weight 72 g
Ambient temperature storage, transport -25...+70 oC
operating -25...+55 oC PN-EN 60068-1
Housing protection category IP 40
Relative humidity 15...85% PN-EN 60721-3-3 class 3K3
Shock resistance 15 g 11 ms PN-EN 60068-2-27
Vibration resistance 0,35 mm DA 10...55 Hz PN-EN 60068-2-6
Meassuring circuit data
Functions UNDER, UNDER+SEQ, WIN, WIN+SEQ
monitoring of phase sequence and phase failure,
connection of neutral wire optional
Time intervals (timing adjustment) tripping delay (0,1...10 s)
Base accuracy 5% (calculate from final range value)
Setting accuracy 5% (calculate from final range value)
Repeatability 2%
Temperature influence 0,05% / C
Recovery time 500 ms
LED indicator red LED ON/OFF - indication of failure
red LED flashes - indication of tripping delay
yellow LED R ON/OFF - indication of output relay
With adjustable thresholdes.
Selectable.
Selectable by means of rotary switch.
Of the corresponding threshold.

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
MR-EU31UW1P
monitoring relays 35

Dimensions Connections diagrams

1-phase main 3-phase main

Mounting, mechanical design

Relays MR-EU31UW1P are designed for direct mounting on 35 mm DIN rail mount, EN 50022. Mounting position: any.
Self-extinguishing plastic housing, IP 40. Shockproof terminal connection according to VBG 4 (PZ1 required), IP 20.
Maximum screw torgue: 1,0 Nm. Terminal capacity: 1 x 0,5 do 2,5 mm2 with/without multicore cable end, 1 x 4 mm2 without
multicore cable end, 2 x 0,5 do 1,5 mm2 with/without multicore cable end, 2 x 2,5 mm2 flexible without multicore cable end.

Functions

For all functions the LED's MIN and MAX are WIN, WIN+SEQ - voltage monitoring SEQ - phase sequence monitoring
flashing alternating (the relay is fallen off), in windowfunction between MIN and MAX
when the minimum value for the measured values, voltage monitoring in window-
voltage was chosen to be greater than the
function between MIN and MAX values and
maximum value. If a failure already exists,
when the device is activated, the output relay monitoring of phase sequence
R remains in off-position and the LED for
the corresponding threshold is illuminated.
The device includes seperately every phase
voltage (L-N) and monitors it according to the
selected function (UNDER or WINDOW). Phase sequence monitoring is selectable for
all functions. In single phase circuit, the phase
sequence monitoring must be disconnected.
UNDER, UNDER+SEQ - undervoltage If a change in phase sequence is detected
monitoring, undervoltage monitoring and The output relay R switches into on-position (red LED SEQ illuminated), the output relay
monitoring of phase sequence (yellow LED illuminated), when the measured R switches into off-position after the set
voltage (all phase voltages) exceeds the interval of tripping delay (Delay) has expired
value adjusted at the MIN-regulator. When (yellow LED not illuminated).
the measured voltage (one of the phase
voltages) exceeds the value adjusted at the Loss of neutral wire by means of evaluation
MAX-regulator, the set interval of tripping of asymmetry
delay (Delay) begins (red LED MAX flashes).
After the interval has expired (red LED MAX
illuminated) the output relay R switches
When the measured voltage (one of the phase into off-position (yellow LED not illuminated).
voltages) falls below the value adjusted The output relay switches into on-position
at the MIN-regulator, the set interval of the again (yellow LED illuminated) when
tripping delay (Delay) begins (red LED MIN the measured voltage falls below the value
flashes). After the interval has expired adjusted at the MAX-regulator (red LED MAX The device monitors every phase (L1, L2 and
(red LED MIN illuminated), the output relay R not illuminated). When the measured voltage L3) against the neutral wire N. A shift of neutral
switches into off-position (yellow LED not (one of the phase voltage) falls below the point occurs by an asymmetrical phase load
illuminated). The output relay R switches into value adjusted at the Min-regulator, the set if the neutral wire breaks in the power line.
on-position again (yellow LED illuminated), interval of tripping delay (Delay) begins again If one of the phase voltages exceeds the value
when the measured voltage (all phase (red LED MIN flashes). After the interval has adjusted at the trip point, the set interval
voltages) exceeds the value adjusted at the expired (red LED MIN illuminated), the output of tripping delay (Delay) begins (red LED MIN
MAX-regulator. relay R switches into off-positon (yellow LED or MAX flashes). After the interval has expired
not illuminated). (red LED MIN or MAX illuminated), the output
relay switches into off-position (yellow LED
U - supply voltage; R - output relay not illuminated).

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
MR-EU1W1P
36 monitoring relays

AC/DC voltage monitoring in 1-phase mains


Multifunctions monitoring relays
Minimum value supervision with the histeresis mode
Supply voltage = measuring voltage
1 changeover contact: 1 C/O
Rated load: 5 A / 250 V AC at cat. AC1
Installation design: width 17,5 mm
Recognitions, certifications, directives:

Type of relay MR-EU1W1P


Output circuit
Number and type of contacts 1 C/O - changeover
Rated load AC1 5 A / 250 V AC
Max. breaking capacity AC1 1 250 VA
Max. operating frequency
at 100 VA resistive load 3 600 cycles/hour
PN-EN 60947-5-1
at 1 000 VA resistive load 360 cycles/hour
Input circuit
Supply voltage U = measuring voltage;
terminals: 230 V AC: E-F3 24 V AC: E-F2 24 V DC: E-F1
Rated voltage Un 24 V AC/DC, 230 V AC
Drop-out voltage determined by undervoltage detection (see measured circuit)
Operating range of supply voltage 0,75 < Un < 1,2
Rated power consumption 230 V AC: 10,0 VA / 0,6 W 24 V AC: 1,3 VA / 0,8 W 24 V DC: 0,6 W
Rated frequency \ wave form AC: 48...63 Hz \ DC, AC sinus
Duty cycle 100%
Measuring circuit terminals 230 V AC: E-F3 24 V AC: E-F2 24 V DC: E-F1
measuring variable DC or AC sinus, 48...63 Hz
measuring input = supply voltage
overload capacity 1,2 Un
swiching threshold Us max.: 0,8 < Un < 1,2 min.: 0,75 < Un < 1,15
hysteresis H see table ordering information or printing on the unit
Insulation
Rated surge voltage 4 000 V AC
Overvoltage category III PN-EN 60664-1
Insulation pollution degree 2, if built-in 3 PN-EN 60664-1
General data
Electrical life resistive AC1 2 x 105 1 000 VA
Mechanical life (cycles) 2 x 107
Dimensions (L x W x H) 87 x 17,5 x 60 mm
Weight 72 g
Ambient temperature storage, transport -25...+70 oC
operating -25...+55 oC PN-EN 60068-1
Housing protection category IP 40
Relative humidity 15...85% PN-EN 60721-3-3 class 3K3
Shock resistance 15 g 11 ms PN-EN 60068-2-27
Vibration resistance 0,35 mm DA 10...55 Hz PN-EN 60068-2-6
Meassuring circuit data
Functions UNDER, WIN
minimum value supervision with the histeresis mode
Base accuracy 5% (calculate from final range value)
Setting accuracy 5% (calculate from final range value)
Repeatability 2%
Temperature influence 1% / C
Recovery time 500 ms
LED indicator green LED ON/OFF - indication of supply voltage
red LED ON/OFF - indication of failure
yellow LED R ON/OFF - indication of output relay
With adjustable threshold.
Selectable by means of rotary switch.
Of the corresponding threshold.

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
MR-EU1W1P
monitoring relays 37

Dimensions Connections diagrams

1-phase main, 1-phase main,


230 V AC 24 V AC 24 V DC

Mounting, mechanical design

Relays MR-EU1W1P are designed for direct mounting on 35 mm DIN rail mount, EN 50022. Mounting position: any.
Self-extinguishing plastic housing, IP 40. Shockproof terminal connection according to VBG 4 (PZ1 required), IP 20.
Maximum screw torgue: 1,0 Nm. Terminal capacity: 1 x 0,5 do 2,5 mm2 with/without multicore cable end, 1 x 4 mm2 without
multicore cable end, 2 x 0,5 do 1,5 mm2 with/without multicore cable end, 2 x 2,5 mm2 flexible without multicore cable end.

Functions

UNDER - undervoltage monitoring WIN - voltage monitoring in windowfunction


between MIN and MAX values

When the supply voltage U is applied, the


output relay R switches into on-position, if the When the supply voltage U is applied, the
measured voltage is beyond the MIN-value. output relay R switches into on-position, if the
When the measured voltage falls below measured voltage is within the adjusted
the MIN-value, the output relay R switches window. When the measured voltage left the
into off-position. The output relay R switches window between MIN and MAX, the output
into on-position again, if the voltage exceeds relay R switches into off-position. The output
the MAX-value. relay R switches into on-position again, if the
voltage re-enter the adjusted window.

U - supply voltage; R - output relay

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
MR-EI1W1P
38 monitoring relays

AC current monitoring in 1-phase mains


Multifunctions monitoring relays
Histeresis mode and the possibility of setting the tripping delay
Supply voltage 230 V AC
1 changeover contact: 1 C/O
Rated load: 5 A / 250 V AC at cat. AC1
Installation design: width 17,5 mm
Recognitions, certifications, directives:

Type of relay MR-EI1W1P


Output circuit
Number and type of contacts 1 C/O - changeover
Rated load AC1 5 A / 250 V AC
Max. breaking capacity AC1 1 250 VA
Max. operating frequency
at 100 VA resistive load 3 600 cycles/hour
PN-EN 60947-5-1
at 1 000 VA resistive load 360 cycles/hour
Input circuit
Supply voltage U 230 V AC; terminals (N)-Li
Rated voltage Un 230 V AC
Drop-out voltage AC: 0,2 Un
Operating range of supply voltage 0,85 < Un < 1,15
Rated power consumption 5,0 VA / 0,8 W
Rated frequency \ wave form AC: 48...63 Hz \ AC sinus
Duty cycle 100%
Measuring circuit terminals (N)-Li-Lk
measuring variable AC sinus, 48...63 Hz
measuring input 10 A AC
overload capacity 13 A
starting current 1 s: 100 A 3 s: 50 A
input resistance 3 m
swiching threshold Us max.: 0,1 < In < 1,0 min.: 0,05 < In < 0,95
hysteresis H adjustable
Insulation
Rated surge voltage 4 000 V AC
Overvoltage category III PN-EN 60664-1
Insulation pollution degree 2, if built-in 3 PN-EN 60664-1
General data
Electrical life resistive AC1 2 x 105 1 000 VA
Mechanical life (cycles) 2 x 107
Dimensions (L x W x H) 87 x 17,5 x 60 mm
Weight 72 g
Ambient temperature storage, transport -25...+70 oC
operating -25...+55 oC PN-EN 60068-1
Housing protection category IP 40
Relative humidity 15...85% PN-EN 60721-3-3 class 3K3
Shock resistance 15 g 11 ms PN-EN 60068-2-27
Vibration resistance 0,35 mm DA 10...55 Hz PN-EN 60068-2-6
Meassuring circuit data
Functions OVER, OVER+LATCH, UNDER, UNDER+LATCH, WIN, WIN+LATCH
histeresis mode and the possibility of setting the tripping delay
Time intervals (timing adjustment) tripping delay (0,1...10 s)
Base accuracy 5% (calculate from final range value)
Setting accuracy 5% (calculate from final range value)
Repeatability 2%
Temperature influence 0,05% / C
Recovery time 500 ms
LED indicator green LED U/T ON - indication of supply voltage
red LED ON/OFF - indication of failure
red LED flashes - indication of tripping delay
yellow LED R ON/OFF - indication of output relay
With adjustable thresholdes. Selectable by means of rotary switch.
Of the corresponding threshold.

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
MR-EI1W1P
monitoring relays 39

Dimensions Connections diagram

Mounting, mechanical design

Relays MR-EI1W1P are designed for direct mounting on 35 mm DIN rail mount, EN 50022. Mounting position: any.
Self-extinguishing plastic housing, IP 40. Shockproof terminal connection according to VBG 4 (PZ1 required), IP 20.
Maximum screw torgue: 1,0 Nm. Terminal capacity: 1 x 0,5 do 2,5 mm2 with/without multicore cable end, 1 x 4 mm2 without
multicore cable end, 2 x 0,5 do 1,5 mm2 with/without multicore cable end, 2 x 2,5 mm2 flexible without multicore cable end.

Functions

OVER, OVER+LATCH - overcurrent UNDER, UNDER+LATCH - undercurrent WIN, WIN+LATCH - current monitoring
monitoring, overcurrent monitoring with monitoring, undercurrent monitoring with in windowfunction between MIN and MAX
fault latch fault latch values, current monitoring in window-
function between MIN and MAX values with
fault latch

When the supply voltage U is applied, the When the supply voltage U is applied, the
output relay R switches into on-position, if the output relay R switches into on-position, if the
measured current is below the MAX-value. measured current is beyond the MIN-value. When the supply voltage U is applied, the
When the measured current exceeds the MAX- When the measured current falls below the output relay R switches into on-position, if the
value, the output relay R switches into MIN-value, the output relay R switches into measured current is within the adjusted
off-position after the interval of the tripping off-position after the interval of the tripping window. When the measured current leaves
delay (Delay) has expired. delay (Delay) has expired. the window between MIN and MAX, the
OVER: the output relay R switches into UNDER: the output relay R switches into output relay R switches into off-position after
on-position again, if the current falls below on-position again, if the current exceeds the the interval of the tripping delay (Delay) has
the MIN-value. MIN-value. expired.
OVER+LATCH: the output relay R switches UNDER+LATCH: the output relay R switches WIN: the output relay R switches into
only into on-position again by interrupting and only into on-position again by interrupting and on-position again, if the current re-enter the
re-applying of the supply voltage, provided re-applying of the supply voltage, provided adjusted window.
that the measured current is below the MAX- that the measured current is beyond the MIN- WIN+LATCH: the output relay R switches only
value. value. into on-position again by interrupting and
re-applying of the supply voltage, provided
that the measured current is within the
threshold values.

U - supply voltage; R - output relay

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
MR-ET1P
40 monitoring relays

Monitoring of motor temperature


The relay responds to short circuit or wire break
Test function with integrated Test/Reset key
Rated isolated voltage on the sensor circuit up to 690 V
1 changeover contact: 1 C/O
Rated load: 5 A / 250 V AC at cat. AC1
Installation design: width 35 mm
Recognitions, certifications, directives:

Type of relay MR-ET1P


Output circuit
Number and type of contacts 1 C/O - changeover
Rated load AC1 5 A / 250 V AC
Max. breaking capacity AC1 1 250 VA (thermal constant current 5 A)
Max. operating frequency
at 100 VA resistive load 3 600 cycles/hour
PN-EN 60947-5-1
at 1 000 VA resistive load 360 cycles/hour
Input circuit
Supply voltage U 230 V AC; terminals A1-A2
Rated voltage Un 230 V AC
Drop-out voltage AC: 0,3 Un
Operating range of supply voltage 0,85 < Un < 1,1
Rated power consumption 1,3 VA / 1,0 W
Rated frequency AC: 48...63 Hz
Duty cycle 100%
Measuring circuit terminals T1-T2 or T1-T3
initial resistance < 1,5 k
response value relay in OFF-position: 3,6 k
release value relay in ON-position: 1,65 k
disconnection short circuit thermistor: yes (T1-T2); no (T1-T3)
measuring voltage T1-T2 7,5 V at R 4 k PN-EN 60947-8
Control contact function connection of an external Reset key
loadable no
max. line length R1-R2: 10 m (twisted pair)
control pulse length min. 50 ms
Reset contact 1 NO; terminals R1-R2
Insulation
Rated surge voltage 6 000 V AC
Overvoltage category III PN-EN 60664-1
Insulation pollution degree 2, if built-in 3 PN-EN 60664-1
General data
Electrical life resistive AC1 2 x 105 1 000 VA
Mechanical life (cycles) 2 x 107
Dimensions (L x W x H) 87 x 35 x 60 mm
Weight 100 g
Ambient temperature storage, transport -25...+70 oC
operating -25...+55 oC PN-EN 60068-1
Housing protection category IP 40
Relative humidity 15...85% PN-EN 60721-3-3 class 3K3
Meassuring circuit data
Functions monitoring of temperature of the motor winding (max. 6 PTC)
with fault latch, for temperature sensors DIN 44081,
short circuit monitoring of the thermistor line ,
test function with integrated Test/Reset key
Base accuracy 5% (calculate from final range value)
Repeatability 1%
Temperature influence 0,15% / C
Recovery time 250 ms
Residual ripple to DC 50 ms
LED indicator green LED ON - indication of supply voltage
red LED ON/OFF - indication of failure
Selectable by means of terminals.
Terminals R2-T2 are internal affiliated with each other.

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
MR-ET1P
monitoring relays 41

Dimensions Connections diagrams

Temperature sensor monitoring Thermal contact monitoring

Note: only one of this circuit versions (either monitoring


of the temperature sensor or monitoring of the thermal contact)
can be executed.

Mounting, mechanical design

Relays MR-ET1P are designed for direct mounting on 35 mm DIN rail mount, EN 50022. Mounting position: any.
Self-extinguishing plastic housing, IP 40. Shockproof terminal connection according to VBG 4 (PZ1 required), IP 20.
Maximum screw torgue: 1,0 Nm. Terminal capacity: 1 x 0,5 do 2,5 mm2 with/without multicore cable end, 1 x 4 mm2 without
multicore cable end, 2 x 0,5 do 1,5 mm2 with/without multicore cable end, 2 x 2,5 mm2 flexible without multicore cable end.

Functions

Monitoring of motor temperature with Application of an external Reset key Application of internal Test/Reset key
fault latch
If the supply voltage U is applied (green LED
illuminated) and the cumulative resistance of
the PTC-circuit is less than 3,6 k (standard
temperature of the motor), the output relay R
switches into on-position. Pressing the Test/
Reset key under this conditions forces the
output relay R to switch into off-position.
It remains in state as long as the Test/Reset
key is pressed and thus the switching function
can be checked in case of fault. The test
function is not effective by using an external
Reset key. When the comulative resistance
of the PTC-circuit exceeds 3,6 k (at least
one of the PTCs has reached the cut-off
temperature), the output relay R switches
into off-position (red LED illuminated). The
output relay R switches into on-position again
(red LED not illuminated), if the cumulative
resistance drops below 1,65 k by cooling
down of the PTC and either a Reset key
(internal or external) was pressed or the supply
voltage was disconnected and re-applied.

U - supply voltage; R - output relay

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
MR-GI1M2P-TR2
42 monitoring relays

AC/DC current monitoring in 1-phase mains


Multifunctions monitoring relays (16,6...400 Hz)
Timing adjustment for start-up suppression time and tripping delay
Fault latch mode
Relay supply via the supply transformer of TR2 type - see page 58
2 changeover contacts: 2 C/O
Rated load: 5 A / 250 V AC at cat. AC1
Installation design: width 22,5 mm
Recognitions, certifications, directives:

Type of relay MR-GI1M2P-TR2


Output circuit
Number and type of contacts 2 C/O - changeover
Rated load AC1 5 A / 250 V AC
Max. breaking capacity AC1 1 250 VA
Max. operating frequency
at 100 VA resistive load 3 600 cycles/hour
PN-EN 60947-5-1
at 1 000 VA resistive load 360 cycles/hour
Input circuit
Supply voltage U 12...400 V AC; terminals A1-A2 (galvanically separated)
Drop-out voltage AC: 0,3 Un
Operating range of supply voltage as per the specification of TR2 supply transformer
Rated power consumption 2,0 VA / 1,5 W
Rated frequency as per the specification of TR2 supply transformer
Duty cycle 100%
Measuring circuit terminals 0,1 A AC/DC: K-I1 1 A AC/DC: K-I2 10 A AC/DC: K-I3 (distance > 5 mm)
measuring variable DC or AC sinus, 16,6...400 Hz (frequency response: -10+5%)
measuring input 0,1-1-10 A AC/DC
overload capacity 0,1 A AC/DC: 0,8 A 1 A AC/DC: 3 A 10 A AC/DC: 12 A
input resistance 0,1 A AC/DC: 470 m 1 A AC/DC: 47 m 10 A AC/DC: 5 m
swiching threshold Us max.: 0,1 < In < 1,0 min.: 0,05 < In < 0,95

Insulation
Rated surge voltage 4 000 V AC
Overvoltage category III PN-EN 60664-1
Insulation pollution degree 3 PN-EN 60664-1
General data
Electrical life resistive AC1 2 x 105 1 000 VA
Mechanical life (cycles) 2 x 107
Dimensions (L x W x H) 90 x 22,5 x 103 mm
Weight 100 g
Ambient temperature storage, transport -25...+70 oC
operating -25...+55 oC PN-EN 60068-1 -25...+40 oC UL 508
Housing protection category IP 40
Relative humidity 15...85% PN-EN 60721-3-3 class 3K3
Shock resistance 15 g 11 ms PN-EN 60068-2-27
Vibration resistance 0,35 mm DA 10...55 Hz PN-EN 60068-2-6
Meassuring circuit data
Functions OVER, OVER+LATCH, UNDER, UNDER+LATCH, WIN, WIN+LATCH
timing adjustment for start-up suppression time and tripping delay
Time intervals (timing adjustment) start-up suppression time (0...10 s) tripping delay (0,1...10 s)
Base accuracy 5% (calculate from final range value)
Setting accuracy 5% (calculate from final range value)
Repeatability 2%
Temperature influence 0,1% / C
Recovery time 500 ms
LED indicator green LED ON - indication of supply voltage
green LED flashes - indication of start-up suppression time
red LED ON/OFF - indication of failure
red LED flashes - indication of tripping delay
yellow LED ON/OFF - indication of output relay
With adjustable threshold. Selectable via supply transformers TR2.
Separately adjustable. Selectable by means of rotary switch.
TR2 transformers shall be ordered separately. Of the corresponding threshold.

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
MR-GI1M2P-TR2
monitoring relays 43

Dimensions Connections diagrams

Input 0,1 A Input 1 A Input 10 A


with TR2 24 V AC with TR2 230 V AC with TR2 400 V AC
with fault latch with fault latch without fault latch

Mounting, mechanical design

Relays MR-GI1M2P-TR2 are designed for direct mounting on 35 mm DIN rail mount, EN 50022. Mounting position: any.
Self-extinguishing plastic housing, IP 40. Shockproof terminal connection according to VBG 4 (PZ1 required), IP 20.
Maximum screw torgue: 1,0 Nm. Terminal capacity: 1 x 0,5 do 2,5 mm2 with/without multicore cable end, 1 x 4 mm2 without
multicore cable end, 2 x 0,5 do 1,5 mm2 with/without multicore cable end, 2 x 2,5 mm2 flexible without multicore cable end.

Functions

When the supply voltage U is applied, the output voltage), the output relay R again switchs into
relay R switches into on-position (yellow LED on-position and a new measuring cycle begins with
illuminated) and the set interval of the start-up the set interval of the start-up suppression (START).
suppression (START) begins (green LED U flashes).
Changes of the measured current during this UNDER, UNDER+LATCH - undercurrent
period do not affect the state of the output relay R. monitoring, undercurrent monitoring with
After the interval has expired the green LED fault latch
is illuminated steadily. For all the functions
the LEDs MIN and MAX are flashing alternating, When the measured current exceeds the value
when the minimum value for the measured current adjusted at the MAX-regulator, the set interval
was chosen to be greater than the maximum value. of the tripping delay (Delay) begins (red LED MAX
flashes). After the interval has expired (red LED
OVER, OVER+LATCH - overcurrent MAX illuminated), the output relay R switches
monitoring, overcurrent monitoring with into off-position (yellow LED not illuminated).
fault latch The output relay R again switchs into on-position
(yellow LED illuminated) when the measured
When the measured current falls below the value
current falls below the value adjusted at the MAX-
adjusted at the MIN-regulator, the set interval
regulator (red LED MAX not illuminated). When the
of the tripping delay (Delay) begins (red LED MIN
measured current falls below the value adjusted
flashes). After the interval has expired (red LED
at the MIN-regulator, the set interval of the tripping
MIN illuminated), the output relay R switches
delay (Delay) begins again (red LED MIN flashes).
into off-position (yellow LED not illuminated).
After the interval has expired (red LED MIN
The output relay R again switchs into on-position
illuminated), the output relay R switches into
(yellow LED illuminated), when the measured
off-position (yellow LED not illuminated).
When the measured current exceeds the value current exceeds the value adjusted at the MAX-
If the fault latch is activated (WIN+LATCH)
adjusted at the MAX-regulator, the set interval regulator.
and the measured current remains below the MIN-
of the tripping delay (Delay) begins (red LED MAX If the fault latch is activated (UNDER+LATCH)
value longer than the set interval of the tripping
flashes). After the interval has expired (red LED and the measured current remains below the MIN-
delay, the output relay R remains in the off-position
U - supply voltage; R - output relay

MAX illuminated), the output relay R switches value longer than the set interval of the tripping
even if the measured current exceeds the value
into off-position (yellow LED not illuminated). delay, the output relay R remains in the off-position
adjusted at the MIN-regulator. If the measured
The output relay R again switchs into on-position even if the measured current exceeds the value
current remains above the MAX-value longer than
(yellow LED illuminated), when the measured adjusted at the MAX-regulator. After resetting
the set interval of the tripping delay, the output
current falls below the value adjusted at the MIN- the failure (interrupting and re-applying the supply
relay R remains in the off-position even if the
regulator (red LED MAX not illuminated). voltage), the output relay R switches into on-position
measured current falls below the value adjusted
If the fault latch is activated (OVER+LATCH) and a new measuring cycle begins with the set
at the MAX-regulator. After resetting the failure
and the measured current remains above the MAX- interval of the start-up suppression (START).
(interrupting and re-applying the supply voltage),
value longer than the set interval of the tripping the output relay R switches into on-position and
delay, the output relay R remains in the off-position
WIN, WIN+LATCH - current monitoring
a new measuring cycle begins with the set interval
even if the measured current falls below the value in windowfunction between MIN and MAX
of the start-up suppression (START).
adjusted at the MIN-regulator. After resetting values, current monitoring in windowfunction
the failure (interrupting and re-applying the supply between MIN and MAX values with fault latch

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
MR-GI3M2P-TR2
44 monitoring relays

Current monitoring in 3-phase mains


Multifunctions monitoring relays
Timing adjustment for start-up suppression time and tripping delay
Fault latch mode
Relay supply via the supply transformer of TR2 type - see page 58
2 changeover contacts: 2 C/O
Rated load: 5 A / 250 V AC at cat. AC1
Installation design: width 22,5 mm
Recognitions, certifications, directives:

Type of relay MR-GI3M2P-TR2


Output circuit
Number and type of contacts 2 C/O - changeover
Rated load AC1 5 A / 250 V AC
Max. breaking capacity AC1 1 250 VA
Max. operating frequency
at 100 VA resistive load 3 600 cycles/hour
PN-EN 60947-5-1
at 1 000 VA resistive load 360 cycles/hour
Input circuit
Supply voltage U 12...400 V AC; terminals A1-A2 (galvanically separated)
Drop-out voltage AC: 0,3 Un
Operating range of supply voltage as per the specification of TR2 supply transformer
Rated power consumption 2,0 VA / 1,5 W
Rated frequency as per the specification of TR2 supply transformer
Duty cycle 100%
Measuring circuit terminals K-I1 or K-I2 or K-I3 (distance > 5 mm)
measuring variable AC sinus, 48...63 Hz
measuring input 5 A AC
overload capacity 6 A AC
input resistance 10 m
swiching threshold Us max.: 0,1 < In < 1,0 min.: 0,05 < In < 0,95

Insulation
Rated surge voltage 4 000 V AC
Overvoltage category III PN-EN 60664-1
Insulation pollution degree 3 PN-EN 60664-1
General data
Electrical life resistive AC1 2 x 105 1 000 VA
Mechanical life (cycles) 2 x 107
Dimensions (L x W x H) 90 x 22,5 x 103 mm
Weight 100 g
Ambient temperature storage, transport -25...+70 oC
operating -25...+55 oC PN-EN 60068-1 -25...+40 oC UL 508
Housing protection category IP 40
Relative humidity 15...85% PN-EN 60721-3-3 class 3K3
Shock resistance 15 g 11 ms PN-EN 60068-2-27
Vibration resistance 0,35 mm DA 10...55 Hz PN-EN 60068-2-6
Meassuring circuit data
Functions OVER, OVER+LATCH, UNDER, UNDER+LATCH, WIN, WIN+LATCH
timing adjustment for start-up suppression time and tripping delay
Time intervals (timing adjustment) start-up suppression time (0...10 s) tripping delay (0,1...10 s)
Base accuracy 5% (calculate from final range value)
Setting accuracy 5% (calculate from final range value)
Repeatability 2%
Temperature influence 0,1% / C
Recovery time 100 ms
LED indicator green LED ON - indication of supply voltage
red LED ON/OFF - indication of failure
red LED flashes - indication of tripping delay
yellow LED ON/OFF - indication of output relay
With adjustable threshold. Selectable via supply transformers TR2.
Separately adjustable. Selectable by means of rotary switch.
TR2 transformers shall be ordered separately. Of the corresponding threshold.

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
MR-GI3M2P-TR2
monitoring relays 45

Dimensions Connections diagrams

Input 5 A Input 5 A Input 5 A


with TR2 24 V AC with TR2 230 V AC with TR2 400 V AC
without fault latch with fault latch without fault latch

Input 5 A
with TR2 230 V AC
Mounting, mechanical design and current transformer

Relays MR-GI1M2P-TR2 are designed for direct mounting


on 35 mm DIN rail mount, EN 50022. Mounting position: any.
Self-extinguishing plastic housing, IP 40. Shockproof
terminal connection according to VBG 4 (PZ1 required), IP 20.
Maximum screw torgue: 1,0 Nm. Terminal capacity: 1 x 0,5 do
2,5 mm2 with/without multicore cable end, 1 x 4 mm2 without
multicore cable end, 2 x 0,5 do 1,5 mm2 with/without multicore
cable end, 2 x 2,5 mm2 flexible without multicore cable end.

Functions

For all functions the LED's MIN and MAX are UNDER, UNDER+LATCH - undercurrent MIN-regulator. When the measured current of one
flashing alternating, when the minimum value for of the phases exceeds the value adjusted at the
the measured current was chosen to be greater
monitoring, undercurrent monitoring with MAX-regulator, the set interval of the tripping delay
than the maximum value. If a failure already fault latch (Delay) begins (red LED MAX flashes). After the
exists, when the device is activated, the output interval has expired (red LED MAX illuminated), the
relay R remains in off-position and the LED for output relay R switches into off-position (yellow
the corresponding threshold is illuminated. LED not illuminated). The output relay R again
switchs into on-position (yellow LED illuminated)
when the measured current of all the phases falls
OVER, OVER+LATCH - overcurrent below the value adjusted at the MAX-regulator (red
monitoring, overcurrent monitoring with LED MAX not illuminated). When the measured
current of one of the phases falls below the value
fault latch When the measured current of one of the phases adjusted at the MIN-regulator, the set interval
falls below the value adjusted at the MIN-regulator, of the tripping delay (Delay) begins again (red LED
the set interval of the tripping delay (Delay) begins MIN flashes). After the interval has expired (red
(red LED MIN flashes). After the interval has LED MIN illuminated), the output relay R switches
expired (red LED MIN illuminated), the output relay
into off-position (yellow LED not illuminated).
R switches into off-position (yellow LED not
illuminated). The output relay R again switchs into
on-position (yellow LED illuminated), when the
measured current of all the phases exceeds the
When the measured current of one of the phases value adjusted at the MAX-regulator.
exceeds the value adjusted at the MAX-regulator, If the fault latch is activated (UNDER+LATCH)
the set interval of the tripping delay (Delay) begins and the measured current of one of the phases
(red LED MAX flashes). After the interval has remains below the MIN-value longer than the set
expired (red LED MAX illuminated), the output relay interval of the tripping delay, the output relay R
R switches into off-position (yellow LED not remains in the off-position even if the measured If the fault latch is activated (WIN+LATCH)
illuminated). The output relay R again switchs into current of all the phases exceeds the value and the measured current of one of the phases
U - supply voltage; R - output relay

on-position (yellow LED illuminated), when the adjusted at the MAX-regulator. After resetting remains below the MIN-value longer than the set
measured current of all the phases falls below the the failure (interrupting and re-applying the supply interval of the tripping delay, the output relay R
value adjusted at the MIN-regulator (red LED MAX voltage), the output relay R switches into on-position remains in the off-position even if the measured
not illuminated). and a new measuring cycle begins with the set current of all the phases exceeds the value
If the fault latch is activated (OVER+LATCH) interval of the start-up suppression (START). adjusted at the MIN-regulator. If the measured
and the measured current of one of the phases current of one of the phases remains above the
remains above the MAX-value longer than the set MAX-value longer than the set interval of the
interval of the tripping delay, the output relay R WIN, WIN+LATCH - current monitoring tripping delay, the output relay R remains in the
remains in the off-position even if the measured in windowfunction between MIN and MAX off-position even if the measured current of all the
current of all the phases falls below the value values, current monitoring in windowfunction phases falls below the value adjusted at the MAX-
adjusted at the MIN-regulator. After resetting regulator. After resetting the failure (interrupting
the failure (interrupting and re-applying the
between MIN and MAX values with fault latch and re-applying the supply voltage), the output
supply voltage), the output relay R switchs into The output relay R switchs into on-position (yellow relay R switches into on-position and a new
on-position and a new measuring cycle begins with LED illuminated) when the measured current measuring cycle begins with the set interval of
the set interval of the start-up suppression (START). of all the phases exceeds the value adjusted at the the start-up suppression (START).

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
MR-GU1M2P-TR2
46 monitoring relays

AC/DC voltage monitoring in 1-phase mains


Frequency of supply voltage (16,6...400 Hz)
Timing adjustment for start-up suppression time and tripping delay
Fault latch mode
Relay supply via the supply transformer of TR2 type - see page 58
2 changeover contacts: 2 C/O
Rated load: 5 A / 250 V AC at cat. AC1
Installation design: width 22,5 mm
Recognitions, certifications, directives:

Type of relay MR-GU1M2P-TR2


Output circuit
Number and type of contacts 2 C/O - changeover
Rated load AC1 5 A / 250 V AC
Max. breaking capacity AC1 1 250 VA
Max. operating frequency
at 100 VA resistive load 3 600 cycles/hour
PN-EN 60947-5-1
at 1 000 VA resistive load 360 cycles/hour
Input circuit
Supply voltage U 12...400 V AC; terminals A1-A2 (galvanically separated)
Drop-out voltage AC: 0,3 Un
Operating range of supply voltage as per the specification of TR2 supply transformer
Rated power consumption 2,0 VA / 1,5 W
Rated frequency as per the specification of TR2 supply transformer
Duty cycle 100%
Measuring circuit fusing max. 20 A UL 508
terminals 30 V AC/DC: E-F1 60 V AC/DC: E-F2 300 V AC/DC: E-F3
measuring variable DC or AC sinus, 16,6...400 Hz (frequency response: -10+5%)
measuring input 30-60-300 V AC/DC
overload capacity 30 V AC/DC: 100 Veff 60 V AC/DC: 150 Veff 300 V AC/DC: 440 Veff
input resistance 60 V AC/DC: 47 k 60 V AC/DC: 100 k 300 V AC/DC: 470 k
swiching threshold Us max.: 0,1 < Un < 1,0 min.: 0,05 < Un < 0,95

Insulation
Rated surge voltage 4 000 V AC
Overvoltage category III PN-EN 60664-1
Insulation pollution degree 3 PN-EN 60664-1
General data
Electrical life resistive AC1 2 x 105 1 000 VA
Mechanical life (cycles) 2 x 107
Dimensions (L x W x H) 90 x 22,5 x 103 mm
Weight 100 g
Ambient temperature storage, transport -25...+70 oC
operating -25...+55 oC PN-EN 60068-1 -25...+40 oC UL 508
Housing protection category IP 40
Relative humidity 15...85% PN-EN 60721-3-3 class 3K3
Shock resistance 15 g 11 ms PN-EN 60068-2-27
Vibration resistance 0,35 mm DA 10...55 Hz PN-EN 60068-2-6
Meassuring circuit data
Functions OVER, OVER+LATCH, UNDER, UNDER+LATCH, WIN, WIN+LATCH
timing adjustment for start-up suppression time and tripping delay
Time intervals (timing adjustment) start-up suppression time (0...10 s) tripping delay (0,1...10 s)
Base accuracy 5% (calculate from final range value)
Setting accuracy 5% (calculate from final range value)
Repeatability 2%
Wpyw napicia 0,5%
Temperature influence 0,1% / C
Recovery time 500 ms
LED indicator green LED ON - indication of supply voltage
green LED flashes - indication of start-up suppression time
red LED ON/OFF - indication of failure
red LED flashes - indication of tripping delay
yellow LED ON/OFF - indication of output relay
With adjustable thresholdes. Separately adjustable. Selectable via supply transformers TR2.
TR2 transformers shall be ordered separately. Selectable by means of rotary switch.
Of the corresponding threshold.
www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
MR-GU1M2P-TR2
monitoring relays 47

Dimensions Connections diagrams

Input 30 V Input 60 V Input 300 V


with TR2 24 V AC with TR2 230 V AC with TR2 400 V AC
with fault latch with fault latch without fault latch

Mounting, mechanical design

Relays MR-GU1M2P-TR2 are designed for direct mounting on 35 mm DIN rail mount, EN 50022. Mounting position: any.
Self-extinguishing plastic housing, IP 40. Shockproof terminal connection according to VBG 4 (PZ1 required), IP 20.
Maximum screw torgue: 1,0 Nm. Terminal capacity: 1 x 0,5 do 2,5 mm2 with/without multicore cable end, 1 x 4 mm2 without
multicore cable end, 2 x 0,5 do 1,5 mm2 with/without multicore cable end, 2 x 2,5 mm2 flexible without multicore cable end.

Functions

When the supply voltage U is applied, the output voltage), the output relay R again switchs into
relay R switches into on-position (yellow LED on-position and a new measuring cycle begins with
illuminated) and the set interval of the start-up the set interval of the start-up suppression (START).
suppression (START) begins (green LED U flashes).
Changes of the measured voltage during this UNDER, UNDER+LATCH - undervoltage
period do not affect the state of the output relay R. monitoring, undervoltage monitoring with
After the interval has expired the green LED fault latch
is illuminated steadily. For all the functions
the LEDs MIN and MAX are flashing alternating, When the measured voltage exceeds the value
when the minimum value for the measured voltage adjusted at the MAX-regulator, the set interval
was chosen to be greater than the maximum value. of the tripping delay (Delay) begins (red LED MAX
flashes). After the interval has expired (red LED
OVER, OVER+LATCH - overvoltage MAX illuminated), the output relay R switches
monitoring, overvoltage monitoring with into off-position (yellow LED not illuminated).
fault latch The output relay R again switchs into on-position
(yellow LED illuminated) when the measured
When the measured voltage falls below the value
voltage falls below the value adjusted at the MAX-
adjusted at the MIN-regulator, the set interval
regulator (red LED MAX not illuminated). When the
of the tripping delay (Delay) begins (red LED MIN
measured voltage falls below the value adjusted
flashes). After the interval has expired (red LED
at the MIN-regulator, the set interval of the tripping
MIN illuminated), the output relay R switches
delay (Delay) begins again (red LED MIN flashes).
into off-position (yellow LED not illuminated).
After the interval has expired (red LED MIN
The output relay R again switchs into on-position
illuminated), the output relay R switches into
(yellow LED illuminated), when the measured
off-position (yellow LED not illuminated).
When the measured voltage exceeds the value voltage exceeds the value adjusted at the MAX-
If the fault latch is activated (WIN+LATCH)
adjusted at the MAX-regulator, the set interval regulator.
and the measured voltage remains below the MIN-
of the tripping delay (Delay) begins (red LED MAX If the fault latch is activated (UNDER+LATCH)
value longer than the set interval of the tripping
flashes). After the interval has expired (red LED and the measured voltage remains below the MIN-
delay, the output relay R remains in the off-position
U - supply voltage; R - output relay

MAX illuminated), the output relay R switches value longer than the set interval of the tripping
even if the measured voltage exceeds the value
into off-position (yellow LED not illuminated). delay, the output relay R remains in the off-position
adjusted at the MIN-regulator. If the measured
The output relay R again switchs into on-position even if the measured voltage exceeds the value
voltage remains above the MAX-value longer than
(yellow LED illuminated), when the measured adjusted at the MAX-regulator. After resetting
the set interval of the tripping delay, the output
voltage falls below the value adjusted at the MIN- the failure (interrupting and re-applying the supply
relay R remains in the off-position even if the
regulator (red LED MAX not illuminated). voltage), the output relay R switches into on-position
measured voltage falls below the value adjusted
If the fault latch is activated (OVER+LATCH) and a new measuring cycle begins with the set
at the MAX-regulator. After resetting the failure
and the measured voltage remains above the MAX- interval of the start-up suppression (START).
(interrupting and re-applying the supply voltage),
value longer than the set interval of the tripping the output relay R switches into on-position and
delay, the output relay R remains in the off-position
WIN, WIN+LATCH - voltage monitoring
a new measuring cycle begins with the set interval
even if the measured voltage falls below the value in windowfunction between MIN and MAX
of the start-up suppression (START).
adjusted at the MIN-regulator. After resetting values, voltage monitoring in windowfunction
the failure (interrupting and re-applying the supply between MIN and MAX values with fault latch

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
MR-GU32P-TR2
48 monitoring relays

Voltage monitoring in 3-phase mains


Multifunctions monitoring relays Timing adjustment for tripping delay
Fault latch mode
Connection of neutral wire necessary
Relay supply via the supply transformer of TR2 type - see page 58
2 changeover contacts: 2 C/O
Rated load: 5 A / 250 V AC at cat. AC1
Installation design: width 22,5 mm
Recognitions, certifications, directives:

Type of relay MR-GU32P-TR2


Output circuit
Number and type of contacts 2 C/O - changeover
Rated load AC1 5 A / 250 V AC
Max. breaking capacity AC1 1 250 VA
Max. operating frequency
at 100 VA resistive load 3 600 cycles/hour
PN-EN 60947-5-1
at 1 000 VA resistive load 360 cycles/hour
Input circuit
Supply voltage U 12...400 V AC; terminals A1-A2 (galvanically separated)
Drop-out voltage AC: 0,3 Un
Operating range of supply voltage as per the specification of TR2 supply transformer
Rated power consumption 2,0 VA / 1,5 W
Rated frequency as per the specification of TR2 supply transformer
Duty cycle 100%
Measuring circuit fusing max. 20 A UL 508
terminals (N)-L1 or (N)-L2 or (N)-L3
measuring variable AC sinus, 48...63 Hz
measuring input 230 V AC
overload capacity 440 V AC
input resistance 3(N)~400/230 V: 470 k
swiching threshold Us max.: -0,2 < Un < 0,3 min.: -0,3 < Un < 0,2

Insulation
Rated surge voltage 4 000 V AC
Overvoltage category III PN-EN 60664-1
Insulation pollution degree 3 PN-EN 60664-1
General data
Electrical life resistive AC1 2 x 105 1 000 VA
Mechanical life (cycles) 2 x 107
Dimensions (L x W x H) 90 x 22,5 x 103 mm
Weight 100 g
Ambient temperature storage, transport -25...+70 oC
operating -25...+55 oC PN-EN 60068-1 -25...+40 oC UL 508
Housing protection category IP 40
Relative humidity 15...85% PN-EN 60721-3-3 class 3K3
Shock resistance 15 g 11 ms PN-EN 60068-2-27
Vibration resistance 0,35 mm DA 10...55 Hz PN-EN 60068-2-6
Meassuring circuit data
Functions OVER, OVER+LATCH, UNDER, UNDER+LATCH, WIN, WIN+LATCH
timing adjustment for tripping delay
Time intervals (timing adjustment) tripping delay (0,1...10 s)
Base accuracy 5% (calculate from final range value)
Setting accuracy 5% (calculate from final range value)
Repeatability 2%
Temperature influence 0,1% / C
Recovery time 100 ms
LED indicator green LED ON - indication of supply voltage
red LED ON/OFF - indication of failure
red LED flashes - indication of tripping delay
yellow LED ON/OFF - indication of output relay
With adjustable thresholdes. Selectable via supply transformers TR2.
Adjustable. Selectable by means of rotary switch.
TR2 transformers shall be ordered separately. Of the corresponding threshold.

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
MR-GU32P-TR2
monitoring relays 49

Dimensions Connections diagrams

Input 230 V Input 230 V Input 230 V


with TR2 24 V AC with TR2 230 V AC with TR2 400 V AC
without fault latch with fault latch without fault latch

Mounting, mechanical design

Relays MR-GU32P-TR2 are designed for direct mounting on 35 mm DIN rail mount, EN 50022. Mounting position: any.
Self-extinguishing plastic housing, IP 40. Shockproof terminal connection according to VBG 4 (PZ1 required), IP 20.
Maximum screw torgue: 1,0 Nm. Terminal capacity: 1 x 0,5 do 2,5 mm2 with/without multicore cable end, 1 x 4 mm2 without
multicore cable end, 2 x 0,5 do 1,5 mm2 with/without multicore cable end, 2 x 2,5 mm2 flexible without multicore cable end.

Functions

For all functions the LED's MIN and MAX are UNDER, UNDER+LATCH - undervoltage
flashing alternating, when the minimum value for
the measured voltage was chosen to be greater
monitoring, undervoltage monitoring with
than the maximum value. If a failure already fault latch
exists, when the device is activated, the output
relay R remains in off-position and the LED for
the corresponding threshold is illuminated.

OVER, OVER+LATCH - overvoltage The output relay R switchs into on-position (yellow
monitoring, overvoltage monitoring with LED illuminated) when the measured voltage
fault latch of all the phases exceeds the value adjusted at the
MIN-regulator. When the measured voltage of one
of the phases exceeds the value adjusted at the
When the measured voltage of one of the phases
MAX-regulator, the set interval of the tripping delay
falls below the value adjusted at the MIN-regulator,
(Delay) begins (red LED MAX flashes). After the
the set interval of the tripping delay (Delay) begins
interval has expired (red LED MAX illuminated), the
(red LED MIN flashes). After the interval has
output relay R switches into off-position (yellow
expired (red LED MIN illuminated), the output relay
LED not illuminated). The output relay R again
R switches into off-position (yellow LED not
switchs into on-position (yellow LED illuminated)
illuminated). The output relay R again switchs into
when the measured voltage of all the phases falls
on-position (yellow LED illuminated), when the
below the value adjusted at the MAX-regulator (red
measured voltage of all the phases exceeds the
When the measured voltage of one of the phases LED MAX not illuminated). When the measured
value adjusted at the MAX-regulator.
exceeds the value adjusted at the MAX-regulator, voltage of one of the phases falls below the value
If the fault latch is activated (UNDER+LATCH)
the set interval of the tripping delay (Delay) begins adjusted at the MIN-regulator, the set interval
and the measured voltage of one of the phases
(red LED MAX flashes). After the interval has of the tripping delay (Delay) begins again (red LED
remains below the MIN-value longer than the set
expired (red LED MAX illuminated), the output relay MIN flashes). After the interval has expired (red
interval of the tripping delay, the output relay R
R switches into off-position (yellow LED not LED MIN illuminated), the output relay R switches
remains in the off-position even if the measured
illuminated). The output relay R again switchs into into off-position (yellow LED not illuminated).
voltage of all the phases exceeds the value
on-position (yellow LED illuminated), when the If the fault latch is activated (WIN+LATCH)
adjusted at the MAX-regulator. After resetting
measured voltage of all the phases falls below the and the measured voltage of one of the phases
the failure (interrupting and re-applying the supply
value adjusted at the MIN-regulator (red LED MAX remains below the MIN-value longer than the set
U - supply voltage; R - output relay

voltage), the output relay R switches into on-position


not illuminated). interval of the tripping delay, the output relay R
and a new measuring cycle begins with the set
If the fault latch is activated (OVER+LATCH) remains in the off-position even if the measured
interval of the start-up suppression (START).
and the measured voltage of one of the phases voltage of all the phases exceeds the value
remains above the MAX-value longer than the set adjusted at the MIN-regulator. If the measured
interval of the tripping delay, the output relay R voltage of one of the phases remains above the
remains in the off-position even if the measured MAX-value longer than the set interval of the
voltage of all the phases falls below the value WIN, WIN+LATCH - voltage monitoring tripping delay, the output relay R remains in the
adjusted at the MIN-regulator. After resetting in windowfunction between MIN and MAX off-position even if the measured voltage of all the
the failure (interrupting and re-applying the phases falls below the value adjusted at the MAX-
values, voltage monitoring in windowfunction regulator. After resetting the failure (interrupting
supply voltage), the output relay R switchs into
on-position and a new measuring cycle begins with
between MIN and MAX values with fault latch and re-applying the supply voltage), the output
the set interval of the start-up suppression (START). relay R switches into on-position and a new
measuring cycle begins with the set interval of
the start-up suppression (START).

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
MR-GU3M2P-TR2
50 monitoring relays

Voltage monitoring in 3-phase mains Multifunctions monitoring relays


Monitoring of phase sequence, phase failure and asymmetry
Timing adjustment for tripping delay
Connection of neutral wire optional, detection of loss of neutral wire
Relay supply via the supply transformer of TR2 type - see page 58
2 changeover contacts: 2 C/O
Rated load: 5 A / 250 V AC at cat. AC1
Installation design: width 22,5 mm
Recognitions, certifications, directives:

Type of relay MR-GU3M2P-TR2


Output circuit
Number and type of contacts 2 C/O - changeover
Rated load AC1 5 A / 250 V AC
Max. breaking capacity AC1 1 250 VA
Max. operating frequency
at 100 VA resistive load 3 600 cycles/hour
PN-EN 60947-5-1
at 1 000 VA resistive load 360 cycles/hour
Input circuit
Supply voltage U 12...400 V AC; terminals A1-A2 (galvanically separated)
Drop-out voltage AC: 0,3 Un
Operating range of supply voltage as per the specification of TR2 supply transformer
Rated power consumption 2,0 VA / 1,5 W
Rated frequency as per the specification of TR2 supply transformer
Duty cycle 100%
Measuring circuit fusing max. 20 A UL 508
terminals (N)-L1-L2-L3
measuring variable AC sinus, 48...63 Hz
measuring input 3(N)~400/230 V
overload capacity 3(N)~600/346 V
input resistance 3(N)~400/230 V: 1 M
swiching threshold Us max.: -0,2 < Un < 0,3 min.: -0,3 < Un < 0,2
asymmetry 5...25%
Insulation
Rated surge voltage 4 000 V AC
Overvoltage category III PN-EN 60664-1
Insulation pollution degree 3 PN-EN 60664-1
General data
Electrical life resistive AC1 2 x 105 1 000 VA
Mechanical life (cycles) 2 x 107
Dimensions (L x W x H) 90 x 22,5 x 103 mm
Weight 100 g
Ambient temperature storage, transport -25...+70 oC
operating -25...+55 oC PN-EN 60068-1 -25...+40 oC UL 508
Housing protection category IP 40
Relative humidity 15...85% PN-EN 60721-3-3 class 3K3
Shock resistance 15 g 11 ms PN-EN 60068-2-27
Vibration resistance 0,35 mm DA 10...55 Hz PN-EN 60068-2-6
Meassuring circuit data
Functions UNDER, UNDER+SEQ, WIN, WIN+SEQ
monitoring of phase sequence, phase failure and asymmetry
timing adjustment for tripping delay
Time intervals (timing adjustment) tripping delay (0,1...10 s)
Base accuracy 5% (calculate from final range value)
Setting accuracy 5% (calculate from final range value)
Repeatability 2%
Wpyw napicia 0,5%
Temperature influence 0,1% / C
Recovery time 500 ms
LED indicator red LED ON/OFF - indication of failure
red LED flashes - indication of tripping delay
yellow LED ON/OFF - indication of output relay
With adjustable thresholdes. Asymmetry - with adjustable threshold. Selectable via supply transformers TR2.
Adjustable. Selectable by means of rotary switch.
TR2 transformers shall be ordered separately. Of the corresponding threshold.

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
MR-GU3M2P-TR2
monitoring relays 51

Dimensions Connections diagrams

Input Input Input


3(N)~400/230 V 3(N)~400/230 V 3(N)~400/230 V
with TR2 24 V AC with TR2 230 V AC with TR2 400 V AC

Mounting, mechanical design

Relays MR-GU3M2P-TR2 are designed for direct mounting on 35 mm DIN rail mount, EN 50022. Mounting position: any.
Self-extinguishing plastic housing, IP 40. Shockproof terminal connection according to VBG 4 (PZ1 required), IP 20.
Maximum screw torgue: 1,0 Nm. Terminal capacity: 1 x 0,5 do 2,5 mm2 with/without multicore cable end, 1 x 4 mm2 without
multicore cable end, 2 x 0,5 do 1,5 mm2 with/without multicore cable end, 2 x 2,5 mm2 flexible without multicore cable end.

Functions

For all functions the LED's MIN and MAX are When the measured voltage exceeds the value the disconnection but can be monitored by using
flashing alternating, when the minimum value for adjusted at the MAX-regulator, the set interval a proper value for the asymmetry.
the measured voltage was chosen to be greater of the tripping delay (Delay) begins (red LED MAX
than the maximum value. If a failure already flashes). After the interval has expired (red LED Asymmetry monitoring
exists, when the device is activated, the output MAX illuminated), the output relay R switches into
relay R remains in off-position and the LED for off-position (yellow LED not illuminated). The out-
the corresponding threshold is illuminated. put relay R again switches into on-position (yellow
LED illuminated) when the measured voltage falls
UNDER, UNDER+SEQ - undervoltage monitoring, below the value adjusted at the MAX-regulator
undervoltage monitoring and monitoring of phase (red LED MAX not illuminated). When the measured
voltage falls below the value adjusted at the
sequence MIN-regulator, the set interval of the tripping delay
(Delay) begins again (red LED MIN flashes). After If the asymmetry of the phase-to-phase voltages
the interval has expired (red LED MIN illuminated), exceeds the value set at the ASYM-regulator, the
the output relay R switches into off-position set interval of the tripping delay (DELAY) begins
(yellow LED not illuminated). (red LED ASYM flashes). After the interval has
expired (red LED ASYM illuminated), the output
SEQ - phase sequence monitoring relays switch into off-position (yellow LED not illu-
minated). If the neutral wire is connected to the
When the measured voltage (mean value of device, the asymmetry of the phase voltages re-
phase-to-phase voltages) falls below the value ferred to the neutral wire (Y-voltage) is monitored
adjusted at the MIN-regulator, the set interval also. In that case both values of the asymmetry
of the tripping delay (Delay) begins (red LED MIN are evaluated and if one of the values exceeds the
flashes). After the interval has expired (red LED value set at the ASYM-regulator, the set interval of
MIN illuminated), the output relay R switches the tripping delay (DELAY) begins (red LED ASYM
into off-position (yellow LED not illuminated). flashes). After the interval has expired (red LED
Phase sequence monitoring is selectable for
The output relay R again switches into on-position ASYM illuminated), the output relays switch into
all functions.If a change in phase sequence is
(yellow LED illuminated), when the measured off-position (yellow LED not illuminated).
detected (red LED SEQ illuminated), the output
voltage exceeds the value adjusted at the MAX- relay R switches into off-position immediately
regulator. (yellow LED not illuminated). Loss of neutral wire by means of evaluation
of asymmetry: a break of the neutral wire between
WIN, WIN+SEQ - voltage monitoring in window- SEQ - phase failure monitoring power line and machinery is detected as soon
U - supply voltage; R - output relay

function between MIN and MAX values, voltage as asymmetry between


monitoring in windowfunction between MIN and MAX phase-to-phase voltage and
values and monitoring of phase sequence neutral wire occurs. If the
asymmetry exceeds the
value set at the ASYM-
regulator, the set interval
of the tripping delay
(Delay) begins (red LED
If one of the phase voltages fails, the set interval ASYM flashes). After the
of the tripping delay (Delay) begins (red LED SEQ interval has expired (red LED ASYM illuminated),
flashes). After the interval has expired (red LED the output relays switch into off-position (yellow
The output relay R switches into on-position SEQ illuminated), the output relay R switches into LED not illuminated). A break of the neutral wire
(yellow LED illuminated) when the measured off-position (yellow LED not illuminated). Reverse between our device and the machinery can not be
voltage (mean value of phase-to-phase voltages) voltages of a consumer (e.g. a motor which detected.
exceeds the value adjusted at the MIN-regulator. continues to run on two phases only) do not effect

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
MR-GU3M2P
52 monitoring relays

Voltage monitoring in 3-phase mains


Monitoring of phase sequence and phase failure
Detection of reverse voltage
Connection of neutral wire optional
Supply voltage = measuring voltage
2 changeover contacts: 2 C/O
Rated load: 5 A / 250 V AC at cat. AC1
Installation design: width 22,5 mm
Recognitions, certifications, directives:

Type of relay MR-GU3M2P


Output circuit
Number and type of contacts 2 C/O - changeover
Rated load AC1 5 A / 250 V AC
Max. breaking capacity AC1 1 250 VA
Max. operating frequency
at 100 VA resistive load 3 600 cycles/hour
PN-EN 60947-5-1
at 1 000 VA resistive load 360 cycles/hour
Input circuit
Supply voltage U = measuring voltage; terminals (N)-L1-L2-L3 (galvanically separated)
Drop-out voltage AC: 0,2 Un
Operating range of supply voltage 3(N)~ 342...457 V
Rated power consumption 2,0 VA / 1,5 W
Rated frequency AC: 48...63 Hz
Duty cycle 100%
Measuring circuit terminals (N)-L1-L2-L3
measuring variable AC sinus, 48...63 Hz
measuring input = supply voltage
overload capacity 3(N)~ 457/264 V
input resistance 3(N)~400/230 V: 15 k
asymmetry fixed, typical value 30%
Insulation
Rated surge voltage 4 000 V AC
Overvoltage category III PN-EN 60664-1
Insulation pollution degree 3 PN-EN 60664-1
General data
Electrical life resistive AC1 2 x 105 1 000 VA
Mechanical life (cycles) 2 x 107
Dimensions (L x W x H) 90 x 22,5 x 103 mm
Weight 100 g
Ambient temperature storage, transport -25...+70 oC
operating -25...+55 oC PN-EN 60068-1 -25...+40 oC UL 508
Housing protection category IP 40
Relative humidity 15...85% PN-EN 60721-3-3 class 3K3
Shock resistance 15 g 11 ms PN-EN 60068-2-27
Vibration resistance 0,35 mm DA 10...55 Hz PN-EN 60068-2-6
Meassuring circuit data
Functions monitoring of phase sequence and phase failure
detection of reverse voltage
Time intervals start-up suppression time (staa, max. 0,5 s)
tripping delay (stae, max. 0,35 s)
Recovery time 100 ms
LED indicator green LED ON - indication of supply voltage
yellow LED ON/OFF - indication of output relay
By means of evaluating the asymmetry.

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
MR-GU3M2P
monitoring relays 53

Dimensions Connections diagram

Mounting, mechanical design

Relays MR-GU3M2P are designed for direct mounting on 35 mm DIN rail mount, EN 50022. Mounting position: any.
Self-extinguishing plastic housing, IP 40. Shockproof terminal connection according to VBG 4 (PZ1 required), IP 20.
Maximum screw torgue: 1,0 Nm. Terminal capacity: 1 x 0,5 do 2,5 mm2 with/without multicore cable end, 1 x 4 mm2 without
multicore cable end, 2 x 0,5 do 1,5 mm2 with/without multicore cable end, 2 x 2,5 mm2 flexible without multicore cable end.

Functions

Phase sequence monitoring Phase failure monitoring Detection of reverse voltage (by means
of evaluation of asymmetry)

When all the phases are connected in The output relay R switches into off-position
the correct sequence and the measured (yellow LED not illuminated), when one The output relay R switches into off-position
asymmetry is less than the fixed value, of the three phases fails. (yellow LED not illuminated) when the asym-
the output relay R switches into on-position metry between the phase voltages exceeds
(yellow LED illuminated). When the phase the fixed value of the asymmetry in monito-
sequence changes, the output relay R ring relay. An asymmetry caused by the
switches into off-position (yellow LED not reverse voltage of a consumer (e.g. a motor
illuminated). which continues to run on two phases only)
does not effect the disconnection.

U - supply voltage; R - output relay

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
MR-GT2P-TR2
54 monitoring relays

Monitoring of motor temperature


Test function with integrated Test/Reset key
External Reset key connectable
Relay supply via the supply transformer of TR2 type - see page 58
2 changeover contacts: 2 C/O
Rated load: 5 A / 250 V AC at cat. AC1
Installation design: width 22,5 mm
Recognitions, certifications, directives:

Type of relay MR-GT2P-TR2


Output circuit
Number and type of contacts 2 C/O - changeover
Rated load AC1 5 A / 250 V AC
Max. breaking capacity AC1 1 250 VA
Max. operating frequency
at 100 VA resistive load 3 600 cycles/hour
PN-EN 60947-5-1
at 1 000 VA resistive load 360 cycles/hour
Input circuit
Supply voltage U 12...400 V AC; terminals A1-A2 (galvanically separated)
Drop-out voltage AC: 0,3 Un
Operating range of supply voltage as per the specification of TR2 supply transformer
Rated power consumption 2,0 VA / 1,5 W
Rated frequency as per the specification of TR2 supply transformer
Duty cycle 100%
Measuring circuit terminals T1-T2
initial resistance < 1,5 k
response value relay in OFF-position: 3,6 k
release value relay in ON-position: 1,8 k
disconnection no
measuring voltage T1-T2 2,5 V at R 4 k PN-EN 60947-8
Control contact function connection of an external Reset key
loadable no
max. line length R1-R2: 10 m (twisted pair)
Reset contact 1 NO; terminals R-T2
Insulation
Rated surge voltage 4 000 V AC
Overvoltage category III PN-EN 60664-1
Insulation pollution degree 3 PN-EN 60664-1
General data
Electrical life resistive AC1 2 x 105 1 000 VA
Mechanical life (cycles) 2 x 107
Dimensions (L x W x H) 90 x 22,5 x 103 mm
Weight 100 g
Ambient temperature storage, transport -25...+70 oC
operating -25...+55 oC PN-EN 60068-1 -25...+40 oC UL 508
Housing protection category IP 40
Relative humidity 15...85% PN-EN 60721-3-3 class 3K3
Shock resistance 15 g 11 ms PN-EN 60068-2-27
Vibration resistance 0,35 mm DA 10...55 Hz PN-EN 60068-2-6
Meassuring circuit data
Functions monitoring of temperature of the motor winding (max. 6 PTC)
with fault latch, for temperature sensors DIN 44081,
test function with integrated Test/Reset key
Base accuracy 10% (calculate from final range value)
Repeatability 1%
Wpyw napicia 2,2%
Temperature influence 0,1% / C
Recovery time 500 ms
LED indicator green LED ON - indication of supply voltage
red LED ON/OFF - indication of failure
TR2 transformers shall be ordered separately.
Selectable via supply transformers TR2.

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
MR-GT2P-TR2
monitoring relays 55

Dimensions Connections diagram

Mounting, mechanical design

Relays MR-GT2P-TR2 are designed for direct mounting on 35 mm DIN rail mount, EN 50022. Mounting position: any.
Self-extinguishing plastic housing, IP 40. Shockproof terminal connection according to VBG 4 (PZ1 required), IP 20.
Maximum screw torgue: 1,0 Nm. Terminal capacity: 1 x 0,5 do 2,5 mm2 with/without multicore cable end, 1 x 4 mm2 without
multicore cable end, 2 x 0,5 do 1,5 mm2 with/without multicore cable end, 2 x 2,5 mm2 flexible without multicore cable end.

Functions

Monitoring of motor temperature with Application of an external Reset key Application of internal Test/Reset key
fault latch
If the supply voltage U is applied (green LED
illuminated) and the cumulative resistance of
the PTC-circuit is less than 3,6 k (standard
temperature of the motor), the output relay R
switches into on-position. Pressing the Test/
Reset key under this conditions forces the
output relay R to switch into off-position.
It remains in state as long as the Test/Reset
key is pressed and thus the switching function
can be checked in case of fault. The test
function is not effective by using an external
Reset key. When the comulative resistance
of the PTC-circuit exceeds 3,6 k (at least
one of the PTCs has reached the cut-off
temperature), the output relay R switches
into off-position (red LED illuminated). The
output relay R switches into on-position again
(red LED not illuminated), if the cumulative
resistance drops below 1,8 k by cooling
down of the PTC and either a Reset key
(internal or external) was pressed or the supply
voltage was disconnected and re-applied.

U - supply voltage; R - output relay

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
MR-GP2P
56 monitoring relays

Level monitoring of conductive liquids MIN, MAX


Multifunctions monitoring relays
Timing adjustment for tripping delay (Delay ON) and turn-off delay (Delay OFF)
Secure isolation of the measuring circuit
2 changeover contacts: 2 C/O
Rated load: 5 A / 250 V AC at cat. AC1
Installation design: width 22,5 mm
Recognitions, certifications, directives:

Type of relay MR-GP2P


Output circuit
Number and type of contacts 2 C/O - changeover
Rated load AC1 5 A / 250 V AC
Max. breaking capacity AC1 1 250 VA
Max. operating frequency
at 100 VA resistive load 3 600 cycles/hour
PN-EN 60947-5-1
at 1 000 VA resistive load 360 cycles/hour
Input circuit
Supply voltage U 24-110-230 V AC; terminals A1-A2 (galvanically separated)
Drop-out voltage AC: 0,3 Un
Operating range of supply voltage 24-110 V AC: -0,15 < Un < 0,1 230 V AC: -0,15 < Un < 0,15
Rated power consumption 2,0 VA / 1,5 W
Rated frequency AC: 48...63 Hz
Duty cycle 100%
Measuring circuit terminals probes (type SK1, SK2, SK3); terminals E1-E2-E3
sensitivity 0,25...100 k (4 mS...1 S)
sensor voltage 12 V AC
sensor current max. 7 mA
wiring distance capacity of cable 100 nF/km: max. 1000 m (set value < 50%)
max. 100 m (set value 100%)
Insulation
Rated surge voltage 6 000 V AC
Overvoltage category III PN-EN 60664-1
Insulation pollution degree 3 PN-EN 60664-1
General data
Electrical life resistive AC1 2 x 105 1 000 VA
Mechanical life (cycles) 2 x 107
Dimensions (L x W x H) 90 x 22,5 x 103 mm
Weight 100 g
Ambient temperature storage, transport -25...+70 oC
operating -25...+55 oC PN-EN 60068-1 -25...+40 oC UL 508
Housing protection category IP 40
Relative humidity 15...85% PN-EN 60721-3-3 class 3K3
Shock resistance 15 g 11 ms PN-EN 60068-2-27
Vibration resistance 0,35 mm DA 10...55 Hz PN-EN 60068-2-6
Meassuring circuit data
Functions PUMP UP, PUMP DOWN
timing adjustment for tripping delay (Delay ON)
and turn-off delay (Delay OFF)
Time intervals (timing adjustment) tripping delay (0,5...10 s)
turn-off delay (0,5...10 s)
Recovery time 500 ms
LED indicator green LED ON - indication of supply voltage
yellow LED ON/OFF - indication of output relay
Separately adjustable.
Selectable by means of rotary switch.

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
MR-GP2P
monitoring relays 57

Dimensions Connections diagram

Mounting, mechanical design

Relays MR-GP2P are designed for direct mounting on 35 mm DIN rail mount, EN 50022. Mounting position: any.
Self-extinguishing plastic housing, IP 40. Shockproof terminal connection according to VBG 4 (PZ1 required), IP 20.
Maximum screw torgue: 1,0 Nm. Terminal capacity: 1 x 0,5 do 2,5 mm2 with/without multicore cable end, 1 x 4 mm2 without
multicore cable end, 2 x 0,5 do 1,5 mm2 with/without multicore cable end, 2 x 2,5 mm2 flexible without multicore cable end.

Functions

PUMP UP (Delay OFF) begins. After the expiration of the on-position (yellow LED illuminated). When
interval the output relay R switches into the air-fluid level sinks below the probe E2,
off-position (yellow LED not illuminated). the set interval of the turn-off delay (Delay
OFF) begins. After the expiration of the
Minimum monitoring (PUMP UP) interval the output relay R switches into
off-position (yellow LED not illuminated).

Connection of the probe rods E1, E2 and E3. Note: use cables with low capacity for wiring
Alternatively the electrically conducting the probes especially with extended wiring
container can be connected in lieu of the test length.
probe E3. When the air-fluid level falls below
the minimum probe E2 the set interval of the Connection of probe rods E2 and E3 (bridge Following processes are suggested for the
tripping delay (Delay ON) begins. After the E1-E3). Alternatively the electrically conduc- adjustment:
expiration of the interval the output relay R ting container can be connected in lieu of the - the existent time delay should be to mini-
switches into on-position (yellow LED test probe E3. When the air-fluid level falls mum (0,5 s),
illuminated). When the air-fluid level again below the probe E2 the set interval of the - the function selector switch must be in posi-
rises above the maximum probe E1, the set tripping delay (DELAY ON) begins. After the tion pump down,
interval of the turn-off delay (Delay OFF) expiration of the interval the output relays - turn the sensitivity controller slowly clockwi-
begins. After the expiration of the interval the switch into on-position (yellow LED illumina- se from min. to max. until the relais switch
output relay R switches into off-position ted). When the air-fluid level again rises abo- into on-position (probes must be in dipped
(yellow LED not illuminated). ve the probe E2, the set interval of the turn-off state),
delay (DELAY OFF) begins. After the expira- - the moistened probes should be taken out
tion of the interval the output relays switch of the liquid to control if the relais switch
PUMP DOWN into off-position; if the relais doesn't switch
into off-position (yellow LED not illuminated).
into off-position, turn the sensitivity control-
ler slightly back to min. (counter clockwise),
Maximum monitoring (PUMP DOWN) - set the existent time delay to desired value
to fade out a short term moisten the probes
by waves in the liquid,
- set the function selector switch to desired
Connection of the probe rods E1, E2 and E3. position (either pump up or pump down).
Alternatively the electrically conducting con-
tainer can be connected in lieu of the test
probe E3. When the maximum probe E1 gets Connection of probe rods E2 and E3 (Bridge
moistened the set interval of the tripping E1-E3). Alternatively the electrically conduc-
delay (Delay ON) begins. After the expiration ting container can be connected in lieu of the
of the interval the output relay R switches into test probe E3. When the max. probe E2 gets
on-position (yellow LED illuminated). When moistened the set interval of the tripping de-
the air-fluid level falls below the minimum lay (Delay ON) begins. After the expiration of
probe E2, the set interval of the turn-off delay the interval the output relay R switches into U - supply voltage; R - output relay

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
TR2
58 supply transformers for relays MR-G... series

Separating supply transformers TR2... for the monitoring relays


of MR-G... series to reduce the input voltage applied to the terminals
A1 and A2 of monitoring relays to the internal level of 24 V AC
TR2 transformers shall be ordered separately.

Type of transformer TR2


Input circuit
Supply voltage U 12-24-42-48-110-127-230-400 V AC
Operating range of supply voltage 0,85 < Un < 1,1
Rated power consumption 0,5...2,0 VA
Rated frequency AC: 50/60 Hz
Duty cycle 100%
General data
Dimensions (L x W x H) 32 x 35 x 16 mm
Weight 40 g
Ambient temperature storage, transport -25...+70 oC
operating -25...+55 oC PN-EN 60068-1 -25...+40 oC UL 508
Housing protection category IP 40
Relative humidity 15...85% PN-EN 60721-3-3 class 3K3

Dimensions Mounting, mechanical design

TR2 supply transformers are designed for mounting in


MR-G... monitoring relays and they are inseparable for their
operation. MR-G... relays will not operate without the TR2...
transformers. In order to mount the TR2... transformer in the
monitoring relay, it is necessary to remove the protective cap
from the relay, which protects the terminals of TR2... Then,
TR2... shall be placed in the assembly opening of the MR-G...
relay. The housing of TR2... is made of self-extinguishing
plastic. When mounted, the tightness of TR2... is IP 40.

Ordering codes

Ordering codes: TR2-12VAC, TR2-24VAC, TR2-42VAC,


TR2-48VAC, TR2-110VAC, TR2-127VAC, TR2-230VAC,
TR2-400VAC.

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820
Trade offer of Relpol S.A.
59

electromagnetic time and


and interface relays monitoring relays
NEED
programmable relays

RPS - DIN rail


power supply

solid state relays

softstarts

contactors

motor protection
switches and circiut breakers
rotary switches overvoltage
digital protection arresters
sets CZIP

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
60

Returnable card 6E

Kindly send this card by fax +48 68 37 43 830 or by letter.

RELPOL S.A. Export Sales Department Phone +48 68 47 90 832


ul. 11 Listopada 37 Fax +48 68 47 90 837, e-mail: export@relpol.com.pl
68-200 ary, Poland Marketing Department Phone +48 68 47 90 900
e-mail: relpol@relpol.com.pl e-mail: marketing@relpol.com.pl

www.relpol.com.pl Dzia Marketingu Tel./Fax +48 68 This


47 90returnable card originates
830 Wsparcie fromTel.
Techniczne catalogues Time
+48 68 47 90 relays.
820 Monitoring relays 03/2007
63

Dzia Marketingu Tel./Fax +48 68 47 90 830 Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl
64
Due to the permanent development policy, Relpol S.A. reserves the right to introduce
changes of data and characteristics of the products. The devices shall be operated
by skilled personnel in accordance with the regulations in force pertaining to
electrical systems. The technical data are of informational nature. Thus, Relpol S.A.
does not accept any liability for inappropriate use of the presented products.

The offer of Relpol S.A.


includes the following products:
subminiature signal relays
rated switching capacity: from 1 A to 3 A,
coil voltage range: from 3 V to 48 V DC

miniature relays RELPOL S.A.


rated switching capacity: from 5 A to 20 A ul. 11 Listopada 37
68-200 ary, Poland
industrial relays
rated switching capacity: from 5 A to 30 A,
e-mail: relpol@relpol.com.pl
mounting: to plug-in sockets on 35 mm DIN rail mount, www.relpol.com.pl
EN 50022 or on panel mounting, for PCB Export Sales Department
interface relays Phone +48 68 47 90 832
rated switching capacity: from 0,5 A to 16 A, Fax +48 68 47 90 837
number of contacts: from 1 to 4 e-mail: export@relpol.com.pl
plug-in sockets for relays Marketing Department
PCB plug-in sockets, plug-in sockets Phone +48 68 47 90 900
for 35 mm DIN rail mount, EN 50022 e-mail: marketing@relpol.com.pl
contactors
rated switching power: from 2,2 kW to 200 kW RELPOL M Minsk / Belarus
/at 400 V/
Phone +375 17 298 44 11
motor protection circiut breakers e-mail: info@relpol-m.com
setting range: from 0,1 A to 63 A

time relays RELPOL BG Varna / Bulgaria


single- and multifunction time relays, Phone +359 5 261 02 57
wide range of time adjustments
e-mail: office@relpol.biz
monitoring relays
monitoring of current, voltage, temperature
RELPOL HUNGARY Budapest / Hungary
NEED programmable relays Phone +361 265 19 71
versions: 8 inputs / 4 relay outputs,
e-mail: relpol@relpol.hu
16 inputs / 8 relay outputs, programming: LAD, STL,
supply voltages: 230 V AC, 24 V DC, 12 V DC,
LED indicators of the relay and input / output status RELPOL BALTIJA Vilnius / Lithuania
RPS - DIN rail power supply Phone +370 5 275 23 01
for automation systems, output circuit: 12 or 24 V DC, e-mail: baltija@relpol.com.pl
rated currents: from 1,5 A to 10 A

solid state relays RELPOL ELTIM Sankt-Petersburg / Russia


rated load currents: from 1 A to 100 A, Phone +7 812 327 35 99
switching at zero or at any time
e-mail: relpol@mail.ru
overvoltage arresters
classes I, II and III, available with changeover
signal contact
RELPOL ALTERA Kiev / Ukraine
Phone +380 44 496 18 88
switches and rotary switches e-mail: svaltera@svaltera.kiev.ua
lever switches of 1-, 2-, 3- and 4-pole versions,
rotary switches from 1 to 6 sections
and from 2 to 12 positions RELPOL FRANCE Paris / France
digital protection sets for automation, Phone +33 160 798 500
measurements and control e-mail: relpol.france@relpol.fr
03/2007

for mid-voltage fields


production and installation RELPOL LTD. London / England
of stationary devices for monitoring Phone +44 1582 487707
of radioactive radiation e-mail: phil@relpol.com.pl

www.relpol.com.pl