               Safety and aesthetics are just two compelling                    Insulated splice kits allow for simple interconnection in the field.
               reasons to use metal-enclosed PFC systems.
                                                                              Features
                                                                              	   Viewing window
                                                                              	   Top and side entry
                                                                              	   Removable front cover
                                                                              Fusing
                   Univar XV fixed medium voltage PFC unit                    Fuses are rated 50,000A symmetrical interrupting capacity. Ratings
                                                                              are 165% to 250% of rated current. Fuses have visual pop-up blown
                                                                              fuse indication standard.
Product description
Capacitors for medium voltage, heavy-duty applications:                       Discharge resistors
	   Univar capacitors are designed for power factor correction in appli-     These reduce the residual voltage to less than 50V residual within
     cations where a fixed amount of capacitance (kVAR) is required           five minutes of de-energization.
	   Available in voltage ratings of 2400V, 4160V, and 4800V                  Grounding stud
	   Fast economical payback                                                  	   Standard
	   Individual units or multiple assemblies can be designed
                                                                              Power line terminals
	   Indoor dustproof/outdoor waterproof enclosures
     (NEMA 12, NEMA 3R)                                                       	   Large size for easy connection
	   Floor mounting                                                           	   Plated copper one-hole termination pad
	   Two- or three-phase fused options for 24004800V
                                                                              Operating temperature
	   NEMA 3R terminal box
                                                                              	   40F to 115F (40C to 46C)
NNote: NECT Article 460.8 (b)(1) requires capacitors to have overcurrent
protection in all ungrounded conductors (except when connected on the load
                                                                              Optional features
side of a motor overload protection device). Three-phase capacitors fused     	   CSAT testing and labels
only on two phases will not provide adequate protection if a line-to-ground
fault should occur in the unfused phase.                                      Technical data
NNote: To be used on ungrounded delta systems or high resistance grounding systems only.
                                                                            Fusing
                                                                            Fuses are rated 50,000A symmetrical interrupting capacity.
                                                                            Ratings are 165% to 250% of rated current. Fuses have visual
                                                                            pop-up blown fuse indication standard.
                                                                            Discharge resistors
                                                                            These reduce the residual voltage to less than 50V residual
                                                                            within 5 minutes of de-energization.
                       Univar fixed medium voltage PFC unit
                                                                            Grounding stud
Product description                                                         	   Standard
Capacitors for medium voltage, heavy-duty applications:                     Power line terminals
	   Univar capacitors are designed for power factor correction             	   Large size for easy connection
     in applications where a fixed amount of capacitance (kVAR)
     is required                                                            Operating temperature
	   Available in voltage ratings of 6.6 kV, 7.2 kV, 12.47 kV and 13.8 kV   	   40F to 115F (40C to 46C)
	   Fast economical payback
                                                                            Optional features
	   Individual units or multiple assemblies can be designed
                                                                            	   CSA testing and labels
	   Indoor dustproof/outdoor waterproof enclosures
     (NEMA 12, NEMA 3R)                                                     Technical data
	   Floor mounting
                                                                            Table 4. Univar Three-Phase Ratings
	   Fuses supplied on all three phases
                                                                            Volts                    Hz                    kVAR
	   NEMA 3R terminal box
                                                                            6600                     60                    50400
Application description                                                     7200                     60                    50400
	   Large motors                                                           12,470                   60                    50500
                                                                            13,800                   60                    50500
	   Motor control centers
	   Branch circuits
	   Service entrances
Dimensions
       Removable
       Top Cover                                0.250-20
                                                Ground Screw
       16.42                     34.00
                                                       Barriers When
                                                       Necessary
                                                       Solderless Conn.
                                                       for A #10 Solid
                                                       to A #4 Str'd. Conn.
                    B
                                  24.12
         A                        25.08
Product description
Autovar medium voltage automatic power factor capacitor systems
are designed for power factor correction in applications where
plant power factor can be constant or changing and a custom
solution is required. These systems can be a fixed amount of
capacitance with a disconnect, a number of switched capacitance
stages, or a combination of both. The Autovar medium voltage                                  Medium voltage PFC enclosure
capacitor system can switch stages of capacitance in and out
automatically based on information collected by the power factor
controller on the door-in-door control panel.
     	   IEEE
     	   NEC
     	   NESC
     	   CSA (when specified)
	   Main incoming fuses are rated 50 kAIC to provide main bus pro-
     tection, as well as backup protection for the capacitor systems
	   4.00-inch base channel is standard                                                             Incoming section
                                                                        Capacitors
                                                                        Low loss, double-bushing capacitors that meet or exceed IEC 871,
                                                                        IEEE Std. 18, and CSA standards are supplied. Capacitors are
                                                                        available in delta, ungrounded wye, or solidly grounded wye.
                                                                        The dielectric fluid is environmentally friendly and biodegradable,
                                                                        and contains no PCBs. Capacitor units are equipped with internal
                                                                        discharge resistors that reduce the residual voltage to less than
                                                                        50 volts within 5 minutes of de-energization.
                                                                        Harmonic filtering
                                                                        Eatons medium voltage harmonic filter systems are designed
                                                                        for industrial, utility, and commercial power systems to improve
                                                                        power factor, to reduce harmonic distortion, and to increase system
                                                                        capacity. The reactors are typically tuned to either the 4.2nd or the
                                                                        4.7th harmonic, to filter the 5th level harmonic. Other tuning orders
                15 kV switched capacitor stage enclosure                are available. This is the most common harmonic produced by six-
                                                                        pulse variable speed drives. These filters are designed to the unique
The type SL power contactors are self-supporting, compact,              specifications of each electrical distribution system. Medium voltage
three-pole vacuum contactors, rated for capacitor switching.            capacitor banks can also be configured with de-tuned anti-resonant
The SL contactor uses a solid-state control board, allowing the         harmonic filters, typically set to the 4.2nd harmonic. Capacitor banks
user maximum flexibility to change control voltages and dropout         tuned to the 4.2nd or 4.7th harmonic prevent parallel resonance
times in the field simply by adjusting DIP switch settings. The         conditions, reduce transients, and provide harmonic filtering.
SL contactor is available in voltage ratings from 2.4 to 4.8 kV
with current ratings of 200A and 800A (the highest rated capacitor
switching contactor available), and the SL contactor has interruption
ratings of 8500A, allowing for better coordination with power fuses.
                                                                       Bus
                                                                       Standard main bus is continuous 1/4 x 2-inch silver-plated copper
                                                                       bus rated 600A and is provided throughout the lineup for easy
                                                                       interconnection, field installation, and future expansion.
                                                                       Ground bus is continuous 1/4 x 1-inch silver-plated copper rated
                                                                       300A and is provided throughout the lineup for easy intercon-
                                                                       nection, field installation, and future expansion. Ground studs
                                                                       are available in all structures for customer connection.
Control panel
Iron core reactors provide the necessary reactance to tune the            Enclosure options
capacitor system to a desired frequency. Standard filters can be
tuned to 4.2, 4.4, 4.6, or 4.7, with other tuning frequencies available   NEMA 3R stainless steel construction for highly caustic
if needed. Iron core reactors are 100% copper windings, 115C             environments.
rise with 220C insulation VPI varnish.
                                                                          Alarm strobe
                                                                          Strobe light can be provided for visual indication of faults and alarms.
                                                                          Unbalance protection
                                                                          Neutral PT or CT-based unbalance protection for wye ungrounded
                                                                          capacitor configuration.
                                                                          Other options
                                                                          	   Second PT for voltage sensing of all three phases
                                                                          	   Special CSA label for assembly
                                                                          	   Individual harmonic filter current monitoring
                                                                          	   Overload protection
Technical data
                                                                                                                                                                                                                           Top Power
                                                                                                                                                                                                                          Cable Entry
                                                                                                                                                                                                                Lifting Eyes
                                                                                Shipping Split
                                                                                                             Incoming Main Section
                                                                                                                                                                         Main Switch
                                                                                                                                                                                          92.56                 24.00
                                                                                                                                                                   K1                    (2351.0)              (609.6)
                                                                                                                                Control
                                                                                                                                 Panel                                                                                    18.00
                                CAUTION                    CAUTION                                 CAUTION
                                                                                                                                                                                                           Customer      (457.2)
                                DANGER                     DANGER                                  DANGER
                                                                                                                                                NAMEPLATE
                                                                                                                                                                                                           Cable
                                                                                                                                                                         Ground Switch
                                                                                                                                                                                                           Termination
                   Danger                    Danger                                  Danger                                        Danger
                                                                                                                                                    CAUTION
                                                                                                                                                                   K1                                      (Approximate
                                                                                                                                                                                                           Location, See
                 High Voltage              High Voltage                            High Voltage                                  High Voltage       DANGER
                                                                                                                                                                                                           Actual Unit
                                                                                                                                                                    D1
                                                                                                                                                                                                           for Exact
                                                                                                                                                                    D2
                                                                                                                                                                    D3
                                                                                                                                                                                                           Dimensions)
                                   D2                         D3                                      D2                                                      D1
                                                                                                                                                                          90.33                               Ground Bus
                                                                                                                         Door Interlocks
                                                                                                                                                                         (2294.4)                             1/4-inch x 1-inch
                                                                                                                                                                                                             Base Channel
                                                                      180.80                                                                                                                               Bottom Power
                                                                     (4592.3)                                                                                                                              Cable Entry
          8 Tie-Down Points                                                                                                      45.00                                                                          49.00
          per Enclosure                                   Front Elevation                           1.50
                                                                                                                                (1143.0)                                                                       (1244.6)
          Front and Rear                                                                           (38.1)
                                                                                                                       13.50       15.00                 13.50
          for 1/2 Inch Hardware            Rear Access Doors Optional                              (Typ)              (342.9)     (381.0)               (342.9)                                            Right Side Elevation
                                                                                                                                                                                                              Each Section is
                 Base Channel                                                                                                                                                                       45.00 (1143.0) W x 49.00 (1244.6) D
                                                                                                                          18.00                  21.79
                 40-Inches High
                                                                                                                         (457.2)                (553.5)
                                                                                                                                                                                          49.00
                                                                                                                       Bottom Entry                    18.00                             (1244.6)
                                                                                                                        Cover Plate
                                                                                                                                                      (457.2)
                                                                                                   5.09                                                 9.07
                                                                                                  (129.3)                                             (230.4)
Floor Plan
                                                                                                                                  19.00
                                                                                                                                 (482.6)
                                                                                       Top Entry                                                         16.00
                                                                                        Control                                                         (406.4)
                                                                                        Conduit
                                                                                      4.00 x 4.00                                15.00                   13.00
                                                                                                                                (381.0)                 (330.2)
Figure 5. Typical Engineered Metal-Enclosed Power Factor Correction System Dimensional Data
Utility Line
                                                         Utility
                                                         Transformer
Main Breaker
                             CT
                        A-Phase             1
Feeder Breaker K0
Plant Loads
K-K Interlock
                                         Fuse
                        S1
                      Enclosure
                      Door
                                       C1
                                   Vacuum
                                   Contactor
Reactor
Figure 6. Typical Medium Voltage Automatic Power Factor Correction Single-Line Drawing