DIAL THERMOMETER FOR WINDING AND OIL page;
2
2 cae
baa.
aX
aon
il Temperature Indicator ‘Winding Temperature Indicator Oil Temperature Indicator
(without cover) with two (without cover) with four micro- with four microswitches.
microswitches. switches.
OilTemperature Indicator, OTI
Series 34
GENERAL
The Oil Temperature Indicator Series 34
measures the top-oil temperature. It is a
standard accessory for cooling, control and
protection on all transformers.
Winding Temperature
Indicator, WTI Series 35
GENERAL
The life of the transformer depends on the
winding temperature because the winding
temperature is determinating for the
temperature and deterioration of the insulating
material
Due to the high electric potential of the
winding, itis not practical to measure the
winding temperature directly
AB KIHLSTROMS MANOMETERFABRIK
Flygftepatan 6 ¢ PHONE: +48 8931060
Suze30 SKARPNACK TELEFAX: 14886048910 DG NO, 14- /
‘SWEDEN TELEX: 17508 AKM S eSDIAL THERMOMETER FOR WINDING AND OIL
Page :2
1. Oilfilled pocket
2. Capillary tubing
3. Heating element
4, Current transformer C.T.
Alt. A 5. Matching unit AKM 44677 or AKM 44678
Alt. B 6, Matching resistance TD 76 or TD 50
(nw [=
DWG NO, :14-16936 REV |DIAL THERMOMETER FOR WINDING AND OIL Pa°:3
By making a "Thermal Image" of the winding
‘our Winding Temperature Indicator, WTI-
Series 35, simulates the winding temperature.
‘The WTI is basically an Oil Temperature
Indicator, OTI Series 34, with a specially
designed heating element connected to the
current transformer (C.T.).
For safe overloading of a transformer our WTI
is a necessary protection device
OPERATING PRINCIPLES
Please refer to pictures of the operating
principles on page 4.
‘The temperature of the winding depends on
the transformer load, (ie. current through
winding) and the temperature of the cooling
medium - the ol
These two parameters are measured and
made to interact in the instrument. The oil
temperature is measured as usual with a bulb
in the pocket
The measuring system also has a specially
designed heating element, to measure the
transformer load. This heating element is a
thermal model of the winding.
The heating element is. connected to the
current transformer (CT) via a Matching
Resistance TD76 or a Matching Unit. See
Page 4.
CALIBRATION
Calibration is based on information (from
heatrun test) about the gradient (difference
between winding- and top oil temperature) and
the corresponding output from the current
transformer (CT)
Graph TDS2 (see page 5) indicates the
current required (!) through the heating
element to give a corresponding gradient.
The current, to the heating element, can then
be calibrated either with Matching
Resistance TD76 or Matching Unit to this,
Value. Calibration is only necessary for one
known relation between load and gradient
TECHNICAL DATA
GENERAL
This product is designed for Power
transformers.
Its a special construction for long life, heavy
duty and maintenance free control ofthe oll
(OT) and winding- (WT) temperature.
itis made for outdoor mounting directly on the
transformer in any climate, tropical as well as
arctical
Al parts are made of non-corrosive or surface
treated material.
‘A powerful measuring system secures the
safe and accurate operation of the high
Capacity contacts
Besides the basic models, described in this
bulletin, many accesoris are available. For
example:
“Transmitter for remote indication (see TD66
and T0114).
“Earthquake-proof execution (see TD101).
Extreme climate execution.
_Pigtectve class IP 85 oF 85 ace to DIN or
‘SPECIFICATION
Casing: Die casted aluminium with two-pack
trethanebased primer,
Clear transparent window of tough
polycarbonate plastic. The case is ventilated
‘and weather proof according to DIN 40050
protective class IP 43,
‘Temperature sensing system: Of expansion
type (no mercury) and compensated for
ambient temperature changes.
Capillary tubing: Of copper nickel avaiable
with a protective tubing of stainless steel or
Pvc:
‘Switches: Two up to five microswitches,
terminal connected as twoway switches (open
or close on temperature rise). Electrically
separated circuits. Each switch has a dial for
setting the contact temperature. Making and
breaking capacity: 15 A, 250 V AC, see last
page.
Option: Switches with Magnetic Blow Out -
MIB O type - with higher BC switching
capacity, see last page.
Insulation test: 2000 V 50 Hz to ground 60 s.
Wiring diagram: See Instruction TD34
‘Maximum indicating pointer: Resettable
from outside with a screwdriver
Instrument operating temperature:
standard execution max.+70, min -40 °C.
Anti-vibration mountings: Included
Dimensions: See last page,
DWG NO. :14-16937 REV 1DIAL THERMOMETER FOR WINDING AND OIL ,,,..,
Winding Temperature Indicator WTI Series 35
Gradient
at°c :
S
s
40 S
\
\Y GRAPH TD52
Bulb in ol filled wel \\
Approximate temperature rise \Y
304 above oil temperature. w
w
\Y
w
x
w
20: &
§
&
w
ws
\
a w Imax = 2,3 A continuously
w Inax= 10, 53
Thermal time constant (63,2% value) ca. 9 min,
08 1 15 2 1A)
Gradientcalculation
Conditions: Bulb type | "Kk" value
Bulbtemperature 60 °C. 4142
(assumed same as top oil 15,18 20,5
temperature) i
Ailreadings, with cover mounted | __ 16 23
and minimum 30 min. after 19 22.2
stabilized current value. *
Where:
dT = Kx F(Accuracy +5%)
dT = Gradient (Winding-oil) °C.
sonstant ace. to table.
I= Current A to heating element (from C.T)
Exampel:
Calculate | for: bulbtype 12
and dT = 18°C.
18=20,5xI"
120,944
DWG NO. :14-16938 REV 1DIAL THERMOMETER FOR WINDING AND OIL
‘Type number specifyi
Serial number 34 for ol temperature OT!
Serial number 35* for winding tem»peratu
Number of switches
Measuring and switching range
Bulbtype
Accessories - if requested
Capillary length in meters
Sram
|
Serial number
Two switches
Measuring and switching range 01
Bulb type 15
‘Accessories
Capillary length 4,0 meters
* Instrument with builtin thermal image.
MEASURING RANGES
Page :5
re WTI
» Suitehing deren
Meauringrange| Mesuringacauacy | Suteningrange| Switching acouracy
© Sorc
ar} o-ssre” | 220 so-rs0°e] 0-500 | sae sn-rs0%¢ | 5-108
oz | s0-1e0°¢ | £3°C nereen 30-1708] a0-170°¢ | 42°C nerneen @0-170°C | 6-110
3 | ao-as0e | tare sore] 70-2208 | 4500 ro-220%¢ | 5158
05 | -20-1a0ec | 380 zo-1a0°¢| -20-100° | 348 so-r0ee | 5-108
a6 | o-eore | 2380 so-re0rc] o-r00°c | 40 somra0°e | 510°C
BULB TYPES
we ‘imerson we Dimenion
10 Special
15
n
anne
16 former}
2
18
13
19
a
4 Leet
DNG NO. :14-16939 REV 1DIAL THERMOMETER FOR WINDING AND OIL
Page :6
- 190 ~ 60-100 =
280 |
J
|
Q oo} Lape
FT Weight: 4g.
N cobtagnds 4255-15 mm Al dmersone ae subject o change without noi.
CONTACT RATING
Breaking capacity
‘Switchtype | Rated voltageV | RatedcurrentA 7
Resistive load | Inductive load
De 30 10 10
Standard switch 110 06 of
220 03 0,05
ac 110 15 15
220 15 18
M.B.0. switch | AC/DC 30 10 10
110 10 6
220 3 15
Service life: 500 000 operations minimum.
‘Ambient temperature range: - 40 to + 70°C.
Note: 1. Inductive load means that power
factor is 0,4 for AC and time
constant LR = 7 ms max for DC.
2. M.B.O. = Magnetic Blow Out.
AB KIHLSTROMS MANOMETERFABRIK
Fiygfaltsgatan 6 C PHONE: +46 8 93 10 50 '
$128.30 SKARPNACK TELEFAX: +46 8 604 68 10 DWG NO. :14-16940 REVI
‘SWEDEN TELEX: 17508 AKMSDIAL THERMOMETER FOR WINDING AND OIL
age 7
MANUAL/MANUEL ae
OIL TEMPERATURE INDICATOR WINDING TEMPERATURE INDICATOR
INDICATEUR DE TEMPERATURE INDICATEUR DE TEMPERATURE DE
D’HUILE L’ENROULEMENT
Series 34 Series 35
Q- DQ
(itilti i
ity
Q
Indicator
Indicateur
61 62
Output ace. to TDs
Emetteur selon TD66
oe
HMR SEHD
hs LH
[ft
55
Micro switches “Thermal image" heating element
Micro-rupteur Elément de chauffage pour "image thermique
Options
oe 8 5 5
Output ace. to TO11t “Thermal image" heating element
with matching resistance TDS0/76
Elément de chauttage pour “image thermique”
avec resistance incorporee TDSO/76
Emetteur selon TD111
DWG NO.: 14-16940-1 REV1